Type RXTCS: Trip Circuit Supervision Relay
Type RXTCS: Trip Circuit Supervision Relay
Station
Automation
Type RXTCS
& Protection
11
UAUX 17
18
12
21
13 22
Trip 23
V 0.6s
contact I
14
24
15
25
V 26
I
27
Breaker 16 28
Fault OK
Red Green
52a 52b Contact position is shown for un-energized state
Trip
coil
15 15 15
V V V
I I I
16 16 16
TC TC TC
Fig. 2. Supervision in Pre-close condition Fig. 3. Supervision in Post-close condition Fig. 4. Supervision with latched trip relay
Technical data
Energizing quantities, rated values and limits
Rated Voltage of supervised and
auxiliary circuit UAUX : 24,30, 48,110-125, 220-250,V ac or dc
Operative voltage range : 80-110% of rated UAUX
Permitted ambient temperature range : 00 C to +550 C
Pick-up & Drop-off current : 0.3 - 0.7 mA
at rated voltage UAUX& 25 0 C
Operate (Drop-off) time : 0.6 - 0.7 sec.
at rated voltage UAUX & 250 C
Burden at rated voltage 24 30 48 110 125 220 250
Auxiliary circuit (W) 1 1.3 1.4 2 2.5 2.7 3.5
Supervision circuit (W) 0.08 0.08 0.15 0.25 0.32 0.54 0.7
Contact data
Contact configuration (self reset) : 1 N/O +1 N/C +2C/O
Max voltage within a contact system : 250 V dc / ac
Rated current : 5 A.
Make and carry for 0.5 s : 10 A
Make and carry for 3.0 s : 8A
Breaking capacity for dc with circuit : 1A/0.25A/0.15A
time-constant L/R # 40 ms, at 48/110/220 Vdc
Electrical endurance : 10,000 operations, at 110 V dc, 0.35A resistive,
tested according to IEC 255-23 360 op/hr
Electrical tests
Temperature-rise; Tested acc. to IEC 255-6 : Enclosure, pcb relays, heat dissipating components
Insulation resistance; Tested acc. to IEC 255-5 : >100 M Ohm at 500 V dc
Dielectric; Tested acc. to IEC 255-5 : 2,0 kV, 50 Hz, 1 min
Impulse; Tested acc. to IEC 255-5 : 5 kV, 1,2/50us, 0,5J
1 MHz burst disturbance test acc. to IEC 255-22-1 : Class III
- common mode : 2,5 kV, 1 MHz, 400 pls/s
- differential mode : 1 kV, 1 MHz, 400 pls/s
Technical data (Cont)
Electrostatic discharge test acc. to IEC 255-22-2 : Class III
- contact discharge : 6 kV, 150 pF/330 ohm
- air discharge : 8 kV, 150 pF/330 ohm
Fast transient disturbance test
acc. to IEC 255-22-4 : Class IV
- common mode : 4 kV, 5/50 ns, 5kHz, Rs = 50 ohm
Surge immunity test acc. to IEC 255-22-5 Class III
- common mode : 2 kV, 1,2/50 us, Rs = 10 ohm
- differential mode : 1 kV, 1,2/50 us, Rs = 2 ohm
Environmental tests
Vibration response and endurance
Tested acc. to IEC 255-21-1 : Class I, 10......150Hz
Shock response and endurance
Tested acc. to IEC 255-21-2 : Class I, 11 ms
Dry heat; test acc. to IEC 68-22-2 : +550 C /+700 C
Dry cold; test acc. to IEC 68-2-1 : -100 C / -250 C
Damp heat (cyclic - 12+12 Hr) : 12 Hr/550 C + 12 Hr/250 C x 6 days at 95% RH
test acc. to IEC 68-2-30
Ordering details:
Relay type Contact Rate voltage Article no
RXTCS 1N/O+1N/C+2C/O 24 1MYN569698-A
30 1MYN569698-B
48 1MYN569698-C
110-125 1MYN569698-E
220-250 1MYN569698-G
Connection diagram and Contact configuration
17
UAUX 18
13 11 12
Trip
Contact 21
14 22
15 23
16
24
Trip
25
coil
26
27
28
Dimensions
6C
67
85
2U
41 135
Station
Automation