ENG-HV-2013 - Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser With Accessories

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

F01 (PEG-P-102)

Rev No.00
Eff. Date: 01.04.2019

___________________________________________________________________________________________________________________

TECHNICAL SPECIFICATION COVER SHEET

Document No: ENG-HV-2013

Document Title: Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with
Accessories

As per periodic 2021


SKA
00 revision cycle 15.05.2020 ED RMB VK PV
BND
(ENG-HV-4013) 5538

For tender
03 -sd- SS -sd- DRD -sd- HCS -sd-
(ENG-HV-54) 15.09.2015 - PP

For tender NK/


02 AP/BK/ -sd- -sd- DRD -sd- HCS -sd-
(ENG-HV-54) 26.05.2015 - SSK
GG
For tender
01 -sd- JC -sd- JKS -sd- HCS -sd-
(ENG-HV-54) 31.01.2013 AB/RB
-

Initials Sign Initials Sign Initials Sign Initials Sign


Rev Date ERM
Remarks
No. No.
Reviewed By Approved By Issued By
Prepared By

Issuing Office

HoG/HoD/ Head (Plant Engineering)


<Tata Power Delhi Distribution Limited>
< Behind MTNL office, Yogashram Marg, Institutional Area, Sector-3, Rohini – 110085>

___________________________________________________________________________________________________________________

Property of TATA Power-DDL – Not to be reproduced without permission of TATA Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.2019
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 1 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

CONTENTS

1. Scope

2. Applicable Standards

3. Climatic Conditions Of The Installation

4. General Technical Requirements

5. General Constructions
6. Name Plate And Marking

7. Tests

8. Type Test Certificates

9. Pre-Dispatch Inspection

10. Inspection After Receipt At Stores

11. Guarantee
12. Packing And Transport

13. Tender Sample


14. Training

15. Quality Control


16. Testing Facilities

17. Manufacturing Activities


18. Spares, Accessories & Tools

19. Drawings, Documents

20. Guaranteed Technical Particulars


21. Schedule Of Deviations
ANNEXURES- 1

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 2 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

1.0 SCOPE This specification covers the technical requirements of design, manufacture, testing at
manufacturer’s works, packing, forwarding, supply and unloading at site/store and
performance of 11kV Pole Mounted Autorecloser and Sectionaliser with all accessories
and necessary training for trouble free & efficient performance.

It is not the intent to specify completely herein all the details of tech design and construction
of material. However, the material shall conform in all respects to high standards of
engineering, design and workmanship and shall be capable of performing in continuous
commercial operation in manner acceptable to the TATA POWER-DDL, who will interpret
the meanings of drawings and specification and shall have the power to reject any work or
material which, in his judgment is not in accordance therewith. The offered material shall
be complete with all components necessary for their effective and trouble free operation.
Such components shall be deemed to be within the scope of Bidder’s supply irrespective
of whether those are specifically brought out in this specification and/or the commercial
order or not.

2.0 APPLICABLE The equipment covered by this specification shall unless otherwise stated, be designed,
STANDARDS manufactured and tested in accordance with latest editions of the following Standards /IEC
and shall conform to the regulations of local statutory authorities.

Standards Details
IEC 62271-111 2019 / Standard requirements for Overhead Automatic Circuit
IEEE C37.60 Reclosers and Fault Interrupters for Alternating
Current System up to 38 KV
IEC 62271-102 HV switchgear and control gear-Alternating current
disconnector and earthing switches
IEC 62271-1 Alternating-current circuit-breakers
IS 513 Cold Rolled Low Carbon Steel Sheets and Strips.
IEC 60529 Degrees of protection provided by enclosures (IP
Code)
IEC 62262 Degrees of protection provided by enclosures for
electrical equipment against mechanical impacts (IK
Code)
IEC 60060-1 High-voltage test techniques
IEC 60060-3 High-voltage test techniques - Part 3: Definitions and
requirements for on-site testing
IEC 60947 /IS 13947 Low voltage switchgear and control gear
IEC 60439-1 Low-voltage switchgear and control gear assemblies-
Type tested and partially type tested assemblies
IEC 60255-3 Electrical relays – Part 3: Single input energizing
quantity measuring relays with dependent or
independent time.
IEC 61869-2 / IS 2705 Current Transformers
IEC 60376 Specification of technical grade sulphur hexafluoride
(SF6) for use in electrical equipment
IEC 61869-3/ IS 3156 Voltage Transformers
IEC 62271-206 High-voltage prefabricated switchgear and control gear
assemblies – Voltage presence indicating systems.
IS 13573-2 Cable accessories for extruded power cable for
Working Voltages from 3.3 kV up to and Including 33kV
IS 2629 Practice for Hot Dip Galvanizing of iron and steel

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 3 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

IEC 61000-4 Electromagnetic Compatibility for relays


IEC 60099-4:2014 Metal-oxide surge arresters without gaps for a.c.
systems
IS 9921 Alternating Current Disconnectors (Isolators) for
Voltages Above 1000 V - Part III : Design and
Construction & Part 4 : Tests
Note- In case of any conflict on any technical particular in the specification, the stricter
requirement mentioned in the relevant standard shall be valid.

3.0 CLIMATIC
CONDITIONS AT Max. Ambient Temperature 50 0C
THE Average Ambient Temperature in peak 40 0C
INSTALLATION summer months May to July
Min. Ambient Temperature in winter months 0 0C
Relative humidity 20 to 90%
Average Annual Rainfall 760 mm
Average rainy days per annum 60 days
Max. Altitude above MSL Not exceeding 300 meters
Max. wind pressure 126 kg/sq. m. up to height of 10 meters
Seismic level (horizontal ground 0.3 g
acceleration)
Note- The atmosphere is generally laden with mild acid and dust in suspension during the
dry months and is subjected to fog in cold months. The design of equipment and
accessories shall be suitable to withstand seismic forces corresponding to an acceleration
of 0.3 g.

