CM-UFD.M31: Grid Feeding Monitoring According To VDE-AR-N 4105 and BDEW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

Data sheet

Grid feeding monitoring according to VDE-AR-N 4105


and BDEW
CM-UFD.M31

The CM-UFD.M31 is a multifunctional grid feeding


monitoring relay. It provides different monitoring
functions in accordance with VDE-AR-N 4105
and BDEW to detect over- and undervoltage
(10-minutes average value, voltage increase

2CDC 251 001 S0014


and decrease protection) as well as over- and
underfrequency (frequency increase and decrease
protection).
The device trips the section switch which is
connected between the distributed generation
and the public grid in order to disconnect the
distributed generation, in case of problems (e.g.
unstable grid), faults or maintenance on the grid.
Additionally, monitoring of ROCOF (rate of change
of frequency) and vector shift can be configured.

Characteristics
–– Monitoring of voltage and frequency in single- and three-phase mains (2-wire, 3-wire or 4-wire AC systems)
–– Third party certificate confirming accordance with VDE-AR-N 4105 and BDEW
–– Over- and undervoltage, 10-minutes average value as well as over- and underfrequency monitoring
–– Two-level threshold settings for over-/undervoltage and over-/underfrequency
–– ROCOF (rate of change of frequency) monitoring and vector shift detection configurable
–– Interrupted neutral detection
–– Default settings according to VDE-AR-N 4105 and BDEW
–– True RMS measuring principle
–– All threshold values and tripping delays adjustable
–– Error memory for up to 99 entries (incl. cause of error, measured value, relative timestamp)
–– Password setting protection
–– 3 control inputs, e.g. for feedback signal, remote trip
–– 3 c/o (SPDT) contacts
–– Multiline, backlit LCD display

Order data
Type Rated control supply voltage Measuring range Order code
CM-UFD.M31 24-240 V AC/DC L-L: 0-540 V AC / L-N: 0-312 V AC 1SVR 560 730 R3401
Functions

Operating controls
A1 A2 Y1 Y2 Y3 Y0 L1 L2 L3 N 1 Display

2 Measured values

3 Status of output relays


CM-UFD
1
ESC Test In this case R3 is de-energized
U/T
5
2 F
4 Status of control inputs
3 In this case Y3-Y0 is open
OK
6
4
5 Indication of operational states
2CDC 253 007 F0014

U/T: green LED – V Control supply voltage applied


14 11 12 24 21 22 34 31 32
W Timing
F: red LED - Fault message
18 15 16 28 25 26 38 35 36

6 Operating buttons

Application
The CM-UFD.M31 is a grid feeding monitoring relay which monitors the voltage and the frequency of the public grid. Whenever
the measured values are not within the range of the adjusted threshold values, the CM-UFD.M31 causes tripping of the
section switch. This tripping disconnects the power generation such as photovoltaic systems, wind turbines, block-type
thermal power stations from the grid. The fault is indicated by LED and the corresponding plain text failure message is shown
on the display.
In conformity with VDE-AR-N 4105, the CM-UFD.M31 relay can be used in all low voltage plants and in medium voltage
plants. The grid feeding monitoring relay is mandatory in all low voltage generation plants with power > 30 kW.
In applications according to BDEW, the auxiliary voltage supply of the protection equipment must be equipped additionally
with a network-independent energy source (e.g. battery, UPS).

Operating mode
The CM-UFD.M31 can be set up to monitor single- and three-phase mains (2-wire, 3-wire as well as 4-wire AC systems). The
unit is configurable by front-face push-buttons. A display with the corresponding menu enables the selection of pre-settings
as well as the precise adjustment of the different threshold values and corresponding time delays. Furthermore, the display
visualizes the measured values clearly. Together with the front-face LEDs, it shows all information about operational states of
output relays and control inputs.
The CM-UFD.M31 provides 3 output relays and 3 control inputs. Output relays R1 (1115-1216/1418) and R2 (2125-2226/2428)
are required for disconnection of a distributed generation from the public grid. The corresponding feedback signals from the
external contacts are monitored via the control inputs Y1-Y0 and Y2-Y0. The third output relay R3 (31 35-3236/3438) can be
used for the closing command of a motor drive for circuit breaker or as signalization of output relays R1 and R2. The additional
control input Y3-Y0 allows to trip the grid feeding monitoring relay from remote (remote trip). With control input Y3-Y0 it is also
possible to suppress input Y1-Y0, input Y2-Y0, both together or the vector shift detection.

