MMR FR Hosp Seismic
MMR FR Hosp Seismic
MMR FR Hosp Seismic
CAR RAILS
[762]
2’−6"
PF3 11593# 11593# 11543# 11593#
HD CL HSTWY & PIT
L1 L2 L1 L2 PF4 PF2
[854]
CL
L3 L4 L3 L4 193248N 193248N 193248N 193248N
0
PF3 PF3
0
CWT
F
[762]
PF4
150848N 146235N 141436N 141627N
Gen2
SPACING
11/16" [17]
R
C R. O. D R. O. RAIL SIZE #1-1/2
RH & RH ENTRANCE ARRANGEMENT REQUIREMENTS FOR RAIL BRACKET SUPPORT (NOT BY OTIS):
DEFLECTION NOT TO EXCEED 1/8"[3mm] BASED ON
HORIZONTAL RAIL FORCES.
LH & LH ENTRANCE IS OPPOSITE PIT FLOOR FORCES, RAIL FORCES, AND OVERHEAD
BUILDING REACTIONS ARE BASED ON MAXIMUM
CAB WEIGHTS. ACTUAL CONTRACT CONDITIONS A United Technologies Company
CAN VARY.
* CAB WITH STANDARD 9/16" [15] WALL PANELS CL. OPNG. = CLEAR OPENING R. O. = ROUGH OPENING REVISION DATE: SHEET 2
CAPACITY HD HW HW2 HW3 HW4 * CWI CDI CL. OPNG. A B R. O. C D F
9'-10 5/8" 7'-5 5/8" 4'-10 5/8"
DWG. NO.: GEN2−TYP−HR−234−PN
4000
[3013] [2276] [1488] BUILDING
4500
10'-4 5/8" 8' 4" 17'-0" 25'-8" 34'-4" 5'-8 5/16" 7'-11 5/8" 4'-0" 3'-5 5/16" 4'-8" 5'-8 3/4" 2'-7 5/16" 2'-11 5/16" 5'-1 9/16" LOCATION
[3165] [2540] [5182] [7823] [10465] [1735] [2428] [1219] [1049] [1422] [1746] [795] [897] [1563] CONT. WITH
11'-5 9/16" 9'-0 9/16" 5'-7 1/4"
5000AIA OWNER
[3494] [2758] [1708]
10'-11 5/8" 8' 7" 17'-6" 26'-5" 35'-4" 5'-11 5/16" 8'-6 5/8" 4'-6" 3'-2 5/16" 4'-5" 6'-2 3/4" 2'-4 5/16" 2'-8 5/16" 5'-4 7/8" ARCHT.
5000 CONTRACT NO.
[3343] [2616] [5334] [8052] [10770] [1811] [2606] [1371] [972] [1347] [1898] [719] [821] [1648]
REVISIONS
STRUCTURAL SLAB MACHINE BEAM
ARRANGEMENT ARRANGEMENT
(NOTES 16−20, SHEET 1) (NOTES 16−20, SHEET 1)
BY OTIS
BY OTIS
FLOOR TO REAR FRONT
FLOOR FLOOR FLOOR
HEIGHT MARKING MARKING
BL TOP LNDG. TO UPPER MOST RAIL SUPPORT
AA CLEAR OVERHEAD
SHEET 4
AA CLEAR OVERHEAD
THIS SHEET COVERS THE FOLLOWING CONDITIONS
PASSENGER CAR HOSPITAL CAR
CAB HEIGHT
CAB HEIGHT
ED − EXTENDED DUTY LIMITED DUTY
MRL − MACHINE MMR − MACHINE
ROOMLESS ROOM
REAR OPENING GLASS BACK
SEISMIC ZONE 0 OR 1 SEISMIC ZONE 2, 3 OR 4
TOP TOP
FLOOR FLOOR CWT WITH SAFETY CWT WITHOUT
SAFETY
"DETAIL A"
BOTTOM FLOOR
SILL ASSEMBLY (BY OTIS)
Gen2 R
10,6KN 10,6KN
SEE SHEET 2
3’−4 15/16"
3’−4 15/16"
A
L1 L2 L1 L2 L1 L2 L1 L2
[1040]
[1040]
SEE SHEET 2
L3 L4 L3 L4 L3 L4 L3 L4
B D
B B
D
D
D
CL CAR CL CAR
B
CL CAR CL CAR
M
M
FRONT FRONT FRONT FRONT
THIS SHEET COVERS THE FOLLOWING CONDITIONS:
(MIN.)
(MIN.)
