IEC Health Care Locations Presentation
IEC Health Care Locations Presentation
IEC Health Care Locations Presentation
2
2
Requirements
according to
IEC-60364
3
The differences between medical locations
3 and other types of buildings.
• Room calcifications.
4
Room classifications
4
Group 0 :
Medical location where no applied parts are
intended to be used.
Group 1 :
Medical location where discontinuity of
supply is not a threat to human life.
Group 2 :
Medical location where discontinuity (failure)
of the supply can cause danger to life.
5
Room classifications
5
Examples
6
Requirements for fault protection
6 IT-System (First fault condition)
Overview of earthing
systems and earth fault
loops
7
Requirements for fault protection
7 IT-System (Second fault condition)
Overview of earthing
systems and earth fault
loops
8
Requirements for fault protection
8
• In medical locations of Group 1 and Group 2,
the following shall apply:
1. (i) For TN, TT and IT systems, the voltage
presented between simultaneously accessible
exposed-conductive-parts and/or extraneous-
conductive-parts shall not exceed 25 V a.c.
9
Requirements for fault protection
9 3. For TN system
In final circuits of Group 1 rated up to 63 A, RCDs shall be
used.
In medical locations of Group 2 (except for the medical
IT system), RCDs shall only be used in circuits for:
(i) The supply of operating tables
(ii) X-ray units
(iii) large equipment with a rated power greater than 5 kVA.
4. For TT system
In medical locations of Group 1 and Group 2, RCDs shall be used
as protective devices .
5. For IT system
In Group 2 medical locations, an IT system shall be used for final
circuits supplying ME equipment and systems intended for life
support, surgical applications and other electrical equipment
located or that may be moved into the "patient environment" .
10
Requirements for fault protection
10
Isolation
panel
11
Requirements for fault protection
11 In each medical location of Group 1 and Group 2, supplementary
equipotential bonding shall be installed and the supplementary
bonding conductors shall be connected to the equipotential
bonding busbar for the purpose of equalizing potential differences
between the following parts, which are located or that may be
moved into the “patient environment”:
(i) Extraneous-conductive-parts
Additional (ii) Screening against electrical interference fields, if installed
(iii) Connection to conductive floor grids, if installed
protection (iv) Metal screens of isolating transformers.
12
Requirements for fault protection
12
Additional
protection
13
Typical operation room layout
13
14
Safety services
14
A power supply for safety services is required which will
maintain the supply for continuous operation for a defined
period within a pre-set changeover time.
15
Safety services
15
A power supply for safety services is required which will
maintain the supply for continuous operation for a defined
period within a pre-set changeover time.
16
Detailed requirements for safety power supply
16 services
In the event of a voltage failure on one or more line conductors
at the distribution board, a safety power supply source shall be
used and be capable of providing power for a period of at least
Power supply 3 h for the following:
sources with a (i) Luminaires of operating theatre tables
changeover (ii) ME equipment containing light sources being essential for
the application of the equipment,
period less than
(iii) Life-supporting ME equipment.
or equal to 0.5 s
The duration of 3 h may be reduced to 1 h for items (ii) and (iii)
if a power source meeting the requirements of Regulation
below is installed.
The normal power supply shall be restored within a
changeover period not exceeding 0.5 s.
17
Detailed requirements for safety power supply
17 services
The following equipment shall be connected within 15 s to a
safety power supply source capable of maintaining it for a
minimum period of 24 h, when the voltage of one or more live
conductors at the main distribution board for the safety
Power supply services has decreased by more than 10 % of the nominal
value of supply voltage :
sources with a • Safety lighting.
changeover • Selected lifts for firefighters
period less than • Ventilation systems for smoke extraction
or equal to 15 s • Paging/communication systems
• ME equipment used in Group 2 medical locations which
serves for surgical or other procedures of vital importance.
Such equipment will be defined by responsible staff
• Electrical equipment of medical gas supply including
compressed air, vacuum supply .
• Fire detection and fire alarms .
18
Detailed requirements for safety power supply
18 services
Loads other than mentioned shall be connected either
automatically or manually to a safety power supply source
capable of maintaining it for a minimum period of 24 h. This
equipment may include, for example:
Power supply
sources with a • Sterilization equipment
changeover • Technical building installations, in particular air conditioning,
period greater heating and ventilation systems, building services and waste
than 15 s disposal systems
• Cooling equipment
• Catering equipment
• Storage battery chargers.
19
Detailed requirements for safety power supply
19 services
EXAMPLE
SCHEMATIC
SLD
20
Socket-outlet circuits in Group-2 locations
20
Socket-outlets intended to supply ME equipment shall be
unswitched.
21
Lighting Design consideration
22
EXAMPLE OF RECOMMENDED LUX LEVELS
22
According to EN-12464-1
23
PATIENT ROOM LIGHTING
23
(a)
(b) (c)
24
OPERATING ROOM LIGHTING
24
The luminaire shall be arranged on the
room perimeter and shall incorporate
with the surgical light to provide the
illumination level without causing
ceiling surface glare.
25
MRI ROOM LIGHTING
25
26
MRI ROOM LIGHTING
26
-All conduits and cable trays passing through the room should be
aluminum type.
27
EXAMPLE OF MRI ROOM LIGHTING FIXTURE
27
28
GENERAL CONSIDERATIONS
28
-In examination and preparation rooms and any locations where
the patient is lying, its recommended that the lighting fixture
selected to be indirect, achieve minimum glare or the location
selected to not be in patient's direct line of sight.
29
SAFTY LIGHTING
29
In the event of mains power failure, the changeover period to
the safety services source shall not exceed 15 s. The necessary
minimum illuminance shall be provided for the following:
• Emergency lighting and exit signs
• Locations for switchgear for emergency generating sets, for
main distribution boards of the normal power supply and
for power supply for safety services
• Rooms in which essential services are intended. In each such
room at least one luminaire shall be supplied from the
power source for safety services
• Locations of central fire alarm and monitoring systems
• Rooms of Group 1 medical locations; in each such room at
least one luminaire shall be supplied from the power supply
source for safety services
• Rooms of Group 2 medical locations; a minimum of 90 % of
the lighting shall be supplied from the power source for
safety services.
30
Thank you