SL, SLX e SLXe Manual de Manutenção TK 50045 Rev 14 02-2016
SL, SLX e SLXe Manual de Manutenção TK 50045 Rev 14 02-2016
SL, SLX e SLXe Manual de Manutenção TK 50045 Rev 14 02-2016
Trailer Units
SL-100
SL-200
SL-300
SL-400
SL-TCI
SL-100e
SL-200e
SL-400e
SPECTRUM SL
SLX-100
SLX-200
SLX-300
SLX-400
SLX SPECTRUM
SLX Whisper
SLX Ferry
SLXe-100
SLXe-200
SLXe-300
SLXe-400
SLXe SPECTRUM
SLXe Whisper
SLXe-300 Whisper Pro
SLXe SPECTRUM Whisper Pro
SLXe Ferry
©1997 to 2015 by Thermo King Ingersoll Rand, Galway, Ireland. All rights reserved.
Printed in Ireland.
The contents of this manual are the property of Thermo King Europe and are copyrighted. No part of this document
may be reproduced or transmitted in any form or by an means, electronic or mechanical, for any purpose, without the
express written permission of Thermo King.
This maintenance manual is published for informational purposes only and the information should not be considered
as all-inclusive or covering all contingencies. If further information is required, Thermo King should be consulted.
Information in this document is subject to change without notice.
Sale of product shown in this Maintenance Manual is subject to Thermo Kingís terms and conditions including, but
not limited to, the THERMO KING EXPRESS WARRANTY. Such terms and conditions are available on request.
The Thermo King warranty will not apply to any equipment which has been “so repaired or altered outside the
manufacturer’s plants as, in the manufacturer’s judgment, to effect its stability”.
No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or
warranties arising from course or dealing or usage of trade, are made regarding the information, recommendations
and descriptions contained herein. Manufacturer is not responsible and will not be held liable in contract or in tort
(including negligence) for any special, indirect or consequential damages, including injury or damage caused to
vehicles, contents or persons, by reason of the installation of any Thermo King product or its mechanical failure.
Table Of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Units Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Other Reference Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Auto Start/Stop Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
SL-400e, SLXe and slx with Smart Reefer 2/3 (SR-2/SR-3) Controller . . . . . . . . . . . . . . . . . . . 2-2
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Microprocessor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Welding of Units or Truck Bodies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Unit Decals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
R-404A/ R452A* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Electrical Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Heat/Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Electrical Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Evaporator Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Electric Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Electric Drive Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Standby Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Remote Evaporator Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
........................................................................... 3-11
Maintenance Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
SL and SLe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Remote Evaporators: ECT, ELT, EW, SPECTRUM and TLE . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
UNIT MODELS: All SLX, SLXe Range and Spectrum Models Host Unit . . . . . . . . . . . . . . . . 4-5
UNIT MODELS: All SLX, SLXe and Spectrum Models Host Unit . . . . . . . . . . . . . . . . . . . . . . 4-6
UNIT MODELS: All SLX, SLXe and Spectrum Models Host Unit . . . . . . . . . . . . . . . . . . . . . . 4-7
UNIT MODELS: SLX/SLXe SPECTRUM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
UNIT MODELS: All SLX, SLXe and Spectrum MOdels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Unit Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Single Temperature Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Multi-temperature Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Service Test Mode (Standard on TG-VI, µP-IV, µP-V, µP-VI, SR-2 and SR-3 Controllers) . 5-5
Electric Standby Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Refrigeration Modulation Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Discharge Air Modulation Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Data Logging Option (µP-IV, µP-V, µP-VI, SR-2 and SR-3 Controllers) . . . . . . . . . . . . . . . . 5-5
Sleep Mode Option (Option on µP-IV and µP-V Controllers, Standard on µP-VI, SR-2 and SR-3
Controllers) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Tracker Option (µP-IV, µP-V, µP-V, SR-2 and SR-3 Controllers) . . . . . . . . . . . . . . . . . . . . . 5-6
CYCLE-SENTRY (Start/Stop) Control Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Economy Mode Control Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
OptiSet™ Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Data Acquisition System (DAS) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Remote Control Options (TG-V, µP-IV Multi-Temp, µP-V and µP-VI Controllers) . . . . . . . 5-7
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
SL-100, SL-100e, SL-200 and SL-200e (TG-VI Controller) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
SL-300 (µP-IV or µP-V Controller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
SL-400, SLX/SLXe and SLX/SLXe Spectrum (µP-VI, SR-2 and SR-3 Controller) . . . . . . . . 5-15
Thermo King SR basic operational sequence Diesel Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
Thermo King SR basic operational sequence Electric Standby Mode . . . . . . . . . . . . . . . . . . . . . 5-20
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
SL TCI, SPECTRUM SL (Multi-Temp µP-IV Controller) and SLX SPECTRUM (with Multi-temp
SR-2/SR-3 Controller). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Engine Compartment Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
Remote Evaporator Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
TG-VI, µP-IV, µP-V, µP-VI and SR-2 Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Spectrum Remote Evaporator Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Serial Number Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
TLE and SPECTRUM Remote Evaporator Nameplate: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Engine Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Compressor Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Electric Motor Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Unit Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
SMART REEFER 2/3 Multi-Temp (SR-2/SR-3 MT) Control System . . . . . . . . . . . . . . . . . . 6-6
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Control Panel Keys (Single or Multi-temp SR-2/SR-3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Unit Operation (Single or Multi-Temp SR-2/SR-3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
2