Protective functions
If control supply voltage is applied, all phases are present and the switch-on conditions for voltages and frequency are fulfilled,
output relays R1 and R2 energize synchronously after the adjusted switch-on delay. The green LED U/T flashes while timing
and turns steady when the switch-on delay is complete.
If a measured value exceeds or falls below the set threshold value (overvoltage, undervoltage, overfrequency or underfrequency),
R1 and R2 de-energize after the adjusted tripping delay. As soon as the measured value returns to the tolerance range -
taking into account an adjustable hysteresis – and all further switch-on conditions are fulfilled, R1 and R2 re-energize. The
fault is indicated by the red LED F and the type of fault is shown on the display as a plain text message. The event that has
caused tripping of the relay is recorded in the event list. The green LED U/T flashes while timing and turns steady when the
delay is complete.

2 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Output relay R3 (31 35-3236/3438)
Output relay R3 can be used for the closing command of a breaker motor. For this function either the “closed-circuit” or the
“open-circuit” working principle must be selected. When output relays R1 and R2 energize, the adjusted ON-delay starts.
When timing is complete, R3 will be activated for the duration of the ON-time or until R1 and R2 de-energize.
Additionally R3 can be configured as “synchronous with R1/R2” or “disabled”. With these two configurations the settings for
the ON-delay and the ON-time have no influence on the operating function.

Control inputs Y1-Y0, Y2-Y0


Both control inputs Y1-Y0 and Y2-Y0 are used as feedback contacts for the 2 switching devices of the section switch. The
current status of the switching devices is monitored by the grid feeding monitoring relay. The working principle of the control
inputs can be configured as “normally closed”, “normally open”, “auto detection” or completely “disabled”. Please note that
“normally” here refers to “good status” of the grid, when all the monitored voltages and the frequency stay within the set
threshold values and output relays R1 and R2 are energized. A failure in the feedback loop has to be removed manually on
the device.

Control input Y3-Y0


The function of control input Y3-Y0 can be configured as “remote trip”, “suppress Y1”, “suppress Y2”, “suppress Y1/Y2”
or “suppress vector shift detection”. Working principle of the control input can be configured as “normally open”, “normally
closed” or completely “disabled”.
Remote trip: With Y3-Y0 configured as “normally closed”, output relays R1 and R2 de-energize if Y3-Y0 is opened, and vice
versa.
Suppress Y1, suppress Y2, suppress Y1/Y2: These functions can be used to suppress evaluation of the chosen feedback
loop during synchronization of a generator, so that the status of the feedback signal will not be considered as a feedback
error. An alternative solution is to set the release window of the corresponding feedback loop larger than the possible duration
of synchronization process.

ROCOF (Rate of change of frequency df/dt)


This function can be used to detect a possible loss of mains (islanding). If a loss of mains is not detected, the distributed
generation remains connected within the islanded network and might become out of synchronism with the public grid.
Therefore a later restoration of the grid supply could lead to damage of the distributed generation and other devices within
the islanded network.
The monitoring function ROCOF is disabled by default. It can be manually enabled in the menu. The grid feeding monitoring
relay detects voltage zero crossings over an adjustable number of cycles in order to calculate the rate of change of frequency.
If the ROCOF exceeds the adjusted threshold value e.g. 1 Hz/s, output relays R1 and R2 de-energize after the corresponding
tripping delay. Only after the set error time the switch-on conditions will be evaluated in order to start an auto reconnection.

Vector shift detection


This function is another possibility of detecting a loss of mains (islanding).
The vector shift detection is also disabled by default and can be manually enabled in the menu. Through zero crossings the
device detects the vector shift of mains voltage and de-energizes output relays R1 and R2 immediately if the shift exceeds
the adjusted threshold value, e.g. 10 °. Only after the set error time the switch-on conditions will be evaluated in order to start
an auto reconnection.

Switch-on conditions
In order to switch on the section switch after having applied control supply voltage or after a fault, the voltages as well as the
frequency must stay within the set switch-on conditions during the switch-on delay. This window of voltage and frequency
can be further restricted in the menu “Switch-on conditions”. If one parameter leaves the window, the switch-on process is
interrupted. When all parameters fulfill the switch-on conditions again, the switch-on delay restarts. When the switch-on time
is complete, relays R1 and R2 re-energize automatically. If the function “Short interruption” is enabled in the menu “Switch-on
conditions” -> “Switch-on delay”, the switch-on delay will be reduced to 5 s in case of a short interruption of < 3 s.

