Air System Sizing Summary For AHU06 Sys: Appendix C - HAP Output
This document summarizes the air system sizing for AHU06 Sys which serves 1 zone covering 807.9 square feet. The central cooling coil is sized to handle a peak cooling load of 17.9 tons occurring in August when outdoor conditions are 91.5/74.9°F. The central heating coil is sized to handle a maximum load of 133.3 MBH occurring during heating. The supply fan is sized for an actual maximum airflow of 2424 CFM requiring 7.5 BHP. Outdoor ventilation is designed for 2424 CFM or 3.0 CFM/ft2.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
42 views1 page
Air System Sizing Summary For AHU06 Sys: Appendix C - HAP Output
This document summarizes the air system sizing for AHU06 Sys which serves 1 zone covering 807.9 square feet. The central cooling coil is sized to handle a peak cooling load of 17.9 tons occurring in August when outdoor conditions are 91.5/74.9°F. The central heating coil is sized to handle a maximum load of 133.3 MBH occurring during heating. The supply fan is sized for an actual maximum airflow of 2424 CFM requiring 7.5 BHP. Outdoor ventilation is designed for 2424 CFM or 3.0 CFM/ft2.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for AHU06 Sys
Project Name: jxf_lab_mech2b_ACH Appendix C - HAP Output 10/29/2003
Prepared by: psuae 07:17AM
Air System Information
Air System Name AHU06 Sys Number of zones 1 Equipment Class PKG ROOF Floor Area 807.9 ft² Air System Type SZCAV
Sizing Calculation Information
Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Calculation Months Jan to Dec Space CFM Individual peak space loads Sizing Data Calculated
Central Cooling Coil Sizing Data
Total coil load 17.9 Tons Load occurs at Aug 1600 Total coil load 214.9 MBH OA DB / WB 91.5 / 74.9 °F Sensible coil load 118.4 MBH Entering DB / WB 91.5 / 74.9 °F Coil CFM at Aug 1600 2424 CFM Leaving DB / WB 46.2 / 45.7 °F Max block CFM 2424 CFM Coil ADP 41.2 °F Sum of peak zone CFM 2399 CFM Bypass Factor 0.100 Sensible heat ratio 0.551 Resulting RH 41 % ft²/Ton 45.1 Design supply temp. 47.4 °F BTU/(hr-ft²) 266.0 Zone T-stat Check 1 of 1 OK Water flow @ 10.0 °F rise N/A Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data
Max coil load 133.3 MBH Load occurs at Des Htg Coil CFM at Des Htg 2424 CFM BTU/(hr-ft²) 164.9 Max coil CFM 2424 CFM Ent. DB / Lvg DB 11.0 / 62.0 °F Water flow @ 20.0 °F drop N/A
Supply Fan Sizing Data
Actual max CFM 2424 CFM Fan motor BHP 7.50 BHP Standard CFM 2421 CFM Fan motor kW 5.59 kW Actual max CFM/ft² 3.00 CFM/ft²