0% found this document useful (0 votes)
85 views

Main Cooling Water Circulation Pump / Lines Pipe Line Pump Discharge Pump Suction

The document provides calculations for pipe sizing and head loss for various pump lines. It calculates parameters such as flow rate, velocity, pipe diameter, head loss from friction, bends, valves etc. for pump discharge and suction lines. The total head loss is calculated for each line and the required pump head is estimated by adding factors for safety. Pipes of appropriate sizes are selected based on the calculations.

Uploaded by

Ramdas Talole
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views

Main Cooling Water Circulation Pump / Lines Pipe Line Pump Discharge Pump Suction

The document provides calculations for pipe sizing and head loss for various pump lines. It calculates parameters such as flow rate, velocity, pipe diameter, head loss from friction, bends, valves etc. for pump discharge and suction lines. The total head loss is calculated for each line and the required pump head is estimated by adding factors for safety. Pipes of appropriate sizes are selected based on the calculations.

Uploaded by

Ramdas Talole
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

Main cooling water circulation pump / lines

pipe line pump discharge pump suction


4229 m^3/hr Flow 2400 m^3/hr Flow 2400
1.174722 per sec flow 0.666667 per sec flow 0.666667 per sec flow
2.1 m/s velocity 2 m/s velocity 1 velocity
0.559392 m^2 cross sec area required 0.333333 cross sec area required 0.666667 cross sec area required
0.712601 0.424628 0.849257
0.844157 m dia in mtr 0.651635 dia in mtr 0.921551 dia in mtr
1000 mm i/d of pipe selected 650 mm i/d of pipe selected 1000mm i/d of pipe selected
120 m Pipe length 10 m Pipe length 10 m Pipe length
0.4 m head loss in line 0.4 m head loss in pipe line 0.2 m head loss in pipe line
0.4 m head loss in reducers 2 nos 0.4 m head loss in reducers 1 nos
0.8 m head loss in vlaves 2 nos 0.8 m head loss in vlave
0.4 m head loss in NRV 0.8 m head loss in NRV
0.6 m head loss in bends 6 nos 0.6 m head loss in bends 6 nos
0.1 m head loss in entry 0.1 m head loss in strainer

0.4 m 2.7 m 2.9 m

head loss in pipe line 0.4 m


head loss in discharge line 2.7 m
head loss in suction line 2.9 m
for old pipes multiply by 1.5 9 m
head Static 9 m
NPSH 0.5 m 2070 2114.5
Pressure drop across condencer 15 m
33.5 m
Hence 35 mtr head
Head Calculations for DM makeup water pump / lines
pump discharge pump suction
30 m^3/hr Flow 30
0.008333 per sec flow 0.008333 per sec flow
2 m/s velocity 1 velocity
0.004167 cross sec area required 0.008333 cross sec area required
0.005308 0.010616
0.072855 dia in mtr 0.103033 dia in mtr
100NB x 20 sch pipe selected 100 NB x sch 20 Pipe selected
108 mm i/d of pipe selected 108 i/d of pipe selected
400 m Pipe length 10 m Pipe length

6.6 m head loss in pipe line 0.2 m head loss in pipe line
0.1 m head loss in reducers 2 nos 0.1 m head loss in reducers 1 nos
0.4 m head loss in vlaves 2 nos 0.2 m head loss in vlave
0.1 m head loss in NRV 0.1 m head loss in NRV
0.1 m head loss in bends 6 nos 0.1 m head loss in bends1 nos
0.2 m head loss in strainer

7.3 m total discharge line head 0.9 m total suction line head

head loss in discharge line 7.3 m


head loss in suction line 0.9 m
for old pipe multiply by 1.1 9.02 m
pressure head 35 m
44.02 m
Hence 45 mtr head
Head Calculations for cooling makeup water pump / lines
pump discharge pump suction
150 m^3/hr Flow 150
0.041667 per sec flow 0.041667 per sec flow
2 m/s velocity 1 velocity
0.020833 cross sec area required 0.041667 cross sec area required
0.026539 0.053079
0.162909 dia in mtr 0.230388 dia in mtr
200 NB x 20 sch pipe selected 250 NB x sch 20 pipe selected
205 mm i/d of pipe selected 257.45 i/d of pipe selected
400 m Pipe length 10 m Pipe length

5.3 m head loss in pipe line 0.3 m head loss in pipe line
0.9 m head loss in reducers 1 nos 1 m head loss in reducers 1 nos
0.8 m head loss in vlaves 2 nos 0.1 m head loss in vlave
0.9 m head loss in NRV 0.4 m head loss in NRV
0.5 m head loss in bends 6 nos 0.1 m head loss in bends1 nos
0.1 m head loss in strainer

8.4 m total discharge line head 2 m total suction line head

head loss in discharge line 8.4 m


head loss in suction line 2 m
for old pipe multiply by 1.5 15.6 m
15.6 m
Hence 20 mtr head
Aux. cooling water circulation pump / lines
pipe line pump discharge pump suction
600 m^3/hr Flow 600 m^3/hr Flow 600
0.166667 per sec flow 0.166667 per sec flow 0.166667 per sec flow
2.1 m/s velocity 2.1 m/s velocity 1 m/s velocity
0.079365 m^2 cross sec area required 0.079365 m^2 cross sec area required 0.166667 m^2 cross sec area required
0.101102 0.101102 0.212314
0.317965 m dia in mtr 0.317965 m dia in mtr 0.460776 m dia in mtr
350 mm i/d of pipe selected 350 mm i/d of pipe selected 500 mm i/d of pipe selected
120 m Pipe length 10 m Pipe length 10 m Pipe length
1.9 m head loss in line 0.4 m head loss in pipe line 0.2 m head loss in pipe line
0.4 m head loss in reducers 2 nos 0.4 m head loss in reducers 2 nos
0.8 m head loss in vlaves 2 nos 0.8 m head loss in vlave
0.4 m head loss in NRV 0.8 m head loss in NRV
0.6 m head loss in bends 6 nos 0.6 m head loss in bends 6 nos
0.1 m head loss in entry 0.1 m head loss in strainer

1.9 m 2.7 m 2.9 m

head loss in pipe line 1.9 m


head loss in discharge line 2.7 m
head loss in suction line 2.9 m
head Static 2 m
for old pipe multiply by 1.5 plus 11 m 22.25 m
NPSH 0.5 m
24.75 m
Hence 25 mtr head
c area required

s in reducers 2 nos

s in bends 6 nos
Dia of steam condensor pipe

Water req. Q 4229 m3/hr


Let water velocity V 2 m/sec
Calculated pipe dia D 0.8650033033412 m
Liquid velocity in selected pipe Vcal 1.3580551862457 m/sec
Reynold no. Re 1174722.2222222
E/D 0.0004624259797
Friction factor from Moody chart f 0.017

Pressure drop(∆P) f*L*p/(D*10000)(Vcal/ 3.0224138122091 kg/cm2

61.1042

167243
865.003303341221

Length of straight pipe Considered 170 m

0.005
0.001
0.002
0.017