3. Example Of Numerical Application: ==> Pn = 2200kW - cosϕ = 0.8 ==> ==> ==> ==> ==> ==> ==>

This document provides an example numerical application of motor protection settings for a MiCOM P220 relay. It includes network and motor data, such as cable length, transformer ratios, motor power rating and currents. It also lists the protection elements configured in the relay, including thermal overload, short circuit and earth fault settings, as well as assignment of outputs to indicators and alarms.

Uploaded by

Kunjan Dalwadi
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views

3. Example Of Numerical Application: ==> Pn = 2200kW - cosϕ = 0.8 ==> ==> ==> ==> ==> ==> ==>

This document provides an example numerical application of motor protection settings for a MiCOM P220 relay. It includes network and motor data, such as cable length, transformer ratios, motor power rating and currents. It also lists the protection elements configured in the relay, including thermal overload, short circuit and earth fault settings, as well as assignment of outputs to indicators and alarms.

Uploaded by

Kunjan Dalwadi
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Technical Guide P220/EN AP/B43

Application Guide
MiCOM P220 Page 25/40

3. EXAMPLE OF NUMERICAL APPLICATION


3.1 Network data
• MiCOM P220 current input ranges:
− Phase current input : In = 5 A ;
− Earth current input : Ion = 1 A
• Breaking device type : circuit breaker
• Maximum value of the three-phase short-circuit current on the busbars 6.2 kV:
Icc3φ = 9 kA
• Neutral point connection mode for the network 6.2 kV : by a resistance limiting
the maximum value of the earth fault current to 30 A
• Length of the feeder cable connecting the motor to the busbars 6.2k V : 100 m
• Measuring transformers :
− CT ratio: 300 / 5A
− Core balance CT connection: ratio 25
• "Speed switch" device available
3.2 Motor data:

Induction motor:
– rated power ==> Pn = 2200kW - cosϕ = 0.8
– rated voltage ==> Vn = 6.2kV – 50 Hz
– rated current ==> In = 256 A
– open-circuit (no-load) current ==> Ino-load = 134A
– start-up type (direct-on -line, soft) ==> Direct
– start-up current ==> ---
– direct start-up current (if soft start used) ==> Id = 5.4*In i.e. 1382A
– start-up time ==> td = 4 s
– maximum repetition frequency of starts ----> Hot = …x 2, cold = …x 3
– withstand time for locked rotor (for hot & cold start) ----> 2s
– heating curve ==> ---
– time-constants of: heating , start-up, cooling- down ==> 14min, 10min, 28min
– transient characteristic curve at unbalance ----> ---
– permanent allowable unbalance ----> ---
– motor service use (driven equipment: compressor, ==> pump
crasher, mill, pump, fan...)
– start-up : no-load/ load ----> no-load
(30 s loading after the end of
start-up)
P220/EN AP/B43 Technical Guide
Application Guide
Page 26/40 MiCOM P220

3.3 List of settings:


OP PARAMETERS Menu

Password AAAA
Reference ALST
Frequency 50 Hz

CONFIGURATION Menu
CONFIG.SELECT Submenu

Change Group Input EDGE


Setting Group 1
Default display % I LOAD
Start detection criterion 52A (closing of the breaking
device)
Analogue output type (optional) 4 - 20 mA
Value transmitted by the analogue output (optional) % I LOAD
RTD type (optional) PT100

CT RATIO Submenu

Primary rating of the phase CT 300


Secondary rating of the phase CT 5
Primary rating of the earth CT 25
Secondary rating of the earth CT 1

LED 5, LED 6, LED 7 and LED 8 Submenus LED 5 LED 6 LED 7 LED 8
Assignment: thermal tripping (overload) No No Yes No
Assignment: thermal alarm θALARM No No No Yes
Assignment: tI>> Yes No No No
Assignment: tIo> Yes No No No
Assignment: tIo>> Yes No No No
Assignment: tIi> Yes No No No
Assignment: tIi>> Yes No No No
Assignment: tI< Yes No No No
Assignment: tIstart (excessively long start) No Yes No No
Assignment: tIstall (stalled rotor when running) No Yes No No
Assignment: locked rotor at start No Yes No No
Assignment: emergency restart No No No No
Assignment: forbidden start No No No Yes
Assignment: tRTD1 ALARM, tRTD2 ALARM, tRTD3 ALARM No No No Yes
(optional)
Assignment: tRTD1TRIP, tRTD2 TRIP, tRTD3 TRIP (optional) No No Yes No
Technical Guide P220/EN AP/B43
Application Guide
MiCOM P220 Page 27/40