Interrupted neutral detection


Interrupted neutral detection is always active when one of the phase-neutral measuring principles is selected in the menu
“Nominal voltage”. The interruption of the neutral conductor will result in an immediate tripping of the output relays R1 and R2.

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 3


Automatic reconnecting attempts
If an error occurs at feedback loop Y1-Y0 or Y2-Y0 (e.g. undervoltage release because of a lightning strike), 0…3 automatic
reconnecting attempts will be carried out, taking into account the switch-on conditions. Therefore a temporary feedback error
doesn’t have to be handled manually. The corresponding error in the feedback loop is stored in the error list.

Test function
The test function can be used to simulate an error in the installation. This way, the time delays of the feedback loops can
be determined. A feedback loop includes the output relay, the corresponding switching device and the feedback contact.
The test function can be started by pressing the ESC button for 3 seconds. The output relays R1 and R2 de-energize
immediately and the CM-UFD.M31 gets feedback signals from the section switch through control inputs Y1-Y0 and Y2-Y0
respectively. The time intervals from de-energizing both output relays to receiving both feedback signals is shown on the
display. Return to the menu is realized by confirming with the OK button.

Electrical connection

A1 A2 Y1 Y2 Y3 Y0 L1 L2 L3 N A1-A2 Control supply voltage Us


L1, L2, L3, N Measuring inputs
Y1-Y0 Control input 1: Feedback from switching device 1
Y2-Y0 Control input 2: Feedback from switching device 2
Y3-Y0 Control input 3: Remote trip, suppress Y1, suppress
CM-UFD
ESC Test Y2, suppress Y1/Y2 or suppress vector shift
U/T detection
F 11 15-1216/1418 Output relay 1: Relay for tripping switching device 1
of the section switch, closed-circuit principle
OK 21 25-2226/2428 Output relay 2: Relay for tripping switching device 2
of the section switch, closed-circuit principle
31 35-3236/3438 Output relay 3: Closing command for circuit breaker
2CDC 253 007 F0014

motor, configuration possibilities: closed-circuit


14 11 12 24 21 22 34 31 32
principle, open-circuit principle, disabled or
synchronous with R1/R2

18 15 16 28 25 26 38 35 36

Configuration
The relay is delivered with default settings in accordance to VDE-AR-N 4105 table 2. Thanks to the wide backlit display and
to appropriate buttons all parameters can be easily set. The user-friendly menu structure starts with the main page that shows
the real time measured values. Use the arrow keys to switch between the real time voltages and the 10-minutes average
voltages.

Basic operation

Back light of the display switches off automatically after an adjustable duration. With a dark display, press any button to light
it up again.

Measurement screen:
ESC > 3 s: Test function
Arrow buttons: next measurement display
OK: menu

Menu:
ESC: leave the menu/submenu
Arrow buttons: select the submenu/parameter, > 1 s scroll
OK: enter the submenu/parameter

Adjust parameters:
ESC: move to the previous digit or cancel the change, > 1 s cancel the change
Arrow buttons: change the parameter, > 1 s scroll
OK: move to the next digit or confirm the change, > 1 s confirm the change

4 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Password protection
Every CM-UFD.M31 is delivered with the same default password [0000] for protection of its settings. In order to protect the
device from unwanted changes, the password must be changed and the password protection must be enabled. With enabled
password protection you can view the parameters, modifications are only possible after having entered the password. If the
input password is correct, the protection will be disabled until you leave the menu. The parameters “language”, “switch-off
delay” and “contrast” are not password protected.

Designation of the protective functions according to VDE-AR-N 4105 and BDEW

Device parameters acc. to VDE-AR-N 4105 para. 6.5.2 acc. to BDEW table 3.2.3.3-2
Overvoltage >UAV Voltage increase protection U> not required
Overvoltage >U1 Voltage increase protection U>> not required
Overvoltage >U2 not required Voltage increase protection U>>
Undervoltage <U1 Voltage decrease protection U< Voltage decrease protection U<
Undervoltage <U2 not required Voltage decrease protection U<<
Overfrequency >F1 Frequency increase protection f> Frequency increase protection f>
Overfrequency >F2 not required not required
Underfrequency <F1 Frequency decrease protection f< Frequency decrease protection f<
Underfrequency <F2 not required not required

Menu structure
The following tables show the submenu structure and configuration possibilities as well as the two sets of pre-settings
according to VDE-AR-N 4105 and BDEW, which can be loaded in the submenu “General settings” -> “Load settings”.
Additionally, 5 sets of self-defined pre-settings can be saved in the memory and loaded by the user.

