Ntelligent Detection Devices: Data Sheet
Ntelligent Detection Devices: Data Sheet
Each Model FDT421 detector provides seven (7) pre- Application Data
programmed, FACP-selectable parameter sets. Installation of Model FDT421 detectors requires a (2) two-
Detector Supervision and Testing wire circuit. In many retrofit cases, existing wiring may be
used. ’T-tapping’ is permitted only for Style 4 (Class B)
Model FDT421, which is listed as a self-testing device,
wiring. Model FDT421 is polarity insensitive, which allows
contains a tri-color light emitting diode (LED) indicator,
a substantial reduction in installation and debugging time.
capable of flashing any one (1) of three (3) distinct colors:
Green, Yellow, or Red. During each flash interval, the Model FDT421 can be applied within the maximum 50-feet
microprocessor-based detector monitors the following: center spacing (2,500 sq. ft. areas), per UL. This application
• Temperatures reaching programmed thresholds guideline is based on ideal conditions specifically, smooth
• Internal sensors and electronics are functional ceiling surfaces, minimal air movement, and no physical
obstructions between potential fire sources and the actual
Based on the monitoring results, the LED indicator flashes detector. Do not mount detectors in close proximity to
the following colors based on the following conditions: ventilation or heating and air conditioning outlets. Exposed
Flash joints or beamed ceilings may also affect safe spacing
Flash
Condition Interval limitations for detectors.
Color
(in seconds)
Should questions arise regarding detector placement,
Normal supervisory operation.
observe NFPA 72 guidelines. Good fire-protection system
Temperature has not reached 10
Green*: engineering and common sense dictate how and when fire
programmed alarm thresholds
or set points. detectors are installed and used. Contact your local
Detector is in trouble and Siemens Fire Safety distributor or sales office whenever
Yellow: 4
needs replacement. you need assistance applying Model FDT421 in unusual
Red: Alarm condition. 1 applications. Be sure to follow NFPA guidelines and UL
Listed / ULC Listed installation instructions included with
No Flash: Detector is not powered.
every Siemens Fire Safety detector and local codes as
* LED can be turned OFF. for all fire protection equipment.
Please follow the corresponding description of the panel used.
s Industry, Inc.
Building Technologies Division
Specifications Technical Data
Model FDT421 is a plug-in, (2) two-wire thermal (heat) Operating
detector, compatible with FireFinder XLS and Desigo Temperature +32°F (0°C) to 100°F (38°C)
Fire Safety panels. Each Model FDT421 detector has Range: [with 135°F (57°C) alarm-threshold setting]
microcomputer-chip technology and highly stable, solid-
Relative Humidity: 0-95%; non-condensing
state electronic circuitry.
The Model FDT421 detector utilizes a modern, accurate Air Pressure: No effect
and shock-resistant thermistor to sense temperature
Input Voltage Range: 16VDC 30VDC
changes.
This electronic-sensing method virtually eliminates thermal Alarm Current (max.): 410 A
lag associated with mechanical temperature-sensing
Standby Current (max.): 250 A, max.
devices, and provides almost instantaneous temperature
(Average )
status to the FACP.
Model FDT421 provides seven (7) field-selectable, pre- Maximum Spacing: 50-foot centers (2,500 sq. ft.),
programmed temperature settings: per NFPA 72 and ULC-S524
• Fixed 135°F (57°C)
• Fixed 145°F (63°C)
Thermal Rating:
• Fixed 155°F (68°C) Model FDT421 provides up to seven (7) field-selectable, pre-
• Fixed 165°F (74°C) programmed temperature settings:
• Fixed 174°F (79°C) Fixed 135°F (57°C)
• Rate-of-Rise: 15°F / min. (8.3°C) at fixed 135°F (57°C) Fixed 145°F (63°C)
• Rate-of-Rise: 15°F / min. (8.3°C) at fixed 174°F (79°C) Fixed 155°F (68°C)
Fixed 165°F (74°C)
Additionally, the Model FDT421 detector has the Fixed 174°F (79°C)
following optional feature:
Rate-of-Rise: 15°F / min. (8.3°C / min) at fixed 135°F (57°C)
• Model FDT421 provides indication of potential freezing Rate-of-Rise: 15°F / min. (8.3°C / min) at fixed 174°F (79°C)
for sprinkler systems, via a configuration for reporting a
low-temperature warning of 40°F (4.4°C). Detector Weight:
This feature is compatible with Models FC2025, FC2050 0.32 Lbs.
and FireFinder XLS. (0.144 Kg.)
s Industry, Inc.
Building Technologies Division
Mounting Diagram Details for Ordering
Dimensions Part
Model Number Description
FDT421 S54320-F5-A1 Thermal (Heat) Detector
DB-11 500-094151 Detector Mounting Base
DB-11E 500-094151E Detector Base {small}
DB2-HR S54320-F12-A1 Relay Base
Remote Alarm Indicator:
RL-HC 500-033230
4” octagon-box mount, red
Remote Alarm Indicator:
RL-HW 500-033310
Compatible FACPs Single-gang box mount, red
LK-11 500-695350 Base Locking Kit
Data
Model Sheet Description STI-9604 STI Mechanical Protection Guard
Number See: www.ST I-USA.com for further details on ordering
6300 FireFinder XLS Model STI-9604.
FC2005 6813 50-point addressable FACP
FC2025 6815 252-point addressable FACP
FC2050 6815 504-point addressable FACP
In Canada, order:
Part
Model Number Description