4.0 GENERAL As specified by TATA Power-DDL Bidder to


TECHNICAL SNo Description
(Options defined in specs) furnished
REQUIREMENTS
Pole mounted (TATA POWER-DDL pole
1 Mounting
is trapezoidal in shape)
2 Application Outdoor
Bidder to provide details
Offered Model number
3 a. OEM name
and OEM Name
b. Model
a. Autorecloser- HCPE (Hydrophobic
Cycloaliphatic Epoxy)
4 Dielectric medium b. SF6 for Sectionaliser- (If Autorecloser
if offered in place of Sectionaliser then
dialectic shall be HCPE)
a. Vacuum for Autorecloser
b. SF6 for Sectionaliser (Autorecloser
5 Interrupting medium with Vacuum interrupter in place of
Sectionaliser also acceptable if tripping
coordination achieved)
6 System Frequency 50 Hz

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 4 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

7 Rated Voltage 12 kV or above


8 Service Voltage 11 kV
9 Rated Current 630 A
10 Number of phases Three phase
Rated Short time as per
11 12.5kA for 3 sec
current withstand (3sec) type test
Rated Short time
as per
12 Making capacity for 31.25kA
type test
Autorecloser
Rated short circuit
13 Symmetrical breaking / 12.5kA
Interrupting current
Rated load interrupting
14 630 A
line current
Lightning Impulse as per
15 75 kVp Min.
withstand Voltage type test
Power Frequency as per
16 28 kVrms for 1 Minute or better
withstand voltage type test
Power frequency Wet as per
17 23kVrms for 10 sec. or better
withstand voltage type test
Minimum Creepage
18 25mm/kV
distance
a) Autorecloser
Dimension (LxWxH)
19 b) Sectionaliser
(mm x mm x mm)
c) Controller box
a) Autorecloser
20 Total weight b) Sectionaliser
c) Controller box
a) Magnetic Actuator for Autorecloser
b) Motorized operation for Sectionaliser
21 Operating mechanism (If Autorecloser is offered as
Sectionaliser the operation mechanism
shall be magnetic actuator)
22 Mode of operation Gang operated
Minimum number of as per
23 10000
rated load operations type test
24 Ingress protection IP55 for Outdoor Application
25 Contact resistance ˂150µΩ for each pole
O-0.5s-CO-10s-CO-10s-CO
Operating ( Duty cycle and the recloser delay time
26
sequence/Duty shall be programmable at site and
remotely)

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 5 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

Contact martial in Copper chromium with silver plating or


27
Vacuum bottle better
Bidder to mention make, should be same
28 Make of vacuum bottle as mentioned in type tested report of
same model and design.
Current density of
29 current carrying parts in Bidder to provide details as per design
phase of switchgear
Autorecloser or
30 Sectionaliser Ingress IP55
protection
Autorecloser or
Bidder to provide details of housing
31 Sectionaliser Enclosure
material like grade of SS
material
Manual Operation
32 To be provided by bidder.
Provision
Visual display of switch Marking to be provided by bidder such
33 status with ON/OFF that it can be visible from ground at
marking around minimum 9 meter length.
a. Bidder to specify the resin cast CT or
sensor used in offered product with its
details.
34 CT/ Current Sensor
b. Accuracy up to 630A +0.5%
c. Fault data 1000A & above accuracy
range to be shared.
Should be provided internal to
Voltage senor for
35 equipment. Bidder to specify details.
metering and protection
Accuracy up to 12kV +0.5%
Insulation cap on HT
terminals of With HT insulation cap on HT terminals
36
Autorecloser or (property of material to be provided)
Sectionaliser
The connectors for
Autorecloser and
Sectionaliser shall be Bidders to provide suitable tinned
37
suitable for single core connectors
300sq.mm covered
conductor.
GI material suitable for TATA POWER-
The mounting bracket
DDL poles to be provided for single pole
38 for Autorecloser and
and double pole installation with
Sectionaliser
cantilever type arrangement

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 6 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

The pole top Autorecloser or


39 Earthing provision Sectionaliser should have two body
earthing provisions.
Total Six numbers to be provided. Three
Surge arresters for
on each side of the equipment along
40 Autorecloser and
with mounting arrangement near
Sectionaliser
equipment
Polymeric type
9kV rated, 10KA
Class DH as per IEC
41 Surge arrester 7.65kV MCOV
Approved make- Raychem, Oblem,
Elpro. (Bidder to mention offered make)
With insulation cap on HT terminal
Double break Isolator with polymeric
insulator with,
Material – Tinned copper all current
carrying parts and GI for noncurrent
carrying parts. All hardware Hot dipped
galvanized.
Rating 11kV
Current rating 400A
11kV Isolator - the
Autorecloser should be BIL- 12kV/28kV/75kVp
42 Current density of current carrying
accompanied with
separate isolator parts, Max.2A/sqmm
Short Circuit withstand 16kA for 3 sec.
Peak withstand current shall be 40kAp
Creepage distance Min. 320mm
Phase to phase clearance min. 255mm
No. of operations 2000
All hardware bolts shall be 8.8 grade
Name of OEM
The mounting bracket GI material suitable for TATA POWER-
for Autorecloser , DDL poles to be provided for single pole
43
Sectionaliser and and double pole installation with
Isolator cantilever type arrangement
Outdoor application
Type- Resin cast PT double pole
44 Auxiliary PT Details
Voltage ratio- 11kV/230V
Burden- 100VA

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 7 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

Voltage factor- 1.2 continuous, 1.9 for 8


hours
BIL- 12kV/28kV/110 KV peak
With fuse on secondary in terminal box.
With insulation cap on HT bushing
Creepage distance- Min. 700mm phase
to earth
Primary winding wire- Double enamel-
Grade 3
The HT connecting terminal- L shape-
Tinned copper plate
GI material suitable for TATA POWER-
Mounting bracket for DDL poles to be provided for single pole
45
Auxiliary PT and double pole installation with
cantilever type arrangement
All hardware bolts shall be 8.8 grade in
all Autorecloser, Sectionaliser, and
46 Hardware bolts
accessories along with mounting
hardware.
The control panel should have inbuilt
firmware in hardware or relay with
feature that the same control panel can
be used for Autorecloser or Sectionaliser
with reprogramming of firmware. The
firmware updates and reprogramming
for ACR or SEC tutorials should be
provided by bidder.
The enclosure shall be made up of
stainless steel with IP55 tested for
protecting internal components against
electromagnetic, electrostatic and
47 Controller Cabinet environmental influence.
It should have pad lock provisions.
The control cabinet shall be of sufficient
size to accommodate the addition of a
4G/RF modem, customer SCADA wiring.
The controller shall have battery which
shall be charged by a temperature
compensated charging circuit, allowing
the battery to charge at an optimal rate
to extend battery life.
Shielded Control cable for connection
from pole top unit to controller cabinet

