Ducted Blower Split Systems: Models: MDB 075 - 500D MDB 075 - 500DR
Ducted Blower Split Systems: Models: MDB 075 - 500D MDB 075 - 500DR
Note : Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning : Moving machinery and electrical power hazard. May cause severe personal
injury or death. Disconnect and lock off power before servicing equipment.
"McQuay" is a registered trademark of McQuay International. All rights reserved throughout the world.
"Bulletin illustrations cover the general appearance of McQuay International products at the time of publication
and we reserve the right to make changes in design and construction at any time without notice."
Refrigerant Circuitry
e.g. 2 : 2 circuit
Omitted if single circuit
Model Type
R : heatpump
Omitted if Cooling
Series
D : D series
Capacity
e.g. 150 : 150,000 Btu/h
Model Name
DB : Ducted Static Blower
MC : Modular Condenser
Brand
M : McQuay
Features
Easy Maintenance
The simple design concept has provided the ease of maintenance and servicing. Access to the internal part
of the unit can be from the service panel or other side of the unit by loosening a few screws.
Only for model MDB075/100 D/DR with additional service panel from bottom
Versatility
Multiple rooms can be cooled together at the same time by using just one unit of fan coil unit.
Coil
Each coil consists of staggered rows of 3/8” OD seamless copper tubes, mechanically expanded into die-
formed corrugated aluminum fins. All coils are using aluminum fin except heatpump models which are using
hydrophilic blue fin to have better deicing during defrost cycle.
Compressor
All outdoor units are using high efficiency, refrigerant-cooled, Scroll compressor. Compressor has the
internal overload protection and supplied with crank case heater to prevent liquid migration, which can
damage compressor scroll, during off-cycle and eases start-up.
Safety Controls
Outdoor units are equipped with auto reset high pressure and low pressure cut-out and discharge thermostat
(heatpump only) to protect against compressor damage due to high head pressure and system leakage
respectively. Phase protector is used to detect for any wrong phase and phase loss during installation and
operation.
CONDENSER FAN
TYPE INDUCTION PERMANENT SPLIT CAPACITOR
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM GLASS R. ACRYL STYRENE RESIN
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36) 609.6 (24)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50 230/1/50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 550 550 923 250
MOTOR OUTPUT W 350 350 560 160
MOTOR POLES 10 12 6
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000) 3800 (1794)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 13.6 16.9 17.9 8.6
RATED INPUT POWER W 6810 9040 10200 5092
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0 74.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING R-22
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2
RATED INPUT POWER W 923 550 550 923
MOTOR OUTPUT W 560 350 350 560
MOTOR POLES 12 10 10 10
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 23.5 13.6 16.9 17.9
RATED INPUT POWER W 13300 6810 9040 10200
MAXIMUM STARTING CURRENT A 198.0 95.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 11250 6000 7500 8940
CONTROL MODULE &
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
AUTO RESET H/L PRESS
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
QUANTITY 1
BLOWER DIAMETER mm (in) 469.90 (18.50) 591.82 (23.30)
BLOWER LENGTH mm (in) 459.99 (18.11) 563.88 (22.20)
AIR FLOW L/s (CFM) 4248 (9000) 5664 (12000) 7080 (15000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 20.3 (0.8) 30.5 (1.2) 45.7 (1.8)
BLOWER PULLEY DIAMETER mm 2 SPZ250 2 SPZ315 3 SPA250
MOTOR PULLEY DIAMETER mm 2 SPZ132 2 SPZ140 3 SPA125
PULLEY TYPE 2 SPZ 3 SPA
V-BELT TYPE SPZ 1650 SPZ 1987 SPA 1900
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 10.9 14.4 20.7
NUMBER x RATED INPUT POWER W 5000 5900 11100
NUMBER x MOTOR OUTPUT W 5500 7500 11000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1 5/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 616 x 397 474 x 493 593 x 493
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 8 12
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
VOLUME m3 2.120 1.654 1.957
NET WEIGHT kg (lb) 268 (590) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x2
FIN PER INCH 16
2 2
FACE AREA m (ft ) 2.82 (30.40) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2 1.2
RATED INPUT POWER W 923 500 923
MOTOR OUTPUT W 560 350 560
MOTOR POLES 10 10 10
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 23.5 16.9 17.9
RATED INPUT POWER W 13300 9040 10200
MAXIMUM STARTING CURRENT A 198.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 11250 7500 8940
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
2 1 1
BLOWER DIAMETER mm (in) 282.70 (11.13) 394.97 (15.55)
BLOWER LENGTH mm (in) 203.20 (8.00) 381.00 (15.00)
AIR FLOW L/s (CFM) 1062 (2250) 1416 (3000) 1770 (3750)
EXTERNAL STATIC PRESSURE mmWG(inWG) 10.16 (0.40) 15.2 (0.6)
BLOWER PULLEY DIAMETER mm - - 1 SPZ 160
MOTOR PULLEY DIAMETER mm - - 1 SPZ 85
PULLEY TYPE - - 1 SPZ
V-BELT TYPE - - SPZ 760
EVAPORATOR BLOWER MOTOR
TYPE PERMANENT SPLIT CAPACITOR SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 240 / 1 / 50 415 / 3 / 50 400/3/50
NUMBER x RATED RUNNING CURRENT A 2 x 1.80 2 x 2.60 2.9 3.0
NUMBER x MOTOR OUTPUT W 2 x 233 2 x 373 1500 1420
NUMBER x RATED INPUT W 2 x 369 2 x 505 1420 950
MOTOR POLES 6 4 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE CAPILLARY TUBE
PIPE CONNECTION BRAZING FLARE VALVE
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8) 12.70 (1/2)
PIPE SIZE
GAS mm (in) 28.57 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8) 19.05 (3/4)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 399 x 385 536 x 385 508 x 581
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 850 (33.46)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 1083 (42.63) 1030 (40.55)
DEPTH (D) mm (in) 981 (38.62) 1083 (42.63) 460 (18.11)
VOLUME m3 1.654 1.654 1.957 0.678
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434) 108
NOISE LEVEL (SOUND POWER) dBA 64 64 66 61
CONDENSER COIL
TYPE CROSS FINNED TUBES HYDROPHILIC BLUE FIN
MATERIAL INNER GROOVED SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM (HYDROPHILIC BLUE FIN) ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2 3
FIN PER INCH 20 16 14
FACE AREA m2 (ft2) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38) 0.95 (10.21)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365) 113.39 (372)
CONDENSER FAN
OUTDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
BLOWER DIAMETER mm (in) 394.97 (15.55) 394.97 (15.55) 394.97 (15.55) 469.90 (18.50)
BLOWER LENGTH mm (in) 381.00 (15.00) 381.00 (15.00) 381.00 (15.00) 459.99 (18.11)
AIR FLOW L/s (CFM) 2124 (4500) 2124 (4500) 2832 (6000) 3540 (7500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 15.2 (0.6) 15.2 (0.6) 15.2 (0.6) 20.3 (0.8)
