OML07127 - UFP ModBus Table

The document describes the Modbus registers available on UFP panels for RTB.2 systems. It provides information on the Modbus serial communication ports, Modbus RTU RS485 settings and hardware, and Modbus TCP/IP implementation using a converting gateway. It then lists the Modbus registers organized by section - general information, rectifier alarms/states/measures, with register addresses, names, and descriptions.

Uploaded by

JOSE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views16 pages

OML07127 - UFP ModBus Table

The document describes the Modbus registers available on UFP panels for RTB.2 systems. It provides information on the Modbus serial communication ports, Modbus RTU RS485 settings and hardware, and Modbus TCP/IP implementation using a converting gateway. It then lists the Modbus registers organized by section - general information, rectifier alarms/states/measures, with register addresses, names, and descriptions.

Uploaded by

JOSE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

UFP ModBus table

UFP MODBUS TABLE

Indice

1. MODBUS SERIAL COM IN UFP ........................................................ 3


2. MODBUS RTU - RS485 ON UFP PANEL .......................................... 4
2.1 MODBUS RTU - RS485 PARAMETERS SETTING ......................................... 4
2.2 MODBUS RTU - RS485 HARDWARE SETTING ............................................. 4
2.3 MODBUS RTU - RS485 TERMINAL BOARDS ................................................ 4
3. MODBUS TCP/IP ON UFP PANEL .................................................... 5
4. MODBUS REGISTERS RTB.2 ........................................................... 6
4.1 GENERAL MODBUS REGISTERS ................................................................. 8
4.1.1 GENERAL ALARMS ................................................................................. 8
4.1.2 GENERAL STATES .................................................................................. 9
4.1.3 GENERAL INFO ...................................................................................... 10
4.2 RECTIFIER MODBUS REGISTERS ............................................................... 11
42.1 RECTIFIER ALARMS ................................................................................. 11
4.2.2 RECTIFIER STATES ............................................................................... 12
4.2.3 RECTIFIER MEASURES ......................................................................... 13
4.2.4 RECTIFIER BATTERY TEST .................................................................. 16

Descrizione Data Emesso Approvato Lingua Pagina di Pag.


Rev.
Description Date Issued Approved Language Page of Pag.
C Upgrade modbus registers 08.04.19 E. Biancucci N. Fognani
E 1 16
Codice / Code

OML07127
UFP ModBus table

Indice delle figure


Fig. 1 – Terminal boards and dip-switches position of the RS485 ports 4
Fig. 2 – Modbus RTU RS485/Modbus TCP/IP converting gateway 5

2 OML07127 REV. C
UFP ModBus table

1. MODBUS SERIAL COM IN UFP


UFP panel, centralizing device for all the signals and the measures available inside RTB.2
systems, has basically a redundant ModBus serial communication port to send informations
about measures and alarms to external devices to the panel; ModBus can be available in the
two most used protocol versions:
 ModBus RTU RS485
 ModBus TCP/IP
ModBus RTU RS485 consists in a master-slave serial communication composed by
messages framed by idle periods and defined by a high-level communication protocol; in this
format a cyclic redundancy checksum (CRC) ensures the reliability of data. On UFP panel
ModBus RTU is supported by a RS485 physical layer for both ports.
ModBus TCP/IP (available on request) is a ModBus variant used for communications over
TCP/IP networks. It is very similar to ModBus RTU but it transmits packets of the protocol within
the TCP / IP data packets and requires an Ethernet connection. ModBus TCP/IP is derived from
the ModBus RTU RS485 using external gateway adaptor making ModBus TCP/IP available on
a RJ45 port of the gateway for the network connection.