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 8 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

should be provided with length of


around 7 meter.
The control cable shall have easy plugin
and plug out male female plugs at both
ends.
The controller should have two pole
MCB for AC input from PT and DC MCB
for isolation of battery.
The wiring should be such that the
controller relay shall be powered up with
Aux. AC supply or charger dc supply and
in case of no power via auxiliary PT the
relay shall automatically take power
from battery. Battery shall take charging
power through charger.
The fuse protected DC supply for 4G/RF
modem to be provided.
The controller should monitor battery
voltage and provide alarm if the voltage
falls below 18V.
The input voltage should have inbuilt
surge protection.
All control wires shall be PVC, single core
copper, multi stranded, flexible wires
without any joints in between runs.
Control Wire identification with tubular
printed ferrules
Communication protocol- The controller
should be supplied with IEC104 protocol
and proprietary protocol is not accepted.
The unit shall include “flash” boot loader
that will support re-programming of the
main control unit firmware via RS232
serial port/Ethernet port
The controller internal PCB shall be
provided with conformal coating.
32 bit ARM Core CPU operating @
minimum 450 MHz
RAM-64 MB
Controller must have External DO
contact (to capture ON/OFF Status.)
Controller must have at least one TCP/IP
Ethernet port to for communication with

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 9 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

master station over IEC-60870-5-104


&MQTT.
Without external protocol converter.
Support IEC - 60870-5-104/MQTT for
communicating with master station.
Preferably support FTP protocol to
transfer disturbance recorder to remote
server.
Device should support periodic data
reporting configurable from 2 second to
1 hr interval and spontaneous data as
well.
Digital data should have higher priority
than Analog data. The dead band for
reporting Analog data by exception shall
be initially set to 1 % (in 1%) of full scale
value.
Multi-Master reporting- 8 masters with
single CSADU
Cyber security- User level
authentication, Disabling the DNS,
Disabling/enabling/ configurable
TCP/UDP port, PT Failure, Charger
Failure, Battery Failure/Door lock alarm
integrated to Controller
Event storage in internal memory of
controller.
Measurement event-10000
System Event- 1000
Alarm Event- 1000
Normal event- 5000
GPRS (2G/3/4G)/RF Modem to be
connected in one Ethernet port for
47 Modem/Router SCADA communication. Preferred
modem make -ARG-600 (ABB-2G/3G/4G
LTE)
The bidder should provide necessary
support for integration of field device
48 Integration with SCADA
with TATA POWER-DDL SCADA/ ADMS/
DA.
Bidder shall provide a software for
Software for re-
downloading all event and fault data at
49 programming and data
site and remotely via 4G modem. The
downloading
communication chord should be

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 10 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

provided for data downloading at site as


spare. Software should be compatible to
Windows 10 and latest operating
systems.
The Sectionaliser should have indication
on tank and controller showing the gas
leakage status, if the gas pressure in the
switchgear tank reduced then there shall
50 Sectionaliser be red flag on main tank which shall be
visible from 9 meter distance and
controller should show leakage status.
(Only manometer on tank shall not be
accepted being non visible from 9 meter)
5.0 GENERAL CONSTRUCTION

5.1 POLE TOP 5.1.1 The Autorecloser or Sectionaliser shall be made of stainless steel enclosure with
SWITCHGEAR lightweight design suitable for outdoor application with IP-55 degree of protection.
The Autorecloser/Sectionaliser shall consist of three pole assemblies where
vacuum bottles interrupt current, providing minimum and even contact wear, long
life and maximum reliability.
5.1.2 The cabinet shall house maintenance-free magnetic actuators, which provide the
required force to open and close the vacuum pole assemblies. The material of
insulating dielectric shall be HCEP Hydrophobic Cycloaliphatic Epoxy solid or
equivalent with superior hydrophobicity. The minimum acceptable Creepage
distance shall be 25 mm/kV.
5.1.3 Stud type Connectors shall be provided with the Autorecloser unit for connecting
the incoming and outgoing cables to the bushings. Necessary provisions shall be
provided for electrical close and electrical / manual trip. ON/OFF indication shall be
visible from outside from distance of around 9 meters.
5.1.4 The Autorecloser or Sectionaliser shall be supplied with necessary control cables
required for interconnection with Control cabinet.
5.1.5 The unit shall be designed for minimum 10,000 mechanical operations on load.
5.1.6 All current carrying components shall be of tinned copper inside tank.
5.1.7 For each terminals bolt should be provided with Cup or Belleville Washer and
flat washers. (Note- The cut spring washers are not accepted)
1 Temp rise above ambient of Type Tested as per IEC and complying to
50 deg. requirements)
1. Designed ambient temp. 1. Bidder to mention design ambient
2. Any de-rating temperature.
applicable at 50 deg 2. Bidder to provide de-rating chart for 45,
ambient 50 & 55 deg ambient temperature.
2 Tank material and grade of Should be of SS and non-corrosive, offered
SS and welding grade of SS to be mentioned. Minimum grade
shall be SS304. The welding shall be such that
there shall be corrosion of welding for useful
life of equipment.