Manual Pretrip Inspection (Before Starting Unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Turning Unit On (Single or Multi-temp SR-2/SR-3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Turning Unit Off (Single or Multi-Temp SR-2/SR-3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
Operating The Unit In Single Zone Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
Standard Display Variations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
Temperature Watch Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Other Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Unit Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-20
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-20
Visual Pre-trip Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-20
Selection of Operating Modes on CYCLE-SENTRY Equipped Units . . . . . . . . . . . . . . . . . . 6-22
Starting Units on Continuous Run, Diesel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-23
Starting Units on CYCLE-SENTRY, Diesel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-23
Starting Model 50 Units on Electric Standby Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
Loading Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-25
Post Load Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Post Trip Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Thermoguard Multi-temp MT µP-IV and µP-V Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Entering Setpoint Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Selecting CYCLE-SENTRY or Continuous Run Mode (Multi-Temp MT µP-IV and µP-V ONLY)
7-3
Initiating Manual Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Viewing Information (Display) Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Checking the Software Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Displaying and Clearing Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Unit Pre-trip Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Thermoguard TG-VI Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Entering Setpoint Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
Selecting CYCLE-SENTRY or Continuous Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
Initiating Manual Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Checking the Software Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Displaying and Clearing Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Viewing Information (Display) Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Unit Self-Check Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Multi-Temp Remote Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
Displaying Operating Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Entering Setpoint Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Thermoguard µP-VI Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-13
Entering Setpoint Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
Selecting CYCLE-SENTRY or Continuous Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
Initiating Manual Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
Selecting Economy Mode - Revision 4000 and 4010 Software Only . . . . . . . . . . . . . . . . . . . 7-15
Viewing Information (Display) Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-15
Checking the Software Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17
Displaying and Clearing Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18
Unit Pre-trip Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18
Entering a Start of Trip in the Data Logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19
SR-2/SR-3 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20
3
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Selecting CYCLE-SENTRY or Continuous Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Navigating the Operator Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Alarm Codes for µP-IV, Multi-Temp µP-IV, µP-V, µP-VI, TG-VI , SR-2 and SR-3 Controllers 7-25
Electrical Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Alternator (Australian Bosch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Charging System Diagnostic Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Field Current Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Alternator Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Alternator Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Inspecting and Diagnosing Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
Alternator Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
Alternator Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Alternator (Thermo King, P/N 41-6780, 41-6781, 41-6782) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-13
Alternator Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-15
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-15
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
12 Vdc Charging System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
Fuse Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
Fuses (Units with TG-VI, MT µP-IV, µP-V, µP-VI, SR-2 or SR-3) . . . . . . . . . . . . . . . . . . . . 8-17
Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
TG-VI, MT µP-IV, µP-V, µP-VI, SR-2 or SR-3 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-19
Air Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-20
Low Oil Level Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21
Switch Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21
Switch Removal and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21
Bench Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21
High Water Temperature Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-22
Switch Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-22
Condenser and Evaporator Fan Rotation (Electric Standby Operation) . . . . . . . . . . . . . . . . . . . . 8-22
Evaporator Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
SL, SLe, SLX, SLXe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
AC Components (Model 50 Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
Electrical Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
Phase Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
Phase Correction Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24
Diagnosing the Phase Correction System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24
Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-26
Defrost Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-26
Defrost Cycle Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-26
Defrost Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27
Engine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Engine Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Engine Oil Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Oil Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Crankcase Breather . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
TK 482, TK 486, TK 486V Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Engine Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
4
Dry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
Cyclonic Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
Engine Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
Antifreeze Maintenance Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-9
