0% found this document useful (0 votes)
249 views7 pages

Amendment No 1 - IS 875 - Part 3

This document provides amendments to IS 875 (Part 3):2015 Design Loads (Other than Earthquake) for Buildings and Structures - Code of Practice Part 3 Wind Loads (Third revision). It details corrections and substitutions to be made throughout the code document.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
249 views7 pages

Amendment No 1 - IS 875 - Part 3

This document provides amendments to IS 875 (Part 3):2015 Design Loads (Other than Earthquake) for Buildings and Structures - Code of Practice Part 3 Wind Loads (Third revision). It details corrections and substitutions to be made throughout the code document.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

AMENDMENT NO.

1 JANUARY 2016
To
IS 875 (Part 3):2015 DESIGN LOADS (OTHER THAN EARTHQUAKE) FOR
BUILDINGS AND STRUCTURES - CODE OF PRACTICE
PART 3 WIND LOADS
(Third revision)

(Foreword, second cover, sixth Para, second line) – Substitute ‘discipline’ for ‘descriptive’
(Foreword, second cover, sixth Para, bullet (c)) – Substitute ‘k2’ for ‘k2’
(Foreword, third cover, Para after (j), line 8) – Insert ‘anemometer’ after ‘with the help of’
(Page 2, Clause 3.1) – Substitute ‘Cf’ for ‘Cfd’’
(Page 3) – Substitute ‘ z,d’ for ‘ d,z’

(Page 3, Symbol r) – Insert ‘, Ih,i’ after ‘height ‘h’.


(Page 6, Fig. 1) – Insert the following notes at the end of the figure
‘NOTE 1- The occurrence of a tornado is possible in virtually any part of India. They are particularly more severe in
the northern parts of India. The recorded number of these tornados is too small to assign any frequency. The
devastation caused by a tornado is due to exceptionally high winds about its periphery, and the sudden reduction in
atmospheric pressure at its centre, resulting in an explosive outward pressure on the elements of the structure. The
regional basic wind speeds do not include any specific allowance for tornados. It is not the usual practice to allow for
the effect of tornados unless special requirements are called for as in the case of important structures such as, nuclear
power reactors and satellite communication towers.

NOTE 2 – The total number of cyclonic storms that have struck different sections of east and west coasts are
included in Fig. 1, based on available records for the period from 1877 to 1982. The Figures above the line (between
the stations) indicate the total number of severe cyclonic storms with or without a core of hurricane winds (speeds
above 87 km/h) and the figures in the brackets below the lines indicate the total number of cyclonic storms. These
have been included only as additional information.’

(Page 10, Table 4) – Replace the existing footer with ‘Linear interpolation for intermediate values of A is
permitted’.
(Page 11, Clause 7.3.3.3, para 2) – Substitute ‘the solidity ratio  ’ for ‘the solidity ratio f’.
(Page 11, Clause 7.3.3.3, para 2, lines 3, 5 and 10) –Substitute ‘  ’ for ‘f’.
(Page 12, Figure 2(b), Right-topmost figure) – Substitute the existing figure with the figure below:
 l   3  l  3
(Page 13, Table 5, 4throw) – Substitute‘ 1   ’for‘ 1   ’.
 w  2  w  2
3 l 3 l
(Page 13, Table 5, 5throw) – Substitute ‘  4 ’for‘  4 ’.
2  w 2  w
(Page 14, Table 6, bottommost figure) – Substitute the following key plan for the existing:

(Page 17, Table 8 ) – Add ‘α,’ after ‘ROOF ANGLE’.