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 11 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

5.2 CONTROL 5.2.1 Autorecloser control Panel Features,


PANEL DETAILS
a)Open (Separate LED and button)
b)Close (Separate LED and button)
Push buttons
c)Local/Remote
i) with indications
d) Autorecloser blocked or Auto – ON/OFF
LEDs
e)Protection – ON/OFF
f)Hot line tag- ON/OFF
a)Open (Separate LED)
b)Close (Separate LED)
c)Over current pickup with phase & ground
Indicating LEDs indication
ii) shall be provided b)Lockout
by bidder c)Unit status
d)Two user programmable LEDs
e)Contact & breaker health status
f)Battery & battery charger health status
a)Over current-Instantaneous & IDMT along with
different selection curves & DT
b)Earth fault - Instantaneous & IDMT along with
different selection curves & DT
c)Multiple settings group
d) Cold Load Pickup
e) Inrush Restraint
f) switching over from one protection group to
another with power flow direction –Automatically
g)Recloser function with high current lockout
h)Live load blocking
i)Loss of phase protection
Protective
j) Minimum TMS settings for IDMT element shall be
features shall be
iii) 0.01 for better relay co-ordination with upstream
provided by
breaker.
bidder
K) The high set/definite time delay shall have
minimum 20ms setting.
l) Auto reset of the relay after tripping wit definite
time of 1min. (All elements & LED should reset and
fault data shall be displayed)
m) Negative phase sequence element or equivalent
for detecting broken conductor or conductor open
without earth fault or with high resistance fault.
n)The fault labels should be easily readable like
reclose1, Trip1, High current Lockout, Overload
lockout etc. (Bidder to mention the details and get
approval before manufacturing of relay )

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 12 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

a)Current: Phase & Neutral


Metering
b)voltage: Phase to phase & Phase to Neutral
capabilities shall
c)KW- Single & Three phase
be provided by
d)KWh- Single & Three phase
bidder which
e)KVAr- Single & Three phase
iv) shall be
f) Power Factor
monitored
g)Frequency
through local &
h) Positive, Zero and Negative Sequence Currents
remote (using
i) Positive, Zero and Negative Sequence voltage
SCADA)
j)Load profile-current ,voltage & Power
Control shall a)Load profile, current, voltage , power for all three
operate on GPRS phases
technology & b)Peak demand current, voltage & Power values
shall have data c)Last 512 Operations
v)
recording d)Detailed fault information for last 128 trip
capabilities that operations
be download e)Data logging shall be on first in first out (FIFO)
remotely. basis
a)Remote On-OFF operation of recloser
b) On Front panel-RS232 Port/RJ485/Ethernet
c) Remote RJ485 port-The RJ 485 must have the
capability for multi-drop connectivity.
e) Radio RS232 Port. The port must include
Communication RTS/CTS handshaking for direct connection to a
features to be radio & delayed message flow control.
vi)
provided by f) TCP/IP Ethernet Port- 2 nos. One must be
bidder engineering port
g) Data Transmission Rate of TCP/IP Eathernet
Port- 10/100Mbps.
g) All ports shall be capable of simultaneous
operation & shall be optically isolated & protected
from surge.
a) LCD display that constantly shows metered
currents
b)After a trip or Lockout, the phase shall read the
phase currents, tripping current
c)A keypad for navigating the control unit
User interface d) All protective functions data records, metered
vii) provided by the values to be accessible & configurable through
bidder front panel.
e) It shall be possible to configure the protection
and control parameters from remote as well as
local, with appropriate authorization level.
f) Any protective setting or deletion on records will
require the use of a 4 digit password.
Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 13 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

g) Switches to disable electronic close & trip


operations shall be provided for safety.
5.2.2 Sectionaliser control Panel Features,
a)Open (Separate LED and button)
Push buttons with b)Close (Separate LED and button)
i)
indications LEDs c)Local/Remote
d)sectionalizing blocked/Auto
a) Open (Separate LED)
b)Close (Separate LED)
c) Over current pickup with phase & ground
Indicating LEDs shall
ii) indication
be provided by bidder
d) Gas leakage- LED
e) Contact & breaker health status
f) Battery & battery charger health status
a)Over current-Instantaneous & IDMT along
with different selection curves & DT
b)Earth fault - Instantaneous & IDMT along
with different selection curves & DT
c) Cold Load Pickup
d) Inrush Restraint
e) switching over from one protection group
to another with power flow direction –
Automatically
Protective features
f) Live load blocking
iii) shall be provided by
g) Minimum TMS settings for IDMT element
bidder
shall be 0.01 for better relay co-ordination
with upstream recloser.
h) The highest/definite time delay shall have
minimum 10ms setting.
i)Fault interrupt counter up to 4
j) Interruption detection logic shall be
combination of fault current threshold, source
voltage zero and load current zero for precise
sectionalizing of fault.
a)Current: Phase & Neutral
b)voltage: Phase to phase & Phase to Neutral
Metering capabilities
c)KW- Single & Three phase
shall be provided by
d)KWh- Single & Three phase
bidder which shall be
iv) e)KVAr- Single & Three phase
monitored through
f) Power Factor
local & remote (using
g)Frequency
SCADA)
h) Positive, Zero and Negative Sequence
Currents

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 14 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

i) Positive, Zero and Negative Sequence


voltage
j)Load profile-current ,voltage & Power
k)Load outage
a)Load profile, current, voltage , power for all
three phases
Control shall operate b)Peak demand current, voltage & Power
on GSM/GPRS values
technology & shall c)Last 512 Operations
v)
have data recording d)Detailed fault information for last 128 trip
capabilities that be operations
download remotely. e)Data logging shall be on first in first out
(FIFO) basis

a a)Remote On-OFF operation of recloser


b) On Front panel-RS232
Port/RJ485/Ethernet
c) Remote RJ485 port-The RJ 485 must have
the capability for multi-drop connectivity.
e)Radio RS232 Port. The port must include
Communication RTS/CTS handshaking for direct connection to
vi) features to be a radio & delayed message flow control.
provided by bidder f) TCP/IP Ethernet Port- 2 nos. One must be
engineering port
g) Data Transmission Rate of TCP/IP Eathernet
Port- 10/100Mbps.
g) All ports shall be capable of simultaneous
operation & shall be optically isolated &
protected from surge.
a)Two line LCD display that constantly shows
metered currents
b)After a trip or Lockout, the phase shall read
the phase currents, tripping current
c)A keypad for navigating the control unit
d) All protective functions data records,
metered values to be accessible & configurable
User interface
through front panel.
vii) provided by the
e) It shall be possible to configure the
bidder
protection and control parameters from
remote as well as local, with appropriate
authorization level.
f) Any protective setting or deletion on records
will require the use of a 4 digit password.
g) Switches to disable electronic close & trip
operations shall be provided for safety.
Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 15 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