Checking the Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Changing the Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Bleeding Air from the Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Engine Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-11
Engine Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
TK 482, TK 486 and TK 486V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-14
Bleeding the Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-14
Water in the Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-15
Single Element Fuel Filter/Water Separator Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-16
TK 482, TK 486 and TK 486V Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-17
Integral Fuel Solenoid – TK 482, TK 486 and TK 486V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-17
Diagnosing the Integral Fuel Solenoid System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-18
Fuel Solenoid Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-22
Injection Pump Service and Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-22
Injection Pump Installation & Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-22
TK 482, TK 486 and TK 486V Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-24
TK 482, TK 486 and TK 486V Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-29
Belt Tension Adjustment and Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-31
SL Belt Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-32
SLe, SLX, SLXe and Spectrum Belt Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-36
Blower Belts - Upper and Lower Poly-V Groove Belt Replacement on SL Units and Upper Belt Only
on SLX, SLXe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-37
SLX, SLXe Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-39
SLX, SLXe Upper Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-39
Compressor Drive Belt Replacement and Adjustment (Model 50) . . . . . . . . . . . . . . . . . . . . 9-42
Clutch drive tensioning Schematic SLXe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-44
Clutch Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-48
SL and SLe Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-49
Refrigeration Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Service Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Leak Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Vacuum Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Gauge Manifold Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
System Clean-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Refrigerant Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Refrigeration Maintenance Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
Additional Information Low Side Pump Down for TCI and SPECTRUM Models . . . . . . . . 10-3
Compressor Oil Acid Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
Checking Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
Checking Refrigerant Charge with an Empty Trailer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
Checking Refrigerant Charge with a Loaded Trailer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
Refrigerant Overcharge Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-6
Moisture Indicating Sight Glass (where fitted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-7
SLX/SLXe Spectrum Charging Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-8
Micro-channel condenser and auxiliary receiver design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-8
Charging procedure for SLX SPECTRUM categories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-8
5
SLX/SLXe SPECTRUM charging procedure: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-9
Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-10
Evacuating and Charging Smart Reefer Multi-Temp Systems . . . . . . . . . . . . . . . . . . . . . . . . . . .10-10
Set-up Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-10
System Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-10
Evacuation is Important and Critical to System Performance . . . . . . . . . . . . . . . . . . . . . . . . .10-10
Set-up and Test Evacuation Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-13
Unit Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-15
Unit Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-16
Remove Evacuation Hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-18
High Pressure Cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-18
Head Pressure Control switch (SL TCI and SL Spectrum) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-18
Three-Way Valve Condenser Pressure Bypass Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-18
Modulation Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-19
Electronic Throttling Valve (ETV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-20
Hot Gas or Hot Gas Bypass valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-20
Refrigeration Service Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Refrigeration System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
Low Side Pump Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
High Pressure Cutout Switch or High Pressure Cycle (Control) Switch . . . . . . . . . . . . . . . . . 11-3
Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
Discharge Vibrasorber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
Suction Vibrasorber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
Condenser Inlet Check Valve, Condenser Outlet Check Valve or Receiver Tank Outlet Check Valve
11-5
Receiver Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-6
Bypass Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-6
High Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-7
Dehydrator (Filter-Drier) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-7
Expansion Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-7
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-8
Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-9
Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-9
Pilot Solenoid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-10
Modulation Valve (SL and SLE only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-10
Hot Gas Bypass Solenoid Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-10
Throttling Valve (non-ETV Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-11
Three-Way Valve Condenser Pressure Bypass Check Valve Repair . . . . . . . . . . . . . . . . . . . .11-14
Three-Way Valve Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-15
Compressor Oil Filter – X214, X426 or X430 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . .11-17
Electronic Throttling Valve (ETV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-18
Multi-Temperature System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-20
Discharge Pressure Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-20
Liquid Line Solenoid Valve (LLS, LLS2, LLS3, RLLS or CLLS) or Suction Line Solenoid Valve
(SLS, SLS2, SLS3, RSLS or CSLS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-20
Condenser Inlet Solenoid Valve (CIS) or Hot Gas Solenoid Valve (HGS, HGS2, HGS3, RHGS or
CHGS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-21
Suction Line Check Valve (SLCV, SLCV2, SLCV3, RSLCV or CSLCV), Purge Check Valve (PCV)
