V Sem em II Lab Manual
V Sem em II Lab Manual
V SEMESTER
LABORATORY MANUAL
1
CONTENT
2
REGULATION OF A THREE PHASE ALTRENATOR BY EMF AND MMF METHODS
AIM:
To conduct OC and SC tests on a given 3-Φ alternator and hence to predetermine the regulation by
(i) EMF method (ii) MMF method.
APPARATUS REQUIRED:
THEORY:
Loading an alternator causes its terminal voltage to drop or rise depending upon (i) Magnitude of
load (ii) Nature of load. For a pure resistive load it drops by 8-12% below no-load value while for a
lagging p.f. load the drop is 25-50% below no load value and it is 20-30% higher for leading p.f. loads. The
reasons are 1) Armature resistance 2) Armature winding leakage reactance and 3) Armature reaction.
Electromotive force (EMF) and Magnetomotive force (MMF) methods are used to predetermine the
regulation of non-salient pole alternators. In emf method, the effect of armature reaction is represented as a
fictitious reactance Xar for each phase of the alternator. In mmf method effect of armature leakage reactance
is replaced by additional armature reaction. MMF method is more accurate.
Direct load Test is not preferred due to the absence of large sized loads and the enormous power
wastage involved in testing. Voltage regulation is defined as a percentage of rated voltage when load
current is reduced to zero suddenly by throwing off the load keeping If and speed constant.
PROCEDURE:
1. Using the 200 ohm potential divider, current in field circuit is increased in steps of 0.1A and at each
step the alternator induced voltage indicated by voltmeter and the corresponding field current (I f) are
noted in tabular column.
2. This procedure is continued until the alternator voltage is 120% of its rated voltage.
3. After completing O.C. Test, the potential divider and motor field rheostat are brought to its
minimum position.
4. After completing the experiment, calculate Synchronous Impedance, Synchronous Reactance &
Regulation using the formulae given.
5. Using the data, Plot the graph between Eo Vs If.
S.C. TEST:
1. The alternator terminals are short circuited by closing TPST switch through an ammeter.
2. The rated current is made to flow through the armature of the stator windings by carefully adjusting
220 ohms potential divider from the minimum position.
3. After completing the experiment, calculate the Load current, Field Current and Regulation.
4. Using the data, Plot the graph Isc vs If and % Regulation vs Power Factor for both the EMF and
MMF methods.
CIRCUIT DIAGRAM:
FUSE CALCULATION:
MOTOR
4
ALTERNATOR
TABULATION:
If Vg(1-1) Vg (ph)
S. No.
(A) (V) (V)
S.C TEST
S. No. If ISC
(A) (A)
FORMULAE USED:
EMF Method:
From the O.C.C. graph, find (1) If1 - Field current required to produce rated voltage per phase.
(2) If2 - Field current required to produce rated current per phase during
S.C. test.
If = {If1 +If2 -2If1If2cos(90±Φ)}1/2
2 2
Where ‘+’ for lagging p.f. load, ‘-‘for leading p.f. load.
5
E0 V
Now determine Vo corresponding to I from graph. % Reg X 100
V
EMF METHOD:
1. 0.2 0.2
2. 0.4 0.4
3. 0.6 0.6
4. 0.8 0.8
5. 1.0 1.0
MODEL GRAPH:
6
MMF METHOD:
1. 0.2 0.2
2. 0.4 0.4
3. 0.6 0.6
4. 0.8 0.8
5. 1.0 1.0
RESULT:
REVIEW QUESTIONS:
1. Define – Regulation
2. What is meant by pessimistic method?
3. Which method is called as optimistic method?
4. What are the advantages of EMF and MMF method?
5. List out the various methods used to predetermine the regulation.
7
REGULATION OF A THREE PHASE ALTRENATOR BY ZPF AND ASA METHODS
AIM:
To conduct OC and SC tests on a given 3-Φ alternator and hence to predetermine the regulation by
(i) ZPF method (ii) ASA method
APPARATUS REQUIRED:
THEORY:
Loading an alternator causes its terminal voltage to drop or rise depending upon (i) Magnitude of
load (ii) Nature of load. For a pure resistive load it drops by 8-12% below no-load value while for a
lagging p.f. load the drop is 25-50% below no load value and it is 20-30% higher for leading p.f. loads. The
reasons are 1) Armature resistance 2) Armature winding leakage reactance and 3) Armature reaction.