OML07127 REV. C 3
UFP ModBus table

2. MODBUS RTU - RS485 ON UFP PANEL


2.1 MODBUS RTU - RS485 PARAMETERS SETTING
The dafult values for the RS485 parameters setting are the following:
 Format: RTU format
 Data: 8 bits
 Stop bit number: 2 stop bits
 Parity: no parity bit
 BAUD rate: 9600
 Address: 1
Baudrate, parity, stop bit number and slave address can be modified from the front panel
display entering the menu SETTING and MODBUS PORT 1(or MODBUS PORT 2 for the
second channel).
2.2 MODBUS RTU - RS485 HARDWARE SETTING
It is possible to configure the RS485 line through 3 dip-switches (3 dips for each port) under
the rear cover of the panel as in the picture hereunder; two small windows on the rear cover,
each one of them located over the relevant port, allows to enable a 120ohm termination resistor
(dip 2) and two 1k polarization resistors (dip 1 and 3).

Fig. 1 – Terminal boards and dip-switches position of the RS485 ports


2.3 MODBUS RTU - RS485 TERMINAL BOARDS
Two 3-poles terminal boards for the ModBus connection are provided in the back of the
panel as in the picture. For the convention used here ‘Data+’ refers to line A and ‘Data-’ refers
to line B for both ports P1 and P2.

4 OML07127 REV. C
UFP ModBus table

3. MODBUS TCP/IP ON UFP PANEL


ModBus TCP/IP is made available through a gateway converting ModBus RTU RS485
format into ModBus TCP/IP.
The gateway is directly connected to the UFP acting as MASTER from RS485 side; all the
communication settings in the RS485 side are already internally done and don’t need to be
modified.
The gateway made ModBus TCP/IP available on an RJ45 port suitable for Ethernet
connection. The gateway IP configuration must be done using a special software and
connecting to it through one of the RJ45 port available. Further informations can be found inside
the gateway user’s manual supplied together with the electrical panel documentation.
As for the ModBus RTU RS485, it is available a redundant serial connection.

Fig. 2 – Modbus RTU RS485/Modbus TCP/IP converting gateway

OML07127 REV. C 5
UFP ModBus table

4. MODBUS REGISTERS RTB.2


In RTB.2 systems data are sent using the function coded as 03 of the PDU (Holding
Register). Receiving this kind of instruction, the unit answers by sending the data table
described in the following pages.

WARNING: the address of the Register 1 is 0!

Register Register
Variable Name Description
Address Number
GENERAL
General alarms present in the
0-3 1-4 GENERAL ALARMS ALARMS
system
(see §4.1.1)
General states present in the GENERAL STATES
4-5 5-6 GENERAL STATES
system (see §4.1.2)
6 7 DEVICE NAME (CHAR 0)
7 8 DEVICE NAME (CHAR 1)
8 9 DEVICE NAME (CHAR 2)
9 10 DEVICE NAME (CHAR 3)
10 11 DEVICE NAME (CHAR 4)
11 12 DEVICE NAME (CHAR 5)
12 13 DEVICE NAME (CHAR 6)
13 14 DEVICE NAME (CHAR 7)
14 15 DEVICE NAME (CHAR 8)
15 16 DEVICE NAME (CHAR 9)
16 17 DEVICE NAME (CHAR 10)
17 18 DEVICE NAME (CHAR 11)
18 19 DEVICE NAME (CHAR 12)
19 20 DEVICE NAME (CHAR 13)
20 21 DEVICE NAME (CHAR 14) Device name
GENERAL INFO
21 22 DEVICE NAME (CHAR 15)
(see §4.1.3)
22 23 DEVICE NAME (CHAR 16)
23 24 DEVICE NAME (CHAR 17)
24 25 DEVICE NAME (CHAR 18)
25 26 DEVICE NAME (CHAR 19)
26 27 DEVICE NAME (CHAR 20)
27 28 DEVICE NAME (CHAR 21)
28 29 DEVICE NAME (CHAR 22)
29 30 DEVICE NAME (CHAR 23)
30 31 DEVICE NAME (CHAR 24)
31 32 DEVICE NAME (CHAR 25)
32 33 DEVICE NAME (CHAR 26)
33 34 DEVICE NAME (CHAR 27)
34 35 DEVICE NAME (CHAR 28)
35 36 DEVICE NAME (CHAR 29)
36 37 SYSTEM CONFIGURATION Configuration of the system
37 38 MODBUS ADDRESS - PORT 1 Modbus address of Port 1 MODBUS INFO
38 39 MODBUS BAUDRATE - PORT 1 Modbus baudrate of Port 1 PORT 1
39 40 MODBUS MODE - PORT 1 Modbus mode of Port 1 (see §4.1.3)
40 41 MODBUS ADDRESS - PORT 2 Modbus address of Port 2 MODBUS INFO
41 42 MODBUS BAUDRATE - PORT 2 Modbus baudrate of Port 2 PORT 2
42 43 MODBUS MODE - PORT 2 Modbus mode of Port 2 (see §4.1.3)
43 44 FW UFP (VALUE 0)
44 45 FW UFP (VALUE 1) FIRMWARE INFO
Firmware of the UFP
45 46 FW UFP (VALUE 2) (see §4.1.3)
46 47 FW UFP (VALUE 3)
47 ... 99 48...100 ... ...reserved...
RECTIFIER
Rectifier alarms present in the
100 - 103 101 - 104 RECTIFIER ALARMS ALLARMS
system
(see §4.2.1)