BLOWER PULLEY DIAMETER mm 1 SPZ 160 2 SPZ125 2 SPZ180
MOTOR PULLEY DIAMETER mm 1 SPZ 85 2 SPZ 75 2 SPZ95
PULLEY TYPE 1 SPZ 2 SPZ
V-BELT TYPE SPZ 760 SPZ 1150 SPZ 1400
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 3.3 3.3 5.4 7.8
MOTOR OUTPUT W 1500 1500 3000 4000
NUMBER x RATED INPUT W 1740 1740 2800 4300
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8) 12.70 (1/2) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1-5/8) 28.57 (1-1/8) 34.92 (1-3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 601 x 581 601 x 581 470 x 346 514 x 397
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3 8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 981 (38.62) 1083 (42.63)
VOLUME M3 2.12 1.654 2.056 2.675
NET WEIGHT kg (lb) 268 (590) 170 (374) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM (HYDROPHILIC BLUE FIN)
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x2 2x1 2x2
FIN PER INCH 16 20 16
2 2
FACE AREA m (ft ) 2.82 (30.40) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 86.25 (283) 87.47 (287) 111.25 (365)
CONDENSER FAN
TYPE INDUCTION
OUTDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
1
BLOWER DIAMETER mm (in) 469.90 (18.50) 591.82 (23.30)
BLOWER LENGTH mm (in) 459.99 (18.11) 563.88 (22.20)
AIR FLOW L/s (CFM) 4248 (9000) 5664 (12000) 7080 (15000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 20.3 (0.8) 30.5 (1.2) 45.7 (1.8)
BLOWER PULLEY DIAMETER mm 2 SPZ250 2 SPZ315 3 SPA250
MOTOR PULLEY DIAMETER mm 2 SPZ132 2 SPZ140 3 SPA125
PULLEY TYPE 2 SPZ 3 SPA
V-BELT TYPE SPZ 1650 SPZ 1987 SPA 1900
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 9.0 11.0 18.3
MOTOR OUTPUT W 5500 7500 11000
NUMBER x RATED INPUT W 5000 5900 11100
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1-5/8) 34.92 (1-3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 616 x 397 474 x 493 593 x 493
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 8 12
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
VOLUME M3 2.120 1.654 1.957
NET WEIGHT kg (lb) 268 (590) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED
WALL THICKNESS mm (in) 0.35 (0.013)
TUBE
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM (HYDROPHILIC BLUE FIN)
THICKNESS mm (in) 0.127 (0.005)
FIN NUMBER x ROWS 2x2
FIN PER INCH 16
FACE AREA m2 (ft2) 2.82 (30.40) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 87.47 (287) 111.25 (365)
CONDENSER FAN
TYPE INDUCTION
OUTDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
10
QUANTITY 2 1
BLOWER DIAMETER mm (in) 282.70 (11.13) 394.97 (15.55)
BLOWER LENGTH mm (in) 203.20 (8.00) 381.00 (15.00)
AIR FLOW L/s (CFM) 1218 (2580) 1529 (3240) 2029 (4300) 2360 (5000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 10.2 (0.4) 15.2 (0.6)
BLOWER PULLEY DIAMETER mm - - 1 SPZ 160
MOTOR PULLEY DIAMETER mm - - 1 SPZ 85
PULLEY TYPE - - 1 SPZ
V-BELT TYPE - - SPZ 760
EVAPORATOR BLOWER MOTOR
TYPE PERMANENT SPLIT CAPACITOR SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 240 / 1 / 50 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 2 x 1.85 2 x 2.11 2.90 3.30
NUMBER x RATED INPUT POWER W 2 x 369 2 x 505 1420 1740
NUMBER x MOTOR OUTPUT W 2 x 236 2 x 378 1500
MOTOR POLES 6 4
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 399 x 385 536 x 385 508 x 581 601 x 581
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1142 (44.96)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 1083 (42.63)
VOLUME M3 1.654 1.654 1.957 2.12
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434) 268 (590)
NOISE LEVEL (SOUND POWER) dBA 64 64 66 67
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38) 2.82 (30.40)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365) 100.27 (329)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 570 600 820
MOTOR OUTPUT W 350 560
MOTOR POLES 10 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 12.7 15.9 17.5 23.9
RATED INPUT POWER W 6772 8550 9860 13679
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0 198.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940 11250
CONTROL MODULE & AUTO
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
11
QUANTITY 1
BLOWER DIAMETER mm (in) 394.97 (15.55) 469.90 (18.50)
BLOWER LENGTH mm (in) 381.00 (15.00) 459.99 (18.11)
AIR FLOW L/s (CFM) 2360 (5000) 2832 (6000) 3540 (7500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 15.2 (0.6) 20.3 (0.8)
BLOWER PULLEY DIAMETER mm 1 SPZ 160 2 SPZ125 2 SPZ180
MOTOR PULLEY DIAMETER mm 1 SPZ 85 2 SPZ 75 2 SPZ95
PULLEY TYPE 1 SPZ 2 SPZ
V-BELT TYPE SPZ 760 SPZ 1150 SPZ 1400
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 3.3 5.40 7.80
NUMBER x RATED INPUT POWER W 1740 2800 4300
NUMBER x MOTOR OUTPUT W 1500 3000 4000
MOTOR POLES 4
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1 1/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 601 x 581 470 x 346 514 x 397
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3 8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
VOLUME M3 1.654 2.056 2.675
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 64 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
FACE AREA m2 (ft2) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2
RATED INPUT POWER W 600 820
MOTOR OUTPUT W 350 560
MOTOR POLES 10 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 12.7 15.9 17.5
RATED INPUT POWER W 6772 8550 9860
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940
OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
12
QUANTITY 1
BLOWER DIAMETER mm (in) 469.90 (18.50) 591.82 (23.30)
BLOWER LENGTH mm (in) 459.99 (18.11) 563.88 (22.20)
AIR FLOW L/s (CFM) 4248 (9000) 5664 (12000) 7080 (15000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 20.3 (0.8) 30.5 (1.2) 45.7 (1.8)
BLOWER PULLEY DIAMETER mm 2 SPZ250 2 SPZ315 3 SPA250
MOTOR PULLEY DIAMETER mm 2 SPZ132 2 SPZ140 3 SPA125
PULLEY TYPE 2 SPZ 3 SPA
V-BELT TYPE SPZ 1650 SPZ 1987 SPA 1900
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 9.0 11.0 18.3
NUMBER x RATED INPUT POWER W 5000 5900 11100
NUMBER x MOTOR OUTPUT W 5500 7500 11000
MOTOR POLES 4
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1 5/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 616 x 397 474 x 493 593 x 493
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 8 12
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
VOLUME M3 2.120 1.654 1.957
NET WEIGHT kg (lb) 268 (590) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x2
FIN PER INCH 16
FACE AREA m2 (ft2) 2.82 (30.40) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2 1.2 1.2
RATED INPUT POWER W 820 600 820
MOTOR OUTPUT W 560 350 560
MOTOR POLES 10 10 10
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
.
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380-415 / 3 / 50
RATED RUNNING CURRENT A 23.9 15.9 17.5
RATED INPUT POWER W 13679 8550 9860
MAXIMUM STARTING CURRENT A 198.0 125.0 110.0
COMPRESSOR MOTOR OUTPUT W 11250 7500 8940
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
13
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
14
