h07rn F en 50525 2 21 Flexible Rubber Cable
h07rn F en 50525 2 21 Flexible Rubber Cable
h07rn F en 50525 2 21 Flexible Rubber Cable
APPLICATION STANDARDS
These cables are designed to provide high flexibility and have the EN 50525-2-21, EN 60228
capacity to withstand weather, oil/grease, mechanical and thermal
stresses. Applications include handling equipment, mobile power Flame Retardant according to IEC/EN 60332-1-2
supplies, worksites, stage and audio visual equipment, port areas Water Resistant according to AD7
and dams. Also for use in drainage and water treatment, cold
environments and severe industrial environments.
CONSTRUCTION
This cable meets the requirements of the Low Voltage Directive 2014/35/EU
Conductor and the RoHS Directive 2011/65/EU. RoHS compliance has been tested and
Class 5 flexible copper conductor confirmed by The Cable Lab® as meeting the requirements of the BSI RoHS
Trusted KitemarkTM. HAR approved.
Insulation
EPR (Ethylene Propylene Rubber) RoHS Trusted
KITEMARK™
Sheath KM 634267
PCP (Polychloroprene)
Core Identification
1 core: Black
2 core: Blue Brown
3 core: Green/Yellow Blue Brown
4 core: Green/Yellow Brown Black Grey
5 core: Green/Yellow Blue Brown Black Grey
6 core and above: Black with White numbers
Green/Yellow
Sheath Colour
Black
DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL NOMINAL NOMINAL A2 GLANDS A2PL GLAND
CORES SECTIONAL AREA THICKNESS OVERALL DIAMETER WEIGHT Brass Plastic
mm2 OF INSULATION mm kg/km
mm
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL THICKNESS NOMINAL OVERALL NOMINAL A2 GLANDS A2PL GLAND
CORES SECTIONAL AREA OF INSULATION DIAMETER WEIGHT Brass Plastic
mm2 mm mm kg/km
CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
1 0.21 19.5
1.5 0.26 13.3
2.5 0.26 7.98
4 0.31 4.95
6 0.31 3.3
10 0.41 1.91
16 0.41 1.21
25 0.41 0.78
35 0.41 0.554
50 0.41 0.386
70 0.51 0.272
95 0.51 0.206
120 0.51 0.161
150 0.51 0.129
185 0.51 0.106
240 0.51 0.0801
300 0.51 0.0641
400 0.51 0.0486
500 0.61 0.0384
630 0.61 0.0287
The above table is in accordance with EN 60228
NOMINAL CROSS CURRENT CARRYING CAPACITY MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CABLE
SECTIONAL AREA Amps (See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition
mm2 of IEE Wiring Regulations)
Single-Phase AC Three-Phase AC kg
1 10 10 5
1.5 16 16 5
2.5 25 20 5
Voltage Drop
1 46 40
1.5 32 27
2.5 19 16
Conductor operating temperature: 60ºC
NOMINAL CROSS 60°C CONDUCTOR OPERATING TEMPERATURE 85°C CONDUCTOR OPERATING TEMPERATURE**
SECTIONAL AREA Amps Amps
mm2
Single-Phase AC Three-Phase AC Single-Phase AC Three-Phase AC
1 Two Core Cable, With 2 Single Core 1 Three Core, 1 Two Core Cable, With 2 Single Core 1 Three Core,
or Without Protective Cables Four Core or or Without Protective Cables Touching Four Core or
Conductor Five Core Cable Conductor Five Core Cable
4 30 - 26 41 - 36
6 39 - 34 53 - 47
10 51 - 47 73 - 64
16 73 - 63 99 - 86
25 97 - 83 131 - 114
35 - 140 102 - 192 140
50 - 175 124 - 240 170
70 - 216 158 - 297 216
95 - 258 192 - 354 262
120 - 302 222 - 414 303
150 - 347 255 - 476 348
185 - 394 291 - 540 397
240 - 471 343 - 645 467
300 - 541 394 - 741 537
400 - 644 - - 885 -
500 - 738 - - 1017 -
630 - 861 - - 1190 -
Ambient temperature: 30ºC
Conductor operating temperature: 60ºC / 85ºC
The above table for 60ºC conductor operating temperature is in accordance with Table 4F1A of the 18th Edition of IEE Wiring Regulations BS7671 and IEC 60364-5-52
** 85ºC Table is in accordance with Table 4H2A of the 16th Edition of IEE Wiring Regulations.
The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface. If the cable is to be wound on a drum on load the ratings should
be reduced in accordance with NOTE 2 below and for cables which may be covered, NOTE 3 below.
The current ratings of cables used on reeling drums are to be reduced by the following factors:
A radial type drum is one where spiral layers of cable are accommodated between closely spaced flanges; if fitted with solid flanges the ratings given above should be reduced
and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is described as ventilated.
A ventilated cylindrical cable drum is one where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable ventilating
apertures.
3. Where cable may be covered or coiled up whilst on load, or the air movement over the cable restricted, the current rating should be reduced.
It is not possible to specify the amount of reduction but the table of rating factors for reeling drums can be used as a guide.
VOLTAGE DROP
NOMINAL CROSS TWO CORE TWO CORE CABLE, 1 THREE CORE, FOUR CORE OR FIVE 2 SINGLE CORE CABLES, TOUCHING
SECTIONAL AREA CABLES DC SINGLE-PHASE AC CORE CABLE, THREE-PHASE AC mV/A/m
mm2 mV/A/m mV/A/m mV/A/m
DC Single-Phase AC*
4 12 12 10 - -
6 7.8 7.8 6.7 - -
10 4.6 4.6 4 - -
16 2.9 2.9 2.5 - -
r x z r x z r x z
25 1.80 1.80 0.175 1.85 1.55 0.150 1.55 - - - -
35 - - - - 1.10 0.150 1.15 1.31 1.31 0.21 1.32
50 - - - - 0.83 0.145 0.84 0.91 0.91 0.21 0.93
70 - - - - 0.57 0.140 0.58 0.64 0.64 0.20 0.67
95 - - - - 0.42 0.135 0.44 0.49 0.49 0.195 0.53
120 - - - - 0.33 0.135 0.36 0.38 0.38 0.190 0.43
150 - - - - 0.27 0.130 0.30 0.31 0.31 0.190 0.36
185 - - - - 0.22 0.130 0.26 0.25 0.25 0.190 0.32
240 - - - - 0.170 0.130 0.21 0.190 0.195 0.185 0.27
300 - - - - 0.135 0.125 0.185 0.150 0.155 0.180 0.24
400 - - - - - - - 0.115 0.120 0.175 0.21
500 - - - - - - - 0.090 0.099 0.170 0.20
630 - - - - - - - 0.068 0.079 0.170 0.185
r = Resistive Component
x = Reactive Component
z = Impedance Value
DE-RATING FACTORS
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.