6 OML07127 REV. C
UFP ModBus table

RECTIFIER
Rectifier states present in the
104 - 105 105 - 106 RETIFIER STATES STATES
system
(see §4.2.2)
106 107 MAINS VOLTAGE PHASE L1
Mains voltage phase- phase
107 108 MAINS VOLTAGE PHASE L2
(Vx10)
108 109 MAINS VOLTAGE PHASE L3
MAINS VOLTAGE PHASE L1
109 110
(L-N)
MAINS VOLTAGE PHASE L2 Mains voltage phase- neutral RECTIFIER INPUT
110 111
(L-N) (Vx10) MEASURES
MAINS VOLTAGE PHASE L3 (see §4.2.3)
111 112
(L-N)
112 113 MAINS CURRENT PHASE L1
113 114 MAINS CURRENT PHASE L2 Mains current (Ax10)
114 115 MAINS CURRENT PHASE L3
115 116 MAINS FREQUENCY Mains frequency (Hzx10)
116 117 BATTERY AUTONOMY MIN Battery autonomy (minuti)
117 118 BATTERY ENERGY % Battery energy (%) RECTIFIER
118 119 BATTERY VOLTAGE Battery voltage (Vx10) BATTERY
119 120 BATTERY CURRENT Battery current (Ax10) MEASURES
120 121 SECOND BATTERY CURRENT Second battery current (Ax10) (see §4.2.3)
121 122 THIRD BATTERY CURRENT Third battery current (Ax10)
122 123 DC OUTPUT VOLTAGE DC output voltage (Vx10) RECTIFIER
123 124 OUTPUT CURRENT Output current (Ax10) OUTPUT
MEASURES
124 125 INTERMEDIATE VOLTAGE Intermediate voltage (Vx10)
(see §4.2.3)
125 126 OUTPUT POWER kW Output power (kWx10)
Input active power (average)
126 127 INPUT ACTIVE POWER
(kWx10)
127 128 ACTIVE POWER PHASE L1 Active power L1 (kWx10)
128 129 ACTIVE POWER PHASE L2 Active power L2 (kWx10)
129 130 ACTIVE POWER PHASE L3 Active power L3 (kWx10)
Reactive power (average)
130 131 AVERAGE REACTIVE POWER
(kWx10)
131 132 REACTIVE POWER PHASE L1 Reactive power L1 (kWx10) RECTIFIER
132 133 REACTIVE POWER PHASE L2 Reactive power L2 (kWx10) POWER
133 134 REACTIVE POWER PHASE L3 Reactive power L3 (kWx10) MEASURES
Apparent power (average) (see §4.2.3)
134 135 AVERAGE APPARENT POWER
(kVAx10)
135 136 APPARENT POWER PHASE L1 Apparent power L1 (kVAx10)
136 137 APPARENT POWER PHASE L2 Apparent power L2 (kVAx10)
137 138 APPARENT POWER PHASE L3 Apparent power L3 (kVAx10)
138 139 AVERAGE COS PHI Cos PHI (average) (x1000)
139 140 COS PHI L1 Cos PHI L1 (x1000)
140 141 COS PHI L2 Cos PHI L2 (x1000)
141 142 COS PHI L3 Cos PHI L3 (x1000)
Probe 1 temperature (Degx10)
Valid only if the probe is
142 143 PROBE 1 TEMPERATURE
connected (Register
address145)
Probe 2 temperature (Degx10)
Valid only if the probe is
143 144 PROBE 2 TEMPERATURE
connected (Register
address146) RECTIFIER
Probe 3 tem5erature (Degx10) TEMPERATURE
Valid only if the probe is MEASURES
144 145 PROBE 3 TEMPERATURE
connected (Register (vedi §4.2.4)
address147)
TEMPERATURE PROBE 1
145 146 Temperature Probe 1failed
FAILURE
TEMPERATURE PROBE 2
146 147 Temperature Probe 2 failed
FAILURE
TEMPERATURE PROBE 3
147 148 Temperature Probe 3 failed
FAILURE

