2600T Series Pressure Transmitters
2600T Series Pressure Transmitters
2600T Series Pressure Transmitters
SS/264XS_7
Model 264DS Differential
Model 264PS Gauge
Model 264VS Absolute
maximum working pressure up to 21MPa, 3045psi
■ Span limits
– 0.05 to 16000kPa; 0.2inH2O to 2320psi
– 0.27 to 16000kPa abs; 2mmHg to 2320psia
■ 5–year stability
Functional Specifications
Range and span limits
(§) Lower Range Limit is 0.135kPa abs, 1.35mbar abs, 1mmHg for inert Galden or 0.4kPa abs, 4mbar abs, 3mmHg for inert Halocarbon.
2
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
(1) 100°C (212°F) for application below atmospheric pressure The transmitter can be exposed without leaking to line pressure of up
to 48MPa, 480bar, 6960psi. Meet ANSI/ISA–S 82.03 hydrostatic test
(2) 65°C (150°F) for application below atmospheric pressure requirements and SAMA PMC 27.1.
Storage
Lower limit: –50°C (–58°F); –40°C (–40°F) for LCD indicators
Upper limit: +85°C (+185°F)
3
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
4
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
(volts)
10.5 10.7 12.3 12.5 13.3 15.3
Load limitations
4 to 20mA and HART total loop resistance :
Supply voltage – min. operating voltage (VDC)
R(kΩ) = –––––––––––––––––––––––––––––––––––––––
22.5
A minimum of 250Ω is required for HART communication.
Optional indicators
Output meter
CoMeter and Prometer LCD :
5-digit (±99999 counts) programmable with 7.6mm. high (3in),
7-segment numeric characters plus sign and digital point for digital
indication of output value in percentage, current or engineer unit;
10-segment bargraph display (10% per segment) for analog
indication of output in percentage;
7-digit with 6mm. high (2.3in), 14-segment alphanumeric
characters, for engineer units and configuration display
Analog : 36mm (1.4in) scale on 90°.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of analog output
in percentage.
User-definable matrix display mode with HART communication:
– process variable in pressure unit or
– output signal as percentage, current or engineering units
Display also indicates in/out transfer function, static pressure, sensor
temperature and diagnostic messages and provides configuration
facilities.
5
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
6
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
Stability
±0.15% of URL over a five years period (±0.25% for sensor code A)
Vibration effect
±0.10% of URL (according to IEC 61298–3)
7
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
Plated alloy steel bolts per ASTM-A-193-77a grade B7M and nuts Special communication connector (on request)
per ASTM A194/A 194 M-90 grade 2HM, in compliance with NACE – HART : straight or angle Harting Han connector and one plug.
MR0175 Class II.
– FOUNDATION Fieldbus, PROFIBUS PA: M12x1 or 7/8.
Electronic housing and covers
Terminal block
Barrel version
HART version: three terminals for signal/external meter wiring up to
– Aluminium alloy with baked epoxy finish; 2.5mm2 (14AWG) and three connection points for test and
– Copper-free content aluminium alloy with baked epoxy finish; communication purposes.
– AISI 316 L ss. Fieldbus versions: two terminals for signal wiring (bus connection)
up to 2.5mm2 (14AWG)
DIN version
– Aluminium alloy with baked epoxy finish. Grounding
Internal and external 6mm2 (10AWG) ground termination points are
Covers O-ring provided.
Buna N.
Mounting position
Local zero and span adjustments: Transmitter can be mounted in any position.
Glass filled polycarbonate plastic (removable). Electronics housing may be rotated to any position. A positive stop
prevents over travel.
Tagging
AISI 316ss data plate attached to the electronics housing. Mass (without options)
3.5kg approx (8lb); add 1.5kg (3.4lb) for AISI housing.
Calibration Add 650g (1.5lb) for packing.
Standard: at maximum span, zero based range, ambient temperature
and pressure; Packing
Optional: at specified range and ambient conditions. Carton 26 x 26 x 18cm approx (10 x 10 x 7in).