(Page 17, Table 8, Note 2) – Replace ‘overhangs,’ with ‘overhangs.’
(Page 18, Table 9) – Replace the figures with the following
(Page 19, Table 10) – Replace the figureswith the following:

(Page 19, Table 10) – Replace the bottom table on pressure coefficients with the following:

PRESSURE COEFFICIENTS, CP
θ D D’ E E’ END SURFACES
C C’ G G’
0° +0.6 -1.0 -0.5 -0.9
45° +0.1 -0.3 -0.6 -0.3
90° -0.3 -0.4 -0.3 -0.4 -0.3 +0.8 +0.3 -0.4
FOR ALL FOR J : CP Top = 1.0, CP bottom = -0.2
VALUE Tangentially acting friction : R90° = 0.05 pdbd
OF θ

(Page 20, Table 11) – Replace the bottom table on pressure coefficients with the following:

PRESSURE COEFFICIENTS, CP
θ D D’ E E’ END SURFACES
C C’ G G’
0° +0.1 +0.8 -0.7 +0.9
45° -0.1 +0.5 -0.8 +0.5
90° -0.4 -0.5 -0.4 -0.5 -0.3 +0.6 +0.3 -0.4
180° -0.3 -0.6 +0.4 -0.6
FOR ALL FOR J : CP Top = -1.5, CP bottom = 0.5
VALUE Tangentially acting friction : R90° = 0.05 pdbd
OF θ
(Page 21, Table 12) – below the figure replace ‘ = 0’ to ‘ = 90’

(Page 21, Table 12) – Replace the bottom table on pressure coefficients with the following:

PRESSURE COEFFICIENTS, CP
θ D D’ E E’ END SURFACES
C C’ G G’
0° -1.0 +0.3 -0.5 +0.2
45° -0.3 +0.1 -0.3 +0.1
90° -0.3 0 -0.3 0 -0.4 +0.8 +0.3 -0.6
FOR ALL FOR f : CP Top = -1.0, CP bottom = 0.4
VALUE Tangentially acting friction : R90° = 0.1 pdbd
OF θ

(Page 22, Table 13, 1st Figure) – Substitute ‘h=0.8h’ for ‘h=0.θh’

(Page 22, Table 13) – Replace the bottom table on pressure coefficients with the following:

PRESSURE COEFFICIENTS, CP
θ D D’ E E’ END SURFACES
C C’ G G’
0° -1.3 +0.8 -0.6 0.7
45° -0.5 +0.4 -0.3 +0.3
90° -0.3 0 -0.3 0 -0.4 +0.8 +0.3 -0.6
180° -0.4 -0.3 -0.6 -0.3
FOR ALL FOR f : CP Top = -1.6, CP bottom = -0.9
VALUE Tangentially acting friction : R90° = 0.1 pdbd
OF θ

(Page 23, Table 14) – Delete ‘ x ’ and ‘ ’on the top in figure.

(Page 24, Table 15) –Delete ‘ x’ and ‘ ’on the top in figure.
(Page 24, Table 15) – Substitute ‘Tangentially’ for ‘Tengentially’.
(Page 26, Table 17) – Replace the entry against 270° in bottom table with:‘Similar to 90°, h1, h2, h3, are needed
to be reckoned from windward edge in the same order’
(Page 27, Table 18)— Substitute the following table for the existing:
Table 18 External Pressure Coefficients (Cpe) for Curved Roofs
(Clause 7.3.3.6)
(Page28, Table 19) – Substitute ‘D’ for ‘d’ in both figures on the top.
(Page 31, Table 21) – Substitute ‘0.6’ in y-axis coefficient (Cpe) in the figure for‘0.8’(between 0.4 and 0.8)
(Page 31, Table 21) –Substitute ‘7.3.3.5’ against e in the bottom table, for‘6.3.3.5’
(Page 32, Table 22) – Substitute ‘See Table 21 for combined roofs’ in the bottom table for‘See Table for
combined roofs’.
[Page 34, Clause 7.4.1 (a)] — Substitute the following for the existing:

‘a) If , and’
(Page 36, Table 25, clause ref) - Substitute ‘7.4.2.1’ for ‘7.4.2.2’.
(Page 39, Fig .5andTable 26) – Substitute ‘FORCE COEFFICIENT’ for ‘DRAG COEFFICIENT’.