Electromotive force (EMF) and Magnetomotive force (MMF) methods are used to predetermine the
regulation of non-salient pole alternators. In emf method, the effect of armature reaction is represented as a
fictitious reactance Xar for each phase of the alternator. In mmf method effect of armature leakage reactance
is replaced by additional armature reaction. MMF method is more accurate.
Direct load Test is not preferred due to the absence of large sized loads and the enormous power
wastage involved in testing. Voltage regulation is defined as a percentage of rated voltage when load
current is reduced to zero suddenly by throwing off the load keeping If and speed constant.
PROCEDURE:
1. Using the 200 ohm potential divider, current in field circuit is increased in steps of 0.1A and at each
step the alternator induced voltage indicated by voltmeter and the corresponding field current (If) are
noted in tabular column.
2. This procedure is continued until the alternator voltage is 120% of its rated voltage.
3. After completing O.C. Test, the potential divider and motor field rheostat are brought to its
minimum position.
4. After completing the experiment, calculate Synchronous Impedance, Synchronous Reactance &
Regulation using the formulae given.
5. Using the data, Plot the graph between Eo Vs If.
S.C. TEST:
1. The alternator terminals are short circuited by closing TPST switch through an ammeter.
2. The rated current is made to flow through the armature of the stator windings by carefully adjusting
220 ohms potential divider from the minimum position.
3. After completing the experiment, calculate the Load current, Field Current and Regulation.
4. Using the data, Plot the graph Isc vs If and % Regulation vs Power Factor for both the EMF and
MMF methods.
CIRCUIT DIAGRAM:
FUSE CALCULATION:
MOTOR
9
ALTERNATOR
TABULATION:
If Vg(1-1) Vg (ph)
S. No.
(A) (V) (V)
S.C TEST
S. No. If ISC
(A) (A)
FORMULAE USED:
PROCEDURE
ZPF TEST
10
TABULAR COLOUMN
ZPF test
FORMULAE TO BE USED
At Lagging power factor
E0 =
√ (V cosφ + IaRa)2 + (V sinφ + IXL)2
0.2
0.4
LAG
0.6
0.8
UNITY 1
0.2
0.4
LEAD
0.6
0.8
RESULT
The predetermination of percentage of voltage regulation of given alternator using ZPF and ASA
methods were found.
11
REGULATION OF A THREE PHASE ALTRENATOR BY SLIP TEST
AIM:
To conduct OC and SC tests on a given 3-Φ alternator and hence to predetermine the regulation by
Slip test
APPARATUS REQUIRED:
THEORY:
Loading an alternator causes its terminal voltage to drop or rise depending upon (i) Magnitude of
load (ii) Nature of load. For a pure resistive load it drops by 8-12% below no-load value while for a
lagging p.f. load the drop is 25-50% below no load value and it is 20-30% higher for leading p.f. loads. The
reasons are 1) Armature resistance 2) Armature winding leakage reactance and 3) Armature reaction.
Electromotive force (EMF) and Magnetomotive force (MMF) methods are used to predetermine the
regulation of non-salient pole alternators. In emf method, the effect of armature reaction is represented as a
fictitious reactance Xar for each phase of the alternator. In mmf method effect of armature leakage reactance
is replaced by additional armature reaction. MMF method is more accurate.
Direct load Test is not preferred due to the absence of large sized loads and the enormous power
wastage involved in testing. Voltage regulation is defined as a percentage of rated voltage when load
current is reduced to zero suddenly by throwing off the load keeping If and speed constant.
