Absorbed power 10 W
k
F2
J1 J2 J3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
OP COM CL CL COM OP + — OP — CL NC — B — A — + — + —
N L LAMP MOTOR 1 MOTOR 2 30 Vcc FSW STOP FSWTX W.LIGHT LOCK
BLU
BLU
24 Vdc
3W
M1 M2
230 V 50 Hz
N.B.: The capacitors are provided with the operators. For the safety and fail-safe devices, see the “Safety devices” section.
Fig. 2
Caution: Before touching the electronic unit (connections, Warning: the max. accessory load is 500 mA. To calculate
programming, maintenance) always switch off the power absorption values, refer to table 2.
supply.
Safety devices
a J1 terminal block (fig. 2) These are all devices (photocells, safety edges, magnetic
: Earth connection coils, etc.) with an N.C. (normally closed) contact which
N. : power supply 230 V~ ( Neutre ) activate if an obstacle obstructs the area protected by the
L. : power supply 230 V~ ( Phase)
N.B.: For correct operation the card must be connected to the Opening, closing or opening/closing photocells
system’s earth. Install a suitable differential magneto-thermal
circuit-breaker upstream of the system.
b J2 terminal block (fig. 2)
LAMP.: flashing light output ( 230 V ~)
MOTOR 1 Open /Common/ Close: Motor 1 connection
Can be used in one-leaf application.
(leaf closing delay)
A A
MOTOR 2 Close /Common/ Open: Motor 2 connection
Not to be used in one-leaf application. A
N.B. To check the operation of the equipment at the test B
B
bench, a load must be connected on the MOTOR 1 input.
c J3 terminal block: low voltage (fig. 2) used to connect all
accessories (see table 2).
30 Vdc Opening
Closing photocells
– accessories power supply negative photocells
+ accessories power supply positive (+ 30 Vdc)
Fig. 3
10
ENGLISH
safety devices and stop the movement of the gate leaves The purpose of the opening safety devices is to safeguard
(fig. 3). the zone behind the gate leaves (A, fig. 3).
The 450 MPS card has an additional FAIL-SAFE device which CL. - Closing safety device contact (N.C.): in the A-S-E-EP-AD
serves to check that the N.C. contact on the photocell logics, during the closing phase the safety devices reverse
receiver is working efficiently before any operation (Can the direction of movement of the gate leaves, or they stop
be disabled through bridge Fig. 1 ref.15) . the movement of the leaves then reverse direction when
N.B.: If the Opening safety devices are engaged when the they are disengaged (see microswitch SW4 settings). They
gate is closed, they prevent the leaves from opening. do not engage during the opening cycle.
If the Closing safety devices are engaged when the gate In B, C and B/C logics, they interrupt movement during the
is open, they prevent the leaves from closing. closing cycle. They do not engage during the opening
OP. - Opening safety device contact (N.C.): in the A-S-E-EP-AD cycle.
logics, during the opening phase the safety devices stop N.B.: If closing safety devices are not connected, jumper
the movement of the gate leaves; when they are inputs OP and FSWTX (fig. 4).
disengaged the opening movement recommences. They The purpose of the closing safety devices is to safeguard
do not engage during closure. the zone in which the leaves move during the closing cycle
In the B, C and B/C logics, they interrupt movement during (B, fig. 3).
the opening cycle. They do not engage during the closing If the Fail-Safe function is not used, see cabling at page 4
cycle. for connections of photocells.
N.B.: If opening safety devices are not connected, jumper
inputs OP and FSW TX (Fig. 4).
Application examples
The following are the commonly used connection arrangements (enable fail -safe):
No safety device connected One pneumatic edge connected as closing safety device and
one connected as opening safety device
14 15 16 23 24 14 15 16 23 24
OP — CL + — OP — CL + —
FSW FSWTX FSW FSWTX
Fig. 4 Fig. 5
1 1
2 2
1 1
3 3
2 2
4 4
5 5
RX TX RX TX
Fig. 6 Fig. 7
1 pair of opening photocells and 1 pair of closing 1 pair of closing photocells and 1 pair of opening/closing
photocells connected photocells connected
12 13 14 15 16 23 24 12 13 14 15 16 23 24
+ — OP — CL + — + — OP — CL + —
30Vcc FSW FSWTX 30Vcc FSW FSWTX
1 1
2 2
1 1
3 3
2 2
4 4
5 5
RX CL TX CL RX CL TX CL
1
1
2
2
1
1 3
3
2
2 4
4
5
5
TX OP RX OP
TX OP RX OP
Fig. 8 Fig. 9
Important: for further information on the operation of the safety devices, see table 3.