CONTROLLER CONTROLLER CONTROLLER CONTROLLER PASSENGER CAR HOSPITAL CAR
S
S
.8K/3,6KN .8K/3,6KN .8K/3,6KN .8K/3,6KN
ED − EXTENDED DUTY LIMITED DUTY
MRL − MACHINE MMR − MACHINE
HW, HW2, HW3, OR HW4 SEE SHEET 2 HW, HW2, HW3, OR HW4 SEE SHEET 2 ROOMLESS ROOM
DETAIL 2: CWT ON LEFT; L1 (RIGHT HAND OPENING) DETAIL 2: CWT ON RIGHT; L2 (LEFT HAND OPENING) REAR OPENING GLASS BACK
STRUCTURAL SLAB ARRANGEMENT STRUCTURAL SLAB ARRANGEMENT SEISMIC ZONE 0 OR 1 SEISMIC ZONE 2, 3 OR 4
(COUNTERWEIGHT SAFETY NOT AVAILABLE (COUNTERWEIGHT SAFETY NOT AVAILABLE CWT WITH SAFETY CWT WITHOUT
WITH "SLAB" ARRANGEMENT) WITH "SLAB" ARRANGEMENT) SAFETY
NOTES 16−20, SHEET 1 NOTES 16−20, SHEET 1
SLAB ARR. WITH CWT @ LEFT SLAB ARR. WITH CWT @ RIGHT
(RIGHT HAND OPENING ZONE, 2, 3, 4) (LEFT HAND OPENING ZONE, 2, 3, 4)
CAPACITY CAPACITY
REF REF
4000 4500 5000AIA 5000 4000 4500 5000AIA 5000
3'-2 1/8" 3'-5 1/16" 3'-10 13/16" 3'-8 7/16" 3'-2 1/8" 3'-5 1/16" 3'-10 13/16" 3'-8 7/16"
M M APPROVAL
[968] [1043] [1189] [1129] [968] [1043] [1189] [1129]
9 5/16" 9 5/16" 9 5/16" 9 5/16" OVERHEAD BUILDING REACTIONS THIS ARRANGEMENT AND
3'-10 3/4" 3'-10 3/4" 3'-10 3/4" 4'-0 1/4" SUPPLEMENTARY NOTES APPROVED
*P CAPACITY P
[237] [237] [237] [237] REF [1187] [1187] [1187] [1226]
4'-5 1/4" 4'-5 1/4" 4'-5 1/4" 4'-6 3/4" 4000 4500 5000AIA 5000 7'-6 11/16" 7'-6 11/16" 7'-6 11/16" 7'-9 11/16" SIGNED: DATE:
**Q *Q
[1353] [1353] [1353] [1391] 6.3K 6.3K 6.3K 6.3K [2303] [2303] [2303] [2380] THIS WORK AND THE INFORMATION IT CONTAINS ARE THE PROPERTY OF OTIS
A
2'-4 3/4" 2'-1 13/16" 1'-8 1/8" 1'-10 7/16" 28,0KN 28,0KN 28,0KN 28,0KN 2'-4 3/4" 2'-1 13/16" 1'-8 1/8" 1'-10 7/16" ELEVATOR COMPANY ("OTIS"). IT IS DELIVERED TO OTHERS ON THE EXPRESS
S S CONDITION THAT IT WILL BE USED ONLY FOR OR ON BEHALF OF OTIS; THAT
[730] [656] [511] [571] 6.3K 6.3K 6.3K 6.3K [730] [656] [511] [571] NEITHER IT NOR THE INFORMATION IT CONTAINS WILL BE REPRODUCED OR
B DISCLOSED. IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF OTIS;
* FOR CWT W/SAFETY DECREASE VALUE BY 5/16"/8mm 28,0KN 28,0KN 28,0KN 28,0KN * FOR CWT W/SAFETY INCREASE VALUE BY 3 5/16"/84mm
STATIC AND THAT ON DEMAND IT AND ANY COPIES WILL BE PROMPTLY RETURNED TO
** FOR CWT W/SAFETY INCREASE VALUE BY 3"/76mm 5.0K 4.8K 4.7K 4.7K OTIS.
C
22,2KN 21,4KN 20,9KN 20,9KN UNPUBLISHED WORK C OTIS ELEVATOR COMPANY 2004
ALL RIGHTS RESERVED.
5.0K 4.8K 4.7 4.7K
Gen2
D
22,2KN 21,4KN 20,9KN 20,9KN R
DETAIL A
HD CLEAR HSTWY & PIT
MACHINE ROOM DEPTH (MIN.)
A C
SEE SHEET 2
2’−7 5/8"
L1 L2 L1 L2
[804]
D
BEAM
1'-9 7/16" 1'-5 13/16" 1'-2 1/2" 1'-2 1/2"
S
FRONT FRONT [545] [452] [368] [368]
THIS SHEET COVERS THE FOLLOWING CONDITIONS:
(MIN.)
.8K/3,6KN .8K/3,6KN
ED − EXTENDED DUTY LIMITED DUTY
MRL − MACHINE MMR − MACHINE
ROOMLESS ROOM
MACHINE BEAMS REAR OPENING GLASS BACK
HW, HW2, HW3, OR HW4 SEE SHEET 2
CL CWT SEISMIC ZONE 0 OR 1 SEISMIC ZONE 2, 3 OR 4
DETAIL 1: MACHINE BEAM ARRANGEMENT
(NOTES 16−20, SHEET 1) CWT WITH SAFETY CWT WITHOUT
SUITABLE CONTROL ROOM WITH LEGAL ACCESS SAFETY
AND MINIMUM CLEAR HEIGHT OF 7’−6" (2286mm)
TO BE PROVIDED (SEE SHEET 1).
