CM-UFD.M31: Grid Feeding Monitoring According To VDE-AR-N 4105 and BDEW
CM-UFD.M31: Grid Feeding Monitoring According To VDE-AR-N 4105 and BDEW
CM-UFD.M31: Grid Feeding Monitoring According To VDE-AR-N 4105 and BDEW
Characteristics
–– Monitoring of voltage and frequency in single- and three-phase mains (2-wire, 3-wire or 4-wire AC systems)
–– Third party certificate confirming accordance with VDE-AR-N 4105 and BDEW
–– Over- and undervoltage, 10-minutes average value as well as over- and underfrequency monitoring
–– Two-level threshold settings for over-/undervoltage and over-/underfrequency
–– ROCOF (rate of change of frequency) monitoring and vector shift detection configurable
–– Interrupted neutral detection
–– Default settings according to VDE-AR-N 4105 and BDEW
–– True RMS measuring principle
–– All threshold values and tripping delays adjustable
–– Error memory for up to 99 entries (incl. cause of error, measured value, relative timestamp)
–– Password setting protection
–– 3 control inputs, e.g. for feedback signal, remote trip
–– 3 c/o (SPDT) contacts
–– Multiline, backlit LCD display
Order data
Type Rated control supply voltage Measuring range Order code
CM-UFD.M31 24-240 V AC/DC L-L: 0-540 V AC / L-N: 0-312 V AC 1SVR 560 730 R3401
Functions
Operating controls
A1 A2 Y1 Y2 Y3 Y0 L1 L2 L3 N 1 Display
2 Measured values
6 Operating buttons
Application
The CM-UFD.M31 is a grid feeding monitoring relay which monitors the voltage and the frequency of the public grid. Whenever
the measured values are not within the range of the adjusted threshold values, the CM-UFD.M31 causes tripping of the
section switch. This tripping disconnects the power generation such as photovoltaic systems, wind turbines, block-type
thermal power stations from the grid. The fault is indicated by LED and the corresponding plain text failure message is shown
on the display.
In conformity with VDE-AR-N 4105, the CM-UFD.M31 relay can be used in all low voltage plants and in medium voltage
plants. The grid feeding monitoring relay is mandatory in all low voltage generation plants with power > 30 kW.
In applications according to BDEW, the auxiliary voltage supply of the protection equipment must be equipped additionally
with a network-independent energy source (e.g. battery, UPS).
Operating mode
The CM-UFD.M31 can be set up to monitor single- and three-phase mains (2-wire, 3-wire as well as 4-wire AC systems). The
unit is configurable by front-face push-buttons. A display with the corresponding menu enables the selection of pre-settings
as well as the precise adjustment of the different threshold values and corresponding time delays. Furthermore, the display
visualizes the measured values clearly. Together with the front-face LEDs, it shows all information about operational states of
output relays and control inputs.
The CM-UFD.M31 provides 3 output relays and 3 control inputs. Output relays R1 (1115-1216/1418) and R2 (2125-2226/2428)
are required for disconnection of a distributed generation from the public grid. The corresponding feedback signals from the
external contacts are monitored via the control inputs Y1-Y0 and Y2-Y0. The third output relay R3 (31 35-3236/3438) can be
used for the closing command of a motor drive for circuit breaker or as signalization of output relays R1 and R2. The additional
control input Y3-Y0 allows to trip the grid feeding monitoring relay from remote (remote trip). With control input Y3-Y0 it is also
possible to suppress input Y1-Y0, input Y2-Y0, both together or the vector shift detection.
Protective functions
If control supply voltage is applied, all phases are present and the switch-on conditions for voltages and frequency are fulfilled,
output relays R1 and R2 energize synchronously after the adjusted switch-on delay. The green LED U/T flashes while timing
and turns steady when the switch-on delay is complete.
If a measured value exceeds or falls below the set threshold value (overvoltage, undervoltage, overfrequency or underfrequency),
R1 and R2 de-energize after the adjusted tripping delay. As soon as the measured value returns to the tolerance range -
taking into account an adjustable hysteresis – and all further switch-on conditions are fulfilled, R1 and R2 re-energize. The
fault is indicated by the red LED F and the type of fault is shown on the display as a plain text message. The event that has
caused tripping of the relay is recorded in the event list. The green LED U/T flashes while timing and turns steady when the
delay is complete.
