Analytical Research of Integrity Testing On Bore Pile
Analytical Research of Integrity Testing On Bore Pile
Analytical Research of Integrity Testing On Bore Pile
https://doi.org/10.22214/ijraset.2021.38873
International Journal for Research in Applied Science & Engineering Technology (IJRASET)
ISSN: 2321-9653; IC Value: 45.98; SJ Impact Factor: 7.429
Volume 9 Issue XI Nov 2021- Available at www.ijraset.com
Abstract: The integrity test is conducted on RCC bore pile this test is conducted as per the guidelines of ASTM D5882
respectively. This test is conducted on “Perstorp site which is located in dis -Bharuch Gujrat. In this region the Strata of soil is
soft aquifer hence to carry heavy structural load, pile foundation is best solution. The experimental study is carries out on 20
meter length of Bore pile of 600mm in diameter. This paper is based on experimental study on bore pile due to assess the pile
integrity for potential problem like cross section change, honeycombing, concrete quality, continuity etc.
I. INTRODUCTION
This experimental test is carried out at Perstorp site project of chemical production which is located in dist.-Bharuch Gujrat come in
seismic zone 3 and the geological condition of this region is soft rock aquifer having very high ground water table
Approximate of 5-10 m from ground level so, there is only pile foundation is option to Carry heavy structural load. In the paper
perform experimental study on RCC bore pile . This test is performed on 20 m depth of pile of 600 mm diameter. This test is
performed commercial corporate geo Dynamics. In this experiment all the testing procedure and equipment are as per ASTM
D5882. The report presents the result the pile integrity testing using pile integrity tester (PIT) .base on the detail available and the
site condition at the time of testing.
Refer to the typical trace for trace of the defective pile in Fig. 1b the method cannot identify the nature of defect as the wave
reflection from reduction in either elastic modulus or cross section. Thus whether the defect is necking, honeycombs, void, soil
inclusion, termite chock etc. they all are classified as a defects.
The curve after the toe response is basically a second cycle of the wave moving through the pile. If the energy of impact is sufficient
or for shorter pile length, it is possible that the wave move a few time along the pile before it dies down where I some cases, it only
completes partial second cycle. Generally the wave form after the first cycle is inconsequential for interpretation
The length is the important input in the test system which uses to compute wave speed. Typical range of wave speed for good and
consistent concrete is 3500 m/sec to 4200 m/sec and wave speed lesser than 3500 m/sec it may time likely for larger job with the
lesser quality control or low percentage reinforcement. The pile with permanent liners may have higher speed from 3800 m/sec to
4300 m/sec.
V. LIMITATION OF THE TEST SYSTEM
A. The method does not evaluate minor defect and also multiple defect inside the pile as the wave generally reflect from the first
major defect. Similarly it may be difficult to evaluate the pile integrity beyond a major bulge and in such case; it’s likely that
the pile integrity is inconclusive.
B. Although the test system can be used to evaluate length of the pile, the determination of pile length is the approximate range of
5 -10 % due to variation of concrete density. this implies that the method cannot evaluate the defect that could be present in
bottom 5-10 % of the pile shaft
C. The method does not provide information on pile capacity.
D. The test method can generally evaluate the for the pile up to an L/D ratio 45 to 50. However this also depend on the soil
resistance that may attenuate the signal and thus is a general settlement .
Sr.no Pile no. Toe Length of Wave Shaft cross section and soil changes Pile Remark
response pile from speed integrity
test (m) (m/sec)
1 PL2017A Evident 20 3950 Fairly uniform pile Shift OK -
2 PL2018A Evident 20 4200 Fairly uniform pile Shift OK -
3 PL2020A Evident 20 3700 Fairly uniform pile Shift OK -
4 PL2021A Evident 20 4000 Fairly uniform pile Shift expect bulge OK -
increases in soil resistance seem evident
around 15 m from test level
GRAPH
Photographs
Cc
VII. CONCLUSION
A. Wave speed for the pile varies generally from 3450 m/sec to 4200 m/sec and can be termed as consistent concrete quality
B. Most of the pile show bulge /increase in soil resistance around 4m to 6m from test level
C. No major defect seem evidence for all tested pile
D. Pile integrity is classified as OK based on low strain test records and subjected to above mention comment
E. This report has been prepared with the generally accepted engineering practice and the result of integrity testing as per ASTM
D5882.
REFERENCE
[1] IS 2911 (Part 4 )-2013, “Code of Practice for Design and Construction of Pile Foundation -Load Teat on Pile.
[2] GEO DYNAMICS (ISO 17025:2005 NABL Accredited & ISO 9001:20015 Regd.