Submenu: Nominal voltage

Contents of Configuration possibilities Step size VDE-AR-N 4105 BDEW


submenu
Measuring principle [3L-N + 3L-L], [3L-N], [3L-L], [1L-N] 3L-N + 3L-L 3L-N
Nominal voltage [57.7] - [230.9] V L-N / [99.9] - [400.0] V L-L 0.1 V 230 V L-N / 230 V L-N
398.4 V L-L

Submenu: I/O setup

Contents of Options Configuration possibilities Step size VDE-AR-N 4105 BDEW


submenu
Relay 3 Working prinicple [closed-circuit], [open-circuit], [disabled], disabled disabled
[synchronous with R1/R2]
ON-delay [0.00] - [10.00] s 0.01 s 0s 0s
ON-time [0.05] - [10.00] s 0.01 s 0.5 s 0.5 s
Feedback Y1 Working prinicple [normally closed], [normally open], normally closed disabled
[auto detection], [disabled]
Trip window [0.05] - [0.50] s 0.01 s 0.1 s 0.1 s
Release window [0.50] - [600.00] s 0.01 s 0.5 s 0.5 s
Feedback Y2 Working prinicple [normally closed], [normally open], normally closed disabled
[auto detection], [disabled]
Trip window [0.05] - [0.50] s 0.01 s 0.1 s 0.1 s
Release window [0.50] - [600.00] s 0.01 s 0.5 s 0.5 s
Control input Y3 Function [remote trip], [suppress Y1], [suppress Y2], remote trip remote trip
[suppress Y1/Y2], [suppress VS]
Working prinicple [normally closed], [normally open], [disabled] disabled disabled
Auto reconnection Number of attempts [0] - [3] 1 0 0

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 5


Submenu: Monitoring functions

Contents of Options Configuration possibilities Step size VDE-AR-N 4105 BDEW


submenu
Overvoltage >UAV Monitoring [disabled], [enabled] enabled disabled
Threshold value [1.000] - [1.300] x Un 0.005 x Un 1.1 x Un 1.1 x Un
Hysteresis [0.1] - [10.0] % 0.1 % 0.1 % 0.1 %
Overvoltage >U1 Monitoring [disabled], [enabled] enabled disabled
Threshold value [1.000] - [1.300] x Un 0.005 x Un 1.15 x Un 1.15 x Un
Hysteresis [0.5] - [10.0] % 0.1 % 1% 1%
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
Overvoltage >U2 Monitoring [disabled], [enabled] disabled enabled
Threshold value [1.000] - [1.300] x Un 0.005 x Un 1.15 x Un 1.2 x Un
Hysteresis [0.5] - [10.0] % 0.1 % 1% 1%
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
Undervoltage <U1 Monitoring [disabled], [enabled] enabled enabled
Threshold value [0.100] - [1.000] x Un 0.005 x Un 0.8 x Un 0.8 x Un
Hysteresis [0.5] - [10.0] % 0.1 % 1% 1%
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 2.4 s
Undervoltage <U2 Monitoring [disabled], [enabled] disabled enabled
Threshold value [0.100] - [1.000] x Un 0.005 x Un 0.8 x Un 0.45 x Un
Hysteresis [0.5] - [10.0] % 0.1 % 1% 1%
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.3 s
Overfrequency >F1 Monitoring [disabled], [enabled] enabled enabled
Threshold value [50.00] - [65.00] Hz 0.01 Hz 51.5 Hz 51.5 Hz
Hysteresis [0.05] - [4.00] Hz 0.01 Hz 0.1 Hz 0.1 Hz
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
Overfrequency >F2 Monitoring [disabled], [enabled] disabled disabled
Threshold value [50.00] - [65.00] Hz 0.01 Hz 51.5 Hz 51.5 Hz
Hysteresis [0.05] - [4.00] Hz 0.01 Hz 0.1 Hz 0.1 Hz
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
Underfrequency <F1 Monitoring [disabled], [enabled] enabled enabled
Threshold value [45.00] - [60.00] Hz 0.01 Hz 47.5 Hz 47.5 Hz
Hysteresis [0.05] - [4.00] Hz 0.01 Hz 0.1 Hz 0.1 Hz
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
Underfrequency <F2 Monitoring [disabled], [enabled] disabled disabled
Threshold value [45.00] - [60.00] Hz 0.01 Hz 47.5 Hz 47.5 Hz
Hysteresis [0.05] - [4.00] Hz 0.01 Hz 0.1 Hz 0.1 Hz
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
ROCOF Monitoring [disabled], [enabled] disabled disabled
Threshold value [0.100] - [5.000] Hz/s 0.005 Hz/s 1 Hz/s 1 Hz/s
Number of cycles [4] - [50] 1 50 50
Tripping delay [0.06] - [600.00] s 0.01 s 0.1 s 0.1 s
Error time [0.50] - [600.00] s 0.01 s 30 s 30 s
Vector shift VS Monitoring [disabled], [enabled] disabled disabled
Threshold value [2.0] - [40.0] ° 0.1 ° 10 ° 10 °
Error time [0.50] - [600.00] s 0.01 s 30 s 30 s

