Difference between actual


Versus installed KVAR
1 Comment

Harmonic filter banks are vital components in an electric system. The primary purpose of the banks is to provide an
alternate low impedance path for harmonic current, thus reducing the amount of harmonic current in a distribution
system. When purchasing the banks, the primary consideration for the engineer is to understand the primary difference
between the actual and installed kVAR.

This article by our member Marvin M. provides a guide on the difference between the two as well as why understanding
the two distinct values is important when installing harmonic filter banks.

Understanding the Difference Between Actual Versus Installed


KVAR
For starters, note that the harmonic filter reactor does result to significant rises in voltage. About a decade ago, most
applications of low and medium voltage consisted on linear loads. This means that resonance was uncommon, and a
simple addition of capacitors did suffice as a power factor correction measure.

Nowadays, however, non-linear loads and variable speed drives are very common. These loads, which include motors,
mills, battery charging equipment and invertors introduces harmonics into the systems by generating non-sinusoidal
current from sinusoidal voltage.

Ads by
Stop seeing this ad Why this ad? 

Download &

Customize
Learn More

Chrome
Google

Engineers usually recommend a series reactor to sort out the resonance problems. Though capacitors are designed to
absorb reasonable amounts of harmonics, the peaks and excessive harmonics in an industry utilizing medium voltage
equipment can lead to voltage rise and eventual break down. This is easily expressed using the following formula.

Vrise=N²/ (N²-1)

Vrise is the voltage rise while N is Filter Bank Turning point

Application of these variables means that when the tuning point is decreased, the voltage rise increases. To
accommodate these scenarios, the capacitors used should be rated higher than the system voltage. The three primary
tuning points are detuned filters(between 4.0 and 4.4),partially tuned(4.4-4.8), and tuned filters (4.8-5.0).

Detuned filters are used primarily for power factor correction. They are the cheapest options. However, they do little
to sort out any harmonic distortion. 
Electrical Equipment
Partially tuned filters are used in cases where power factor correction is required, as well as sort out excess
Ads by Home Categories  Resources  About us  
distortion
Download
levels.
Stop seeing this ad& Why
Customize

this ad? 
Lear
Tuned harmonics are used when the sole objective is to bring down the distortion levels to acceptable levels. They
Chrome
however require precise engineering design due to the high risks associated with drawing harmonics from the
industrial and local utility system.

Harmonics Filter Bank

Harmonic Voltage Rise


As highlighted, the filter capacitor is rated lower than the nameplate rating (in most cases, the installed kVAR is 20%-40%
more than the actual kVAR output to accommodate the voltage rises). Thus, proper understanding of the following terms
comes in handy in equipment selection and installation.

Effective kVAR- the harmonic filter bank kVAR output at a specified system voltage. Ensure that you specify this value
when selecting the filter banks for installation.
Actual kVAR- installed kVAR in the filter banks. This rating is usually left for the manufacturer to specify. The
engineers on their part have to ensure that the available capacitor kVAR and the voltage rating are suitable to
optimize filter capability.

Conclusion
In conclusion, given the variables that make up an optimised and working harmonics filtering installation, the following
elements are fundamental in the final decision-making.

Harmonic filter bank tuning point


Filter bank effective kVAR
Capacitor voltage and kVAR rating
Justification for capacitor voltage determination

Marvin M.

What do you think of this guide? Would you add or correct some things?

#filter bank #harmonic filter #installed kvar

  

1 Comment

Sanjeev Kr
2017/06/27 at 8:22 am

Dear Sir,

Good day!!

How we can calculate effective kVar output of detuned filter if we have 12.5 kVar 7% detuned reactor and 15.5 kavr 480V
capacitor ?

Electrical Equipment
Ads by
Reply
Home Categories  Resources  About us  
Download & Customize
Stop seeing this ad Why this ad? 
Lear
Chrome

Ingersoll Rand SimplAir Piping


Lower Cost, Higher Performance
Expect consistent, clean air at the lowest possible operating cost. Get in touch

ingersollrand.com OPEN

Leave a Comment

Comment

Name * Email * Website

Post Comment

Copyright © 2022. Electrical Equipment.

You might also like