Switch-on conditions
In order to switch on the section switch after having applied control supply voltage or after a fault, the voltages as well as the
frequency must stay within the set switch-on conditions during the switch-on delay. This window of voltage and frequency
can be further restricted in the menu “Switch-on conditions”. If one parameter leaves the window, the switch-on process is
interrupted. When all parameters fulfill the switch-on conditions again, the switch-on delay restarts. When the switch-on time
is complete, relays R1 and R2 re-energize automatically. If the function “Short interruption” is enabled in the menu “Switch-on
conditions” -> “Switch-on delay”, the switch-on delay will be reduced to 5 s in case of a short interruption of < 3 s.
Test function
The test function can be used to simulate an error in the installation. This way, the time delays of the feedback loops can
be determined. A feedback loop includes the output relay, the corresponding switching device and the feedback contact.
The test function can be started by pressing the ESC button for 3 seconds. The output relays R1 and R2 de-energize
immediately and the CM-UFD.M31 gets feedback signals from the section switch through control inputs Y1-Y0 and Y2-Y0
respectively. The time intervals from de-energizing both output relays to receiving both feedback signals is shown on the
display. Return to the menu is realized by confirming with the OK button.
Electrical connection
18 15 16 28 25 26 38 35 36
Configuration
The relay is delivered with default settings in accordance to VDE-AR-N 4105 table 2. Thanks to the wide backlit display and
to appropriate buttons all parameters can be easily set. The user-friendly menu structure starts with the main page that shows
the real time measured values. Use the arrow keys to switch between the real time voltages and the 10-minutes average
voltages.
Basic operation
Back light of the display switches off automatically after an adjustable duration. With a dark display, press any button to light
it up again.
Measurement screen:
ESC > 3 s: Test function
Arrow buttons: next measurement display
OK: menu
Menu:
ESC: leave the menu/submenu
Arrow buttons: select the submenu/parameter, > 1 s scroll
OK: enter the submenu/parameter
Adjust parameters:
ESC: move to the previous digit or cancel the change, > 1 s cancel the change
Arrow buttons: change the parameter, > 1 s scroll
OK: move to the next digit or confirm the change, > 1 s confirm the change
Device parameters acc. to VDE-AR-N 4105 para. 6.5.2 acc. to BDEW table 3.2.3.3-2
Overvoltage >UAV Voltage increase protection U> not required
Overvoltage >U1 Voltage increase protection U>> not required
Overvoltage >U2 not required Voltage increase protection U>>
Undervoltage <U1 Voltage decrease protection U< Voltage decrease protection U<
Undervoltage <U2 not required Voltage decrease protection U<<
Overfrequency >F1 Frequency increase protection f> Frequency increase protection f>
Overfrequency >F2 not required not required
Underfrequency <F1 Frequency decrease protection f< Frequency decrease protection f<
Underfrequency <F2 not required not required
Menu structure
The following tables show the submenu structure and configuration possibilities as well as the two sets of pre-settings
according to VDE-AR-N 4105 and BDEW, which can be loaded in the submenu “General settings” -> “Load settings”.
Additionally, 5 sets of self-defined pre-settings can be saved in the memory and loaded by the user.
The voltage at L3 has fallen below the first Remote trip from control input Y3-Y0
undervoltage threshold. The voltages at detected.
L1 and L2 have fallen below the switch-on
conditions, yet not below the undervoltage
threshold.
The threshold for rate of change of Error in feedback loop Y1-Y0, e.g. wiring
frequency was exceeded. failure or welded feedback contact.
Please check wiring.
The threshold for vector shift detection Error in feedback loop is removed. Press
was exceeded. ESC to reset the grid feeding monitoring
relay.
The last 99 events that caused tripping of the grid feeding monitoring relay, as well as any interruption of the control supply
voltage, will be recorded by the device. The type of error as well as the time stamp is recorded in the internal error list,
accessible via the menu “Error memory”. The list is stored in a non-volatile memory which can be reset by the user.