6 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Submenu: Switch-on conditions

Contents of Options Configuration possibilities Step size VDE-AR-N 4105 BDEW


submenu
Switch-on delay Switch-on delay [1.00] - [600.00] s 0.01 s 60 s 60 s
Short interruption [disabled], [enabled] enabled disabled
Voltage window Monitoring [disabled], [enabled] enabled disabled
Minimum [0.100] - [1.000] x Un 0.005 x Un 0.85 x Un 0.95 x Un
Maximum [1.000] - [1.300] x Un 0.005 x Un 1.1 x Un 1.2 x Un
Frequency window Monitoring [disabled], [enabled] enabled disabled
Minimum [45.00] - [60.00] Hz 0.01 Hz 47.5 Hz 47.5 Hz
Maximum [50.00] - [65.00] Hz 0.01 Hz 50.05 Hz 50.05 Hz

Submenu: General settings

Contents of Options Configuration possibilities


submenu
Language Language [English], [Deutsch]
Display Switch-off delay [10] - [600] s
Contrast [0] - [9]
Password Protection [disabled], [enabled]
Change password [****]
Load settings "Setting name“
Save settings „Setting name“
Information

Submenu: Error memory

Contents of Options Configuration possibilities


submenu
Error list
Error recording Remote trip [disabled], [enabled]
Power OFF [disabled], [enabled]
Reset error memory
Operating counter
Cumulated OFF-time

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 7


Display and failure messages

The voltage at L3 has fallen below the first Remote trip from control input Y3-Y0
undervoltage threshold. The voltages at detected.
L1 and L2 have fallen below the switch-on
conditions, yet not below the undervoltage
threshold.

The first overfrequency threshold was The neutral conductor is disconnected or


exceeded. interrupted.
Please check wiring.

The threshold for rate of change of Error in feedback loop Y1-Y0, e.g. wiring
frequency was exceeded. failure or welded feedback contact.
Please check wiring.

The threshold for vector shift detection Error in feedback loop is removed. Press
was exceeded. ESC to reset the grid feeding monitoring
relay.

8 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Error memory

The last 99 events that caused tripping of the grid feeding monitoring relay, as well as any interruption of the control supply
voltage, will be recorded by the device. The type of error as well as the time stamp is recorded in the internal error list,
accessible via the menu “Error memory”. The list is stored in a non-volatile memory which can be reset by the user.

Storage position in the error list

Error code

Time stamp
In this case the error occured
4 hours, 8 minutes and 17 seconds
seconds after commissioning