11
ENGLISH
Application examples
The following are the commonly used connection arrangements (disable fail -safe)
No safety device connected One pneumatic edge connected as closing safety device and
one connected as opening safety device
14 15 16 23 24 14 15 16 23 24
OP — CL + — OP — CL + —
FSW FSWTX FSW FSWTX
12 13 14 15 16 23 24
12 13 14 15 16 23 24 + —
+ — OP — CL
+ — OP — CL + — 30Vcc FSW FSWTX
30Vcc FSW FSWTX
1 1
2 2
1 1
3 3
2 2
4 4
5 5
RX TX
RX TX
Two pair of closure photocells connected 1 pair of closing photocells and 1 pair of opening/closing
photocells connected
12 13 14 15 16 23 24 12 13 14 15 16 23 24
+ — OP — CL + — + — OP — CL + —
30Vcc FSW FSWTX 30Vcc FSW FSWTX
1 1
2 2
1 1
3 3
2 2
4 4
5 5
RX TX RX TX
5 5
4 4
1 1
3 3
2 2
2 2
1 1
TX RX TX RX
Fig. 8/A Fig. 9/A
12
ENGLISH
safety system).
f PAUSE trimmer: pause time adjusting trimmer (A/S/AD Fig. 10 Fig. 11
logics).
Pause time is adjustable from 0 to 240 seconds.
g OP/CL trimmer: Opening/Closing time adjusting trimmer
Time is adjustable from 0 to 120 seconds.
h LEAF DELAY trimmer: closing leaf delay adjusting trimmer.
Leaf delay time is adjustable from 0 to 28 seconds.
N.B.:
1) If the opening/closing time is less than the set delay
time, the delayed leaf closes at the end of the closing
time.
2) In one-leaf application, set the leaf delay time to
minimum
i Programming microswitches
j Fuse F1 5x20 5 A/250 V rapid (motor power supply)
k Fuse F2 5x20 800 mA/250 V delayed (accessories power
supply)
l Fuse F3 5x20 1.6 A/250 V delayed (electric power supply)
m Fuse F4 5x20 250 mA/250 V delayed (transformer power
supply)
n Bridge to enable/disable the Fail-Safe (Fig. 14). N.B. Use a dedicated decoder for other accessory types.
Fig. 13
13
ENGLISH
2. START-UP
1) Program the 450 MPS electronic control unit according to
specific requirements as shown in fig. 14.
2) Check led status as shown in table.
LED functions
LEDS ON OFF
DL 1 (OPEN INPUT A) Command active Command not active
DL 2 (OPEN INPUT B) Command active Command not active
DL 3 (STOP) Command not active Command active
DL 4 (FTSW OPEN) Safeties disengaged Safeties engaged
DL 5 (FTSW CLOSE) Safeties disengaged Safeties engaged
N.B.: the bold text indicates led status with gate idle.
2.1. DIRECTION OF ROTATION
1) Switch off the power.
2) Manually move the gate to halfway.
3) Lock the operators.
14
Table 3/a
LOGICS "A" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
CLOSED Opens leaves and Opens single leaf and re-closes
No effect (OPEN inhibited) No effect No effect (OPEN inhibited) off
recloses after pause time after pause time
OPEN on PAUSE Recloses leaves immediately Recloses leaf immediately No effect Freezes pause until disengagement (*1) (OPEN inhibited) on
CLOSING Reopens leaves immediately Reopens leaf immediately No effect (OPEN inhibited) See paragraph 1.3 Stops closing and, when disengaged, opens flashing light
Stops
OPENING No effect Stops opening and, when disengaged, closes Stops opening and, when disengaged,
No effect on
continues to open
STOPPED Closes the leaf/leaves No effect (OPEN inhibited) No effect No effect (OPEN inhibited) on
Table 3/b
LOGICS "S" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
Opens leaves and Opens single leaf and No effect (OPEN inhibited) No effect No effect (OPEN inhibited) off
CLOSED recloses after pause time recloses after pause time
OPEN on PAUSE Recloses leaves immediately Recloses leaf immediately No effect Freezes pause until disengagement (*1) (OPEN inhibited) on
CLOSING Reopens leaves immediately Reopens leaf immediately No effect (OPEN inhibited) See paragraph 1.3 Stops closing and, when disengaged, opens flashing light
Stops
Stops opening and, when disengaged,
OPENING Recloses leaves immediately Recloses leaf immediately Stops opening and, when disengaged, closes No effect on
continues to open
STOPPED Closes the leaf/leaves No effect (OPEN inhibited) No effect No effect (OPEN inhibited) on
15
Table 3/c
LOGICS "E" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
CLOSED Opens leaves Opens single leaf No effect (OPEN inhibited) No effect No effect (OPEN inhibited) off
OPEN Recloses leaves immediately Recloses leaf immediately No effect No effect (OPEN inhibited) on
CLOSING Reopens leaves immediately Reopens leaf immediately Stops No effect (OPEN inhibited) See paragraph 1.3 Stops closing and, when disengaged, opens flashing light
STOPPED Closes the leaf/leaves No effect (OPEN inhibited) No effect No effect (OPEN inhibited) on
Table 3/d
LOGICS "EP" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
CLOSED Opens leaves Opens single leaf No effect (OPEN inhibited) No effect No effect (OPEN inhibited) off
STOPPED Inverts the direction No effect (OPEN inhibited) No effect (if the gate must open, inhibits OPEN) No effect (if gate must close, inhibits OPEN) No effect (OPEN inhibited) on
Table 3/e
LOGICS "B" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
No effect No effect No effect No effect off
CLOSED Opens the leaf/leaves Closes the leaf/leaves (OPEN A/B inhibited) (OPEN-A inhibited) (OPEN A/B inhibited)
(OPEN-B inhibited)
ENGLISH
16
STOPPED Opens leaves or 1 leaf Closes leaves or 1 leaf on
(OPEN A/B inhibited) (OPEN-A inhibited) (OPEN-B inhibited) (OPEN A/B inhibited)
Table 3/g
LOGICS "C" HOLD-TO-RUN CONTROLS
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
No effect No effect Interrupts operation No effect off
CLOSED Opens the leaf/leaves Closes the leaf/leaves (OPEN A/B inhibited) (OPEN-A inhibited) (OPEN-B inhibited) (OPEN A/B inhibited)
Table 3/h
LOGICS "AD" PULSES
GATE STATUS OPEN-A OPEN-B STOP OPENING SAFETIES CLOSING SAFETIES OPENING/CLOSING SAFETIES W.L.
