Power Range kVA: Professional
Power Range kVA: Professional
Pro
Power range 10-500 kVA
Professional
www.elcos.net
.pro
Power range 10-500 kVA
Generating sets 1500-1800/3000-3600 RPM
EU
Standards
50/60Hz - 400-230 V/480-277 V Compliant
Diesel Generators Safe for the operator and easy to Fully customizable to fit
maintain all needs
The generating sets of our PRO All operations, such as use, Thanks to a wide range
range cover emergency needs in commissioning and of accessories you can
support to the standard supply maintenance are carried out in configure the generator
of electricity. complete safety. to be perfectly suited
They are built with elements They guarantee a reliable power to your requests.
of ultimate technology, which supply and the maximum
allow to reduce the noise gener- level of performance in the
ated from the engine. event of a sudden power
failure.
The PRO range covers the reference power from 10 to 500 KVA. Engine and Alternator Brands
2
Electric power supply solutions
Designed for a high loadability index on trucks and in containers
Index of loading capacity
Power range GS per camion GS per container The generating sets of our
10-20 kVA 32 GS 26 GS PRO range cover emergency
needs in support to the stan-
30-40 kVA 26 GS 24 GS dard supply of electricity.
50-100 kVA 10 GS 8 GS
They guarantee a reliable
130-165 kVA 4 GS 3 GS power supply and the
180-200 kVA 3 GS 3 GS maximum level of
performance in the event of
a sudden power failure.
Applications
These generators can be used in a variety of applications, such as:
Industries - Shops - Hotels - Restaurants - Nursing homes - Gas stations - Malls - Farms - Livestock farm -
Recreation centers
www.elcos.net
QAIC/IT/91790-A
3
.pro
Power range 10-500 kVA
Generating sets 1500-1800/3000-3600 RPM
50/60Hz - 400-230 V/480-277 V
4 lifting hooks
for safe handling
QLE MC2
EMERGENCY PANEL
Engines liquids 4 lifting hooks
-20 °C oil and antifreeze for safe handling
Variant +011
Without integrated switching
Lead-acid starter Aspiration louvres With this variant the SWITCHING is externally
battery guarantee a suitable managed through separate ATS panels (optional).
è Controls è Protections/Alarms
l Manual start up and stop l Failed to start
l Automatic start up and stop from AMF l Failed to stop
l Test NO load with external timer l Low oil pressure
l Remote start from dry-contact l High temperature
l G.S. locked from external l Generator battery charger
l Emergency stop button l Fuel reserve (Warning)
Galvanized metal General switch l Mains counter command closed l No Fuel (Shutdown)
l Genset counter command closed l Genset overvoltage
sheet mounted on the panel l Genset undervoltage
è Engine Measures l Genset maximum frequency
to increase strength for a comfortable l Fuel level % l Genset minimum frequency
l Phase rotation
and durability and safe connection l Total operating hours
l Battery charger voltage
l Start up counter è Signals
l Engine speed l Start up
l Stop
è Alternator Measures l Battery connected
l Gen set voltage three-phase RST l Battery charging
l Gen set star voltage RN.SN.TN. l Battery undervoltage
l Gen set frequency l Battery overvoltage
l Genset connected
è Main Measures l Mains connected
l Mains voltage RST l Mains overvoltage
l Mains frequency l Mains undervoltage
l Emergency button pressed
è Equipment
Safe handling Residential muffler l Microprocessor logic
l Cumulative alarm
l Fuel reserve
with forklift and pallet -35 dBA l Backlit refractive display l No fuel
l 10 events alarm history list
truck It guarantees reliable l Icons management
l Troubleshooting with suggestions
sound installation