BUILDING STEEL
SUPPORT BY OTHERS
BEAM BELOW
NOTE:
3" [76] MIN.
Gen2
POCKET (TYP)
CL REACTION LOAD R
18" [457]
The platform is to be located at the top landing of the hoistway(s) and shall be securely fastened to the building a) For each group of elevators, provide a normally closed contact representing the smoke detector at the 36 In areas under the jurisdiction of AMSE A17.1−2004 where the elevator travel is greater than or equal to 60’, provide
structure. The platform shall be designed for not less than 50−psf uniform live load and a concentrated point designated return landing. two−way voice communications means that shall enable emergency personnel within the building to establish communications to
load of 500 lb. each car individually without intervention by a person within the car. The communication means shall override communications to
b) For each group of elevators, provide a normally closed contact representing all smoke detectors located in the outside of the building and once established shall only be terminated by emergency personnel outside the car.
The platform shall be installed complete with guardrails at the perimeter of any opening in the platform. lobbies, hoistways, or machine room, but not the smoke detector at the designated return landing (see above) or Refer to ASME A17.1−2004, section 2.27.1.1.4 for exact requirements.
the smoke detectors as described in i. & ii. Below.
The working surface of the platform shall have within easy reach, secure anchorage points for attachment of fall You agree to indemnify and save Otis harmless against any and all liability and costs arising out of your failure to
arrest lifelines, lanyards, or deceleration devices. i. If a smoke detector is located in the hoistway at or below the lower of the two recall landings, it shall be
wired to activate the same normally closed contact as the smoke detector located in the lobby at the lower of carry out any of the foregoing requirements.
Gen2
the two recall landings. R MACHINE ROOM (MMR)
The design and installation of the temporary platform shall be in accordance with the applicable provisions of all
federal, state and local codes and regulations including but not limited to the latest amendments of American ii. If the machine room are located at the designated return landing, the smoke detectors located therein shall PREPARATORY WORK
National Standards Institute, Inc. (ANSI), the Occupational Safety and Health Act (OSHA), and the State Building be wired to activate the same normally closed contact as the smoke detector at the designated landing. BY OTHERS
Code in effect in the state in which the elevator is being installed.
c) Requirements for intermittently illuminating the fire hat visual signal in the car operating panel, either i) or ii)
Otis has a temporary work platform design that meets these requirements. Request a copy of Otis drawing apply.
AAA27CR for details. i. For a single unit or for a group of elevators having one common machine room and one common hoistway,
provide one additional normally closed contact representing the control room/space and hoistway smoke detectors. A United Technologies Company
10. Provide guarding and protection of the hoistway during construction. Provide a freestanding removable
barricade at each hoistway opening at each floor. Barricades shall be 42" [1067mm] high, have centerboard and ii. If the group contains more than one hoistway and hoistway smoke detectors are installed, or if the group
kick board, and withstand 200 lbs. [91kg] of side pressure. Hoistway barricades shall be constructed, maintained, has more than one machine room provide one normally closed contact for each elevator. The contact is to REVISION DATE: SHEET 1 OF 4
and removed by others. represent the smoke detector in the machine room for that particular elevator, and any smoke detectors in the
hoistway containing that particular elevator. DWG. NO.: GEN2−TYP−MMR−PWBO
11. Provide a pit floor designed to sustain vertical forces (forces based on safety impact) on car and 24. If sprinklers are installed in the hoistway(s), control room(s)/space(s), or machine mounting structure THIS WORK AND THE INFORMATION IT CONTAINS ARE THE BUILDING
counterweight rails as shown in the rail force and bracket spacing detail table and impact loads on car and space(s), a means to automatically disconnect the main line power supply of the affected elevator prior to the PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS
counterweight buffers as shown in the pit plan view. The pit must be dry and clean. The elevator pit must have a
application of water is required (unless prohibited by local code). This automatically controlled mainline disconnect
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR OR ON BEHALF OF OTIS;
LOCATION ,
floor drain or sump pump to prevent the accumulation of water, but not be connected directly to a storm drain THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
must be provided with all associated wiring and conduit to the controller. CONT. WITH
or sewer. Location to be coordinated with Otis to avoid all elevator components and access areas.The floor drain WILL BE REPRODUCED OR DISCLOSED. IN WHOLE OR IN
or sump pump should lead to a holding tank rather than a sewer or uncontained area. Otis recommends that PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS:
25. Provide machine room and door to code compliant fire resistive construction. AND THAT ON DEMAND IT AND ANY COPIES WILL BE OWNER
the owner verify the drain or sump pump system is in compliance with all applicable laws. PROMPTLY RETURNED TO OTIS.
26. Provide a fire extinguisher in all machine room(s). ARCHT.
UNPUBLISHED WORKC OTIS ELEVATOR COMPANY 2004
ALL RIGHTS RESERVED. CONTRACT NO.