(Page 40, Table 28, sl. (ii)) – Substitute ‘ DV d ’ for the existing.

(Page 40, Table 28, sl.(iii)) – Substitute ‘b V d ’ for the existing.


(Page 41, Table 29) – Substitute the reference clause ‘7.4.3.2(a)’ in the title for clause ‘7.4.3.2 (b)’.
(Page 42, Table 30, Title) – Substitute the ‘l/D’ in the title in place ‘L/D’.

(Page 42, Table 30, sl. (i) and (ii)) – Substitute the ‘ DV d ’ for the existing under ‘Flow Regime’.
(Page 42, Table 31, solidity ratio) – Substitute ‘Force Coefficient, Cf’ for ‘Force Coefficient, Ct’.
(Page 42, Table 31, solidity ratio) – Substitute ‘0.2’ for ‘02’.

(Page 42, Table 31) – Substitute ‘ DV d ≥ 6 m2/s’ in title of the column 4 for the existing.
(Page 43, Table 32, Title) – Substitute ‘η’ for ‘H’.

(Page 44, Table 34) – Substitute ‘ DV d ’ under the Force Coefficient for the existing symbol for both subcritical
flow and supercritical flow.
(Page 44, clause 8.2, line 4) – Substitute ‘… for c/c distance x between …’ for ‘… for c/c distance (x) between
…’

(Page 44, Table 35) – Substitute ‘ DV d ’ under the Force Coefficient for the existing symbol for both subcritical
flow and supercritical flow.
(Page 45, Figure 7) – Substitute ‘x’ for ‘X’.
(Page 45, Figure 8, Title) – Substitute ‘8.3’ for ‘7.3’ in the end.
(Page 46, clause 9.2.1, Note 2, line 1) —Substitute the following for the existing:
‘2 Unlined welded steel cylindrical structures…’
(Page 46, clause 9.2.1, Note 4, line 1) – Substitute the following for the existing:
‘4 The formulae given in 9.2.1 (a) is valid …’
(Page 47, clause 10.2, line 14) – Substitute ‘Ma =  Fz z’ for the existing.
(Page 47, clause 10.2) – Substitute ‘(1+  )2’ for ‘(1+g)2’ in formula of Gust factor.

(Page 48, clause 10.3) – Substitute‘ p h ’ for ‘ph’ in the formula of peak base bending moment Mc.

(Page 49, Figure 10) – Substitute ‘…6 8 10…’ for ‘…6 6 10…’ in x-axis.
(Page 53, Figure 12(b)) - Substitute‘DESIGN PROFILE AT A’ for ‘OESIGN PROFILE AT A’.
(Page 53, Figure 12(b))– Substitute ‘WIND DIRECTION’ for ‘WINO OIRECTION’.
(Page 53, Figure 12(c)) - Substitute ‘WIND DIRECTION’ for ‘WINO OIRECTION’.
(Page 54, clause C-2) - Substitute ‘θs’ for ‘θs’.
(Page 54, clause C-2, 2nd last line) –Substitute ‘distance, X’ for ‘distance, x’.
(Page 54, Figure 13(a) – Substitute ‘REGION AFFECTED BY TOPOGRAPHICAL FEATURE’ for ‘REGION
AFFECTED BY TOPOGRAHICAL FEATURE’.
(Page 55, Fig.14) — Substitute the following for the existing title:
‘FIG. 14 FACTOR s0 FOR CLIFF AND ESCARPMENT’.
(Page 55, Fig 15) — Substitute the following for the existing title:
‘FIG. 15 FACTOR s0 FOR RIDGE AND HILL’.

(Page 56, Figure 17) – Substitute ‘sp’ for ‘sp’.

(Page 56, clause D-1) – In the third line from bottom of the first column - Substitute ‘sp’ for ‘sp’.

(CED 37)

You might also like