OML07127 REV. C 7
UFP ModBus table

148 149 DISTRIBUTION VOLTAGE Distribution voltage


149 150 DISTRIBUTION CURRENT Distribution current
150 151 BATTERY TEST TIMER Timer of battery test (s)
151 152 BATTERY TEST OK Battery test OK RECTIFIER
152 153 BATTERY TEST FAILED Battery test failed BATTERY TEST
153 154 MANUAL TEST STOPPED Manual test stopped (vedi §4.2.5)
154 155 AUTO BATTERY TEST STOPPED Automatic battery test stopped
155...END 156...END ...reserved

4.1 GENERAL MODBUS REGISTERS

4.1.1 GENERAL ALARMS


General Alarms Address Register Bit
A1_GEN: Communication lost Device 1 Bit 0 =1
A2_GEN Bit 1 =1
A3_GEN Bit 2 =1
A4_GEN Bit 3 =1
A5_GEN Bit 4 =1
A6_GEN Bit 5 =1
A7_GEN Bit 6 =1
A8_GEN Bit 7 =1
0 1
A9_GEN Bit 8 =1
A10_GEN Bit 9 =1
A11_GEN Bit 10 =1
A12_GEN Bit 11 =1
A13_GEN Bit 12 =1
A14_GEN Bit 13 =1
A15_GEN Bit 14 =1
A16_GEN Bit 15 =1
A17_GEN Bit 0 =1
A18_GEN Bit 1 =1
A19_GEN Bit 2 =1
A20_GEN Bit 3 =1
A21_GEN Bit 4 =1
A22_GEN Bit 5 =1
A23_GEN Bit 6 =1
A24_GEN Bit 7 =1
1 2
A25_GEN Bit 8 =1
A26_GEN Bit 9 =1
A27_GEN Bit 10 =1
A28_GEN Bit 11 =1
A29_GEN Bit 12 =1
A30_GEN Bit 13 =1
A31_GEN Bit 14 =1
A32_GEN Bit 15 =1
A33_GEN Bit 0 =1
A34_GEN Bit 1 =1
A35_GEN Bit 2 =1
A36_GEN Bit 3 =1
A37_GEN Bit 4 =1
A38_GEN Bit 5 =1
A39_GEN Bit 6 =1
A40_GEN Bit 7 =1
2 3
A41_GEN Bit 8 =1
A42_GEN Bit 9 =1
A43_GEN Bit 10 =1
A44_GEN Bit 11 =1
A45_GEN Bit 12 =1
A46_GEN Bit 13 =1
A47_GEN Bit 14 =1
A48_GEN Bit 15 =1
A49_GEN 3 4 Bit 0 =1