8
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
9
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
135 (5.31)
side side
Output meter
housing
Integral Drain/vent
display + Valve +
housing
Process
82 (3.23)
82 (3.23)
connection
(*) 54 (2.13)
86 (3.39) 86 (3.39)
Model 264VS
71 (2.80) 62 (2.44) 71 (2.80) 62 (2.44)
(*) FOR MODEL 264DS
51 (2.01), 54 (2.13) or 57 (2.24) mm (in) according to 1/2 – 14 NPT adapters fitting; 54 (2.13) mm (in) on 1/4 – 18 NPT process flange
FOR MODEL 264PS
54 (2.13) mm (in) with low pressure side flange without process connection (a filter is fitted) and drain/vent valve
Electrical
connections
86 (3.39)
Covers locking
screw SONT SO
I TS AL I V US T
CU TS E E
I
CI R I R
NS
U
C
C
IO
L ES
N GARD
IO ! ER
!
NS
E
KE L
GARD
E'T H E N
T QU
E P CO
I TS AL I V US T
CO VER TI GH RM
AN
E
KE L
W
ER
UV
E
E P CO
SONT SO
167 (6.57)
T
E
ERCLE BIEN F
CO VER TI GH RM
UV E
ERCLE BIEN F
CU TS
11 (0.43)
T
I
U W
C
CI R I R E'T H E N
C AN
L ES T QU
E
108 (4.25)
63 (2.48)
Flange
Adapter
70 (2.75)
102 (4.02)
82 (3.23)
84 (3.31)
70 (2.75)
108 (4.25)
NOTE : Process connection, gasket groove and gaskets are in accordance with DIN 19213. Bolting threads for fixing adapter or other devices
(i.e. manifold etc.) on process flange is 7/16 – 20 UNF.
10
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
Transmitter with PVDF Kynar inserts on bracket for vertical or horizontal 60mm (2in) pipe mounting
SONT SO
I TS AL I V US T
CU TS E E
I
CI R I R
NS
U
C
C
IO
L ES
GARD
E'T H E N
T QU
135 (5.31)
AN
KE L
W
ER
E
E P CO T
166 (6.54)
CO VER TI GH RM
UV E
ERCLE BIEN F
63 (2.48)
+
82 (3.23)
100 (3.94)
41.3 (1.63)
70 (2.75)
70 (2.75)
54 (2.13)
62 (2.44) 43 (1.69)
38 (1.50) 51 (2.01) 55 (2.17)
Electrical
Adjustments Identification tag connections
Barrel type 86 (3.39)
26 (1.02) 127 (5.00) 36 (1.42)
housing
17 (0.67) 17 (0.67)
SONT SO
I TS AL I V US T
CU TS E E
Min. clearance I
CI R I R
Certification
NS
U
C
C
IO
L ES
to remove label
!
E
GARD
E'T H E N
T QU
the cover
AN
KE L
W
ER
E
E P CO T
CO VER TI GH RM
185 (7.28)
UV E
ERCLE BIEN F
Electronic Terminal
side side
Output meter
housing
83 (3.27)
Integral Drain/vent
display +
Valve
housing
Adapter
33 (1.30)
41.3 (1.63)
54 (2.13)
74 (2.91)
86 (3.39)
71 (2.80) 62 (2.44)
Process
connection
11
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
Transmitter on bracket for vertical or horizontal 60 mm (2in) pipe mounting (DIN housing)
Terminal
side 179 (7.05) Electrical
63 (2.48) connections
DIN type External
housing ground 41.3 (1.63) 55 (2.17) max 86 (3.39) 7 (0.28)
51 (2.01) (1.30)
33
Output Adapter
SONT SO
I TS AL I V US T
CU TS
meter I
E E
CI R I R
NS
U
C
C
IO
L ES
housing
N
Harting Han
!