CLOSED Opens leaves and Opens single leaf and re-closes
No effect (OPEN inhibited) No effect No effect (OPEN inhibited) off
recloses after pause time after pause time
OPEN on PAUSE It controls the re-counting of the It controls the re-counting of the No effect Freezes pause until disengagement (*1) (OPEN inhibited) on
pause time pause time
No effect (OPEN inhibited) See paragraph 1.3 Stops closing and, when disengaged, opens flashing light
CLOSING Reopens leaves immediately Reopens leaf immediately Stops
Stops opening and, when disengaged, closes Stops opening and, when disengaged,
OPENING No effect on
If held, it remains in pause (timer function). continues to open
STOPPED Closes the leaf/leaves No effect (OPEN inhibited) No effect No effect (OPEN inhibited) on
(*1) If residual pause time is less than 5 seconds on safety disengagement, the gate closes after 5 seconds.
N.B.: Effects of other active impulse inputs are shown in brackets
Le descrizioni e le illustrazioni del presente manuale non sono impegnative. La FAAC si riserva il diritto,
lasciando inalterate le caratteristiche essenziali dell’apparecchiatura, di apportare in qualunque
para la naturaleza
100% papel reciclado
momento e senza impegnarsi ad aggiornare la presente pubblicazione, le modifiche che essa ritiene
convenienti per miglioramenti tecnici o per qualsiasi altra esigenza di carattere costruttivo o
commerciale.
The descriptions and illustrations contained in the present manual are not binding. FAAC reserves the
right, whilst leaving the main features of the equipments unaltered, to undertake any modifications
it holds necessary for either technical or commercial reasons, at any time and without revising the
present publication.
Les descriptions et les illustrations du présent manuel sont fournies à titre indicatif. FAAC se réserve le
droit d’apporter à tout moment les modifications qu’elle jugera utiles sur ce produit tout en conservant
les caractéristiques essentielles, sans devoir pour autant mettre à jour cette publication.
Die Beschreibungen und Abbildungen in vorliegendem Handbuch sind unverbindlich. FAAC behält
ist umweltfreundlich
sich das Recht vor, ohne die wesentlichen Eigenschaften dieses Gerätes zu verändern und ohne
Verbindlichkeiten in Bezug auf die Neufassung der vorliegenden Anleitungen, technisch bzw.
konstruktiv/kommerziell bedingte Verbesserungen vorzunehmen.
100% Altpapier
Las descripciones y las ilustraciones de este manual no comportan compromiso alguno. FAAC se
reserva el derecho, dejando inmutadas las características esenciales de los aparatos, de aportar, en
cualquier momento y sin comprometerse a poner al día la presente publicación, todas las
modificaciones que considere oportunas para el perfeccionamiento técnico o para cualquier otro
tipo de exigencia de carácter constructivo o comercial.
pour la nature
• The present manual is produced in 100% recycled paper
• Respect the environment. Dispose of each type of product packaging material (card, polystyrene)
in accordance with the provisions for waste disposal as specified in the country of installation.
FAAC der Umwelt zuliebe
• Vorliegende Anleitungen sind auf 100% Altpapier gedruckt.
• Verpackungsstoffe der Antriebskomponenten (z.B. Pappe, Styropor) nach den einschlägigen
Normen der Abfallwirtschaft sortenrein sammeln.
FAAC écologique
• La présente notice a été réalisée 100% avec du papier recyclé.
• Ne pas jeter dans la nature les emballages des composants de l’automatisme, mais sélectionner
les différents matériaux (ex.: carton, polystyrène) selon la législation locale pour l’élimination des
déchets et les normes en vigueur.
FAAC por la naturaleza.
• El presente manual de instrucciones se ha realizado, al 100%, en papel reciclado.
• Los materiales utilizados para el embalaje de las distintas partes del sistema automático (cartón,
poliestireno) no deben tirarse al medio ambiente, sino seleccionarse conforme a las prescripciones
locales y las normas vigentes para el desecho de residuos sólidos.
FAAC S.p.A.
Via Benini, 1
40069 Zola Predosa (BO) - ITALIA
Tel.: 051/6172411 - Tlx.: 521087
Fax: 051/758518
per la natura