CABLE SIZING

RATED SYSTEM VOLT. EFF PF RATED CURRENT CABLE TYPE/ DETAILS

FROM T0
S.No TOTAL CABLE
PER CURRENT DERATING DERATED RESISTANCE AND CABLE
POWER VOLT. TYPE RATED START POWER RATIO RATED START KIND CORE SIZE RATED START LENGTH
PHASE RATING FACTOR CURRENT REACTANCE LENGTH
(M)
(%) (%)
EQPT NAME EQPT NAME (kW) (kV) (%) (%) (%) (kVA) (A) (A) (mm2) (A) (A) R (Ohm/km) X (Ohm/km) (m) (V) (V)
<3% <15%
Starter Panel
1.1KV Al/ XLPE/
1 (Dewatering Pump - Dewatering Pump - 100HP 75 0.415 3P 0.95 0.8 0.3 98.68 4 137.29 549.16 3.5 120 1 258 0.9 232.2 0.325 0.072 90.00 12.05 2.90 22.57 5.44 180
PVC/ AR
100HP)

Starter Panel 1.1KV Al/ XLPE/


2 Dewatering Pump - 60HP 45 0.415 3P 0.95 0.8 0.3 59.21 4 82.374 329.5 3.5 70 1 176 0.9 158.4 0.567 0.077 90.00 12.24 2.95 21.25 5.12 180
(Dewatering Pump - 60HP) PVC/ AR

Starter Panel 1.1KV Al/ XLPE/


3 Dewatering Pump - 50HP 37 0.415 3P 0.95 0.8 0.3 48.68 4 67.73 270.92 3.5 70 1 176 0.9 158.4 0.567 0.077 90.00 10.07 2.43 17.47 4.21 180
(Dewatering Pump - 50HP) PVC/ AR

Starter Panel 1.1KV Al/ XLPE/


4 Dewatering Pump - 30HP 22 0.415 3P 0.95 0.8 0.3 28.95 4 40.272 161.09 3.5 35 1 117 0.9 105.3 1.11 0.08 90.00 11.45 2.76 18.64 4.49 180
(Dewatering Pump - 30HP) PVC/ AR

DOL Starter 1.1KV Cu/ XLPE/


5 Dewatering Pump - 10HP 7.5 0.415 3P 0.95 0.8 0.3 9.87 4 13.729 54.916 4 6 1 50 0.9 45 3.94 0.09 90.00 6.86 1.65 10.85 2.62 90
(Dewatering Pump - 10HP) PVC/ AR

1.1kv, Al Cable
Core
Cable Size (sq.mm) Length (In meters) Cable Type Cable Specification
Details
As per following standard
3.5c 120 180
1.1KV Al (Conductor)/ XLPE IS : 7098 (Part-I) : 1988, IS:8130-1984, IS:5831-1984, IS: 3975-1970, IS:10810-1984, IS:10418-1982
(Insulated)/ PVC (Inner & Conductors :
3.5c 70 360 For all types of Cable, aluminium conductor shall be H4 grade, stranded in construction with flexibility class 2, complying with the requirements as specified in IS-8130-1984 with latest amendments. The conductor shall be clean & reasonably uniform
Outer Sheath)/ AR
(Armoured) -A2XWY in size and shape and its surface shall be free from sharp edges.
3.5c 35 180 Insulation :
The Conductor shall be provided with XLPE insulation applied by extrusion. Inner sheath is used for multicore Cables. For multi core Cables, the laid up cores shall be provided with Inner Sheath applied by extrusion. It shall be ensured that it is as
1.1kv, Cu Cable circular as possible. Material of inner sheath should be PVC Type ST2 as per IS:5831-1984.
Armouring:
Armouring is used for multicore armoured cable. The armour wires/strips shall be applied as closely as practicable. A binder tape may be provided on the armour.
1.1KV Cu (Conductor)/ XLPE Outer Sheath :
(Insulated)/ PVC (Inner & The outer sheath shall be black & applied by extrusion. It shall be applied over the armoured multicore Cables.
4c 6 90 Material of outer sheath should be PVC Type ST2 as per IS:5831-1984
Outer Sheath)/ AR
(Armoured) -2XWY

Note:

1) Voltage Drop considerations is as mentioned below


Running Voltage Drop <
a)
3%
Starting Voltage Drop <
b)
15%