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
15
1
BLOWER DIAMETER mm (in) 469.90 (18.50) 591.82 (23.30)
BLOWER LENGTH mm (in) 459.99 (18.11) 563.88 (22.20)
AIR FLOW L/s (CFM) 4248 (9000) 5664 (12000) 7080 (15000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 20.3 (0.8) 30.5 (1.2) 45.7 (1.8)
BLOWER PULLEY DIAMETER mm 2 SPZ250 2 SPZ315 3 SPA250
MOTOR PULLEY DIAMETER mm 2 SPZ132 2 SPZ140 3 SPA125
PULLEY TYPE 2 SPZ 3 SPA
V-BELT TYPE SPZ 1650 SPZ 1987 SPA 1900
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 9.0 11.0 18.3
MOTOR OUTPUT W 5500 7500 11000
NUMBER x RATED INPUT W 5000 5900 11100
MOTOR POLES 4
REFRIGERANT
TYPE R407C
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1-5/8) 34.92 (1-3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 616 x 397 474 x 493 593 x 493
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 8 12
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
VOLUME M3 2.120 1.654 1.957
NET WEIGHT kg (lb) 268 (590) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED
WALL THICKNESS mm (in) 0.35 (0.013)
TUBE
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM (HYDROPHILIC BLUE FIN)
THICKNESS mm (in) 0.127 (0.005)
FIN NUMBER x ROWS 2x2
FIN PER INCH 16
FACE AREA m2 (ft2) 2.82 (30.40) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 87.47 (287) 111.25 (365)
CONDENSER FAN
TYPE INDUCTION
OUTDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
16
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 3.1 3.1 2.2
RATED INPUT POWER W 594 625 728
MOTOR OUTPUT W 350 350 450
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 20.7 32.1 42.0 47.0
RATED INPUT POWER W 6280 8170 10870 12420
MAXIMUM STARTING CURRENT A 95.0 203.0 247.0 245.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750 8940
CONTROL MODULE & AUTO
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SW
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
17
QUANTITY 1
BLOWER DIAMETER mm (in) 394.97 (15.55) 469.90 (18.50)
BLOWER LENGTH mm (in) 381.00 (15.00) 459.99 (18.11)
AIR FLOW L/s (CFM) 2124 (4500) 2832 (6000) 3540 (7500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 15.2 (0.6) 20.3 (0.8)
BLOWER PULLEY DIAMETER mm 1 SPZ 160 2 SPZ125 2 SPZ180
MOTOR PULLEY DIAMETER mm 1 SPZ 85 2 SPZ 75 2 SPZ95
PULLEY TYPE 1 SPZ 2 SPZ
V-BELT TYPE SPZ 760 SPZ 1150 SPZ 1400
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 5.9 9.7 14.0
NUMBER x RATED INPUT POWER W 1681 2744 4303
NUMBER x MOTOR OUTPUT W 1500 3000 4000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1 1/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 601 x 581 470 x 346 514 x 397
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3 8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
VOLUME M3 1.654 2.056 2.675
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 64 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 3.1 3.1 2.2
RATED INPUT POWER W 594 625 728
MOTOR OUTPUT W 350 350 450
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 20.7 32.1 42.0
RATED INPUT POWER W 6280 8170 10870
MAXIMUM STARTING CURRENT A 95.0 203.0 247.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750
OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
18
QUANTITY 1
BLOWER DIAMETER mm (in) 469.90 (18.50) 591.82 (23.30)
BLOWER LENGTH mm (in) 459.99 (18.11) 563.88 (22.20)
AIR FLOW L/s (CFM) 4248 (9000) 5664 (12000) 7080 (15000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 20.3 (0.8) 30.5 (1.2) 45.7 (1.8)
BLOWER PULLEY DIAMETER mm 2 SPZ250 2 SPZ315 3 SPA250
MOTOR PULLEY DIAMETER mm 2 SPZ132 2 SPZ140 3 SPA125
PULLEY TYPE 2 SPZ 3 SPA
V-BELT TYPE SPZ 1650 SPZ 1987 SPA 1900
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 16.0 20.9 32.8
NUMBER x RATED INPUT POWER W 4948 6164 11049
NUMBER x MOTOR OUTPUT W 5000 5500 11000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1 5/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 616 x 397 474 x 493 593 x 493
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 8 12
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
VOLUME M3 2.120 1.654 1.957
NET WEIGHT kg (lb) 268 (590) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x2
FIN PER INCH 16
2 2
FACE AREA m (ft ) 2.82 (30.40) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 3.1 3.1 2.2
RATED INPUT POWER W 625 625 728
MOTOR OUTPUT W 350 350 450
MOTOR POLES 12
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 220 / 3 / 60
RATED RUNNING CURRENT A 47.0 32.1 42.0
RATED INPUT POWER W 12420 8170 10870
MAXIMUM STARTING CURRENT A 245.0 203.0 247.0
COMPRESSOR MOTOR OUTPUT W 8940 7500 9750
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
19
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 1.6 1.6 1.1
RATED INPUT POWER W 606 638 777
MOTOR OUTPUT W 360 360 460
MOTOR POLES 12
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 10.0 16.4 19.2 19.6
RATED INPUT POWER W 6280 8170 10870 12420
MAXIMUM STARTING CURRENT A 74.0 95.0 125.0 125.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 9750 8940
CONTROL MODULE & AUTO
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
RESET H/L PRESS. SW
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
20
QUANTITY 1
BLOWER DIAMETER mm (in) 394.97 (15.55) 469.90 (18.50)
BLOWER LENGTH mm (in) 381.00 (15.00) 459.99 (18.11)
AIR FLOW L/s (CFM) 2124 (4500) 2832 (6000) 3540 (7500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 15.2 (0.6) 20.3 (0.8)
BLOWER PULLEY DIAMETER mm 1 SPZ 160 2 SPZ125 2 SPZ180
MOTOR PULLEY DIAMETER mm 1 SPZ 85 2 SPZ 75 2 SPZ95
PULLEY TYPE 1 SPZ 2 SPZ
V-BELT TYPE SPZ 760 SPZ 1150 SPZ 1400
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 2.9 4.7 6.7
NUMBER x RATED INPUT POWER W 1711 2771 4305
NUMBER x MOTOR OUTPUT W 1500 3000 4000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 28.57 (1 1/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 601 x 581 470 x 346 514 x 397
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3 8
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 981 (38.62) 981 (38.62) 1083 (42.63)
VOLUME M3 1.654 2.056 2.675
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 64 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2
FIN PER INCH 20 16
2 2
FACE AREA m (ft ) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY
OUTDOOR UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
21
QUANTITY 1
BLOWER DIAMETER mm (in) 469.90 (18.50) 591.82 (23.30)
BLOWER LENGTH mm (in) 459.99 (18.11) 563.88 (22.20)
AIR FLOW L/s (CFM) 4248 (9000) 5664 (12000) 7080 (15000)
EXTERNAL STATIC PRESSURE mmWG(inWG) 20.3 (0.8) 30.5 (1.2) 45.7 (1.8)
BLOWER PULLEY DIAMETER mm 2 SPZ250 2 SPZ315 3 SPA250
MOTOR PULLEY DIAMETER mm 2 SPZ132 2 SPZ140 3 SPA125
PULLEY TYPE 2 SPZ 3 SPA
V-BELT TYPE SPZ 1650 SPZ 1987 SPA 1900
EVAPORATOR BLOWER MOTOR
TYPE SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
NUMBER x RATED RUNNING CURRENT A 7.7 10.0 15.7
NUMBER x RATED INPUT POWER W 4949 6162 11077
NUMBER x MOTOR OUTPUT W 5000 5500 11000
MOTOR POLES 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 15.88 (5/8)
PIPE SIZE