CIRCUIT DIAGRAM:
12
PRECAUTION
1. All the switches should be kept open at the time of starting the experiment.
2. There should be no load at the time of starting the experiment.
3. The motor field rheostat should be kept at minimum resistance position.
PROCEDURE
TABULAR COLOUMN
FORMULAE
RESULT
The direct axis and quadrature axis component of the three phase alternator have been calculated.
13
MEASUREMENTS OF NEGATIVE SEQUENCE IMPEDANCE AND
ZERO SEQUENCE IMPEDANCE OF ALTERNATORS
AIM
To obtain the negative sequence and zero sequence reactance of a given three phase
alternator.
APPARATUS REQUIRED
S. No. Name of the apparatus Range Type Quantity
1 Voltmeter (0 – 300 V) M. I. 1
2 Voltmeter (0 – 150 V) M. I. 1
3 Ammeter (0 – 20 A) M. I. 1
4 Ammeter (0 – 10 A) M. I. 1
5 Ammeter (0 – 2 A) M. I. 1
6 Wattmeter 300 V, 10 A UPF 1
7 Rheostat 220 Ω, 2 A - 1
8 Single phase Auto Transformer (0 – 270 V) - 1
9 Tachometer (0 – 10000 rpm) Digital 1
14
TABULAR COLOUMN
NEGATIVE NEGATIVE
VOLTAGE CURRENT POWER SEQUENCE SEQUENCE AVERAGE
S. No.
VRY (V) ISC (A) (W) IMPEDANCE REACTANCE (X2)
(Z2) (X2)
1
2
3
4
FORMULAE
Z2 = VRY / (3 ISC)
X2 = Z2 (W2 / (VRY × ISC ))
15
RESULT
Thus the negative sequence reactance and zero sequence reactance have been determined.
16
V AND INVERTED V CURVES OFTHREE PHASE
SYNCHRONOUS MOTOR
AIM:
To draw V and inverted V curves for given three phase synchronous motor
APPARATUS REQUIRED:
S. No. Name of the apparatus Range Type Quantity
1 Voltmeter (0 – 600 V) M. I. 1
2 Ammeter (0 – 10 A) M. I. 1
3 Ammeter (0 – 2 A) M. C. 1
4 Wattmeter 600 V, 10 A UPF 1
(0 – 10000
5 Tachometer Digital 1
rpm)
Three phase Auto
6 (0 – 470 V) - 1
Transformer
7 Rheostat 950 Ω, 0.8 A - 1
CIRCUIT DIAGRAM:
17
PRECAUTION
1. All the switches should be kept open at the time of starting the experiment.
2. The potential divider in the field circuit of synchronous motor should be kept at minimum
potential position.
PROCEDURE
1. Connections are made as per the circuit diagram.
2. Close the T. P. S. T. switch.
3. The auto transformer is varied gradually to start the motor.
4. The auto transformer is adjusted till the voltmeter reads the rated voltage of the synchronous
motor.
5. Close the D. P. S. T. switch and increase the field current.
6. At no load condition, increase the field current in steps and note down the corresponding
armature current.
7. The potential divider is brought to the minimum potential position.
8. Repeat the same procedure for different load conditions.
9. Reduce the load on the motor.
10. Reduce the field current to zero value.
11. Reduce voltage by varying auto transformer.
12. Open all the switches.
TABULAR COLOUMN
WATTMETER READING
POWER
S. No. Ia (A) If (A)
FACTOR
W1 (W) W2 (W) W1 + W2 (W)
18
10
11
12
13
14
GRAPH
Field current, If Vs Armature current, Ia
Field current, If Vs Power factor, cosф
RESULT
Thus the V and inverted V curves of the given synchronous motor have been drawn.
19
LOAD TEST ON THREE PHASE INDUCTION MOTOR
AIM:
To conduct the direct load test on a given 3-phase induction motor and plot the performance
characteristics of the machine.