LED 5, LED 6, LED 7 and LED 8 Submenus LED 5 LED 6 LED 7 LED 8
Assignment: tRTD4 ALARM, tRTD5 ALARM, tRTD6 ALARM No No No Yes
(optional)
Assignment: tRTD4 TRIP, tRTD5 TRIP, tRTD6 TRIP (optional) No No Yes No
Assignment: Thermist 1 and Thermist 2 (optional) No No No No
Assignment: tEXT1 No No No No
Assignment: tEXT2 No No No No
Assignment: motor stopped No No No No
Assignment: motor running No No No No
Assignment: successful start No No No No

Configuration Inputs submenu

Inputs : 54321 11111

COMMUNICATION MODBUS Menu

Communication enabled ? Yes


Data transmission rate 19 200 Bauds
Parity No
Number of data bits 8
Number of stop bits 1
Relay address 1
Date Format PRIVATE
Programming for Group No.1 of PROTECTION Menu:
THERM.OVERLOAD[49] Primary Secondary
Comments
Submenu setting setting
Thermal overload function
Yes
enabled ?
Thermal inhibition on start
No
enabled ?
5.5% of overload authorised
Threshold Iθ> 270 A 0.9In (CT)
= 1.055 x In(motor)
Ke 3
Te1 14 min See motor characteristics
Te2 10 min See motor characteristics
Tr 28 min See motor characteristics
Influence RTD (optional) No
θALARM enabled? Yes
Thermal alarm threshold
92% 0,92 > (256 / 270)2
θALARM
θ FORBID START enabled ? Yes
0,78 < (1382 / 270)2 * (1-exp(4
FORBID START 78%
/ 10*60)) +exp(5 / 10*60))
P220/EN AP/B43 Technical Guide
Application Guide
Page 28/40 MiCOM P220

Submenu [50/51] Primary Secondary


Comments
SHORT-CIRCUIT setting setting
Short-circuit function enabled ? Yes
Threshold I>> 1800A 6In 130% of motor start-up current
tI>> 0.1s

Submenu [50/51] Primary Secondary


Comments
EARTH FAULT setting setting
Earth fault function enabled ?: No Only one earth fault current
threshold Io> threshold can be programmed
Thresholds Io> 0.002Ion
tIo> 0s
Earth fault function enabled ?: Yes
threshold Io>>
Threshold Io>> 2A 0.08Ion Setting to 6,7 % of maximum
earth fault current
tIo>> 0.1s

Submenu [46] Primary Secondary


Comments
UNBALANCE setting setting
Function Unbalance enabled ?: Yes Alarm threshold enabled
threshold Ii>
Threshold Ii> 25.6 A 0.085 In Setting to 10% of Inmotor
(CT)
tli> 10s
Function Unbalance enabled ?: Yes Tripping threshold enabled
threshold Ii>>
Threshold Ii>> 51.2A 0.171 In Setting to 20% of Inmotor
(CT)

Submenu [48] Primary Secondary


Comments
EXCESS LONG START setting setting
Excess long start function Yes
enabled ?
Threshold Istart 540A 2Iθ Id = 5.4*Inmotor ! Istart = 2*Iθ

tIstart 5s 1.2 * td = 4.8s


Technical Guide P220/EN AP/B43
Application Guide
MiCOM P220 Page 29/40

Submenu [51LR/50S] Primary Secondary


Comments
BLOCK ROTOR setting setting
Block rotor function enabled ? Yes
tIstall 1.8s See motor characteristics

Stalled-in-run rotor function Yes


enabled ?
Threshold Istall 540A 2Iθ Id= 5.4*Inmotor ! Istall = 2*Iθ
Blocked-at-start rotor function Yes Presence of zero speed detector is
enabled ? necessary (speed switch)

Submenu [37] Primary Secondary


Comments
LOSS OF LOAD setting setting
Loss of load function enabled ? Yes Motor-driven pump
Threshold I< 165A 0.55In Higher than no-load current
tI< 3s Depends on process
Tinhib 40s Tinhib > (5 + 30)

Submenu [66] Primary Secondary


Comments
START NUMBER setting setting
Start number limitation function Yes Parameters depend on trade-off
enabled ? of motor characteristics against
process requirements
Treference 60 min
Hot starts number 2
Cold starts number 3
Tinterdiction 30 min

Submenu MIN TIME Primary Secondary


Comments
BETW 2 START setting setting
Time between starts function Yes Parameter depends on trade-off
enabled ? of motor characteristics against
process requirements
Tbetween 2 start 10min

Submenu RE-ACCEL Primary Secondary


Comments
AUTHORIZ setting setting
Re-acceleration authorisation Yes Parameter depends on trade-off
function enabled ? of motor characteristics against
process requirements
Treacc 0.2s