H07RN-F EN 50525-2-21 Flexible Rubber Cable

Eland Product Group: A6G and A5G

APPLICATION STANDARDS
These cables are designed to provide high flexibility and have the EN 50525-2-21, EN 60228
capacity to withstand weather, oil/grease, mechanical and thermal
stresses. Applications include handling equipment, mobile power Flame Retardant according to IEC/EN 60332-1-2
supplies, worksites, stage and audio visual equipment, port areas Water Resistant according to AD7
and dams. Also for use in drainage and water treatment, cold
environments and severe industrial environments.

ISO/IEC 17025 LABORATORY TESTED


This product is subject to the Quality Assurance protocols of The Cable Lab®,
CHARACTERISTICS an ISO/IEC 17025 accredited cable testing laboratory. Testing includes vertical
flame, conductor resistance, tensile & elongation, and dimensional consistency,
Voltage Rating U/Uo
verified to published standards and approved product drawings.
450/750V
ISO/IEC
Temperature Rating 17025
Accredited
Fixed: -30°C to +60°C Testing
Laboratory

Fixed protected installations: +85°C 8578


Flexed: -15°C to +60°C

Insulation tested to +90oC REGULATORY COMPLIANCE


This cable is compliant with European Regulation EN 50575, the Construction
Minimum Bending Radius
Products Regulation.
Fixed: 4 x overall diameter
Flexed: 6 x overall diameter

CONSTRUCTION
This cable meets the requirements of the Low Voltage Directive 2014/35/EU
Conductor and the RoHS Directive 2011/65/EU. RoHS compliance has been tested and
Class 5 flexible copper conductor confirmed by The Cable Lab® as meeting the requirements of the BSI RoHS
Trusted KitemarkTM. HAR approved.
Insulation
EPR (Ethylene Propylene Rubber) RoHS Trusted
KITEMARK™

Sheath KM 634267

PCP (Polychloroprene)

Core Identification
1 core: Black
2 core: Blue Brown
3 core: Green/Yellow Blue Brown
4 core: Green/Yellow Brown Black Grey
5 core: Green/Yellow Blue Brown Black Grey
6 core and above: Black with White numbers
Green/Yellow

Sheath Colour
Black

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected] technicalspecification | 1 of 5
Click here for more information:
elandcables.com | H07RN-F EN 50525-2-21 Flexible Rubber Cable

DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL NOMINAL NOMINAL A2 GLANDS A2PL GLAND
CORES SECTIONAL AREA THICKNESS OVERALL DIAMETER WEIGHT Brass Plastic
mm2 OF INSULATION mm kg/km
mm

A6G10015 1 1.5 0.8 5.8 52 20/16 20S


A6G10025 1 2.5 0.9 6.5 67 20/16 20S
A6G1004 1 4 1 7.4 92 20/16 20S
A6G1006 1 6 1 8.1 119 20S 20S
A6G1010 1 10 1.2 9.8 185 20S 20S
A6G1016 1 16 1.2 11.35 258 20 20
A6G1025 1 25 1.4 13.3 375 25 20
A6G1035 1 35 1.4 14.6 485 25 25
A6G1050 1 50 1.6 17.2 669 25 25
A6G1070 1 70 1.6 19.35 892 32 32
A6G1095 1 95 1.8 22.2 1160 32 32
A6G1120 1 120 1.8 24.3 1436 32 32
A6G1150 1 150 2 25.9 1748 40 40
A6G1185 1 185 2.2 29.7 2142 40 40
A6G1240 1 240 2.4 31.5 2698 50S 50S
A6G1300 1 300 2.6 36.5 3348 50 50S
A6G1400 1 400 2.8 40.4 4293 50 50
A6G1500 1 500 3 42.6 5262 50 50
A6G1630 1 630 3 47.2 6790 63S 63S
A5G02010 2 1 0.8 8.1 94 20S 20S
A5G02015 2 1.5 0.8 9 120 20S 20S
A5G02025 2 2.5 0.9 10.7 173 20S 20S
A5G02040 2 4 1 12.3 239 20 20
A5G02060 2 6 1 13.8 313 25 25
A5G0210 2 10 1.2 18.6 563 32 25
A5G0216 2 16 1.2 21.7 830 32 32
A5G0225 2 25 1.4 25.8 1211 40 40
A5G03010 3 1 0.8 8.74 117 20S 20S
A5G03015 3 1.5 0.8 9.68 147 20S 20S
A5G03025 3 2.5 0.9 11.48 123 20 20
A5G03040 3 4 1 13.2 297 25 25
A5G03060 3 6 1 14.78 390 25 25
A5G0310 3 10 1.2 19.9 705 32 32
A5G0316 3 16 1.2 23.31 1031 32 32
A5G0325 3 25 1.4 27.7 1512 40 40
A5G0335 3 35 1.4 30.2 1907 50S 50S
A5G0350 3 50 1.6 35.8 2651 50 50S
A5G0370 3 70 1.6 40.1 3484 50 50
A5G0395 3 95 1.8 46.4 4594 63S 63S
A5G04010 4 1 0.8 9.63 142 20S 20S
A5G04015 4 1.5 0.8 10.63 180 20S 20S
A5G04025 4 2.5 0.9 12.6 260 20 20
A5G04040 4 4 1 14.6 336 25 25
A5G04060 4 6 1 16.4 449 25 32
A5G0410 4 10 1.2 21.8 833 32 32
A5G0416 4 16 1.2 25.4 1138 40 40
A5G0425 4 25 1.4 30.7 1714 50S 50