Error code Explanation


AVL1N>UAV or AVL2N>UAV or AVL3N>UAV Overvoltage UAV (10-minutes average value)
AVL12>UAV or AVL23>UAV or AVL31>UAV Overvoltage UAV (10-minutes average value)
L1N>U1 or L2N>U1 or L3N>U1 Overvoltage U1
L12>U1 or L23>U1 or L31>U1 Overvoltage U1
L1N>U2 or L2N>U2 or L3N>U2 Overvoltage U2
L12>U2 or L23>U2 or L31>U2 Overvoltage U2
L1N<U1 or L2N<U1 or L3N<U1 Undervoltage U1
L12<U1 or L23<U1 or L31<U1 Undervoltage U1
L1N<U2 or L2N<U2 or L3N<U2 Undervoltage U2
L12<U2 or L23<U2 or L31<U2 Undervoltage U2
F>F1 Overfrequency F1
F>F2 Overfrequency F2
F<F1 Underfrequency F1
F<F2 Underfrequency F2
ROCOF ROCOF
VECTOR Vector shift
REMOTE Remote trip
NEUTRAL Interrupted neutral conductor
POWER Supply voltage is disconnected or too low
FB1 Failure in feedback loop Y1-Y0
FB2 Failure in feedback loop Y2-Y0
TEST Test function
Exxx (e.g. E123) Internal failure (logic or hardware of the device)

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 9


Connection and wiring

Example of single-phase application

L1
N Public grid

where applicable,
a transformer

6 A

10 A 10 A 10 A

A1 A2 1115 2125 3135 L1 L2 L3 N

  
1216 1418 2226 2428 3236 3438 Y3 Y2 Y1 Y0

 
K1

 
K2

2CDC 252 006 F0213


 Control input 1, feedback loop for switching device 1
 Control input 2, feedback loop for switching device 2 Inverter(s)
Generator(s)
 Control input 3 (e.g. for remote trip)
 Switching device 1 of the section switch
 Switching device 2 of the section switch

Example of three-phase application

L1
L2
L3
N Public grid

where applicable,
a transformer

6 A

10 A 10 A 10 A

A1 A2 1115 2125 3135 L1 L2 L3 N

  
1216 1418 2226 2428 3236 3438 Y3 Y2 Y1 Y0

 
K1

 
K2
2CDC 252 007 F0213

 Control input 1, feedback loop for switching device 1


 Control input 2, feedback loop for switching device 2 Inverter(s)
Generator(s)
 Control input 3 (e.g. for remote trip)
 Switching device 1 of the section switch
 Switching device 2 of the section switch

10 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated

Input circuits
Supply circuit A1-A2
Rated control supply voltage Us 24-240 V AC/DC
Rated control supply voltage Us tolerance -15...+10 %
Rated frequency DC or 50 Hz
Frequency range AC 40-70 Hz
Typical current / power consumption 24 V DC 64 mA / 1.5 W
230 V AC 6.4 mA / 1.5 VA
External fusing (necessary) 6 A gG (gL) or circuit breaker 6 A with B characteristic
Power failure buffering time 200 ms, according to LVFRT (Low Voltage Fault Ride Through)

Measuring circuits L1, L2, L3, N


Measuring ranges voltage (4-wire system L1, L2, L3-N) 0-312 V AC
voltage (3-wire system L1, L2, L3) 0-540 V AC
voltage (2-wire system L-N) 0-312 V AC
frequency 40-70 Hz
Accuracy of measurements voltage m 0.5 % w 0.5 V
frequency w 20 mHz
delay times m 0.1 % w 20 ms
Accuracy within the temperature range iU m 0.02 %/°C
Monitoring functions overvoltage 10-min average (>UAV) threshold adjustable, 1.000-1.300*Un in 0.005*Un steps
overvoltage (>U1) threshold adjustable, 1.000-1.300*Un in 0.005*Un steps
overvoltage (>U2) threshold adjustable, 1.000-1.300*Un in 0.005*Un steps
undervoltage (<U1) threshold adjustable, 0.100-1.000*Un in 0.005*Un steps
undervoltage (<U2) threshold adjustable, 0.100-1.000*Un in 0.005*Un steps
overfrequency (>F1) threshold adjustable, 50.00-65.00 Hz in 0.01 Hz steps
overfrequency (>F2) threshold adjustable, 50.00-65.00 Hz in 0.01 Hz steps
underfrequency (<F1) threshold adjustable, 45.00-60.00 Hz in 0.01 Hz steps
underfrequency (<F2) threshold adjustable, 45.00-60.00 Hz in 0.01 Hz steps
ROCOF threshold adjustable, 0.100-5.000 Hz in 0.005 Hz steps
vector shift threshold adjustable, 2.0-40.0 ° in 0.1 ° steps
interrupted neutral conductor enabled if a measuring principle with neutral is selected
Hysteresis related to the overvoltage 10-min average (>UAV) adjustable, 0.1-10.0 % in 0.1 % steps
threshold values
overvoltage (>U1, >U2) adjustable, 0.5-10.0 % in 0.1 % steps
undervoltage (<U1, <U2) adjustable, 0.5-10.0 % in 0.1 % steps
overfrequency (>F1, >F2) adjustable, 0.05-4.00 Hz in 0.01 Hz steps
underfrequency (<F1, <F2) adjustable, 0.05-4.00 Hz in 0.01 Hz steps
Measuring cycle of ROCOF adjustable, 4-50 periods