8 OML07127 REV. C
UFP ModBus table

A50_GEN: Configurable 1 Bit 1 =1


A51_GEN: Configurable 2 Bit 2 =1
A52_GEN: Configurable 3 Bit 3 =1
A53_GEN: Configurable 4 Bit 4 =1
A54_GEN: Configurable 5 Bit 5 =1
A55_GEN: Configurable 6 Bit 6 =1
A56_GEN: Configurable 7 Bit 7 =1
A57_GEN: Configurable 8 Bit 8 =1
A58_GEN: Configurable 9 Bit 9 =1
A59_GEN: Configurable 10 Bit 10 =1
A60_GEN Bit 11 =1
A61_GEN Bit 12 =1
A62_GEN Bit 13 =1
A63_GEN: EEPROM error Bit 14 =1
A64_GEN: Common alarm Bit 15 =1

4.1.2 GENERAL STATES


General States Address Register Bit
S1_GEN Bit 0 =1
S2_GEN Bit 1 =1
S3_GEN Bit 2 =1
S4_GEN Bit 3 =1
S5_GEN Bit 4 =1
S6_GEN Bit 5 =1
S7_GEN Bit 6 =1
S8_GEN Bit 7 =1
4 5
S9_GEN Bit 8 =1
S10_GEN Bit 9 =1
S11_GEN Bit 10 =1
S12_GEN Bit 11 =1
S13_GEN Bit 12 =1
S14_GEN Bit 13 =1
S15_GEN Bit 14 =1
S16_GEN Bit 15 =1
S17_GEN Bit 0 =1
S18_GEN Bit 1 =1
S19_GEN Bit 2 =1
S20_GEN Bit 3 =1
S21_GEN Bit 4 =1
S22_GEN Bit 5 =1
S23_GEN Bit 6 =1
S24_GEN Bit 7 =1
5 6
S25_GEN Bit 8 =1
S26_GEN Bit 9 =1
S27_GEN Bit 10 =1
S28_GEN Bit 11 =1
S29_GEN Bit 12 =1
S30_GEN Bit 13 =1
S31_GEN Bit 14 =1
S32_GEN Bit 15 =1

OML07127 REV. C 9
UFP ModBus table

4.1.3 GENERAL INFO


General Info
Description Address Register Encoding

A - ASCII characters:
Register 7 8 9 10 11 12 13 14 15 16 17 ... 35 36
Device
6  35 47 36 Value 68 69 86 32 78 65 77 69 32 32 32 ... 48 49
Name
Character to
D E V N A M E ... 0 1
be displayed

C - the value represents a code:


System
36 37
Configuration Value 1
Display ONE RECTIFIER
Info Modbus - Port 1
ModBus
Address - 37 38 I – integer (I.e. 80 80)
Port 1
C - the value represents a code:
ModBus
Baudrate - 38 39
Value 0 1
Port 1
Display 9600 19200
C - the value represents a code:
ModBus
Mode - 39 40 Value 0 1 2 3 5 5
Port 1 Display NO PAR PAR EVN PAR ODD NO PAR PAR EVN PAR ODD
2 BIT 1 BIT 1 BIT 1 BIT 2 BIT 2 BIT
STOP STOP STOP STOP STOP STOP
Info Modbus - Port 2
ModBus
Address - 40 41 I – integer (I.e. 80 80)
Port 2
C - the value represents a code:
ModBus
Baudrate - 41 42
Value 0 1
Port 2
Display 9600 19200
C - the value represents a code:
ModBus
Mode - 42 43 Value 0 1 2 3 5 5
Port 2 Display NO PAR PAR EVN PAR ODD NO PAR PAR EVN PAR ODD
2 BIT 1 BIT 1 BIT 1 BIT 2 BIT 2 BIT
STOP STOP STOP STOP STOP STOP
Info Firmware
F - the value is:
Firmware UFP: x.y.z.h
dove x = #reg44, y = #reg45, z = #reg46 and h = #reg47
Ex.
Address Register Variable Value Display
UFP FW (VALUE
Firmware 44 45 1
43  46 44  47 0)
UFP
UFP FW (VALUE
45 46 0
1) UFP Firmware:
UFP FW (VALUE 1.0.3.0
46 47 3
2)
UFP FW (VALUE
47 48 0
3)