Error code
Time stamp
In this case the error occured
4 hours, 8 minutes and 17 seconds
seconds after commissioning
L1
N Public grid
where applicable,
a transformer
6 A
1216 1418 2226 2428 3236 3438 Y3 Y2 Y1 Y0
K1
K2
L1
L2
L3
N Public grid
where applicable,
a transformer
6 A
1216 1418 2226 2428 3236 3438 Y3 Y2 Y1 Y0
K1
K2
2CDC 252 007 F0213
Input circuits
Supply circuit A1-A2
Rated control supply voltage Us 24-240 V AC/DC
Rated control supply voltage Us tolerance -15...+10 %
Rated frequency DC or 50 Hz
Frequency range AC 40-70 Hz
Typical current / power consumption 24 V DC 64 mA / 1.5 W
230 V AC 6.4 mA / 1.5 VA
External fusing (necessary) 6 A gG (gL) or circuit breaker 6 A with B characteristic
Power failure buffering time 200 ms, according to LVFRT (Low Voltage Fault Ride Through)
Timing functions
Switch-on delay (prior to first grid connection or re-connection after interruption) adjustable, 1.00-600.00 s in 0.01 s steps
Tripping delay overvoltage 10-min average (>UAV) <3s
overvoltage (>U1, >U2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
undervoltage (<U1, <U2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
overfrequency (>F1, >F2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
underfrequency (<F1, <F2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
ROCOF adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
vector shift < 50 ms
interrupted neutral conductor < 150 ms
Error time ROCOF adjustable, 0.5-600.00 s in 0.01 s steps
vector shift adjustable, 0.5-600.00 s in 0.01 s steps
Trip window, feedback loops Y1-Y0, Y2-Y0 adjustable, 0.05-0.50 s in 0.01 s steps
Release window, feedback loop Y1-Y0, Y2-Y0 adjustable, 0.50-600.00 s in 0.01 s steps
Accuracy within the temperature range it m 0.01 %
User interface
Indication of operational states
Control supply voltage applied / timing U/T LED green on / flashing
Fault message F LED red on
For details see the message on the display
Display
Backlight on press any button
off switch-off delay adjustable, 10-600 s (default 10 s)
Operating temperature range of the display clearly visible -20...+60 °C
Resolution 112 x 64 pixel
Display size 36 x 22 mm
Operating controls
4 push-buttons for menu navigation, setting and entering
General data
MTBF on request
Repeat accuracy (constant parameters) < w 0.5 %
Duty time 100 %
Dimensions see ‘Dimensional drawing’
Weight 0.306 kg (0.675 lb)
Material of housing PA666FR
Mounting DIN rail (IEC/EN 60715) TH 35-7.5 and TH 35-15,
snap-on mounting without any tool
Mounting position any
Minimum distance to other units horizontal / vertical not necessary
Degree of protection housing / terminals IP20
Electrical connection
Connecting capacity fine‑strand with wire end ferrule 1 x 0.25-4 mm² (1 x 24-12 AWG)
2 x 0.25-0.75 mm² (2 x 24-18 AWG)
fine‑strand without wire end ferrule 1 x 0.2-4 mm² (1 x 24-12 AWG)
2 x 0.2-1.5 mm² (2 x 24-16 AWG)
rigid 1 x 0.2-6 mm² (1 x 24-10 AWG)
2 x 0.2-1.5 mm² (2 x 24-16 AWG)
Stripping length 8 mm (0.315 in)
Tightening torque 0.5-0.6 Nm (4.4-5.3 lb.in)
Isolation data
Rated insulation voltage Ui supply / measuring / output circuits 600 V
output 1 / output 2 / output 3 300 V
Rated impulse withstand voltage Uimp supply / measuring / output circuits 6 kV; 1.2/50 µs
output 1 / output 2 / output 3 4 kV; 1.2/50 µs
Basic insulation supply / measuring / output circuits 600 V AC
output 1 / output 2 / output 3 300 V AC
Protective separation supply / measuring / output circuits 250 V
(IEC/EN 61140)
output 1 / output 2 / output 3 250 V
Pollution degree 3
Overvoltage category III
Standards / Directives
Standards IEC/EN 60255-27, EN 50178, VDE-AR-N 4105,
BDEW ("Technische Richtlinie - Erzeugungsanlagen am
Mittelspannungsnetz")
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV contact discharge, 8 kV air discharge
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m
electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 3, installation class 3,
supply circuit and measuring circuit 1 kV L-L, 2 kV L-N
conducted disturbances, induced by radio- IEC/EN 61000-4-6 Level 3, 10 V
frequency fields
voltage dips, short interruptions and voltage IEC/EN 61000-4-11 Class 3
variations
harmonics and interharmonics IEC/EN 61000-4-13 Class 3
Interference emission IEC/EN 61000-6-3
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
100 100
80 80
60 60
50 50
40 40
30 30
20 20
1.0
Switching cycles
0.9
0.8
F
0.7
0.6
250 V
2CDC 252 192 F0205
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Contact lifetime
90 3.54”
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.