E
GARD
E'T H E N
T QU
connector
142 (5.59)
AN
KE L
W
ER
E
E P CO T
CO VER TI GH RM
UV E
ERCLE BIEN F
108 (4.25)
Certification
label
Identification
tag
Electronic
26 (1.02)
side
17 (0.67)
16 (0.63)
Integral
17 (0.67)
display Certification
housing label
36 (1.42) 148 (5.83) 82 (3.23)
Drain/vent
Valve
Transmitter with barrel AISI ss housing on bracket (flat type for box) for vertical or horizontal 60mm (2in)
pipe mounting
SONT SO
I TS AL I V US T
CU TS E E
I
CI R I R
NS
U
C
C
IO
L ES
N
!
E
GARD
E'T H E N
T QU
AN
KE L
W
ER
E
E P CO T
CO VER TI GH RM
UV E
ERCLE BIEN F
+
204 (8.03)
70 (2.75)
84 (3.31)
70 (2.75)
25 (0.98)
98 (3.86)
47 (1.85)
12
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
Transmitter on bracket for wall mounting (by up to four M8 screws, NOT SUPPLIED)
N GARD
IO ! ER
NS KE L
E
E P CO
I TS AL I V US T
CO VER TI GH RM
E
UV
SONT SO
E
ERCLE BIEN F
CU TS
T
I
U W
C
CI R I R E'T H E N
C AN
L ES T QU
E
25 (1)
70 (2.75)
70 (2.75)
70 (2.75)
13
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
Electrical connections
HART Version
Internal ground
termination point
Remote -
indicator 5
6 7 8
9
4
M+
3 60 10
2 40 80
0
20 10
% 0
0
Kent-Taylor
-
Line load M
+ +
250 ohm min
+
Power GND
source TEST COMM
External ground
- - 691HT
termination point
F1 F2 F3 F4
6 5 4
PV
Optional
REVIEW CONF
TRIM
SERIAL
LINK
- +
7 1 -
A B C D E F G H I
8 2 3
Test points
1 2 3
J K L M N O P Q R
4 5 6
Receiver S T U V W X Y Z #
Hand-held 4 to 20mA Harting pin (male)
+
7 8 9
communicator
@ % & / +
identification
0 -
HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistance
is 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow communications
FIELDBUS Versions
2 4
M12 x 1 connector
Fieldbus line
2 (polarity independent)
3 1 BUS CONNECTIONS
External ground
PIN (male) IDENTIFICATION termination point
FOUNDATION PROFIBUS
Fieldbus PA
1 FF- PA+
2 FF+ GROUND
3 SHIELD PA–
4 GROUND SHIELD
CONNECTOR IS SUPPLIED LOOSE WITHOUT MATING FEMALE PLUG
14
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
15
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
XX XX XX XX XX XX XX XX XX Cont'd
Drain/vent valve (material and position) (wetted parts)
AISI 316 L ss on process axis (Notes 6, 11) NACE V1
AISI 316 L ss on flange side top (Notes 6, 12) NACE V2
AISI 316 L ss on flange side bottom (Notes 6, 12) NACE V3
Hastelloy C276™ on process axis (Notes 6, 13) NACE V4
Hastelloy C276™ on flange side top (Notes 6, 14) NACE V5
Hastelloy C276™ on flange side bottom (Notes 6, 14) NACE V6
Monel 400™ on process axis (Notes 6, 15) NACE V7
Monel 400™ on flange side top (Notes 6, 16) NACE V8
Monel 400™ on flange side bottom (Notes 6, 16) NACE V9
Electrical certification
ATEX Group II Category 1 GD – Intrinsic Safety EEx ia E1
ATEX Group II Category 1/2 GD – Flameproof EEx d E2
ATEX Group II Category 3 GD – Type of protection "N" EEx nL design compliance (Note 17) E3
Canadian Standard Association (CSA) (only 1/2– 14NPT, M20 and Pg 13.5 electrical connection) E4
Standards Australia SAA (Not Ex ia and Ex n for PROFIBUS PA and FOUNDATION Fieldbus) E5
Factory Mutual (FM) approval (only with 1/2– 14NPT, M20 and Pg 13.5 electrical connection) E6
Combined ATEX - Intrinsic Safety and Flameproof E7
Combined ATEX, FM and CSA (only with 1/2– 14NPT, M20 and Pg 13.5 electrical connection) (Note 17) EN
NEPSI (China) - Intrinsic Safety Ex ia EY
NEPSI (China) - Flameproof Ex d EZ
GOST (Russia) EEx ia W1
GOST (Russia) EEx d W2
GOST (Kazakhstan) EEx ia W3
GOST (Kazakhstan) EEx d W4
