SSR Sequence Interface 1: Installation Instructions M37-160

This document provides installation instructions for interfacing an M37-160kW compressor controlled by an Intellisys controller with an approved remote sequencer. The interface assembly is installed in the starter cabinet and connected to the Intellisys controller and remote sequencer. The Intellisys controller parameters must be adjusted to enable remote sequence control. Connections are made between the interface, compressor, and sequencer controller according to the provided diagrams.

Uploaded by

Nikolay Velchev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
167 views9 pages

SSR Sequence Interface 1: Installation Instructions M37-160

This document provides installation instructions for interfacing an M37-160kW compressor controlled by an Intellisys controller with an approved remote sequencer. The interface assembly is installed in the starter cabinet and connected to the Intellisys controller and remote sequencer. The Intellisys controller parameters must be adjusted to enable remote sequence control. Connections are made between the interface, compressor, and sequencer controller according to the provided diagrams.

Uploaded by

Nikolay Velchev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

SSR SEQUENCE INTERFACE 1

INSTALLATION INSTRUCTIONS

M37-160

CCN 93183770
MAY 2001
SSR Sequence Interface 1
Installation Instructions
M37-160kW

PURPOSE
To interface M37-160 Intellisys controlled compressors with Ingersoll-Rand
approved sequencers.

CAUTION!!
The installation of this equipment should only be undertaken by
competent electrical personnel.

CAUTION!!
Disconnect all electrical power before working on the machine.

CONTENTS

1 Interface to the compressor


2 Interface to the remote sequence controller
3 Enabling the controllers

2
1 INTERFACE TO THE COMPRESSOR

Install the interface assembly as illustrated in Figure 1

Interface To Be Secured With


Screws To Pre–Tapped Holes
In Top Left Corner Of Starter
Cabinet
TOP ENCLOSURE

BACK OF
INTELLISYS
Figure 1 STARTER

Ensure the communication cable and 48Vac supply interface


connections are made.

Connect the 48Vac / 0Vac supply cables to starter panel terminals as


follows:

Machine 48Vac 0Vac


M55-160kW CF3 113
M55-75 Water Cooled 101 115
M37-45 CF3 115

3
Connect the serial communication cable into the Intellisys controller
(socket located top left) see Figure 2.

Figure 2

2 INTERFACE TO THE REMOTE SEQUENCE CONTROLLER

Customer to supply connection cables – recommended minimum


0.5mm² PVC multicore cable.

Recommended cable route – enter the compressor via a suitable route


but NOT the power inlet conduit. Direct the cable in the starter panel
through trunking.

Refer to the connection diagrams, wire the interface to the remote


sequence controller as required.

Note: Ensure correct connections

3 ENABLING THE CONTROLLERS

It is necessary to adjust the Intellisys controller operating parameters to


enable remote sequence option, the following describes the procedure:

Power up the compressor.

When display shows “Ready To Start” press the “Set” button to enter
customer set points.

Press the “Set” button repeatedly until “Select Options” LED is


illuminated and the display shows “Sequence Off”.

4
Press the arrow keys to display “Sequence On”, depress the “Set”
button to store sequencer enable function.

Press the “Display Select” button to exit the customer set point routine.

Display will show “Checking Machine”, followed by “Ready To Start”,


the compressor is now ready to operate via the sequencer.

Adjust the sequencer pressure switches to requirements, test to verify


operation.

Note:

The controller maintains all standard display and alarm functions, the
remote sequencer provides on line/off line control only.

Interface sequencer 1 provides a 48Vac output to indicate compressor


running (output terminal 3) if required. An additional relay will be
necessary if utilised, this is not supplied in the kit.

It is not possible to exceed the compressors maximum rated pressure.

5
SSR SEQUENCE INTERFACE 1

KIT CCN 93168920

Parts List

Item Qty CCN Description


1 1 93168987 Cable Assembly Sequence Interface
2 1 39831524 Interface, Sequence Intellisys 1 ESA
3 4 92050376 Setscrew, Cheese head M4
4 4 92340439 Flat washer M4
5 4 92340447 Lock washer M4
6 1 93183770 Fitting Instructions, Sequence Intellisys 1

Use Only Genuine Ingersoll-Rand Parts

6
CONNECTION DIAGRAM 1

COMPRESSOR INTELLISYS
CONTROLLER

STARTER
PANEL 0V 48V

COMMUNICATIONS
COMPRESSOR RUN CABLE AND
SIGNAL 48V OUTPUT 48V SUPPLY
(OPTIONAL) Machine 48V 0V
M55-160kW CF3 113
M55-75WC 101 115
COMMUNICATION M37-45 CF3 115
PLUGS
1 LOAD
2 UNLOAD
3 RUN SEQUENCE
4 INTERFACE 1
LOCAL
5 0V
6 0V
7 48V

1A 2A 3A 4A 5A 6A
SEQUENCE CONTROL PANEL

2 UNIT CCN 92806215


3 UNIT CCN 92806223
4 UNIT CCN 92806231
5 UNIT CCN 92806249

7
CONNECTION DIAGRAM 2

COMPRESSOR INTELLISYS
CONTROLLER

STARTER
PANEL 0V 48V

COMMUNICATIONS
COMPRESSOR RUN CABLE AND
SIGNAL 48V OUTPUT 48V SUPPLY
(OPTIONAL)
Machine 48V 0V
M55-160kW CF3 113
COMMUNICATION M55-75WC 101 115
PLUGS M37-45 CF3 115

1 LOAD
2 UNLOAD
3 RUN SEQUENCE
4 INTERFACE 1
LOCAL
5 0V
6 0V
7 48V

REMOTE
PRESSURE SWITCH

8
9