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


2 of 5 | technicalspecification International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected]
Click here for more information:
elandcables.com | H07RN-F EN 50525-2-21 Flexible Rubber Cable

ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL THICKNESS NOMINAL OVERALL NOMINAL A2 GLANDS A2PL GLAND
CORES SECTIONAL AREA OF INSULATION DIAMETER WEIGHT Brass Plastic
mm2 mm mm kg/km

A5G0435 4 35 1.4 33.4 2204 50S 50


A5G0450 4 50 1.6 39.6 3029 50 -
A5G0470 4 70 1.6 44.9 4121 63 -
A5G0495 4 95 1.8 51.9 5361 63 -
A5G04120 4 120 1.8 55.3 6546 - -
A5G04150 4 150 2.0 60.8 8095 - -
A5G04185 4 185 2.2 65.7 9652 - -
A5G04240 4 240 2.4 75.7 12614 - -
A5G05015 5 1.5 0.8 11.8 206 20 20L
A5G05025 5 2.5 0.9 14 297 25 25
A5G05040 5 4 1 16.2 422 25 25
A5G05060 5 6 1 18.2 567 32 32
A5G0510 5 10 1.2 24 1010 40 40
A5G0516 5 16 1.2 28.2 1400 40 40
A5G0525 5 25 1.4 33.9 2096 50S 50
A5G0535 5 35 1.4 37.2 2700 50 50
A5G0550 5 50 1.6 44 3730 63S 63S
A5G0570 5 70 1.6 48 5033 63 -
A5G0595 5 95 1.6 53.2 6271 63 -
A5G07015 7 1.5 0.8 15.13 315 25 25
A5G07025 7 2.5 0.9 17.6 445 25 32
A5G1215 12 1.5 0.8 18.2 493 25 32
A5G1225 12 2.5 0.9 21.4 702 32 32
A5G1915 19 1.5 0.8 22.1 710 32 32

CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS MAXIMUM DIAMETER OF WIRES MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC


SECTIONAL AREA IN CONDUCTOR ohms/km
mm2 mm

1 0.21 19.5
1.5 0.26 13.3
2.5 0.26 7.98
4 0.31 4.95
6 0.31 3.3
10 0.41 1.91
16 0.41 1.21
25 0.41 0.78
35 0.41 0.554
50 0.41 0.386
70 0.51 0.272
95 0.51 0.206
120 0.51 0.161
150 0.51 0.129
185 0.51 0.106
240 0.51 0.0801
300 0.51 0.0641
400 0.51 0.0486
500 0.61 0.0384
630 0.61 0.0287
The above table is in accordance with EN 60228

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected] technicalspecification | 3 of 5
Click here for more information:
elandcables.com | H07RN-F EN 50525-2-21 Flexible Rubber Cable

ELECTRICAL CHARACTERISTICS (1mm2 to 2.5mm2)


Current Carrying Capacity and Mass Supportable

NOMINAL CROSS CURRENT CARRYING CAPACITY MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CABLE
SECTIONAL AREA Amps (See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition
mm2 of IEE Wiring Regulations)
Single-Phase AC Three-Phase AC kg

1 10 10 5
1.5 16 16 5
2.5 25 20 5

Voltage Drop

NOMINAL CROSS SECTIONAL AREA DC OR SINGLE-PHASE AC THREE-PHASE AC


mm2 mV/A/m mV/A/m

1 46 40
1.5 32 27
2.5 19 16
Conductor operating temperature: 60ºC

ELECTRICAL CHARACTERISTICS (4mm2 and above)