Exhaust pipes Bunded base Cable outlet Inspection doors Exhaust terminal pipe
with exhaust heat wrap enviromental friendly - to allow an easy with wide opening doors with tilting cap rain cover
for high-performance to contain the liquids in connection and airtight gasket
and security the event of a spill 5
GE.pro
Power Generators 10 - 100 kVA
1500 - 1800 / 3000 - 3600 RPM DIESEL
50 - 60 HZ 400 - 480 V
RUNTIME
CM
SPEED dBA switch
50 HZ 60 HZ 50 HZ 60 HZ BRAND CODE COOLING STAGE GOVERNOR LXWXH WEIGHT kg TANK lt LOAD @ 75% - h NOISE @ 7 m SWITCH A
10 kVA
GE.K3W.011/010.PRO 11,7 - 10 - Kohler 3000 KDW702 W50° Stage 0 M 173x92x130 470 90 38 66 16
13 kVA
GE.PK.016/013.PRO 15 - 13 - Perkins 403A-15G1 W50° Stage 0 M 173x92x130 626 90 33 60 20
15 kVA
GE.BD.017/015.PRO 17 25 15 23 Baudouin 4M06G20/5 W50° Stage 0 M 173x92x130 728 90 25 60 20
GE.K3W.017/015.PRO 17,5 - 15,9 - Kohler 3000 KDW1003 W50° Stage 0 M 173x92x130 518 90 29 67 20
20 kVA
GE.BD.022/020.PRO 21 32 20 29 Baudouin 4M06G25/5 W50° Stage 0 E 173x92x130 747 90 20 62 32
25 kVA
GE.CU.030/027.PRO 27,5 - 25 - Cummins X2.5G2 W50° Stage 0 M 188x92x130 771 90 19 65 40
GE.K3W.028/025.PRO 28,7 - 26,1 - Kohler 3000 KDW1603 W50° Stage 0 M 173x92x130 604 90 16 68 40
30 kVA
GE.BD.035/032.PRO 35 42 32 38 Baudouin 4M06G35/5 W50° Stage 0 E 188x92x130 831 90 17 65 50
GE.K3W.037/035.PRO 37,6 - 34,2 - Kohler 3000 KDW2204 W50° Stage 0 M 173x92x130 685 90 13 70 50
40 kVA
GE.BD.044/040.PRO 44 51 40 47 Baudouin 4M06G44/5 W50° Stage 0 E 188x92x130 857 90 14 67 63
50 kVA
GE.AI.056/051.PRO 55 - 50 - FPT N45AM2 W50° Stage 0 M 251x112x164 1136 250 27 67 80
60 kVA
GE.AI.066/060.PRO 66 73 60 66 FPT N45SM1A W50° Stage 2 M 251x112x164 1232 250 26 67 100
80 kVA
GE.AI.090/080.PRO 90 99 80 90 FPT N45SM3 W50° Stage 0 M 251x112x164 1375 250 17 69 125
GE.BD.090/082.PRO 90 103 82 94 Baudouin 4M11G90/5 W50° Stage 0 E 251x112x164 1527 250 19 69 125
GE.PK.088/080.PRO 88 100 80 90 Perkins 1104A-44TG2 W50° Stage 0 M 251x112x164 1449 250 18 68 125
100 kVA
GE.AI.110/100.PRO 110 120 100 110 FPT N45TM2A W50° Stage 2 M 251x112x164 1448 250 16 69 160
GE.BD.110/100.PRO 110 132 100 120 Baudouin 4M11G120/5 W50° Stage 0 E 251x112x164 1594 250 15 69 160
GE.PK.110/100.PRO 110 125 100 112 Perkins 1104C-44TAG2 W50° Stage 2 E 251x112x164 1483 250 15 69 160
www.elcos.net
6
GE.pro
Power Generators 130 - 500 kVA
1500 - 1800 RPM DIESEL
50 - 60 HZ 400 - 480 V
RUNTIME
CM
SPEED dBA switch
50 HZ 60 HZ 50 HZ 60 HZ BRAND CODE COOLING STAGE GOVERNOR LXWXH WEIGHT kg TANK lt LOAD @ 75% - h NOISE @ 7 m SWITCH A
130 kVA
GE.AI.131/120.PRO 135 140 120 130 FPT N45TM3 W50° Stage 0 M 320x122x208 1754 250 12 68 250
GE.BD.150/135.PRO 150 170 135 150 Baudouin 6M11G150/5 W50° Stage 0 E 320x122x208 1960 250 11 69 250
GE.PK.151/137.PRO 150 169 135 152 Perkins 1106A-70TG1 W50° Stage 0 M 320x122x208 1977 250 12 69 250
150 kVA
GE.AI.176/165.PRO 176 187 165 170 FPT N67TM4 W50° Stage 0 M 320x122x208 1949 250 9 70 250
GE.BD.165/150.PRO 165 200 150 181 Baudouin 6M11G165/5 W50° Stage 0 E 320x122x208 1998 250 10 70 250
GE.PK.166/150.PRO 165 188 150 168 Perkins 1106A-70TAG2 W50° Stage 0 M 320x122x208 2078 250 11 69 250
200 kVA
GE.AI.221/201.PRO 220 234 200 210 FPT N67TM7 W50° Stage 0 M 343x122x208 2116 250 7 70 320
GE.BD.220/200.PRO 220 250 200 225 Baudouin 6M16G220/5 W50° Stage 0 E 370x122x208 2523 250 8 70 320
GE.PK.220/200.PRO 220 - 200 - Perkins 1106A-70TAG4 W50° Stage 0 E 343x122x208 2245 250 8 70 320
250 kVA
GE.AI.275/250.PRO 275 290 250 260 FPT N67 TE8W W50° Stage 0 E 343x122x208 2282 250 7 71 400
GE.BD.275/250.PRO 275 313 250 284 Baudouin 6M16G275/5 W50° Stage 0 E 370x122x208 2669 250 6 70 400