10 OML07127 REV. C
UFP ModBus table

4.2 RECTIFIER MODBUS REGISTERS


42.1 RECTIFIER ALARMS
Rectifier Alarms Address Register Bit
A1_R01: Mains not Ok Bit 0 =1
A2_R01: Bridge blown fuses Bit 1 =1
A3 _R01: High temperature Bit 2 =1
A4 _R01: Overload Bit 3 =1
A5 _R01: Max rectifier voltage Bit 4 =1
A6 _R01: Min rectifier voltage Bit 5 =1
A7 _R01: Emergency level Bit 6 =1
A8 _R01: Max floating voltage Bit 7 =1
100 101
A9 _R01: Min floating voltage Bit 8 =1
A10 _R01: Safety timer Bit 9 =1
A11 _R01: Fans failure Bit 10 =1
A12 _R01: RICB open Bit 11 =1
A13 _R01: BCB open Bit 12 =1
A14 _R01: ROCB open Bit 13 =1
A15 _R01: Battery discharge Bit 14 =1
A16 _R01: Min battery level 1 Bit 15 =1
A17 _R01: Min battery level 2 Bit 0 =1
A18_R01: Min battery level 3 Bit 1 =1
A19 _R01 Bit 2 =1
A20 _R01: Thermal image Bit 3 =1
A21_R01: Manual interrupted Bit 4 =1
A22_R01: Battery reverse polarity Bit 5 =1
A23_R01: Battery test failed Bit 6 =1
A24_R01: Q11 open Bit 7 =1
101 102
A25_R01: Parallel CAN error Bit 8 =1
A26_R01: Parallel fault Bit 9 =1
A27_R01: Q12 open Bit 10 =1
A28_R01 Bit 11 =1
A29_R01 Bit 12 =1
A30_R01: Rectifier OFF by user Bit 13 =1
A31_R01: Control error loop Bit 14 =1
A32_R01: Supply fault Bit 15 =1
A33_R01: Thermal probe failure Bit 0 =1
A34_R01 Bit 1 =1
A35 _R01 Bit 2 =1
A36 _R01 Bit 3 =1
A37_R01 Bit 4 =1
A38 _R01 Bit 5 =1
A39 _R01 Bit 6 =1
A40 _R01 Bit 7 =1
102 103
A41 _R01 Bit 8 =1
A42 _R01 Bit 9 =1
A43_R01 Bit 10 =1
A44 _R01 Bit 11 =1
A45 _R01 Bit 12 =1
A46 _R01 Bit 13 =1
A47 _R01 Bit 14 =1
A48 _R01 Bit 15 =1

OML07127 REV. C 11
UFP ModBus table

A49 _R01 Bit 0 =1


A50_R01: Configurable 1 Bit 1 =1
A51_R01: Configurable 2 Bit 2 =1
A52_R01: Configurable 3 Bit 3 =1
A53_R01: Configurable 4 Bit 4 =1
A54_R01: Configurable 5 Bit 5 =1
A55 _R01: Configurable 6 Bit 6 =1
A56_R01: Configurable 7 Bit 7 =1
103 104
A57_R01: Configurable 8 Bit 8 =1
A58_R01: Configurable 9 Bit 9 =1
A59_R01: Configurable 10 Bit 10 =1
A60 _R01 Bit 11 =1
A61_R01 Bit 12 =1
A62_R01 Bit 13 =1
A63_R01: EEPROM error Bit 14 =1
A64_R01: Common alarm Bit 15 =1

