100% found this document useful (1 vote)
469 views6 pages

Classification Generator Tripping

The document discusses generator tripping classification schemes for faults. It describes Class A, B, and C trips which classify faults based on the plant layout and whether a generator circuit breaker is present. Class A faults are serious electrical faults that require isolating the generator. Class B relates to mechanical problems, tripping the turbine then generator. Class C involves external system issues like frequency, not requiring immediate tripping. The schemes classify protections differently based on whether a generator circuit breaker is present to isolate the generator during faults.

Uploaded by

sriface
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
469 views6 pages

Classification Generator Tripping

The document discusses generator tripping classification schemes for faults. It describes Class A, B, and C trips which classify faults based on the plant layout and whether a generator circuit breaker is present. Class A faults are serious electrical faults that require isolating the generator. Class B relates to mechanical problems, tripping the turbine then generator. Class C involves external system issues like frequency, not requiring immediate tripping. The schemes classify protections differently based on whether a generator circuit breaker is present to isolate the generator during faults.

Uploaded by

sriface
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Classification Generator tripping Scheme Class A, Class B & Class C

The generator Tripping classified according to the fault.

Protection of the generator:

• Voltage Controlled Over Current Protection


• (51V)
• Dead Machine Protection (50/27)
• Generator Circuit Breaker Failure (50BF)
• Over Excitation Protection (24G)
• Over Voltage Protection (59)
• Reverse Power Protection (32R)
• Low Forward Power Protection (32F)
• Differential Protection (87G)
• Under Frequency Protection (81G)
• Over Frequency Protection (81G)
• Loss of Excitation (40G)
• 95 % Stator Earth Fault (64G1)
• 100 % Stator Earth Fault (64G2)
• Generator Rotor Earth Fault (64F)
• Exciter Rotor Earth Fault
• I&C Trip from ETS.
• Excitation System Fault
• Generator Pole Slipping (78)
• Negative Phase Sequence Protection (46)
• Backup Impedance Protection (21)
• Generator Cooling Water Loss
• Conductivity High Loss

Classification depends upon following:

1. Plant layout
2. Means how generator is connected to high voltage transmission line.
3. There are two different ways:
• Without GCB scheme => GCB -Generator Circuit Breaker
• With GCB scheme

Without GCB Scheme:


• Generator synchronizing done at switchyard.

• Generator, GT& UAT are directly connected to switchyard.

• If any faults in generator, then we have to open switchyard breaker.

Without GCB we can classified into 3 class

• Class A

• Class B

• Class C

Class A trips:

Class A trip involves a serious electrical fault like differential, stator earth fault etc. and is

considered to be the most dangerous in terms of the shock on the unit. Since it involves serious

electrical faults, connections from both generator and the EHV bus is immediately switched off to

limit the damage at the fault point and also to isolate the healthy system. Hence the unit (turbine,

generator and boiler) has to be tripped.

Class B trip:

Class B primarily relates to mechanical problems. This results in tripping of turbine followed by

generator.

Class C trip:

Class C involves basically external system related problems like frequency, overvoltage etc. This

does not involve instant tripping of the unit. CPP unit operates on house load.
• Generator synchronizing done at TG building.

• Generator is not directly connected to GT, UAT & switchyard

• If any faults in generator then we have to open GCB.

• Classification of generator protection tripping in this scheme are

1. Class A1

2. Class A2

3. Class B
Class A1:

Class A-I trip is mainly for faults in generator transformer and unit transformer. In this class, trip

goes to following equipments without time delay.

• Generator Breaker (GCB).

• EHV Breaker.

• UAT LV breaker and Field Breaker.

Three generator protections come into Class-AI.

• Voltage Controlled Over Current Protection (51V).

• Dead Machine Protection (50/27).

• Generator Circuit Breaker Failure (50BF).

Class A2:

Class AII trip is for faults in generator. In this class, trip goes to following equipments without time

delay.

• Turbine,

• Generator breaker (GCB),

• Field breaker.

Advantage of GCB scheme:

The auxiliaries are fed through unit transformer by back charging of GT. Thus in Class A2 trip we

are able to maintain uninterrupted power to the Unit bus and auxiliaries which was not possible

in the scheme without GCB.


There are 13 generator protections into Class AII:

1. Over Excitation Protection (24G)

2. Over Voltage Protection (59)

3. Reverse Power Protection (32R)

4. Under Frequency stage – 2 (81)

5. Low Forward Power Protection (32F)

6. Differential Protection (87G)

7. Loss of Excitation (40G)

8. 95 % Stator Earth Fault (64G1)

9. 100 % Stator Earth Fault (64G2)

10. Generator Rotor Earth Fault (64F)

11. Exciter Rotor Earth Fault

12. I&C Trip from ETS

13. Excitation System Fault

Class B

Class B trip also leads to generator breaker (GCB) tripping. In this class, trip goes to only
turbine. There are 7 generator protections come into Class B

o Under frequency stage-1 (81)

o Over Frequency Stage-2 (81)

o Generator Pole Slipping (78)

o Negative Phase Sequence Protection (46)

o Backup Impedance Protection (21)

o Generator Cooling Water Loss

o Conductivity High loss.

You might also like