GE.PK.275/250.PRO 275 - 250 - Perkins 1206A-E70TTAG3 W50° Stage 0 E 343x122x208 2363 250 7 70 400
GE.VO.275/250.PRO 275 287 250 255 Volvo TAD 734 GE W50° Stage 2 E 343x122x208 2506 250 7 70 400
300 kVA
GE.AI.332/305.PRO 332 363 305 330 FPT C87TE4 W50° Stage 0 E 395x154x220 3571 400 8 71 630
GE.BD.340/310.PRO 340 385 310 350 Baudouin 6M16G350/5 W50° Stage 0 E 395x154x220 3545 400 8 72 630
GE.PK.335/300.PRO 335 389 300 352 Perkins 1506A-E88TAG5 W50° Stage 0 E 395x154x220 3652 400 9 71 630
GE.SC.335/304.PRO 350 360 320 340 Scania DC09 072A 02 13 W50° Stage 0 E 395x154x220 3618 400 9 69 630
350 kVA
GE.AI.385/350.PRO 385 418 350 380 FPT C13TE2A W50° Stage 2 E 395x154x220 3801 400 8 71 630
GE.BD.385/350.PRO 385 413 350 375 Baudouin 6M21G385/5 W50° Stage 0 E 395x154x220 3756 400 7 72 630
GE.PK.400/350.PRO 400 440 350 400 Perkins 2206A-E13TAG2 W50° Stage 0 E 395x154x220 4088 400 8 71 630
375 kVA
GE.SC.410/375.PRO 410 451 375 410 Scania DC13 072A 02 11 W50° Stage 0 E 395x154x220 4039 400 8 70 630
400 kVA
GE.AI.440/400.PRO 440 462 400 420 FPT C13TE3A W50° Stage 2 E 395x154x220 3985 400 6 71 630
GE.BD.440/400.PRO 440 488 400 438 Baudouin 6M21G440/5 W50° Stage 0 E 395x154x220 3946 400 7 71 630
GE.PK.450/400.PRO 450 438 400 400 Perkins 2206A-E13TAG3 W50° Stage 0 E 395x154x220 4184 400 7 71 630
GE.SC.456/413.PRO 450 501 410 456 Scania DC13 072A 02 12 W50° Stage 0 E 395x154x220 4096 400 7 70 630
450 kVA
GE.SC.503/456.PRO 503 553 450 503 Scania DC13 072A 02 13 W50° Stage 0 E 395x154x220 4166 400 7 73 800
500 kVA
GE.SC.553/503.PRO 553 553 503 503 Scania DC13 072A 02 14 W50° Stage 0 E 395x154x220 4339 400 6 72 800
www.elcos.net
7
.pro
Power range 10-250 kVA
Engine
Fuel/water separator filter
Engine liquids -40 °C
Oil suction pump
Oil pressure level and engine temperature sensors (only with
enhanced controllers)
Engine pre-heater 230 Vac with thermostat on board
Radiator coolant level sensor
Batteries
DC isolator
Maintenance free high efficiency starter batteries
Exhaust
Spark arrestor
Exhaust flex pipe (3 mt lenght)
Exhaust pipe protection kit
Fuel supply
Automatic fuel refilling system on board
Quick coupling connectors with 3-way valve for external
Oversized fuel tank on board
Spare parts
Toolbox for routine maintenance
www.elcos.net
8
Optional
Electrical System
Option with QPE MC4 on board
Option with DSE 7320 on board
Option with ComAp AMF25 on board
Differential protection
Tanks
Double wall fuel tanks with feet and tear valve
Single wall fuel tank for outdoor use with bunded base
and roof
Services
Factory Acceptance Test (FAT)
Vibrations test
www.elcos.net
9
Testing Rooms
60 Hz
480 - 240 - 208 - 220 - 277 V
Features of Testing Room N° 1
l 607 kW x 2 automatic test with 10 load steps
l 35 kW automatic test with 10 load steps
l 10 kW automatic test in DC with 10 load steps
l Full tests with 6 PT 100 probes, 3 thermal probes
l Air flow test with anemometer
l Vibrations test
l Phonometric test
l Data registration by MODBUS
Company
Product quality and customer satisfaction: the passions that guide us.
The R&D department is constantly studying the possibilities of
technological innovation to improve the products proposed, to
explore the possibilities of new products and to improve production
processes. Always focused on quality, ensuring conformity of the
product and the processes according to legislation, by respecting
environmental issues.
www.elcos.net
11
[email protected]
+39.0372.7233300
elcos.net/service
ELCOS SRL
Strada Statale 234 Km 58.250 -
26023 Grumello Cremonese CR - Italy
tel +39 0372 72330 - fax +39 0372 7233220
PI 01084730199
[email protected] - [email protected]
www.elcos.net