4.2.2 RECTIFIER STATES


Rectifier States Address Register Bit
S1_R01: Rectifier ON Bit 0 =1
S2_R01: Rectifier OK Bit 1 =1
S3_R01: Floating charge Bit 2 =1
S4_R01: Boost charge Bit 3 =1
S5_R01: Manual charge Bit 4 =1
S6_R01:Batteriy test Bit 5 =1
S7_R01: Floating imposition Bit 6 =1
S8_R01: Manual inhibition Bit 7 =1
104 105
S9_R01: Master Bit 8 =1
S10_R01: Slave Bit 9 =1
S11_R01: Parallel deactivated Bit 10 =1
S12_R01: Share OK Bit 11 =1
S13_R01: Boost inhibit Bit 12 =1
S14_R01 Bit 13 =1
S15_R01 Bit 14 =1
S16_R01 Bit 15 =1
S17_R01 Bit 0 =1
S18_R01 Bit 1 =1
S19_R01 Bit 2 =1
S20_R01 Bit 3 =1
S21_R01 Bit 4 =1
S22_R01 Bit 5 =1
S23_R01 Bit 6 =1
S24_R01 Bit 7 =1
105 106
S25_R01 Bit 8 =1
S26_R01 Bit 9 =1
S27_R01 Bit 10 =1
S28_R01 Bit 11 =1
S29_R01 Bit 12 =1
S30_R01 Bit 13 =1
S31_R01 Bit 14 =1
S32_R01 Bit 15 =1

12 OML07127 REV. C
UFP ModBus table

4.2.3 RECTIFIER MEASURES


Input Measures
Unit of
Description Address Register Encoding
meas.
Mains voltage phase L1 106 107 V D – value with 1 decimal (i.e. 2315  231.5)
Mains voltage phase L2 107 108 V D – value with 1 decimal (i.e. 2315  231.5)
Mains voltage phase L3 108 109 V D – value with 1 decimal (i.e. 2315  231.5)

Mains voltage phase L1


109 110 V D – value with 1 decimal (i.e. 2315  231.5)
(L-N)
Mains voltage phase L2
110 111 V D – value with 1 decimal (i.e. 2315  231.5)
(L-N)
Mains voltage phase L3
111 112 V D – value with 1 decimal (i.e. 2315  231.5)
(L-N)

Mains current phase L1 112 113 A D – value with 1 decimal (i.e. 2315  231.5)
Mains current phase L2 113 114 A D – value with 1 decimal (i.e. 2315  231.5)
Mains current phase L3 114 115 A D – value with 1 decimal (i.e. 2315  231.5)

Mains frequency 115 116 Hz D – value with 1 decimal (i.e. 2315  231.5)

Battery Measures
Unit of
Description Address Register Encoding
meas.
Battery
116 117 min I – integer (I.e. 80 80)
autonomy [min]
Battery energy
117 118 % I – integer (I.e. 80 80)
[%]
Battery voltage 118 119 V SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
Battery current 119 120 A SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
Second battery
120 121 A SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
current
Third battery
121 122 A SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
current

Output Measures
Unit
Description Address Register of Encoding
meas.
DC output
122 123 V SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
voltage
Output current 123 124 A SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
Intermediate
124 125 V SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)
voltage

OML07127 REV. C 13
UFP ModBus table

Power measures
Unit of
Description Address Register Encoding
meas.
Output power kW 125 126 kW D – value with 1 decimal (i.e. 2315  231.5)