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 11


Control circuits Y0, Y1, Y2, Y3
Number 3
Type of triggering volt-free triggering, signal source Y0
Control function Y1-Y0 control input 1 feedback from switching device 1
Y2-Y0 control input 2 feedback from switching device 2
Y3-Y0 control input 3 remote trip; suppression of Y1, Y2, Y1/Y2 or vector shift detect.
Electrical isolation from the supply voltage yes
from the measuring circuit no
from the relay outputs yes
Maximum switching current in the control circuit 6 mA
No-load voltage at the control inputs (Y1-Y0, Y2-Y0, Y3-Y0) 22-26 V DC
Minimum control pulse length 20 ms
Maximum cable length at the control inputs (unshielded) 10 m

Timing functions
Switch-on delay (prior to first grid connection or re-connection after interruption) adjustable, 1.00-600.00 s in 0.01 s steps
Tripping delay overvoltage 10-min average (>UAV) <3s
overvoltage (>U1, >U2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
undervoltage (<U1, <U2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
overfrequency (>F1, >F2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
underfrequency (<F1, <F2) adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
ROCOF adjustable, 0.06-600.00 s in 0.01 s steps; +0 ms / -50 ms
vector shift < 50 ms
interrupted neutral conductor < 150 ms
Error time ROCOF adjustable, 0.5-600.00 s in 0.01 s steps
vector shift adjustable, 0.5-600.00 s in 0.01 s steps
Trip window, feedback loops Y1-Y0, Y2-Y0 adjustable, 0.05-0.50 s in 0.01 s steps
Release window, feedback loop Y1-Y0, Y2-Y0 adjustable, 0.50-600.00 s in 0.01 s steps
Accuracy within the temperature range it m 0.01 %

User interface
Indication of operational states
Control supply voltage applied / timing U/T LED green on / flashing
Fault message F LED red on
For details see the message on the display

Display
Backlight on press any button
off switch-off delay adjustable, 10-600 s (default 10 s)
Operating temperature range of the display clearly visible -20...+60 °C
Resolution 112 x 64 pixel
Display size 36 x 22 mm

Operating controls
4 push-buttons for menu navigation, setting and entering

12 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Output circuits
Kind of outputs 11-12/14 (15-16/18) 1st c/o (SPDT) contact, tripping relay for switching device 1
21-22/24 (25-26/28) 2nd c/o (SPDT) contact, tripping relay for switching device 2
31-32/34 (35-36/38) 3rd c/o (SPDT) contact, closing command for breaker motor
Operating principle 11-12/14 closed-circuit principle1)
21-22/24 closed-circuit principle1)
31-32/34 open-circuit, closed-circuit, disabled or
synchronous with R1/R2 configurable
Contact material AgNi alloy, Cd free
Rated operational voltage Ue 300 V AC
Minimum switching voltage / minimum switching current 24 V / 10 mA
Maximum switching voltage / maximum switching current see ‘Load limit curves’
Rated operating current Ie AC-12 (resistive) at 230 V 4A
AC-15 (inductive) at 230 V 3A
DC-12 (resistive) at 24 V 4A
DC-13 (inductive) at 24 V 2A
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime at AC-12, 230 V AC, 4 A 50 x 103 switching cycles
Maximum fuse rating to achieve n/c contact 10 A fast-acting
short-circuit protection
n/o contact 10 A fast-acting
Maximum closing current (short time) t < 20 ms 30 A
t < 80 ms 17 A
Conventional thermal current Ith 5A
1) C
 losed-circuit principle: Output relay de-energizes if a fault is occuring
Open-circuit principle: Output relay energizes if a fault is occuring

