Data sheet 3RV2042-4KB10

Circuit breaker size S3 for motor protection, Class 20 A-release 57...75 A


N-release 975 A screw terminal Increased switching capacity 100 kA

product brand name SIRIUS


product designation Circuit breaker
design of the product For motor protection
product type designation 3RV2
General technical data
size of the circuit-breaker S3
size of contactor can be combined company-specific S3
product extension auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 38 W
● at AC in hot operating state per pole 12.7 W
insulation voltage with degree of pollution 3 at AC rated 1 000 V
value
surge voltage resistance rated value 8 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between main and auxiliary circuit 400 V
● between main and auxiliary circuit 400 V
shock resistance acc. to IEC 60068-2-27 25g / 11 ms Sinus
mechanical service life (switching cycles)
● of the main contacts typical 25 000
● of auxiliary contacts typical 25 000
electrical endurance (switching cycles) typical 25 000
reference code acc. to IEC 81346-2 Q
Substance Prohibitance (Date) 01.03.2017
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
temperature compensation -20 ... +60 °C
relative humidity during operation 10 ... 95 %
Main circuit
number of poles for main current circuit 3
adjustable current response value current of the 57 ... 75 A
current-dependent overload release
operating voltage
● rated value 690 V
● rated value 20 ... 690 V

3RV20424KB10 Subject to change without notice


12/2/2021
Page 1/6 © Copyright Siemens
● at AC-3 rated value maximum 690 V
operating frequency rated value 50 ... 60 Hz
operational current rated value 75 A
operational current at AC-3 at 400 V rated value 75 A
operating power at AC-3
● at 230 V rated value 22 kW
● at 400 V rated value 37 kW
● at 500 V rated value 45 kW
● at 690 V rated value 55 kW
operating frequency at AC-3 maximum 15 1/h
Protective and monitoring functions
product function
● ground fault detection No
● phase failure detection Yes
trip class CLASS 20
design of the overload release thermal
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value 100 kA
● at 400 V rated value 50 kA
● at 500 V rated value 5 kA
● at 690 V rated value 3 kA
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value 100 kA
● at AC at 400 V rated value 100 kA
● at AC at 500 V rated value 10 kA
● at AC at 690 V rated value 6 kA
response value current of instantaneous short-circuit trip 975 A
unit
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value 75 A
● at 600 V rated value 75 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value 7.5 hp
— at 230 V rated value 15 hp
● for 3-phase AC motor
— at 200/208 V rated value 25 hp
— at 220/230 V rated value 30 hp
— at 460/480 V rated value 60 hp
— at 575/600 V rated value 75 hp
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit trip magnetic
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height 165 mm
width 70 mm
depth 176 mm
required spacing
● for grounded parts at 400 V
— downwards 70 mm
— upwards 70 mm
— at the side 10 mm
● for live parts at 400 V
— downwards 70 mm
— upwards 70 mm

3RV20424KB10 Subject to change without notice


12/2/2021
Page 2/6 © Copyright Siemens
— at the side 10 mm
● for grounded parts at 500 V
— downwards 110 mm
— upwards 110 mm
— at the side 10 mm
● for live parts at 500 V
— downwards 110 mm
— upwards 110 mm
— at the side 10 mm
● for grounded parts at 690 V
— downwards 150 mm
— upwards 150 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm
● for live parts at 690 V
— downwards 150 mm
— upwards 150 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm
Connections/ Terminals
product component removable terminal for auxiliary No
and control circuit
type of electrical connection
● for main current circuit screw-type terminals
arrangement of electrical connectors for main current Top and bottom
circuit
type of connectable conductor cross-sections
● for main contacts
— solid 2x (2.5 ... 16 mm²)
— solid or stranded 2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
— finely stranded with core end processing 2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
— finely stranded without core end processing 2x (10 ... 35 mm²), 1x (10 ... 50 mm²)
tightening torque
● for main contacts for ring cable lug 4.5 ... 6 N·m
outer diameter of the usable ring cable lug maximum 19 mm
tightening torque
● for main contacts with screw-type terminals 4.5 ... 6 N·m
Safety related data
B10 value
● with high demand rate acc. to SN 31920 5 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920 50 %
● with high demand rate acc. to SN 31920 50 %
T1 value for proof test interval or service life acc. to 10 y
IEC 61508
protection class IP on the front acc. to IEC 60529 IP20
touch protection on the front acc. to IEC 60529 finger-safe, for vertical contact from the front
display version for switching status Handle
Certificates/ approvals
General Product Approval

Confirmation KC

Declaration of Conformity Test Certificates Marine / Shipping

3RV20424KB10 Subject to change without notice


12/2/2021
Page 3/6 © Copyright Siemens
UK Declaration of Type Test Certific- Special Test Certific-
Conformity ates/Test Report ate

Marine / Shipping other

Confirmation

other Railway

Vibration and Shock Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2042-4KB10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2042-4KB10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2042-4KB10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2042-4KB10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2042-4KB10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2042-4KB10&objecttype=14&gridview=view1

3RV20424KB10 Subject to change without notice


12/2/2021
Page 4/6 © Copyright Siemens
1/L1

3/L2

5/L3

-F

I> I> I>


2/T1

4/T2

6/T3

last modified: 11/30/2021

3RV20424KB10 Subject to change without notice


12/2/2021
Page 5/6 © Copyright Siemens
3RV20424KB10 Subject to change without notice
12/2/2021
Page 6/6 © Copyright Siemens