GAS mm (in) 41.28 (1 5/8) 34.92 (1 3/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 616 x 397 474 x 493 593 x 493
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 8 12
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
DEPTH (D) mm (in) 1083 (42.63) 981 (38.62) 1083 (42.63)
VOLUME M3 2.120 1.654 1.957
NET WEIGHT kg (lb) 268 (590) 184 (405) 197 (434)
NOISE LEVEL (SOUND POWER) dBA 67 64 66
CONDENSER COIL
TYPE CROSS FINNED TUBES
MATERIAL INNER GROOVED SEAMLESS COPPER INNER GROOVED
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x2
FIN PER INCH 16
2 2
FACE AREA m (ft ) 2.82 (30.40) 2.26 (24.38) 2.54 (27.38)
FACE VELOCITY m/min (FPM) 100.27 (329) 87.47 (287) 111.25 (365)
OUTDOOR UNIT
CONDENSER FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 914.40 (36) 812.80 (32) 914.40 (36)
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 1.6 1.6 1.1
RATED INPUT POWER W 638 638 777
MOTOR OUTPUT W 360 360 460
MOTOR POLES 12
AIR FLOW L/s (CFM) 4720 (10000) 3304 (7000) 4720 (10000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 460 / 3 / 60
RATED RUNNING CURRENT A 16.4 16.4 19.2
RATED INPUT POWER W 8170 8170 10870
MAXIMUM STARTING CURRENT A 95.0 95.0 125.0
COMPRESSOR MOTOR OUTPUT W 7500 7500 9750
CONTROL MODULE AND OVERLOAD PROTECTION AND
PROTECTION DEVICE
AUTO RESET H/L PRESS. SW. AUTO RESET HIGH/LOW PRESSURE SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
22
QUANTITY 2 1
BLOWER DIAMETER mm (in) 282.70 (11.13) 394.97 (15.55)
BLOWER LENGTH mm (in) 203.20 (8.00) 381.00 (15.00)
AIR FLOW L/s (CFM) 1062 (2250) 1416 (3000) 1770 (3750) 2124 (4500) 2124 (4500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 18.3 (0.72) 25.4 (1.0) 25.4 (1.0) 25.4 (1.0) 25.4 (1.0)
BLOWER PULLEY DIAMETER mm - - 1 SPZ 150 1 SPZ 150 1 SPZ 150
MOTOR PULLEY DIAMETER mm - - 1 SPZ 85 1 SPZ 85 1 SPZ 85
PULLEY TYPE - - 1 SPZ 1 SPZ 1 SPZ
V-BELT TYPE - - SPZ 760 SPZ 760 SPZ 760
INDOOR BLOWER MOTOR
TYPE PERMANENT SPLIT CAPACITOR SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 240 / 1 / 50 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 2 x 2.6 2 x 3.7 3.7 3.8 3.8
NUMBER x RATED INPUT POWER W 2 x 603 2 x 866 1590 1870 1870
NUMBER x MOTOR OUTPUT W 2 x 400 2 x 480 2200 2200 2200
MOTOR POLES 4 4 4 4 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 12.70 (1/2)
PIPE SIZE
GAS mm (in) 28.57 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8) 28.57 (1-1/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 399 x 385 536 x 385 508 x 581 601 x 581 601 x 581
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 1083 (42.63) 1083 (42.63) 981 (38.62)
DEPTH (D) mm (in) 981 (38.62) 1083 (42.63) 1083 (42.63) 981 (38.62)
VOLUME m3 1.654 1.957 2.120 1.654
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434) 268 (590) 170 (374)
GROSS WEIGHT kg (lb) 218 (480) 232 (511) 252 (555) 330 (727) 218 (480)
NOISE LEVEL (SOUND POWER) dBA 64 64 66 67 64
OUTDOOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER SEAMLESS INNER GROOVED COPPER SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2 2x2 2x2 2x1
FIN PER INCH 20 16 16 16 20
FACE AREA m 2 (ft2) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38) 2.82 (30.40) 2.29 (24.72)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365) 100.27 (329) 86.25 (283)
OUTDOOR UNIT
OUTDOOR FAN
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36) 812.20 (32)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2
RATED INPUT POWER W 570 600 820 820 570
MOTOR OUTPUT W 350 350 560 560 350
MOTOR POLES 10 10 12 12 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000) 3304 (7000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380 - 415 / 3 / 50
RATED RUNNING CURRENT A 13.6 16.9 16.4 23.0 13.6
RATED INPUT POWER W 6457 7970 9173 12684 6457
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0 198.0 95.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940 11250 6000
CTRL MODULE & AUTO RESET O/L P & AUTO RESET H/L
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
H/L PRESS. SWITCH PRESS. SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
23
QUANTITY 2 1
BLOWER DIAMETER mm (in) 282.70 (11.13) 394.97 (15.55)
BLOWER LENGTH mm (in) 203.20 (8.00) 381.00 (15.00)
AIR FLOW L/s (CFM) 1062 (2250) 1416 (3000) 1770 (3750) 2124 (4500) 2124 (4500)
EXTERNAL STATIC PRESSURE mmWG(inWG) 18.3 (0.72) 25.4 (1.0) 25.4 (1.0) 25.4 (1.0) 25.4 (1.0)
BLOWER PULLEY DIAMETER mm - - 1 SPZ 150 1 SPZ 150 1 SPZ 150
MOTOR PULLEY DIAMETER mm - - 1 SPZ 85 1 SPZ 85 1 SPZ 85
PULLEY TYPE - - 1 SPZ 1 SPZ 1 SPZ
V-BELT TYPE - - SPZ 760 SPZ 760 SPZ 760
INDOOR BLOWER MOTOR
TYPE PERMANENT SPLIT CAPACITOR SQUIRREL CAGE INDUCTION
POWER SUPPLY V / Ph / Hz 240 / 1 / 50 415 / 3 / 50
NUMBER x RATED RUNNING CURRENT A 2 x 2.6 2 x 3.7 3.7 3.8 3.8
NUMBER x RATED INPUT POWER W 2 x 603 2 x 866 1590 1870 1870
NUMBER x MOTOR OUTPUT W 2 x 400 2 x 480 2200 2200 2200
MOTOR POLES 4 4 4 4 4
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
PIPE CONNECTION BRAZING
LIQUID mm (in) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 12.70 (1/2)
PIPE SIZE
GAS mm (in) 28.57 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8) 28.57 (1-1/8)
DRAIN PIPE CONNECTION mm (in) 25.40 (1.00)
AIR FILTER
TYPE AAF R15
LENGTH x HEIGHT mm 399 x 385 536 x 385 508 x 581 601 x 581 601 x 581
SIZE
DEPTH mm (in) 50.8 (2.00)
QUANTITY 3
MATERIAL ELECTRO GALVANISED MILD STEEL
CASING
FINISHING EPOXY POLYESTER POWDER
HEIGHT (H) mm (in) 1041 (40.98) 1142 (44.96) 1041 (40.98)
DIMENSION WIDTH (W) mm (in) 981 (38.62) 1083 (42.63) 1083 (42.63) 981 (38.62)
DEPTH (D) mm (in) 981 (38.62) 1083 (42.63) 1083 (42.63) 981 (38.62)
VOLUME m3 1.654 1.957 2.120 1.654
NET WEIGHT kg (lb) 170 (374) 184 (405) 197 (434) 268 (590) 170 (374)
GROSS WEIGHT kg (lb) 218 (480) 232 (511) 252 (555) 330 (727) 218 (480)
NOISE LEVEL (SOUND POWER) dBA 64 64 66 67 64
OUTDOOR COIL
TYPE CROSS FINNED TUBES
MATERIAL SEAMLESS COPPER SEAMLESS INNER GROOVED COPPER SEAMLESS COPPER
TUBE WALL THICKNESS mm (in) 0.35 (0.013)
OUTER DIAMETER mm (in) 9.52 (3/8)
MATERIAL ALUMINIUM
THICKNESS mm (in) 0.127 (0.005)
FIN
NUMBER x ROWS 2x1 2x2 2x2 2x2 2x1
FIN PER INCH 20 16 16 16 20
FACE AREA m2 (ft2) 2.29 (24.72) 2.26 (24.38) 2.54 (27.38) 2.82 (30.40) 2.29 (24.72)
FACE VELOCITY m/min (FPM) 86.25 (283) 87.47 (287) 111.25 (365) 100.27 (329) 86.25 (283)
OUTDOOR FAN
OUTDOOR UNIT
TYPE INDUCTION
DRIVE PROPELLER / DIRECT
BLADE MATERIAL ALUMINIUM
BLADE DIAMETER mm (in) 812.80 (32) 914.40 (36) 812.20 (32)
POWER SUPPLY V / Ph / Hz 415 / 3 / 50
RATED RUNNING CURRENT A 1.2
RATED INPUT POWER W 570 600 820 820 570
MOTOR OUTPUT W 350 350 560 560 350
MOTOR POLES 10 10 12 12 10
AIR FLOW L/s (CFM) 3304 (7000) 4720 (10000) 3304 (7000)
COMPRESSOR
TYPE SCROLL COMPRESSOR
POWER SUPPLY V / Ph / Hz 380 - 415 / 3 / 50
RATED RUNNING CURRENT A 13.6 16.9 16.4 23.0 13.6
RATED INPUT POWER W 6457 7970 9173 12684 6457
MAXIMUM STARTING CURRENT A 95.0 125.0 110.0 198.0 95.0
COMPRESSOR MOTOR OUTPUT W 6000 7500 8940 11250 6000
OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE CTRL MODULE & AUTO RESET O/L P & AUTO RESET H/L