6.0 NAME PLATE & All the components and operating devices of switchgear shall be provided with durable and
MARKING: - legible stainless steel (or anodised AL) nameplates containing all technical parameters.
Name plates shall be suitably embossed with” PO no. with date”, “PROPERTY OF Tata
Power-DDL, DELHI’ & “CODE NUMBER” along with the following information. (The
drawing of name plate shall contain following details)

a) Manufacturer’s Name
b) Model No.
c) Serial no.
d) Month and year of Mfg.(MM/YYYY)
e) PO Number and date
f) Rated Voltage
g) Rated current
h) System Frequency
i) Rated Short time withstand current
j) Rated Impulse withstand Voltage
k) Mechanical duty
l) Duty cycle
m) Weight
n) Property of ‘TATA POWER- DDL’

Customer care centre number and e-mail ID to be mentioned in the name plate.

Marking on Control Panel:

a) Manufacturer’s Name
b) Model No.
c) Serial no.
d) Month and year of Mfg.(MM/YYYY)
e) PO Number and date
f) Property of ‘TATA POWER- DDL’
7.0 TESTS FOR All the Routine and acceptance tests shall be carried out in accordance with the relevant
SWITCHGEAR IS/IEC standards. All routine/acceptance tests shall be witnessed by the purchaser/his
authorized representative. All the components within the switchgear enclosure shall have
been tested for Routine/acceptance and Type tests as per the relevant standards. All Type
tests as per latest IS / IEC shall have been carried out on the switchgear as a whole unit
as per relevant IS/IEC. Following tests shall be necessarily conducted on the equipment
and its components as specified in IEC.

Note- In case of any conflict on any technical particular in the specification, the stricter
requirement mentioned in the relevant standard shall be valid.

7.1 TYPE TESTS A. For Autorecloser:

Type Tests stipulated as Acceptance Clause


Sno Applicable standard
per Tender Spec. as per IS / IEC
Insulation (Dielectric Test) -
PF withstand voltage test
IEC 62271-111 & Cl 7.2.IEC 62271-
1 (Dry & Wet), Lightning
IEEEC37.60 111/ IEEEC37.60
Impulse voltage withstand
test.

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 16 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

Measurement of contact IEC 62271-111 & Cl 7.4 of IEC 62271-


2
resistance of Main Circuit IEEEC37.60 111/ IEEEC37.60
IEC 62271-111 & Cl 7.5 of IEC 62271-
3 Continuous current tests
IEEEC37.60 111/ IEEEC37.60
Short Time current and Peak
IEC 62271-111 & Cl 7.6 of IEC 62271-
4 current withstand tests Main
IEEEC37.60 111 & IEEEC37.60
Circuit
IEC 62271-111 & Cl 7.7 of IEC 62271-
5 Verification of the protection
IEEEC37.60 111 & IEEEC37.60
Cl 7.10 of IEC
Additional tests on auxiliary IEC 62271-111 &
6 62271-111 &
and control circuits IEEEC37.60
IEEEC37.60
Line-charging current and
Cl 7.101 of IEC
7 cable-charging current IEC 62271-111
62271-111
interruption tests
Cl 7.102 of IEC
IEC 62271-111 &
8 Making current capability 62271-111 &
IEEEC37.60
IEEEC37.60
Cl 7.103 of IEC
Rated short-circuit breaking IEC 62271-111 &
9 62271-111 &
current tests IEEEC37.60
IEEEC37.60
Cl 7.104 of IEC
IEC 62271-111 &
10 Low current tests 62271-111 &
IEEEC37.60
IEEEC37.60
Cl 7.106 of IEC
Partial discharge (corona) IEC 62271-111 &
11 62271-111 &
tests IEEEC37.60
IEEEC37.60
Cl 7.108 of IEC
IEC 62271-111 &
12 Time-current tests 62271-111 &
IEEEC37.60
IEEEC37.60
Cl 7.109 of IEC
IEC 62271-111 &
13 Mechanical duty tests 62271-111 &
IEEEC37.60
IEEEC37.60
Control electronic elements
IEC 62271-111 & Cl 7.111 IEC 62271-
14 surge withstand capability
IEEEC37.60 111 & IEEEC37.60
(SWC) tests
IEC 62271-111 & Cl 7.113 IEC 62271-
15 Thermal runaway test
IEEEC37.60 111 & IEEEC37.60
Clause 5, IEC-60529
IEC- 60529 & IEC
16 IP55 Test of Switchgear unit & clause 6.14,
62271-1
IEC62271-1
Clause 5, IEC-60529
IP55 Test of Controller IEC- 60529 & IEC
17 & clause 6.14,
Enclosure 62271-1
IEC62271-1

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 17 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

B. For Sectionaliser:

Type Tests stipulated as Acceptance Clause as


Sno Applicable standard
per Tender Spec. per IS / IEC
PF withstand voltage test,
Lightning Impulse voltage Cl 6.2 0f IEC62271-
1 IEC62271-103
withstand test for 103,
Switches, Dielectric Tests
Measurement of contact
2 IEC 62271-103 Cl 6.4 of IEC 62271-103
resistance
3 Temperature rise Test IEC 62271-103 Cl 6.5 of IEC 62271-103
Short Time current and
4 Peak current withstand IEC 62271-103 Cl 6.6 -IEC 62271-103
tests Main Circuit
5 Verification of protection IEC 62271-103 Cl 6.7 -IEC 62271-103
Short Circuit Breaking Cl 6.101, Table3 of IEC
6 IEC 62271-103
current tests LBS 62271-103
Short Circuit Making Cl 6.101.6.2, Table3 of
7 IEC 62271-103
current test on LBS IEC 62271-103
Mechanical Endurance Cl 6.102.2. - IEC 62271-
8 IEC 62271-103
tests on LBS 103
Cl 6.2.9 0f IEC62271-
9 Partial Discharge test IEC 62271-103
103,
Clause 5, IEC-60529 &
IP55 Test of Switchgear IEC- 60529 & IEC
10 clause 6.14, IEC62271-
unit 62271-1
1
Clause 5, IEC-60529 &
IP55 Test of Controller IEC- 60529 & IEC
11 clause 6.14, IEC62271-
Enclosure 62271-1
1
7.2 ROUTINE TESTS Following routine tests are to be done on 100% of the lot quantity,

