Primary Chilled Water Pump Head Loss Calculation

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

PRIMARY CHILLED WATER PUMP HEAD LOSS CALCULAT

Section Flow Pipe Size Description Friction Loss Length No. of Equivalent Length
(gpm) (inch) (ft/100 ft water) (ft) Fittings of fitting (ft)

pipe 3.8 23 0 0.00


3 way plug valve 3.8 0 1 7.67
balancing valve 3.8 0 1 35.00
A-C 125 3
gate valve 3.8 0 1 3.20
tee (branch flow) 3.8 0 1 15.00
reducer 3.8 0 1 2.60
pipe 3.8 20 0 0.00
tee (thru flow) 3.8 0 1 6.70
C-E 250 4
elbow 90 degrees 3.8 0 1 10.00
tee (branch flow) 3.8 0 1 21.00
pipe 3.8 20 0 0.00
elbow 90 degrees 3.8 0 2 7.50
butterfly valve 3.8 0 2 11.51
E-H 125 3 strainer 3.8 0 1 42.00
check valve 3.8 0 1 30.00
balancing valve 3.8 0 1 35.00
tee (branch flow) 3.8 0 1 15.00
pipe 3.8 18 0 0.00
H-K 250 4 elbow 90 degrees 3.8 0 2 10.00
butterfly valve 3.8 0 2 15.10
OSS CALCULATION
Total Equivalent Head Loss
Length (ft) (ft of
water)
23.00 0.87
7.67 0.29
35.00 1.33
3.20 0.12
15.00 0.57
2.60 0.10
20.00 0.76
6.70 0.25
10.00 0.38
21.00 0.80
20.00 0.76
15.00 0.57
23.02 0.87
42.00 1.60
30.00 1.14
35.00 1.33
15.00 0.57
18.00 0.68
20.00 0.76
30.20 1.15

Pump Head (ft) 14.91


SECONDARY CHILLED WATER PUMP HEAD LOSS CALCULA
Flow Pipe Size Friction Loss Length No. of Equivalent Length
Section (gpm) (inch) Description (ft/100 ft water) (ft) Fittings of fitting (ft)

pipe 3.8 25 0 0.00


butterfly valve 3.8 0 2 15.10
L-O 250 4
elbow 90 degrees 3.8 0 2 10.00
tee (branch flow) 3.8 0 1 21.00
pipe 3.8 20 0 0.00
elbow 90 degrees 3.8 0 2 7.50
butterfly valve 3.8 0 2 11.51
O-R 125 3 strainer 3.8 0 1 42.00
check valve 3.8 0 1 30.00
balancing valve 3.8 0 1 35.00
tee (branch flow) 3.8 0 1 15.00
pipe 3.8 25 0 0.00
R-T 250 4 elbow 90 degrees 3.8 0 1 10.00
tee (straight flow) 3.8 0 1 6.70
pipe 3.8 25 0 0.00
reducer 3.8 0 1 2.60
T-V 125 3 tee (branch flow) 3.8 0 1 15.00
gate valve 3.8 0 1 3.20
strainer 3.8 0 1 42
LOSS CALCULATION
Head Loss
Total Equivalent
Length (ft) (ft of
water)
25.00 0.95
30.20 1.15
20.00 0.76
21.00 0.80
20.00 0.76
15.00 0.57
23.02 0.87
42.00 1.60
30.00 1.14
35.00 1.33
15.00 0.57
25.00 0.95
10.00 0.38
6.70 0.25
25.00 0.95
2.60 0.10
15.00 0.57
3.20 0.12
42.00 1.596

Pump Head (ft) 15.42


CONDENSER WATER PUMP HEAD LOSS CALCULATION
Flow Pipe Size Friction Loss Length No. of Equivalent Length
Section (gpm) (inch) Description (ft/100 ft water) (ft) Fittings of fitting (ft)

pipe 2.8 91 0 0.00


butterfly valve 2.8 0 4 18.93
1 to 12 322 5
elbow 90 degrees 2.8 0 7 13.00
tee (branch flow) 2.8 0 2 25.00
pipe 2.6 30 0 0.00
elbow 90 degrees 2.6 0 2 10.00
butterfly valve 2.6 0 1 15.10
12 to 16 161 4
strainer 2.6 0 1 60.00
check valve 2.6 0 1 40.00
tee (branch flow) 2.6 0 1 21.00
pipe 2.8 8 0 0.00
16 to 17 322 5
butterfly valve 2.8 0 2 18.93
CALCULATION
Head Loss
Total Equivalent
Length (ft) (ft of
water)
91.00 2.55
75.72 2.12
91.00 2.55
50.00 1.40
30.00 0.78
20.00 0.52
15.10 0.39
60.00 1.56
40.00 1.04
21.00 0.55
8.00 0.22
37.86 1.06

Pump Head (ft) 14.74