PROTECTION DEVICE
SWITCH H/L PRESS. SWITCH PRESS. SWITCH
STAGE OF CAPACITY CONTROL ON / OFF
STARTER TYPE DOL
REFRIGERANT
TYPE R22
TYPE OF GAS PRECHARGED NITROGEN HOLDING
CONTROL DEVICE THERMOSTATIC EXPANSION VALVE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO 26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO 26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB OUTDOOR
24
25
26
27
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
28
29
30
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula
below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
31
REGION
FROST
SC 14.825 14.719 14.614 14.508 14.265 14.046
-5.0 TC 16.912 16.760 16.609 16.457 16.229 16.025
SC 16.912 16.760 16.609 16.457 16.229 16.025
6.0 TC 22.649 23.404 24.158 24.912 23.098 21.466
SC 22.649 23.404 24.158 24.912 23.098 21.466
12.0 TC 25.779 25.549 25.319 25.089 24.744 24.434
SC 25.779 25.549 25.319 25.089 24.744 24.434
15.0 TC 27.344 27.100 26.856 26.612 26.247 25.918
SC 27.344 27.100 26.856 26.612 26.247 25.918
18.3 TC 29.065 28.806 28.547 28.288 27.899 27.550 1.106
SC 29.065 28.806 28.547 28.288 27.899 27.550 1.106
REGION
FROST
SC 20.265 20.105 19.944 19.783 19.476 19.200
-5.0 TC 23.208 23.000 22.792 22.584 22.272 21.991
SC 23.208 23.000 22.792 22.584 22.272 21.991
6.0 TC 31.301 31.223 31.145 31.067 30.329 29.666
SC 31.301 31.223 31.145 31.067 30.329 29.666
12.0 TC 35.716 35.397 35.079 34.760 34.282 33.852
SC 35.716 35.397 35.079 34.760 34.282 33.852
15.0 TC 37.923 37.585 37.247 36.909 36.401 35.945
SC 37.923 37.585 37.247 36.909 36.401 35.945
18.3 TC 40.351 39.991 39.632 39.272 38.733 38.247
SC 40.351 39.991 39.632 39.272 38.733 38.247
32
REGION
FROST
SC 23.331 23.077 22.822 22.567 22.324 22.105
-5.0 TC 27.116 26.873 26.630 26.387 26.022 25.694
SC 27.116 26.873 26.630 26.387 26.022 25.694
6.0 TC 37.525 36.447 35.369 34.291 34.961 35.564
SC 37.525 36.447 35.369 34.291 34.961 35.564
12.0 TC 43.202 42.817 42.431 42.046 41.468 40.948
SC 43.202 42.817 42.431 42.046 41.468 40.948
15.0 TC 46.041 45.630 45.220 44.809 44.193 43.639
SC 46.041 45.630 45.220 44.809 44.193 43.639
18.3 TC 49.163 48.725 48.287 47.849 47.192 46.600 1.106
SC 49.163 48.725 48.287 47.849 47.192 46.600 1.106
REGION
FROST
SC 29.415 28.891 28.367 27.843 27.857 27.869
-5.0 TC 35.344 35.027 34.711 34.394 33.919 33.491
SC 35.344 35.027 34.711 34.394 33.919 33.491
6.0 TC 51.649 50.063 48.478 46.893 47.976 48.950
SC 51.649 50.063 48.478 46.893 47.976 48.950
12.0 TC 60.542 60.002 59.462 58.922 58.112 57.383
SC 60.542 60.002 59.462 58.922 58.112 57.383
15.0 TC 64.989 64.409 63.830 63.250 62.381 61.599
SC 64.989 64.409 63.830 63.250 62.381 61.599
18.3 TC 69.880 69.257 68.634 68.012 67.078 66.237
SC 69.880 69.257 68.634 68.012 67.078 66.237
33
REGION
FROST
SC 40.401 40.074 39.747 39.420 38.819 38.278
-5.0 TC 46.306 45.891 45.476 45.060 44.438 43.877
SC 46.306 45.891 45.476 45.060 44.438 43.877
6.0 TC 62.544 62.408 62.271 62.134 60.630 59.276
SC 62.544 62.408 62.271 62.134 60.630 59.276
12.0 TC 71.402 70.765 70.128 69.491 68.535 67.675
SC 71.402 70.765 70.128 69.491 68.535 67.675
15.0 TC 75.830 75.154 74.478 73.802 72.788 71.875
SC 75.830 75.154 74.478 73.802 72.788 71.875
18.3 TC 80.702 79.983 79.264 78.544 77.466 76.495 1.106
SC 80.702 79.983 79.264 78.544 77.466 76.495 1.106
REGION
FROST
SC 46.138 45.510 44.883 44.256 43.970 43.713
-5.0 TC 54.328 53.841 53.354 52.867 52.137 51.479
SC 54.328 53.841 53.354 52.867 52.137 51.479
6.0 TC 76.852 76.635 76.418 76.202 74.430 72.836
SC 76.852 76.635 76.418 76.202 74.430 72.836
12.0 TC 89.137 88.342 87.547 86.752 85.559 84.486
SC 89.137 88.342 87.547 86.752 85.559 84.486
15.0 TC 95.280 94.430 93.581 92.731 91.457 90.310
SC 95.280 94.430 93.581 92.731 91.457 90.310
18.3 TC 102.037 101.128 100.218 99.309 97.945 96.717
SC 102.037 101.128 100.218 99.309 97.945 96.717
34
REGION
FROST
SC 80.802 80.148 79.494 78.839 77.637 76.555
-5.0 TC 92.612 91.782 90.951 90.121 88.875 87.754
SC 92.612 91.782 90.951 90.121 88.875 87.754
6.0 TC 125.089 124.815 124.541 124.267 121.259 118.552
SC 125.089 124.815 124.541 124.267 121.259 118.552
12.0 TC 142.804 141.530 140.256 138.982 137.071 135.351
SC 142.804 141.530 140.256 138.982 137.071 135.351
15.0 TC 151.661 150.309 148.956 147.604 145.576 143.750
SC 151.661 150.309 148.956 147.604 145.576 143.750
18.3 TC 161.404 159.966 158.527 157.089 154.931 152.989 1.106
SC 161.404 159.966 158.527 157.089 154.931 152.989 1.106
REGION
FROST
SC 91.985 90.729 89.474 88.218 87.656 87.150
-5.0 TC 108.340 107.369 106.398 105.427 103.970 102.659
SC 108.340 107.369 106.398 105.427 103.970 102.659
6.0 TC 153.317 153.013 152.078 152.403 148.668 145.307
SC 153.317 153.013 152.078 152.403 148.668 145.307
12.0 TC 177.850 176.264 174.677 173.091 170.711 168.570
SC 177.850 176.264 174.677 173.091 170.711 168.570
15.0 TC 190.177 188.422 186.727 185.032 182.489 180.201
SC 190.177 188.422 186.727 185.032 182.489 180.201
18.3 TC 203.610 201.796 199.981 198.167 195.445 192.995
SC 203.610 201.796 199.981 198.167 195.445 192.995
35
36
37
38
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the
formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
39
40
41
42
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the
formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
43
44
45
46
MDB – D/DR Series Sound Power Level (Duct Discharge Sound Power Level)
1/1 Octave Sound Power (dB), ref 1pW
Model A (dBA) **
63 125 250 500 1k 2k 4k 8k
MDB075 D/DR 70 72 73 71 68 65 61 56 73
MDB100 D/DR 72 74 74 73 70 67 63 58 75
MDB125 D/DR 73 75 76 75 72 69 65 60 77
MDB150 D/DR 75 77 78 77 74 71 67 62 79
MDB200 D/DR 82 83 84 83 81 77 73 68 85
MDB250 D/DR 84 85 86 85 83 79 75 70 87
MDB300 D/DR 86 87 88 87 85 81 77 72 89
MDB400 D/DR 87 88 89 88 86 82 78 73 90
MDB500 D/DR 93 94 95 94 92 88 84 79 96
Remark
All sound power level are measured under ISO3741 Standard.
** A is the overall sound power level in dBA
The spectrum data is non-A-weighted sound power level
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
Cooling only
Cooling
54
HIGH AMBIENT
Caution :
UNIT
46
Outdoor temp. (°CDB)
-5
15 24
Indoor temp. (°CWB)
Heat pump
Heating Cooling
54
18 HIGH AMBIENT
UNIT
46
Outdoor temp. (°CWB)
35
STD
6
STD
19
LOW AMBIENT
KIT
-9
-5
15 21 27 15 24
Indoor temp. (°CDB) Indoor temp. (°CWB)
66
In order to obtain 850 RPM, we calculate the new blower pulley as:
We thus need to change the blower pulley from 180 mm to 160 mm in order to obtain the higher
operating static pressure.
Step 4: When the pulley is changed, the V-belt length must be rechecked. We have for horizontal air throw
configuration:
V-belt length, L = 2C + 1.57 (Db + Dm)
= (2 x 580) + 1.57(95 + 160)
= 1560.35 mm
We thus can use a belt with a length of 1600 mm.
By applying a safety factor of 1.2 to account for losses, we calculate that the motor power input
requirement should be = 2.7 x 1.2 = 3.24 kW
Thus, the existing motor is still sufficient to drive the blower with the smaller 160 mm pulley.