1. Autorecloser: As per Clause 8 of IEC 62271-111 2019 & Clause 8 of IEC 62271-1

a) Dielectric withstand test: 1 min dry power-frequency;

b) Control, secondary wiring and accessory devices check tests;

c) Measurement of the resistance of main circuit;

d) Tightness tests;

e) Reclosing and overcurrent calibration;

f) Partial discharge test;

g) No-load mechanical operation test.

h) Reclosing & over current trip calibration

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 18 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

2. Sectionaliser : As per Clause 7 of IEC 62271-103, Clause 8 of IEC 62271-1

a) Dielectric withstand test; 1 min dry power frequency


b) Partial discharge test
c) Resistance Test of Main Circuit
d) design and visual checks
e) tests on auxiliary and control circuits
f) Control, secondary winding and accessory devices check tests
g) Mechanical operation tests

For other components, as per applicability. The RTC as per relevant IS/IEC from
Original Equipment manufacturer (OEM) shall be required:

a) Routine test report of the Relay/Controller


b) Modem
c) Auxiliary PT as per IS 3156
d) Surge Arrester as per IEC 60099 -4 (Inspection at OEM factory can be
conducted by TATA POWER-DDL team)
e) Isolator as per IS 9921 part 4 (Inspection at OEM factory can be conducted
by TATA POWER-DDL team)
7.3 ACCEPTANCE The following test and including test in ITP annexure-1 shall be carried out as acceptance
TEST test on random samples. Minimum 10% units (or minimum 2 nos. if lot size is small) of the
lot shall be selected for acceptance test shall be selected for testing from each offered lot.
The following shall be applicable as per relevant switchgear standards and this
specifications.

SNo. Tests details Applicable Acceptance Clause as per IS


Standards / IEC and specifications
1 PF withstand voltage test IEC62271-103 & Should withstand 28kV for
switches closed position IEC 62271-111 1minute
2 HV withstand test across IEC62271-103 & Should withstand 28kV for
with opened contact of IEC 62271-111 1minute
ACR/ SEC
3 Measurement of contact IEC62271-103 & Should be within limit of <150
resistance with closed IEC 62271-111 micro ohm for each phase.
switch condition
4 Tightness Test (Gas IEC 62271-1 For gas-filled systems tested in
leakage test for gas filled clause 8.5 factory, the probing test using a
switchgears) sniffing device to be done. The
sensitivity of the sniffing device
shall be at least 10-8 Pa × m3/s.
5 Partial discharge test IEC 62271-111 As per clause 8.102
6 Mechanical Operation test IEC62271-103 & As per requirements of this
IEC 62271-111 document & withstand 25
close open operations as per
clause no. 8.103 of IEC 62271-
111
a. 10 operation through
mechanical leaver.

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 19 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

b. 10 operation through
controller.
c. 5 operations through remote
server if applicable (as per
order) else through controller.
7 HV withstand test of control - Should withstand 2kV for one
and auxiliary circuits minute
8 Tests on auxiliary and IEC62271-103 & Control, secondary wiring and
control circuits IEC 62271-111 accessory devices shall be
checked to verify that all
connections have been made
correctly. Devices and relays, if
needed, shall be checked by
actual operation where
feasible. Those circuits for
which operation is not feasible
shall be checked for continuity.
9 Insulation resistance test - With open contacts and closed
contacts of switches. With be in
Giga-ohms.
10 Dimensional & Visual - As per approved drawing and
Checks technical compliance
document for tender &
operation requirements.
11 Vacuum Bottle OEM & RTC Ensure the Vacuum bottle
Make as per approved drawing
& GTP.
12 Reclosing and overcurrent IEC 62271-111 As per clause 8.101 and
trip calibration specification protection
requirements.
13 Compatibility & data All desired functionality shall be
integration check after checked along with auto-
operations, alarms and reclosing and opening. The
reset check relay data and RTU
configuration shall be verified
bidder to keep ready with all
details.
14 The same controller usages Autorecloser and Sectionaliser
for Autorecloser and functioning on same controller
Sectionaliser with firmware update shall be
checked as acceptance of
Sectionaliser as per
specification requirements.
15 Other components, as per As per the requirement of order
applicability, the RTC as per & approved documents,
relevant IS/IEC from
Original Equipment 1. Routine test report of the
manufacturer (OEM) to be Relay/ Controller and
shared for 1.Routine test Functionality shall be as per
report of the Relay/ specification requirements and
Controller approved documents.
2. Modem

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 20 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

3. Auxiliary PT as per IS 2. Modem (Shall be among


3156 approved makes and models)
4. Surge Arrester as per IEC 3. Auxiliary PT as per IS 3156
60099 (Inspection at OEM and approved technical
factory can be conducted by documents
TATA POWER-DDL team) 4. Surge Arrester as per IEC
5.Isolator as per IS 9921 60099 -4 (Inspection at OEM
part 4 (Inspection at OEM factory can be conducted by
factory can be conducted by TATA POWER-DDL team with
TATA POWER-DDL team) destructive tests)
5.Isolator as per IS 9921 part 4
(Inspection at OEM factory can
be conducted by TATA
POWER-DDL team with
operational test as other IS
tests)
8.0 TYPE TEST The Bidder shall furnish the type test certificates of same design as offered in bid for the
CERTIFICATE tests as mentioned above as per the corresponding standards. All the tests shall be
conducted at CPRI/ERDA or International accredited Laboratory like KEMA as per the
relevant standards of IEC/IEEE. Type tests shall have been conducted in certified Test
laboratories during the period not exceeding 5 years from the date of opening the bid. In
the event of any discrepancy in the test reports, i.e. any test report not acceptable or any/all
type tests (including additional type tests, if any) not carried out, same shall be carried out
without any cost implication to TATA POWER-DDL.