Inmetro (Brazil) EEx ia W5
Inmetro (Brazil) EEx d W6
Inmetro (Brazil) EEx nL W7
Metrologic (Russia) WC
Metrologic (Kazakhstan) WD
Output meter
ProMeter, Standard calibration (Note 17) D1
ProMeter, Special calibration (Note 17) D2
Analog output indicator linear 0– 100% scale (Note 17) D3
Analog output indicator square root 0– 10 scale (Note 17) D4
Analog output indicator, special graduation (to be specified for linear scale) (Note 17) D5
Analog output indicator, special graduation (to be specified for square root scale) (Note 17) D6
Programmable signal meter and HART configurator (CoMeter) (Note 17) D7
Programmable signal meter and HART configurator (CoMeter – customer configuration) (Note 17) D8
Integral LCD
Digital LCD integral display L1
16
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
17
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
18
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
19
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
20
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
21
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
XX XX XX XX XX XX XX XX XX Cont'd
Drain/vent valve (material and position) (wetted parts)
AISI 316 L ss on process axis (Note 7) NACE V1
AISI 316 L ss on flange side top (Note 8) NACE V2
AISI 316 L ss on flange side bottom (Note 8) NACE V3
Hastelloy C276™ on process axis (Note 9) NACE V4
Hastelloy C276™ on flange side top (Note 10) NACE V5
Hastelloy C276™ on flange side bottom (Note 10) NACE V6
Monel 400™ on process axis (Note 11) NACE V7
Monel 400™ on flange side top (Note 12) NACE V8
Monel 400™ on flange side bottom (Note 12) NACE V9
Electrical certification
ATEX Group II Category 1 GD – Intrinsic Safety EEx ia E1
ATEX Group II Category 1/2 GD – Flameproof EEx d E2
ATEX Group II Category 3 GD – Type of protection "N" EEx nL design compliance (Note 13) E3
Canadian Standard Association (CSA) (only 1/2– 14NPT, M20 and Pg 13.5 electrical connection) E4
Standards Australia SAA (Not Ex ia and Ex n for PROFIBUS PA and FOUNDATION Fieldbus) E5
Factory Mutual (FM) approval (only with 1/2– 14NPT, M20 and Pg 13.5 electrical connection) E6
Combined ATEX - Intrinsic Safety and Flameproof E7
Combined ATEX, FM and CSA (only with 1/2– 14NPT, M20 and Pg 13.5 electrical connection) (Note 13) EN
NEPSI (China) - Intrinsic Safety Ex ia EY
NEPSI (China) - Flameproof Ex d EZ
GOST (Russia) EEx ia W1
GOST (Russia) EEx d W2
GOST (Kazakhstan) EEx ia W3
GOST (Kazakhstan) EEx d W4
Inmetro (Brazil) EEx ia W5
Inmetro (Brazil) EEx d W6
Inmetro (Brazil) EEx nL W7
Metrologic (Russia) WC
Metrologic (Kazakhstan) WD
Output meter
ProMeter, Standard calibration (Note 13) D1
ProMeter, Special calibration (Note 13) D2
Analog output indicator linear 0– 100% scale (Note 13) D3
Analog output indicator, special graduation (to be specified for linear scale) (Note 13) D5
Programmable signal meter and HART configurator (CoMeter) (Note 13) D7
Programmable signal meter and HART configurator (CoMeter – customer configuration) (Note 13) D8
Integral LCD
Digital LCD integral display L1
22
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS SS/264XS_7
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
23
2600T Pressure Transmitters
Model 264DS, 264PS, 264VS
ABB has Sales & Customer Support The Company’s policy is one of continuous product
expertise in over 100 countries worldwide improvement and the right is reserved to modify the
information contained herein without notice.