Summary:
i) Fan motor kW = 4.0 kW
ii) Blower pulley diameter = 160 mm
iii) V-belt size = 1600 mm
67
MDB250DBLOWER
ADB250D BLOWERPERFORMANCE
PERFORMANCE CURVE
CURVE
70
65
3kW
2kW 5kW
60
55 r
1.5kW
50
Total static pressure, mmAq
46.5 r
45 H
900RPM
40
35
30
26.0 r 800RPM
25
20
700RPM
15
10 INTERNAL
STATIC
WITH FILTER
CFM
5
0
0 2500 5000 7500 10000 12500 15000
Flowrate
68
1 MOTOR
Output kW 1.5 1.5 3.0 4.0 5.5 7.5 11.0
Rated Current at 415V/3PH/50Hz A 3.39 3.39 6.15 8.00 10.90 14.40 20.70
Shaft Size mm 24 24 28 28 38 38 42
2 Blower Pulley Size mm 1SPZ160 1SPZ160 2SPZ125 2SPZ180 2SPZ250 2SPZ315 3SPA250
3 Air Flow CFM 3,750 4,500 6,000 7,500 9,000 12,000 15,000
4 Motor to Blower Centre Point mm 180 180 515 580 615 780 820
Horinzontal Air Discharge V-Belt Size mm SPZ760 SPZ760 SPZ1362 SPZ1600 SPZ1850 SPZ2287 SPA2240
5 Motor to Blower Centre Point mm NIL NIL 410 480 495 630 650
Vertical Air Discharge V-Belt Size mm NIL NIL SPZ1150 SPZ1400 SPZ1600 SPZ1987 SPA1900
9 Blower Wheel Model AT15-15S AT15-15S AT15-15S AT18-18S AT18-18S AT22-22TIC AT22-22TIC
10 Coil Velocity FPM 388 391 389 392 393 385 385
11 External Static inch 0.60 0.60 0.60 0.80 0.80 0.80 1.00
1 MOTOR
Output kW 1.5 1.5 3.0 4.0 5.5 7.5 11.0
Rated Current at 415V/3PH/50Hz A 6.10 6.10 11.10 14.40 19.40 27.40 37.10
Shaft Size mm 24 24 28 28 38 38 42
2 Blower Pulley Size mm 1SPZ200 1SPZ200 2SPZ250 2SPZ250 2SPZ250 2SPA315 3SPA280
3 Air Flow CFM 3,750 4,500 6,000 7,500 9,000 12,000 15,000
4 Motor to Blower Centre Point mm 180 180 510 570 615 780 825
Horinzontal Air Discharge V-Belt Size mm SPZ825 SPZ825 SPZ1600 SPZ1700 SPZ1800 SPA2240 SPA2282
5 Motor to Blower Centre Point mm NIL NIL 410 470 450 610 635
Vertical Air Discharge V-Belt Size mm NIL NIL SPZ1400 SPZ1500 SPZ1550 SPA1907 SPA1907
9 Blower Wheel Model AT15-15S AT15-15S AT15-15S AT18-18S AT18-18S AT22-22TIC AT22-22TIC
10 Coil Velocity FPM 388 391 389 392 393 385 385
11 External Static inch 0.60 0.60 0.60 0.80 0.80 0.80 1.00
69
70
71
72
73
74
65
60
L/s
75
76
77
78
79
80
81
82
NOTE :
1) WITH TORIN BLOWER
2) WITH U1.4 CCT SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
NOTE :
1) WITH TORIN BLOWER
2) WITH U1.4 CCT SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
83
NOTE :
1) WITH TORIN BLOWER
2) WITH U1-125 SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
NOTE :
1) WITH TORIN BLOWER
2) WITH U1-125 SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
84
NOTE :
1) WITH TORIN BLOWER
2) WITH U1-125 SLM EC CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
NOTE :
1) WITH TORIN BLOWER
2) WITH SEQUENTIAL CONTROLLER
3) FOR LOCAL AND EXPORT SPEC.
85
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL DISCHARGE
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
86
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
87
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
88
89
90
91
92
MODEL : MDB 100D vs MMC 100D (WITH U1.4 MAINBOARD AND SLM3 HANDSET)
93
MODEL : MDB 150D vs. MMC 150D (WITH U1-125 MAINBOARD AND SLM3 HANDSET)
94
95
96
MODEL : MDB 100DR vs. MMC 100DR (WITH U1.4 / SLM3 HANDSET)
97
MODEL : MDB 150DR vs. MMC 150DR (WITH U1-125 SLM3 HANDSET)
98
99
100
101
102
103
MOUNTING
a) For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum.
Ensure that overhead supports are strong enough to hold the unit’s weight. Position hanger rods and
check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level
in two horizontal directions.
PIPINGS
Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed or
had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do
not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquid
line into fittings.
OPERATIONAL CHECK
After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operating
properly. Check that:
a) Condenser fans are running, with warm air blowing off the condenser coil.
b) Evaporator blowers are running and discharging cool air.
c) Suction line inside condensing unit feels cool.
d) Liquid line inside condensing unit feels warm.
ELECTRICAL CONNECTION
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for
field wiring regulations and ensure that these are complied with. Besides, observe the following general
precautions:
a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work.
b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.
d) All wiring must be firmly connected.
e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan
motors.
104
a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be
drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the
unit.
b) Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacle which block air
intake or discharge.
c) The location must be well ventilated, so that the unit can draw and distribute plenty of air thus lowering
the condensing temperature.
d) A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
e) A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
f) A place where the hot air discharge and operating sound level will not annoy the neighbours.
g) The location must not be susceptible to dust or oil mist.
CAUTION:If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such substances
may lead to failure of the unit.
105
a) Liquid loops or oil traps must be provided according to the position of the outdoor and the indoor units (depending on
whether the indoor unit is above or below the outdoor unit).
b) Field supplied filter dryer should be provided as close to the expansion valve(s) of the indoor unit (evaporator) as
possible.
c) Field supplied sight glass must be assembled and mounted next to filter dryer.
Always choose the shortest piping path and follow the recommendations as shown below :
CAUTION:
1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height, length and/or the
number of bends of the refrigerant piping system installed is beyond the limit above.
2) Bendings must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe as far as
possible.
INSTALLATION CLEARANCE
A) For MMC – D/DR series (Single/Multiple Condensing Unit)
When two or more outdoor units are installed in a location, they must be positioned such that one unit will not be taking
the hot discharge air from another to avoid hot air short circuiting.
This also applies when two or more units are installed one above the other. Below are the installation clearance
guidelines :
2x 3x 4x
Model MMC 075/100/125/150D/DR
MMC 075/100/125/150D/DR MMC 075/100/125/150D/DR MMC 075/100/125/150D/DR
A (mm) 300 600 600 600
B (mm) 1000 1000 1000 1000
C (mm) 1500 1500 2000 2000
106
INSTALLATION CLEARANCE
VACUUMING
After the system pipings are properly connected, connect the
flexible hoses to the correct charging nipples as shown in the
diagrams. Ensure that flexible hose from charging nipples are
connected to vacuum pump via standard servicing valves and
pressure gauges (gauge manifold). Vacuum the air conditioner
system to at least 500 microns Hg.
CHARGING
Before charging, the vacuum must be held at 500 microns Hg
for at least 15 minutes, then break vacuum by charging R-22
refrigerant. Operate the unit for 15 minutes and ensure that
refrigerant charges is of correct quantity by monitoring running
current and suction and liquid line pressures. Suction and
discharge pipe pressures should be in the region of 75 psig
and 275 psig generally.
107
Other typical field charging problems include undercharging, overcharging, moisture or air in the system etc.
In time each one of these problems can cause compressor failure.
EQUIPMENT
Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory job
is:-
Set of service gauges
Hoses
Vacuum pump
Vacuum gauge
Scales
Thermometer
CHARGING HOSES
Most field-charging is done using standard service hoses. Hoses are made in different colors with different
working pressures and with different leak rates but the most important point is the presence or absence of
Shredder valve depressors. Shredder valve depressors severely restrict the flow through the service hoses.
This slows evacuation and vapor charging dramatically. In most cases the Shredder depressor can be
removed but it is simpler to have one set of hoses with and one set without Shredder depressors.
Hose with Shredder valve Depressor Hose without Shredder valve Depressor
Hose selection is important depending whether the system is being evacuated or charged. Charging liquid
from the cylinder into the liquid line should be carried out using an open hose connected to an unrestricted
fitting. This will reduce charging time.
108
Shredder core
Shredder valves provide easy system access for pressure reading and addition of refrigerant. On small
systems, they provide a reasonable connection for evacuation also. However, Shredder valves and the
hoses connected to them can cause very severe pressure drops and can multiply evacuation time by a factor
of 4 or 5.
On the positive side, Shredder valves provide a restriction that slows the speed of liquid charging into the
suction side. When a pressure drop is desirable (charging liquid into suction), connect via a Shredder valve.
When a pressure drop is detrimental (evacuation), connect via an open fitting.
If the installer cannot find the correct charge but the system must be started, refrigerant should be carefully
added to the system until reasonable sub-cooling is measured in the liquid line and reasonable suction
superheat is measured at the compressor suction. Suction and discharge pressures must be monitored
carefully during the charging process.