Bids without all type test reports shall stand disqualified.

9.0 PRE-DISPATCH Equipment shall be subject to inspection by a duly authorized representative of the TATA
INSPECTION POWER-DDL. Inspection may be made at any stage of manufacture at the option of the
purchaser and the equipment if found unsatisfactory as to workmanship or material is liable
to rejection. Supplier shall grant free access to the places of manufacture to TATA
POWER-DDL’s representatives at all times when the work is in progress. Inspection by the
TATA POWER-DDL authorized representatives shall not relieve the supplier of his
obligation of furnishing equipment in accordance with the specifications.

The first time supplies (new bidder or new models or change of design from previous
supplies) shall be applicable for prototype inspection after CAT-B drawing approval and
before mass manufacturing. In prototype manufacturing bidder have to make one or two
sample product for inspection after CAT-B approval of drawings after award of RC/PO.

Material shall be dispatched after specific MDCC (Material Dispatch Clearance Certificate)
is issued by TATA POWER-DDL. Following documents shall be sent along with material

a) Routine Test reports


b) MDCC issued by TATA POWER-DDL
c) Invoice in duplicate
d) Packing list
e) Drawings
f) Delivery Challen
g) Installation and maintenance Manual soft copy for all componants
h) Other Documents (as applicable)

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 21 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

10.0 INSPECTION The material received at TATA POWER-DDL Store/Site will be inspected for acceptance
AFTER RECEIPT and shall be liable for rejection if found different from the reports of the pre-dispatch
AT STORE inspection. If any deviation or anomaly observed at this stage same need to be rectified by
bidder at bidders own cost at earliest.
11.0 GUARANTEE 1. Bidder shall stand guarantee towards design, materials, workmanship & quality of
process / manufacturing of items under this contract for due and intended
performance of the same, as an integrated product delivered under this contract. In
the event any defect is found by the Purchaser up to a period of at least 12 months
from the date of commissioning or 18 months from the date of last supplies made
under the contract whichever is earlier, Bidder shall be liable to undertake to
replace/rectify such defects at its own costs, within mutually agreed time frame, and
to the entire satisfaction of the Purchaser, failing which the Purchaser will be at liberty
to get it replaced/rectified at Bidder’s risks and costs and recover all such expenses
plus the Purchaser’s own charges (@ 20% of expenses incurred), from the Bidder or
from the “ Security cum Performance Deposit” as the case may be.

2. In case of GP failure, BA shall report at site within 48 hours from intimation and
arrange for rectification of fault within a mutually agreed time. In case rectification at
site is not possible then alternative arrangement (replacement) to be made by BA
within 15 days of intimation of failure. The SLA shall be as per attached.

3. Bidder shall further be responsible for ‘free replacement’ for another period of THREE
years from the end of the guarantee period for any ‘Latent Defects’ if noticed and
reported by the Purchaser.
12.0 PACKING Bidder shall ensure that all equipment covered by this specification shall be prepared for
rail/road transport (local equipment) and be packed in such a manner as to protect it from
damage in transit. The packing should be in such manner that during storage and its
components should not be damaged. No single use plastic to be used in packing
material. Packing should be done with environment friendly recyclable materials.
13.0 TENDER Not applicable. Bidders to mention offered model number along with GA drawing during
SAMPLE tender for each variant & provide demo or link of equipment details video.

14.0 TRAINING The bidder shall arrange to provide the installation and operating training at TATA
POWER-DDL offices as and when required for better installation and usage of the product.
It is preferred that the service engineer present during installation shall arranged to provide
the operation training to the staff during installation and inform about the critical points.
15.0 QUALITY The bidder shall submit with the offer, assurance plan indicating the various stages of
CONTROL inspection, the tests and checks which will be carried out on the material of construction,
components during manufacture and after finishing, bought out items and fully assembled
component and equipment including drives. As part of the plan, a schedule for stage and
final inspection within the parameters of the delivery schedule shall be furnished. The
Purchaser's or its nominated representative engineer shall have free access to the
manufacturer/sub-supplier's works to carry out inspections. To ensure proper operation of
Product the bidder shall provide onsite training of TATA POWER-DDL teams as and when
required. To ensure quality of installations bidder shall provide supervision support during
impartation.

16.0 TESTING Bidder shall have adequate in house testing facilities for carrying out all routine tests,
FACILITIES acceptance tests and special test as per this document and accordance to relevant
International / Indian standards as mentioned. The bidder shall have in-house helium gas
leakage detection system and all RMU main tank shall be checked for leakages.

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 22 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

17.0 MANUFACTURING 1. The successful bidder will have to submit (after placement of RC) technical
ACTIVITIES compliance document and drawing of cable as per RC line items for getting approval
before mass manufacturing.
2. Manufacturing mass quantity to start only after getting CAT-A approved drawings or
as per intimation from Tata POWER-DDL.
3. The first time supplies (new bidder or new models or change of design from previous
supplies) shall be applicable for prototype inspection after CAT-B drawing approval
before mass manufacturing. In prototype manufacturing bidder have to make one or
two sample unit for inspection after CAT-B approval of drawings.
18.0 SPARES, Bidder shall provide a list of recommended spares with quantity and unit prices for 5 years
ACCESSORIES & of operation after commissioning.
SPECIAL TOOLS /
GAUGES TATA POWER-DDL may order all or any of the spare parts listed at the time of contract
award and the spare parts so ordered shall be supplied as part of the definite works. TATA
POWER-DDL may order additional spares at any time during the contract period at the
rates stated in the Contract Document.