General data

MTBF on request
Repeat accuracy (constant parameters) < w 0.5 %
Duty time 100 %
Dimensions see ‘Dimensional drawing’
Weight 0.306 kg (0.675 lb)
Material of housing PA666FR
Mounting DIN rail (IEC/EN 60715) TH 35-7.5 and TH 35-15,
snap-on mounting without any tool
Mounting position any
Minimum distance to other units horizontal / vertical not necessary
Degree of protection housing / terminals IP20

Electrical connection
Connecting capacity fine‑strand with wire end ferrule 1 x 0.25-4 mm² (1 x 24-12 AWG)
2 x 0.25-0.75 mm² (2 x 24-18 AWG)
fine‑strand without wire end ferrule 1 x 0.2-4 mm² (1 x 24-12 AWG)
2 x 0.2-1.5 mm² (2 x 24-16 AWG)
rigid 1 x 0.2-6 mm² (1 x 24-10 AWG)
2 x 0.2-1.5 mm² (2 x 24-16 AWG)
Stripping length 8 mm (0.315 in)
Tightening torque 0.5-0.6 Nm (4.4-5.3 lb.in)

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 13


Environmental data
Ambient temperature ranges operation -20 °C...+60 °C (-4...+140 °F)
storage -20 °C...+80 °C (-4...+176 °F)
Damp heat, cyclic IEC/EN 60068-2-30 6 x 24 h cycle, 55 °C, 95 % RH
Climatic class IEC/EN 60721-3-3 3K5 (no condensation, no ice formation)
Vibration, sinusoidal Class 2
Shock Class 2

Isolation data
Rated insulation voltage Ui supply / measuring / output circuits 600 V
output 1 / output 2 / output 3 300 V
Rated impulse withstand voltage Uimp supply / measuring / output circuits 6 kV; 1.2/50 µs
output 1 / output 2 / output 3 4 kV; 1.2/50 µs
Basic insulation supply / measuring / output circuits 600 V AC
output 1 / output 2 / output 3 300 V AC
Protective separation supply / measuring / output circuits 250 V
(IEC/EN 61140)
output 1 / output 2 / output 3 250 V
Pollution degree 3
Overvoltage category III

Standards / Directives
Standards IEC/EN 60255-27, EN 50178, VDE-AR-N 4105,
BDEW ("Technische Richtlinie - Erzeugungsanlagen am
Mittelspannungsnetz")
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU

Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV contact discharge, 8 kV air discharge
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m
electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 3, installation class 3,
supply circuit and measuring circuit 1 kV L-L, 2 kV L-N
conducted disturbances, induced by radio- IEC/EN 61000-4-6 Level 3, 10 V
frequency fields
voltage dips, short interruptions and voltage IEC/EN 61000-4-11 Class 3
variations
harmonics and interharmonics IEC/EN 61000-4-13 Class 3
Interference emission IEC/EN 61000-6-3
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B

14 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Technical diagrams

Load limits curves


V V
300 300
V 200 V 200

100 100
80 80
60 60
50 50
40 40
30 30
20 20

2CDC 252 194 F0205

2CDC 252 193 F0205


10 10
0.1 0.2 0.5 1 2 4 6 10 0.1 0.2 0.5 1 2 4 6 10
I A I A

AC load (resistive) DC load (resistive)

1.0

Switching cycles
0.9

0.8
F
0.7

0.6
250 V
2CDC 252 192 F0205

0.5 resistive load

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ

2CDC 252 148 F0206


Derating factor F at inductive AC load

Switching current [A]

Contact lifetime

Data sheet | Grid feeding monitoring relay CM-UFD.M31 - 15


Dimensions
in mm and inches

67 2.64” 108 4.25”

90 3.54”

2CDC 252 008 F0013


Further documentation

Document title Document type Document number


Electronic relays and controls Catalog 2CDC 110 004 C02xx
CM-UFD.M31 Grid feeding monitoring relay Instruction sheet 1SVC 560 511 M0000

You can find the documentation on the internet at www.abb.com/lowvoltage


-> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays.

CAD system files


You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com
-> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls.

16 - Grid feeding monitoring relay CM-UFD.M31 | Data sheet


Contact us

ABB STOTZ-KONTAKT GmbH

Document number 2CDC 112 208 D0201 (03.2017)


P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-mail: [email protected]

You can find the address of your


local sales organisation on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems

Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.

We reserve all rights in this document and in the


subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
utilization of its contents – in whole or in parts –
is forbidden without prior written consent of ABB
AG.

Copyright© 2014 ABB


All rights reserved

You might also like