Current Carrying Capacity

NOMINAL CROSS 60°C CONDUCTOR OPERATING TEMPERATURE 85°C CONDUCTOR OPERATING TEMPERATURE**
SECTIONAL AREA Amps Amps
mm2
Single-Phase AC Three-Phase AC Single-Phase AC Three-Phase AC

1 Two Core Cable, With 2 Single Core 1 Three Core, 1 Two Core Cable, With 2 Single Core 1 Three Core,
or Without Protective Cables Four Core or or Without Protective Cables Touching Four Core or
Conductor Five Core Cable Conductor Five Core Cable

4 30 - 26 41 - 36
6 39 - 34 53 - 47
10 51 - 47 73 - 64
16 73 - 63 99 - 86
25 97 - 83 131 - 114
35 - 140 102 - 192 140
50 - 175 124 - 240 170
70 - 216 158 - 297 216
95 - 258 192 - 354 262
120 - 302 222 - 414 303
150 - 347 255 - 476 348
185 - 394 291 - 540 397
240 - 471 343 - 645 467
300 - 541 394 - 741 537
400 - 644 - - 885 -
500 - 738 - - 1017 -
630 - 861 - - 1190 -
Ambient temperature: 30ºC
Conductor operating temperature: 60ºC / 85ºC

The above table for 60ºC conductor operating temperature is in accordance with Table 4F1A of the 18th Edition of IEE Wiring Regulations BS7671 and IEC 60364-5-52

** 85ºC Table is in accordance with Table 4H2A of the 16th Edition of IEE Wiring Regulations.
The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface. If the cable is to be wound on a drum on load the ratings should
be reduced in accordance with NOTE 2 below and for cables which may be covered, NOTE 3 below.

2. Flexible cables wound on reeling drums

The current ratings of cables used on reeling drums are to be reduced by the following factors:

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


4 of 5 | technicalspecification International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected]
Click here for more information:
elandcables.com | H07RN-F EN 50525-2-21 Flexible Rubber Cable

a) Radial type drum b) Ventilated cylindrical type drum

ventilated: 85% 1 layer of cable: 85%


unventilated: 75% 2 layers of cable: 65%
3 layers of cable: 45%
4 layers of cable: 35%

A radial type drum is one where spiral layers of cable are accommodated between closely spaced flanges; if fitted with solid flanges the ratings given above should be reduced
and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is described as ventilated.

A ventilated cylindrical cable drum is one where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable ventilating
apertures.

3. Where cable may be covered or coiled up whilst on load, or the air movement over the cable restricted, the current rating should be reduced.

It is not possible to specify the amount of reduction but the table of rating factors for reeling drums can be used as a guide.

VOLTAGE DROP
NOMINAL CROSS TWO CORE TWO CORE CABLE, 1 THREE CORE, FOUR CORE OR FIVE 2 SINGLE CORE CABLES, TOUCHING
SECTIONAL AREA CABLES DC SINGLE-PHASE AC CORE CABLE, THREE-PHASE AC mV/A/m
mm2 mV/A/m mV/A/m mV/A/m
DC Single-Phase AC*

4 12 12 10 - -
6 7.8 7.8 6.7 - -
10 4.6 4.6 4 - -
16 2.9 2.9 2.5 - -
r x z r x z r x z
25 1.80 1.80 0.175 1.85 1.55 0.150 1.55 - - - -
35 - - - - 1.10 0.150 1.15 1.31 1.31 0.21 1.32
50 - - - - 0.83 0.145 0.84 0.91 0.91 0.21 0.93
70 - - - - 0.57 0.140 0.58 0.64 0.64 0.20 0.67
95 - - - - 0.42 0.135 0.44 0.49 0.49 0.195 0.53
120 - - - - 0.33 0.135 0.36 0.38 0.38 0.190 0.43
150 - - - - 0.27 0.130 0.30 0.31 0.31 0.190 0.36
185 - - - - 0.22 0.130 0.26 0.25 0.25 0.190 0.32
240 - - - - 0.170 0.130 0.21 0.190 0.195 0.185 0.27
300 - - - - 0.135 0.125 0.185 0.150 0.155 0.180 0.24
400 - - - - - - - 0.115 0.120 0.175 0.21
500 - - - - - - - 0.090 0.099 0.170 0.20
630 - - - - - - - 0.068 0.079 0.170 0.185

Conductor operating temperature: 60ºC

r = Resistive Component
x = Reactive Component
z = Impedance Value

* A larger voltage drop will result if the cables are spaced.

DE-RATING FACTORS

AMBIENT TEMPERATURE 35ºC 40ºC 45ºC 50ºC 55ºC

DE-RATING FACTOR 0.95 0.91 0.86 0.82 0.41

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com