1 - Electrical Distribution System Components
1 - Electrical Distribution System Components
Syllabus
Lecture.1 Electrical disturbuation system components
Lecture.2 Electrical disturbuation system components
Lecture.3 Load charcterstics
Lecture.4 Load forecasting
Lecture.5 Various distribuation systems
Lecture.6 Feeders and disturbutors
Lecture.7 Test (1)
Lecture.8 Choise of econmic cross section area
Lecture.9 Capacitors and power factor improvement
Lecture.10 Tariffs
Lecture.11 Harmonics
Lecture.12 Earthing systems
Lecture.13 Test (2)
TEXT BOOK:
1- Electric power generation, transmission and distribution
S.N.Singh
2- Electric power disturbuation system engineering
Turan Gonen
3- Electrical Technology- B.L. Theraja & A.K. Theraja
4- Principles of Power System by V K Mehta & Rohit Mehta
Electrical disturbution system components
In general the electrical power system include three main components
1- Generation
2- Transmission
3- Distribuation
Distrubuation systems represent an important parts in the electrical grids and for this
reasons the electrical companies delicate approximately 40% of the captical investment for
distribuation systems while the remian is given to generation and transmission (40%
generation & 20% transmission. The distribuation system is particularly important for an
electrical utility for two reasons:
1- Its the close part to the custmors and any fialure in distribuation system affect the
custmor directly. For example fialures in transmission and generation sections may not
cause custmor service interruptions.
2- Its high investment cost
Distribution Substations
Substation is important part of power system. The main task of substation is to convert the
voltages in order to match the transmission and distribution levels.
Roles of substations
1- Facilitate the connection of different generation station into electrical power grid.
2- Step down the high and medium voltages to value suitable for distribution at the
customers’ level.
3- Regulate the power system voltage using the tap changer with the power transformer,
capacitors and reactors (the devices lactated at the substation).
4- Facilitate the regional interconnection for neighbouring electrical grids.
5- Facilitate the disconnection of some of subsystem (such as transformer, transmission
line) to achieve maintenance, programming tests or even extension works using
disconnection switches at the substation.
Substation location: To select ideal location for a substation, the following rules should
be observed:
1- Locate the substation as much as feasible close to the load centre of its service area.
2- Locate the substation such that proper voltage regulation is obtained without extensive
measurement.
3- Locate the substation such that it provides proper access for incoming subtransmission
lines and outgoing primary feeders.
4- The substation location should provide enough space for the future substation
expansion.
5- The selected location should not oppose the land use regulations, local ordinances and
neighbours.
6- The selected location must help to minimize the number of customers affected by any
services discontinuity.
Substations types: There are two main types of substations:
Transmission substations: These substations transform the high transmission voltage into
lower high voltage or even medium voltage before delivering the power to distribution
centres.
Distribution substations: Always step down the medium sub-transmission voltages to low
voltage suitable for distribution purposes.
In general the substations are divided according to their nature and design into:
a- Air Insulated substation (AIS) : all the circuits are located in the external space and the
circuits are isolated using the air.
b- Gas Insulated Substations (GIS)—: substations that enclose high voltage bus,
switches, and breakers in containers filled with SF6 gas. GISs greatly reduce the
substation footprint and protect equipment from many causes of equipment failures.
Substation components
1- Power Transformers: Step down the voltages before distribute the electrical power
into load centres. The ratio of primary windings to secondary winding determines the
voltage reducing. This ratio can be adjusted up or down with tap changers located on
secondary windings. 3-phase transformer is commonly used although 3 individual
single phase transformer can be used.
2- Circuit breakers: Open or close the circuit under normal as well as fault conditions.
It designed to operate manual or by remote control under normal conditions and
automatically under fault conditions. The common used circuits’ breakers are SF6 CB.
3- Isolating Switch (Insulator): Switches used to visibly isolate parts of a substation
during maintenance. An isolator is knife switch and design to operate under no-load.