CHARGE LIMITS
Copeland Scroll compressors have the different charge limits for different compressor models as shown in
table below. If the total charge exceeds these limits, the system should have a crankcase heater and/or
pump down cycle and/or accumulator to prevent liquid damage to the compressor. Some systems may
require accumulators to limit liquid floodback even though the charge is lower than the published limit.
Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the liquid line
charging port until refrigerant no longer flows or until the correct charge has been weighed in. If additional
charge is required start the system and slowly bleed liquid into the suction side until the system is full.
109
Copeland recommends charging liquid in a CONTROLLED manner into the suction side until the
system is full. This recommendation does not hold true for reciprocating compressors where liquid charging
into the suction side could cause severe damage.
Carefully monitor the suction and discharge pressures – ensure that the suction pressure does not fall below
25 psig (1.7 bar) at any time during the charging process.
CAUTION: Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and
Manifold valve “A” are both open.
There are many ways of charging liquid in a “controlled manner” into the
suction side:-
1. Use valve A on the manifold gauge set
2. Use the valve on the refrigerant cylinder
3. Charge through a Shredder valve
4. Use a hose with a Shredder valve depressor
5. Charge into the suction side at some distance from the compressor.
6. All of the above
A
Charging Procedures - Three phase compressors
The fundamental procedure is the same as for single phase models but the compressor can run in the wrong
direction on starting. If this happens reverse any two phases and start again. Short term reverse rotation will
not damage the compressor.
As compressors get larger the importance of correct field charging procedures grows exponentially.
Unfortunately larger systems are often field charged which leads to many infant failures. All Specter
compressors have internal discharge temperature protectors which are very effective in preventing
dangerously high discharge temperatures during charging. The protection module will trip and lock the
compressor out for 30 minutes. It is not normally necessary to wait 30 minutes for the module to reset. When
the compressor has cooled down the module can be reset by breaking the power supply to the control circuit.
Very often the serviceman does not understand why the module tripped and uses a jumper wire to bypass it.
He continues to charge the system and removes the jumper when charging is complete. The compressor
may or may not run with the protector back in the circuit but it is certain that the compressor has been
damaged and premature failure is inevitable.
110
Additional charge
Based on liquid pipe size per meter length:
Liquid Pipe Size, inch Additional Charge, kg/meter
1/4” 0.02
5/16” 0.04
3/8” 0.05
1/2” 0.10
5/8” 0.17
3/4” 0.26
7/8” 0.37
Note: Refer to the table of the Recommended Maximum Pipe Length.
111
2) Components
Mixture weight composition R32(23%), R125(25%), R134a(52%)
3) Characteristic
• R407C liquid and vapor components have different compositions when the fluid evaporates or condenses. Hence,
when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the system will change
and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is
recommended that the system should be evacuated thoroughly before recharging with R407C.
• When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid phase.
Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to make
certain that only original composition of R407C is being charged into the system.
• POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22 compressor.
Extra precaution must be taken not to expose the R407C system too long to moist air.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve type. For a
heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.
112
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
R32/R125/R134
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
Invert cylinder
Dip-pipe
without dip-pipe
Liquid
withdrawal
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
113
Upon removal of front and side panel, all the electrical "terminal box", fan and motor assembly and compressor are easily
accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surfaces once
quarterly. However, if a unit is installed in area subjected to much oil, mist and dust, the coil must be regularly cleaned by
qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the
systems life span might be shortened.
CAUTION
When the compressor is to be stopped for a long time, the crankcase heater should be energized for at least
6 hours before start of operation.
Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the refrigeration cycle
when performing a leakage test or an airtight-test. These types of gases are extremely dangerous, because
explosion can occur.
It is recommended that nitrogen or refrigerant be charged for these types of tests.
The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped with a crankcase
heater with the compressor).
Make sure the air conditioner is properly grounded by checking the ground terminal.
MAINTENANCE
For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance.
114
GENERAL PRECAUTION
Ensure that the rated voltage of the unit correspond to the name plate before carrying out proper wiring
according to the wiring diagram.
Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit breaker
for over-current protection should be provided in the exclusive line.
The unit must be GROUNDED to prevent possible hazard due to insulation failures
Every wiring must be firmly connected.
Every wiring should not touch the refrigerant piping, compressor and any moving parts of fan motor.
OPERATIONAL CHECK
After all wiring is completed and the system is charged with refrigerant, make sure the unit is operating
properly. Check that :-
Condenser fans are running with warm air blowing off the condensing unit.
Evaporator blowers are running and discharging cool air from ducts.
Suction line and liquid line pressures are in the region of 75 psig and 275 psig respectively.
(OPTIONAL)
(OPTIONAL)
115
A : Time display
B : Error indication
C : Compressor running display (up to 4
compressors)
D : Key lock display
E : Heater display (up to 2 heaters)
F : Energy saving mode display
G : Compressor defrost cycle display (up to
4 compressors)
H : Operation mode display
I : Temperature set display
2. OPERATING GUIDE
2.1 ON/OFF key
Press once to start the air conditioning unit.
Press again to stop the unit.
The operation lamp next to the key lights up and goes off respectively when the unit is running
or not running.
Caution : In the case when the ON/OFF key is pressed immediately after the operation is
stopped, the unit will not restart until 3 minutes later to protect the compressor.
116
Press the OFF TIMER key to activate auto-OFF timer mode. Under this mode, press the respective
MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to
automatically stop running. Press the ON TIMER key again to save the setting.
Then to activate the 7-days timer, press and hold the TIMER ACTIVE key until the word "TIMER
ACTIVE" appears on the LCD screen. Repeat the same step to disable the 7-days timer.
Test run
Press the TEST key 2 times consecutively to test run the unit.
3. ERROR CODE
When the system is on and an error occurs, the ON/OFF LED on the LCD panel will blink and an error
code is shown. When the system is off and there is a thermistor error, the ON/OFF LED is off but the
error code is still displayed. Each error code represents different message as below
Error Error
code Possible fault code Possible fault
E01 Require manual reset (possible causes) E19 Indoor coil sensor 4 short
E02 Compressor 1 high temperature (overload) E20 Indoor coil sensor 1 open
E03 Compressor 2 high temperature(overload) E21 Indoor coil sensor 2 open
E04 Compressor 3 high temperature(overload) E22 Indoor coil sensor 3 open
E05 Compressor 4 high temperature(overload) E23 Indoor coil sensor 4 open
E06 Compressor 1 high pressure trip / contact open E24 Outdoor coil sensor 1 short
E07 Compressor 2 high pressure trip / contact open E25 Outdoor coil sensor 2 short
E08 Compressor 3 high pressure trip / contact open E26 Outdoor coil sensor 3 short
E09 Compressor 4 high pressure trip / contact open E27 Outdoor coil sensor 4 short
E10 Compressor 1 trip / low R-22 / outdoor abnormal E28 Outdoor coil sensor 1 open
E11 Compressor 2 trip / low R-22 / outdoor abnormal E29 Outdoor coil sensor 2 open
E12 Compressor 3 trip / low R-22 / outdoor abnormal E30 Outdoor coil sensor 3 open
E13 Compressor 4 trip / low R-22 / outdoor abnormal E31 Outdoor coil sensor 4 open
E14 Room sensor short E32 Compressor 1 de-ice
E15 Room sensor open E33 Compressor 2 de-ice
E16 Indoor coil sensor 1 short E34 Compressor 3 de-ice
E17 Indoor coil sensor 2 short E35 Compressor 4 de-ice
E18 Indoor coil sensor 3 short
117
Note : * Cooling or heater model depending on SW1 and SW2 setting. Factory setting for number of
compressor is based on air conditioner models.
2. Number of Heater
Number of Heater SW1(dip1) SW2(dip2)
a. No heater (0 heater) off off
b. 1 heater on off
c. 2 heaters on / off on
118
note that 1.5°C only valid for 2 and 3 compressors model. For 4 compressors model, maximum allowed is
1.0°C.