Rated voltage =
Rated power =
Rated current =
Frequency =
Rated speed =
APPARATUS REQUIRED:
THEORY:
Squirrel cage induction motors are so called because of the rotor construction, which is the most
rugged construction. The rotor conductors are heavy bars of copper, Aluminium that are permanently short-
circuited. The rotor slots are given a slight skew for quieter operation and to prevent the locking tendency of
the rotor. The direct load test is conducted on the squirrel cage induction motor to plot its performance
characteristics under loading condition. This is more accurate than the predetermination techniques as the
latter doesn’t take into account the effect of factors such as temperature, which cause significant change in
its operation.
20
PROCEDURE:
CIRCUIT DIAGRAM:
FUSE CALCULATION:
21
TABULAR COLUMN:
MODEL GRAPHS:
22
FORMULAE USED:
MODEL CALCULATION:
RESULT:
REVIEW QUESTIONS:
1. What is Skewing?
2. What is cogging?
3. What is crawling?
4. Define – Slip
23
NO LOAD AND BLOCKED ROTOR TESTS ON A THREE PHASE INDUCTION MOTOR
AIM:
To draw the equivalent circuit diagram of the given 3-phase squirrel-cage induction motor by
conducting no load and blocked rotor tests.
APPARATUS REQUIRED:
(0-600 V)
2 Voltmeter AC MI 1 each
(0-150 V)
(0-10 A)
3 Ammeter AC MI 1 each
(0-2 A)
12.41 kVA/ 415
4 3 Auto transformer - 1 No
(0-470 V)
THEORY:
This is a predetermination technique used to calculate the characteristics of the motor under
difference load conditions without actually loading the machine. The disadvantages of direct load test are (i)
Absence of loads of large magnitude (ii) Wastage of large amount of power during testing. The results
obtained are accurate enough for practical purposes. Therefore we apply the predetermination techniques to
obtain the load characteristics of the machine. From the losses obtained in these tests the equivalent circuit
of three phase induction motor can be determined and drawn.
1. Remove the fuse carriers before wiring and start wiring as per the circuit diagram.
2. Fuse Calculations: This being a load test, the required fuse ratings are 120% of rated current.
3. The auto transformer should be kept in minimum position.
4. Replace the fuse carrier with appropriate fuse wires after the circuit connections are checked by the
staff-in-charge.
24
PROCEDURE:
CIRCUIT DIAGRAM:
NO LOAD TEST:
FUSE CALCULATION:
25
BLOCKED ROTOR TEST:
FUSE CALCULATION:
TABULATION:
26
FORMULAE USED:
EQUIVALENT CIRCUIT:
MODEL CALCULATIONS:
RESULT:
The No-load and blocked rotor test was conducted on the given three-phase induction motor & the
equivalent circuit is drawn.
REVIEW QUESTIONS:
1. Prove that three phase power can be measure using two watt meters.
2. What is the necessity to have starter for three phase induction motor?
3. How mechanical load is represented in the equivalent circuit of induction motor?
4. Define – Synchronous Speed.
5. Why induction motors cannot run at synchronous speed?
27
LOAD TEST ON SINGLE PHASE INDUCTION MOTOR
AIM:
To draw load characteristics of a single phase induction motor by conducting the load test
APPARATUS REQUIRED:
S. No. Apparatus Range Type Quantity
1 Single phase induction motor - - 1
3 Voltmeter (0-300) V MI 1
4 Ammeter (0-10 ) A MI 1
THEORY:
Constructional of this motor is more or less similar to a poly phase induction motor, except
that its stator is provided with a single phase winding. A centrifugal switch is used in some type of
motor in order to cut out a winding, used in some type of motor, in order to cut out a winding, used
in some type of motors for starting squirrel cage rotor, when fed from a single phase only
alternating one which alternates along one phase axis only. Now, alternating or pulsating flux
acting on a stationary squired cage rotor cannot produce rotation that is why a single phase motor is
not self starting.
