Coordination tables between Merlin Gerin circuit breakers

and Telemecanique Canalis busbar trunking systems


Cascading and reinforced discrimination

voltage: 380/415 V source

E39614E
upstream
circuit-breaker

level of protection
of the upstream upstream busbar
busbar trunking canalisation
reinforced cascading
and discrimination
between the 2 circuit-
breakers

downstream
circuit-breaker

reinforced protection downstream


of the downstream busbar trunking
busbar trunking

rated current of the upstream busbar trunking: 1200 and 1350 A


Upstream circuit breaker C1251N C1251N
Associated trip unit STR35SE / STR55UE STR45AE
Upstream busbar trunking KTA-12 / KTC-13 KTA-12 / KTC-13
1200 and 1350 A 1200 and 1350 A
Level of protection of the 50 50
upstream busbar trunking (kA)
Downstream circuit breaker NS100N NS160N NS250N NS400N NS630N NS100N NS160N NS250N NS400N NS630N
Associated trip unit TMD / STR22SE STR23SE / STR53UE TMD / STR22SE STR23SE / STR53UE
Downstream busbar trunking KSA KSA KSA KSA / KVA / KVC KSA KSA KSA KSA / KVA / KVC
100 A 160 A 250 A 315 - 400 A 500 - 630 A 100 A 160 A 250 A 315 - 400 A 500 - 630 A
Discrimination limit between
upstream and downstream
circuit breakers (kA) 50 50 50 45 40 50 50 50 50 50
Reinforced breaking capacity
of the downstream
circuit breaker (kA) 50 50 50 50 50 50 50 50 50 50
Reinforced protection of the
downstream busbar trunking(kA) 25 50 50 50 50 25 50 50 50 50

Upstream circuit breaker C1251N C1251N


Associated trip unit STR35SE / STR55UE STR45AE
Upstream busbar trunking KTA-12 / KTC-13 KTA-12 / KTC-13
1200 and 1350 A 1200 and 1350 A
Level of protection of the 50 50
upstream busbar trunking (kA)
Downstream circuit breaker NS100N TMD / STR22SE NS100N TMD / STR22SE
Associated trip unit 40 A 63 A 100 A 40 A 63 A 100 A
Downstream busbar trunking KN KN KN KN KN KN
40 A 63 A 100 A 40 A 63 A 100 A
Discrimination limit between
upstream and downstream
circuit breakers (kA) 50 50 50 50 50 50
Reinforced breaking capacity
of the downstream
circuit breaker (kA) 50 50 50 50 50 50
Reinforced protection of the
downstream busbar trunking(kA) 50 50 50 50 50 50