The default differential temperature is base on number of compressor model, the setting is as below :
Model Diff. Temperature
1 compressor Not applicable
2 compressor 1.5°C
3 compressor 1.0°C
4 compressors 0.5°C
Dip switch 6
a. Fan off off
b. Fan on on
6. Operating Modes
The system has 4 operating modes to select with respect to each model selection:
JH1 Setting
a. Last memory backup JH1 Plugged
b. Without last memory backup JH1 Removed
119
2 seconds
Start Indoor fan
15 seconds 2 seconds
outdoor fan 1 compressor 1*
15 seconds 2 seconds
outdoor fan 2 compressor 2*
15 seconds 2 seconds
outdoor fan 3 compressor 3*
15 seconds 2 seconds
outdoor fan 4 compressor 4*
2 seconds 2 seconds
Start Indoor fan all 4 way valves
15 seconds 2 seconds
outdoor fan 1 compressor 1*
15 seconds 2 seconds
outdoor fan 2 compressor 2*
15 seconds 2 seconds
outdoor fan 3 compressor 3*
15 seconds 2 seconds 15 seconds 15 seconds
outdoor fan 4 compressor 4* Heater 1* Heater 2*
The compressors will be turned on one by one depending on the on/off conditions shown in the above.
Troubleshooting
When any air conditioner malfunction is noted, immediately switch off the power supply to the unit and
contact the local dealer, if necessary. Some simple trouble shooting tips are given below :
120
No Cooling
Stop
Evaporator
Fan Motor
Faulty No Voltage or Low Voltage Get the Right Voltage
Unit Power
Supply Repair the Power
Single-Phase
Line
Condenser Stop
Fan Motor
Tripped
Overcurrent High Voltage or Low Voltage Get The Right Voltage
Relay For
Condenser Fan Single-Phase Check The Power Supply To The
Motor : Repair Connections When
Necessary
Running
Faulty Coil Burnt Change The Contactor
Condenser Fan
Contactor
Contact Faulty Change The Contacts
121
Cycling On
Compressor
Cycling
High Discharge Pressure or Low See "High Discharge Pressure" or
Tripping Suction Pressure "Low Suction Pressure"
Dual Pressure
Switch Clogged Capillary or Pressure Repair Clogging and Replace
Switch The Switch If Required
Running Overcurrent Tripping High Voltage or Low Voltage Get The Right Voltage
Relay For
Compressor Check The Power Line To The
Single-Phase
Compressor : Repair When Necessary
High Discharge Pressure And See "High Discharge Pressure"
High Suction Pressure or "High Suction Pressure"
Loose Connections Tighten The Connections
See "High Discharge
Discharge Gas Tripping High Discharge Pressure And
Pressure" or "Low Suction
Thermostat or Low Suction Pressure
Pressure"
Internal
Thermostat Refrigerant Short Charge or Add Refrigerant. Repair
Refrigerant Leakage Leakage If Detected.
See "High Suction
High Suction Pressure
Pressure"
High Discharge
Pressure
Restricted
Condenser Clogged Condenser Coil Clean The Condenser
Air Flow
Check The Voltage
Low Fan Speed And Get The Right
Voltage
Check The System
Malfunction Of Fan Cycling
And Repair If
High System
Condenser Required
Secure Space For
Air Inlet Circulating Air Flow
Required Air Flow
Temperature
Overcharged Refrigerant Purge The Refrigerant
Low Discharge
Pressure
Excessive
Condenser Malfunction Of Fan Cycling Check The System And Repair The
Air Flow System Components If Required
122
Evaporator Low
Air Inlet Excessive Fresh Air Intake Reduce The Fresh Air Intake
Temperature
Insufficient Duct Insulation Reinforce The Duct Insulation
Noisy Operation
Noisy Operation
Noisy
Compressor
Shipping Noisy
Unremoved Shipping Bolt(s) Remove The Bolt(s)
Bolt(s)
Overcharged Refrigerant Purge The Refrigerant
Liquid
Refrigerant Low Suction Pressure See "Low Suction Pressure"
Backing Up
Worn Compressor Parts Replace Or Repair The Compressor
Evaporator Noisy
Knocking Runner Fix The Runner Or Casing Properly
Fan
Worn Bearing Change The Bearing
Strainer
Whistling
Liquid Line Noisy Partially Clogged Clean The Dryer
123
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 6 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
124
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 7.5 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
125
NOTE :
WITH CONTACTOR
126
NOTE :
1) WITH FLARE VALVE
2) WITH SEQUENTIAL CONTROLLER
3) FOR 400V/3PH/50Hz
4) FOR EXPORT SPEC
127
NOTE :
1) WITH FLARE VALVE
2) WITH SEQUENTIAL CONTROLLER
3) FOR HIGH STATIC
4) FOR 400V/3PH/50Hz
5) FOR EXPORT SPEC
128
NOTE :
WITH CONTACTOR
129
NOTE :
WITH CONTACTOR
130
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
131
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
132
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
133
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
134
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
135
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
136
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
137
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
138
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
139
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
140
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 6 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
141
1 ASSY, BASE PAN COVER INS. 18 ASSY, SIDE PANEL BIG RIGHT INS.
2 ASSY, BASE PAN INS. 19 ASSY, TOP PANEL INS.
3 ASSY, FRONT PANEL INS. 20 ASSY, SECTION FILTER
4 ASSY, FLANGE BLOWER 21 ASSY, TERMINAL BOX
5 ASSY, BLOWER 22 SCREW, S.T. TRUSS HEAD PHILIP
6 GROMET, MNTG COMPLETE WITH NUT 23 SCREW, SELF TAPPING PAN HEAD
7 ASSY, BRACKET FAN MOTOR 24 SCREW, TRUSS HEAD PHILIP
8 MOTOR 25 NUT, WELD M5
9 CAPACITOR, 7.5 uF/440V 26 SCREW, WOOD
10 CLAMP, CAPACITOR 27 WASHER, PLAIN
11 SUPPORT, BLOWER BRACKET 28 WASHER, PLAIN
12 ASSY, DRAIN PAN INS. 29 WASHER, SPRING
13 ASSY, COIL TUBING 30 WASHER, SPRING
14 ASSY, COIL SIDE COVER RIGHT INS. 31 BOLT, HEXAGON PAN HEAD
15 ASSY, COIL SIDE COVER LEFT INS. 32 NUT, HEXAGON
16 ASSY, SIDE PANEL LEFT INS. 33 NUT, HEXAGON
17 ASSY, SIDE PANEL SML RIGHT INS.
142
NOTE :
WITH CONTACTOR
143
NOTE :
1) WITH FLARE VALVE
2) WITH SEQUENTIAL CONTROLLER
3) FOR 400V/3PH/50Hz
4) FOR EXPORT SPEC
144
NOTE :
1) WITH FLARE VALVE
2) WITH SEQUENTIAL CONTROLLER
3) FOR HIGH STATIC
4) FOR 400V/3PH/50Hz
5) FOR EXPORT SPEC
145
NOTE :
WITH CONTACTOR
146
NOTE :
WITH CONTACTOR
147
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
148
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
149
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
150
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
151
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
152
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
153
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
154
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
155
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) VERTICAL AIR DISCHARGE
156
NOTE :
1) WITH SEQUENTIAL CONTROLLER
2) HORIZONTAL AIR DISCHARGE
157
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH AUTO RESTART H/L
PRESSURE SWITCH
4) FOR 380 – 420V/3PH/50Hz
5) FOR EXPORT SPEC.
158
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH AUTO RESTART H/L
PRESSURE SWITCH
4) FOR 380 – 420V/3PH/50Hz
5) FOR EXPORT SPEC.
159
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH AUTO RESTART H/L
PRESSURE SWITCH
4) FOR 380 – 420V/3PH/50Hz
5) FOR EXPORT SPEC.
160
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH AUTO RESTART H/L
PRESSURE SWITCH
4) FOR 380 – 420V/3PH/50Hz
5) FOR EXPORT SPEC.
161
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
162
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
163
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
164
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
165
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
166
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
167
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
168
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH TECO FAN MOTOR
3) WITH BALL VALVE
4) WITH AUTO RESTART H/L
PRESSURE SWITCH
5) FOR 380 – 420V/3PH/50Hz
6) FOR EXPORT SPEC.
169
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH HONG LU FAN MOTOR
3) FOR 380 – 415V/3PH/50Hz
4) FOR EXPORT SPEC.
170
NOTE :
1) WITH COPELAND SCROLL COMP.
2) WITH HONG LU FAN MOTOR
3) FOR 380 – 415V/3PH/50Hz
4) FOR EXPORT SPEC.
171
172
173
174
175
ISO 9002