FORMULAE
1. Torque ( T )=S*9.81*R Nm
2. Output power (Po) = 2πNT/60 watts
3. Efficiency (η) = Output power / Input power X 100 %
4. Slip S = (Ns – Nr) / Ns * 100 %
5. Synchronous speed Ns = 120 f / P rpm
6. Power factor cos Φ = Pin / (VL *IL)
where,
R – Radius of brake drum.
VL – Line Voltage
28
IL – Line current
N – Speed in rpm
Nr - Rated speed in rpm
T – Torque in Nm
CIRCUIT DIAGRAM
PRECAUTIONS:
1. Motor should be started and stopped under no load condition.
2. Brake drum should be cooled with water when it is under load.
PROCEDURE:
1. Connections are made as per the circuit diagram.
2. The DPST switch is closed. The autotransformer is adjusted to get rated voltage and
corresponding no load readings are noted down.
3. Gradually increase the load upto the rated current and for each load the corresponding meter
readings are tabulated
4. Then load is removed and autotransformer reduced to zero. Then DPST switch opened.
29
TABULAR COLUMN:
Circumference of the Brake drum =_________m.
Voltage
Current Input Spring Balance Speed Torque Output Power
Reading S=S1 S2 Efficiency SLIP
S. No VL (V) Power N T Power Factor
I L (A) (Kg) % S
Pin (W) S1 (Kg) S2 (Kg) (rpm) (Nm) Po (W) Cos Φ
1
Radius = R=Circumference / (2 π)
= _________meter
MODEL CALCULATION
30
MODEL GRAPH
RESULT:
31
NO LOAD AND BLOCKED ROTOR TESTS ON SINGLE PHASE INDUCTION MOTOR
AIM
To draw the equivalent circuit of the given three phase induction motor by conducting no load and
blocked rotor test.
APPARATUS REQUIRED
S. No. Apparatus Range Type Quantity
1 Single phase induction motor - - 1
(0-300) V
3 Voltmeter MI 1
(0 -150) V
(0-10) A
4 Ammeter MI 1
(0-10) A
150 V, 5 A, LPF
5 Wattmeter 1 each
300 V, 10 A, UPF
CIRCUIT DIAGRAM
NO LOAD TEST
32
BLOCKED ROTOR TEST
PRECAUTION
1. All the switches should be kept open at the time of starting the experiment.
2. The three phase auto transformer should be kept at minimum potential position at the time of
starting the experiment.
3. For the blocked rotor test, the load is applied on the rotor and the rotor is not allowed to rotate.
4. During the blocked rotor test, the three phase auto transformer should be adjusted carefully and the
current should not exceed the rated current of the motor.
PROCEDURE
NO LOAD TEST
33
TABULAR COLOUMN
OPEN CIRCUIT TEST
FORMULAE
W0 = V0 I0 COS ф0
COS ф0 = W0 / (V0 I0)
IC = I0 COS ф0
Im = I0 SIN ф0
R0 = VO / IC
X0 = V0 / Im
X2 = Xeq / 2
R2 = Req - R1
R0 = V0 / (I0 COS ф0)
X0 = V0 / (I0 SIN ф0)
R01 = WSC / ISC2
X01 = √ Z012 - R012
R2 = R01 – (Rm llel Rs)
X2 = X01 – (Xm llel (XS - XL))
XS = √ ZS2 – RS2
Xm = √ Zm2 – Rm2
ZSC = VSC / ISC
RSC = WSC / ISC2
XSC = √ ZSC2 – RSC2
Slip = (Ns - Nr) / Ns
R2l = RSC – R1
X2l = X1 = XSC / 2
Xm = 2 (X0 – X1 – (X2l / 2))
34
RESULT
Thus the equivalent circuit of single phase induction motor has been drawn using no load and
blocked rotor tests.
35