4- Bus-bars: Rigid copper or aluminium bar conductor of rectangular cross section area
used collect the electrical power before distributed it into primary feeders. The
incoming and outgoing lines in sub-station are connected to the bus-bars. The most
commonly used bus-bars arrangements in sub-station are:
(a) Single bus-bar arrangement
(b) Double bus-bar arrangement
(c) Single bus-bar arrangement with sectionalisation
5- Voltage and current transformers
Special transformers use for measuring and protection purpose. There always step down
the current and voltage to values suitable for measuring and protection devices. Voltage
transformers and current transformers are commonly referred as VTs and CTs
6- Capacitors and reactors:
There can be connected in series or parallel and used for voltage regulation by generation
or absorbing the reactive power.
7- Lighting arresters:
They are used to protect the substation devices from the high voltage generated due the
lighting stroke the substation.
8- Earthing switches:
This switches use during maintenance to ground the device in order to protect the power
system engineers.
9- Protection and measurement panels
10- Control panel and communication devices
11- Batteries to supplies protecting and measuring relays.
12- Current limiting reactors uses to limit the fault currents
13- Line trap
Uses to protect the substation from high voltages generated due to switching of the
breakers.
Substation bus schemes
There are several bus-bar arrangements which can be used in substations. The choice of
particular arrangement is is based on safety, reliability, economy, simplicity and other
consideration. The most commonly used substation bus schemes are:
a- Single bus-bar system
Consists of single bus-bar and all incoming and outgoing lines are connected to it. The
advantages of this type are low cost, less maintenance and simple operation. The
disadvantage is the complete outage during maintenance and fault in the bus-bar.
d. Ring Bus
The breakers are so connected and form a ring. There are isolators on both sides of each
breaker. Circuits terminate between the breakers. The number of breakers is same as the
numbers of circuits. Each of the circuits in ring bus system is fed from both sides. Any of
the breakers can be opened and isolated for maintenance without interrupting any of the
circuits. A fault on any of the circuit is isolated by tripping of two breakers on both sides
of the circuit. By tripping the two breakers only the faulted circuit is isolated and all other
circuits continue to operate in open ring state. This scheme has good operational flexibility
and high reliability.
e. Main and transfer bus system
In this scheme one more bus is added. In this arrangement one more breaker may be used,
known as tie circuit breaker. No circuit is associated with this tie breaker. When the tie CB
is not present, for maintenance of a circuit breaker, the transfer bus is energized by closing
the isolator switches to transfer bus. Then the breaker to undergo maintenance is opened
and isolated (opening isolators on both sides of CB) for maintenance.
Where S4 is kilovolt ampere load served by one of the four feeders emanating from a feed
point. A4 is the area served by one of the four feeders emanating from a feed point (m 2). D
is the load density. And l4 is dimension of the primary feeder serve area.
Assume uniform distributed load, the voltage drop at main primary feeder is:
In this equation the total lumped load is assumed to be located at a distance of 2/3l from
central feed point. K constant k is found from conductor voltage drop graph.
If the served area is extend to hexagonally shaped served area supplied by six feeders from
fed central point as shown in Fig.8. each feeder is feed area equal to 1/6 of the
hexagonally
The total lumped load is located at distance of 2/3l from the feed point. voltage drop is:
For hexagonlly seved area, the total area served bt all four feeders
The relation between the served areas of four and six feeders is found under two assuption
1- Feeder circuit are thermaly limited 2- Feeder circuit are voltage drop limited
Thermaly limited (That mean I4=I6)
Than
The six feeder area could carry 1.5 time as much as four feeder if they are thermaly
limited
Voltage drop limited
Dividing equationS
The six feeder area could carry 1.25 time as much as four feeder if they are voltage drop
limited
K constant: The K conatant can be devied using the conductor voltage drop graph
Figure 10 Radial type primary feeder with tie and sectionalizing switches
Figure 12 show another type of the modified primary feeder with express feeder and
backfeed. The section between the substation low voltage bus and the load center of the
service area is called an express feeder. No subfeeders or laterals are allowed to tapped off
the express feeder. However a subfeeder is allowed to provide a backfeed toward the
substation from the load center.
Figure 11 Radial type primary feeder with express feeder and backfeed
Figure 12 shows the redial type phase-area feeder arrangement in which each phase the
three-phase feeder serves its own service. In fig 11 and 12 each dot represents a balanced
three-phase load limped at that location.