SD - value with 1 decimal and the SIGN (i.e. 65535  -


Input active power 126 127 kW
0,1)
Input active power SD - value with 1 decimal and the SIGN (i.e. 65535  -
127 128 kW
phase L1 0,1)
Input active power SD - value with 1 decimal and the SIGN (i.e. 65535  -
128 129 kW
phase L2 0,1)
Input active power SD - value with 1 decimal and the SIGN (i.e. 65535  -
129 130 kW
phase L3 0,1)

Reactive power SD - value with 1 decimal and the SIGN (i.e. 65535  -
130 131 kW
(average) 0,1)
Reactive power SD - value with 1 decimal and the SIGN (i.e. 65535  -
131 132 kW
phase L1 0,1)
Reactive power SD - value with 1 decimal and the SIGN (i.e. 65535  -
132 133 kW
phase L2 0,1)
Reactive power SD - value with 1 decimal and the SIGN (i.e. 65535  -
133 134 kW
phase L3 0,1)

Apparent power
134 135 kVA D – value with 1 decimal (i.e. 2315  231.5)
(average)
Apparent power
135 136 kVA D – value with 1 decimal (i.e. 2315  231.5)
phase L1
Apparent power
136 137 kVA D – value with 1 decimal (i.e. 2315  231.5)
phase L2
Apparent power
137 138 kVA D – value with 1 decimal (i.e. 2315  231.5)
phase L3

Cos phi (average) 138 139 DDD – value with 3 decimals (i.e. 821  0.821)
Cos phi phase L1 139 140 DDD – value with 3 decimals (i.e. 821  0.821)
Cos phi phase L2 140 141 DDD – value with 3 decimals (i.e. 821  0.821)
Cos phi phase L3 141 142 DDD – value with 3 decimals (i.e. 821  0.821)

14 OML07127 REV. C
UFP ModBus table

Temperature Measures
Unit of
Description Address Register Encoding
meas.

SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)


This measure should appear only if the temperature probe is
connected:
Address Register Variable Value Display
PROBE 1
142 143 255 Probe 1
TEMPERATURE
Temperature temp:
142 143 °C PROBE 1
Probe 1 145 146 0 25.5 °C
DISCONNECTED
Address Register Variable Value Display
PROBE 1
142 143 255
TEMPERATURE
---
PROBE 1
145 146 1
DISCONNECTED

SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)


This measure should appear only if the temperature probe is
connected:
Address Register Variable Value Display
PROBE 2
143 144 255 Probe 1
TEMPERATURE
Temperature temp:
143 144 °C PROBE 2
Probe 2 146 147 0 25.5 °C
DISCONNECTED
Address Register Variable Value Display
PROBE 2
143 144 255
TEMPERATURE
---
PROBE 2
146 147 1
DISCONNECTED

SD - value with 1 decimal and the SIGN (i.e. 65535  -0,1)


This measure should appear only if the temperature probe is
connected:
Address Register Variable Value Display
PROBE 3
144 145 255 Probe 1
TEMPERATURE
Temperature temp:
144 145 °C PROBE 3
Probe 3 147 148 0 25.5 °C
DISCONNECTED
Address Register Variable Value Display
PROBE 3
144 145 255
TEMPERATURE
---
PROBE 3
147 148 1
DISCONNECTED

Distribution
148 149 V D – value with 1 decimal (i.e. 2315  231.5)
voltage
Distribution
149 150 A D – value with 1 decimal (i.e. 2315  231.5)
current

OML07127 REV. C 15
UFP ModBus table

4.2.4 RECTIFIER BATTERY TEST


Battery Test
Unit of
Description Address Register Encoding
meas.
Battery test timer 150 151 s I – integer (I.e. 80 80)
Battery test ok 151 152 B - boolean (I.e. 0 false, 1 true)
Battery test failed 152 153 B - boolean (I.e. 0 false, 1 true)
Manual test stopped 153 154 B - boolean (I.e. 0 false, 1 true)
Automatic battery test stopped 154 155 B - boolean (I.e. 0 false, 1 true)

16 OML07127 REV. C