The communication cable for accessing controller from laptop to be provided by bidder as
spare item for minimum 2 numbers.
19.0 DRAWINGS & Following drawings and documents shall be prepared based on TATA POWER-DDL
DOCUMENTS specifications and statutory requirements and shall be submitted with the bid:

a)Completely filled in Technical Particulars and clause compliance


b)Any deviation sheet or No deviation
c)General description of the equipment and all components including brochures.
d)General arrangement for drawing of switchgear
e)GA drawing of controller with internal details
f)Mounting drawing on single pole and double pole structure
g)Experience List
h)All set of Type test certificates & detailed reports for offered design of each
variant
Drawings / documents to be submitted for approval after the award of the contract
are as under:
Sl. No. Description For For Review/
Approval Information
1 General Technical Compliance to 
this document
2 General Arrangement drawings 
3 Bill of materials 
4 Control wiring diagram and 
arrangement in control cubicle
5 The Auxiliary PT, LA, isolator 
technical details and drawings.
6 Installation & Maintenance 
Instructions and manual

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 23 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

All the documents & drawings shall be in English language. After the receipt of the order,
the successful bidder will be required to furnish all detailed drawings of components for
TATA POWER-DDL approval.

Instruction Manuals: Bidder shall furnish softcopies and one hard copy manuals in English
language covering installation and maintenance instructions and all relevant information
and drawings pertaining to the main equipment as well as auxiliary devices.

20.0 GENERAL
Bidder to submit compliance to all above clauses and sub-clauses and shall furnish all
TECHNICAL
desired details as technical compliance document.
PARTICULARS

21.0 SCHEDULE OF (TO BE ENCLOSED WITH TECHNICAL BID)


DEVIATIONS
All deviations from this specification shall be set out by the Bidders, clause by Clause in
this schedule. Unless specifically mentioned in this Schedule, the tender shall be deemed
to confirm the purchaser's specifications:

S.No. Clause No. Details of deviation with


justifications

We confirm that there are no deviations apart from those detailed above.

Seal of the Company:

Designation

Signature

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 24 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

Annexture-1
Inspection Test Plan (ITP)
Applicable Acceptance Clause as per IS / IEC and
SNo Tests details
Standards specifications
PF withstand voltage test switches closed IEC62271-103 &
1
position IEC 62271-111 Should withstand 28kV for 1minute
HV withstand test across with opened IEC62271-103 &
2 Should withstand 28kV for 1minute
contact of ACR/ SEC IEC 62271-111
Measurement of contact resistance with IEC62271-103 & Should be within limit of specs of <150 micro
3
closed switch condition IEC 62271-111 ohm.
For gas-filled systems tested in factory, the
Tightness Test (Gas leakage test for gas IEC 62271-1 probing test using a sniffing device to be done.
4
filled switchgears) clause 8.5 The sensitivity of the sniffing device shall be at
least 10-8 Pa × m3/s.
5 Partial discharge test IEC 62271-111 As per clause 8.102
As per requirements of this document &
withstand 25 close open operations as per
clause no. 8.103 of IEC 62271-111
IEC62271-103 &
6 Mechanical Operation test a. 10 operation through mechanical leaver.
IEC 62271-111
b. 10 operation through controller.
c. 5 operations through remote server if
applicable (as per order) else through controller.
HV withstand test of control and auxiliary
7 - Should withstand 2kV for one minute
circuits
Control, secondary wiring and accessory devices
shall be checked to verify that all connections
IEC62271-103 & have been made correctly. Devices and relays, if
8 Tests on auxiliary and control circuits
IEC 62271-111 needed, shall be checked by actual operation
where feasible. Those circuits for which operation
is not feasible shall be checked for continuity.
With open contacts and closed contacts of
9 Insulation resistance test -
switches. With be in Giga-ohms.
As per approved drawing and technical
Dimensional & Visual Checks
10 - compliance document for tender & operation
requirements.
Ensure the Vacuum bottle Make as per approved
11 Vacuum Bottle OEM & RTC
drawing & technical documents.
As per clause 8.101 and specification protection
12 Reclosing and overcurrent trip calibration IEC 62271-111
requirements.
All desired functionality shall be checked along
Compatibility & data integration check with auto-reclosing and opening. The relay data
13
after operations, alarms and reset check and RTU configuration shall be verified bidder to
keep ready with all details.
Autorecloser and Sectionaliser functioning on
The same controller usages for same controller with firmware update shall be
14
Autorecloser and Sectionaliser checked as acceptance of Sectionaliser as per
specification requirements.

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL


F02 (PEG-P-102)
Rev No.00
Eff. Date: 01.04.19
TATA POWER DELHI DISTRIBUTION LIMITED, DELHI
TECHNICAL SPECIFICATION
Document Title Technical Specification of 11kV Pole Mounted Autorecloser & Sectionaliser with Accessories
Document No. ENG-HV-2013 Eff. Date: 15.05.2020
Revision No. 00 Page 25 of 29
Prepared by: Reviewed By: Approved By: Issued By:
Ravindra Bhanage Vinoth Kumar Sanjeev Kumar Atri / Brajanath Dey Parveen Verma

As per the requirement of order & approved


documents,
Other components, as per applicability, the
RTC as per relevant IS/IEC from Original 1. Routine test report of the Relay/ Controller and
Equipment manufacturer (OEM) to be Functionality shall be as per specification
shared for 1.Routine test report of the requirements and approved documents.
Relay/ Controller 2. Modem (Shall be among approved makes and
2. Modem models)
15 3. Auxiliary PT as per IS 3156 - 3. Auxiliary PT as per IS 3156 and approved
4. Surge Arrester as per IEC 60099 technical documents
(Inspection at OEM factory can be 4. Surge Arrester as per IEC 60099 -4 (Inspection
conducted by TATA POWER-DDL team) at OEM factory can be conducted by TATA
5.Isolator as per IS 9921 part 4 (Inspection POWER-DDL team with destructive tests)
at OEM factory can be conducted by TATA 5.Isolator as per IS 9921 part 4 (Inspection at
POWER-DDL team) OEM factory can be conducted by TATA
POWER-DDL team with operational test as other
IS tests)

Initiator HoG (Plant Engineering-1)

Property of Tata Power-DDL – Not to be reproduced without permission of Tata Power-DDL