or Liquid Return Check Valve (LRCV, LRCV2, LRCV3, RLRCV or CLRCV) . . . . . . . .11-21
Receiver Tank Pressure Solenoid Valve (RTPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-22
Purge Valve (PV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-22
Structural Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
Unit and Engine Mounting Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-2
6
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-3
Defrost Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-3
Condenser, Evaporator and Radiator Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-4
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-6
SL and SLe Top Center Nut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-7
Access to Mounting Holes SLX/SLXe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-8
Defrost Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-8
SL Defrost Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-9
Damper Door Motor with Current Sensing Blade Position Control (SLXe, SLX, SLe and Late Model
SL Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-23
Fan Shaft Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-28
SL and SLe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-28
SLXe, SLX Fan Shaft Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-42
Lower Blower Assembly SLXe, SLX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-43
Jackshaft/ Cross Shaft Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-44
SL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-44
SLe, SLXe, SLX and SPECTRUM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-46
Lower (engine to electric motor or Cross Shaft) Belt (SLX ONLY) . . . . . . . . . . . . . . . . . . . 12-47
SLXe. SLX Cross Shaft Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-51
Remote Evaporator Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-52
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-52
Defrost Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-52
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-52
Mechanical Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
TK 482, TK 486 and TK 486V Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
Refrigeration System Diagnosis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
All Models Except TCI and SPECTRUM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2
TCI and SPECTRUM Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-4
Remote Evaporator System Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-5
Single Temperature Refrigeration System Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1
SL/SLe 100, 200 and SLX/SLXe 100, 200 without modulation . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Cooling Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Heat and Defrost Cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
SL, SLe 200 and 300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-5
SL-400 and SL-400e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-6
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-6
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-7
SLX 200 PPP, 300, 400 and SLXe 300, 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-8
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-8
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-9
Multi-Temperature Refrigeration System Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-1
SL TCI, or SPECTRUM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-2
Zone 1* on Cool and Zone 2** on Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-2
Zone 1* on Cool and Zone 2** on Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-3
Zone 1* on Cool, Zone 2** on Cool and Zone 3*** on Cool . . . . . . . . . . . . . . . . . . . . . . . . 16-4
Zone 1* on Cool, Zone 2** on Cool and Zone 3*** on Heat . . . . . . . . . . . . . . . . . . . . . . . . 16-5
SLX/SLXe Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-6
Zone 1* on Cool, Zone 2** on Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-6
Wiring Diagrams and Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1
7
8
1 Introduction
Introduction 1-2
2 Safety Precautions
GENERAL PRACTICES
1. ALWAYS WEAR GOGGLES OR SAFETY GLASSES. Refrigerant liquid and battery acid can permanently damage the
eyes (see First Aid).
2. Never close the compressor discharge service valve with the unit operating. Never operate the unit with the compressor
discharge valve closed.
3. Keep your hands clear of the fans and belts when the unit is operating. This should also be considered when opening and
closing the compressor service valves.
4. Make sure the gauge manifold hoses are in good condition. Never let them come in contact with a belt, fan motor pulley, or
any hot surface.
5. Never apply heat to a sealed refrigeration system or container.
6. Fluorocarbon refrigerants, in the presence of an open flame or electrical short, produce toxic gases that are severe respiratory
irritants capable of causing death.
7. Make sure all mounting bolts are tight and are of the correct length for their particular application.
8. Use extreme caution when drilling holes in the unit. The holes may weaken structural components, and holes drilled into
electrical wiring can cause fire or explosion.
9. Use caution when working around exposed coil fins. The fins can cause painful lacerations.
10. Use caution when working with a refrigerant or refrigeration system in any enclosed or confined area with a limited air supply
(for example, a truck body or garage). Refrigerant tends to displace air and can cause oxygen depletion which may result in
unconsciousness or death from suffocation.
11. Use caution and follow the manufacturer’s suggested practices when using ladders or scaffolds.
REFRIGERANT
General Information
When removing refrigerant from a unit, a recovery process that prevents or minimises refrigerant loss to the atmosphere is
required by law.
When a refrigerant is exposed to the atmosphere in the liquid state, it evaporates rapidly, freezing anything it contacts. If
refrigerant contacts the skin, severe frostbite can result.
First Aid
In the event of frost bite, the objectives of First Aid are to protect the frozen area from additional injury, to warm the affected
area rapidly, and to maintain respiration.
• EYES: For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical attention.
• SKIN: Flush area with large amounts of lukewarm (not hot) water. Do not apply heat. Remove contaminated clothing and
shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection/injury. Get medical attention. Wash contaminated
clothing before reuse.
• INHALATION: Move victim to fresh air and use cardiopulmonary resuscitation or mouth-to-mouth ventilation if necessary.
Stay with victim until arrival of emergency medical personnel.
•
REFRIGERANT OIL
General Information
Observe the following precautions when working with or around synthetic or polyester refrigerant oil:
• Do not allow refrigerant oil to contact your eyes.
• Do not allow prolonged or repeated contact with skin or clothing.
• To prevent irritation, you should wash thoroughly immediately after handling refrigerant oil. Rubber gloves are recommended
when handling polyol ester oil.
First Aid
• EYES: Immediately flush eyes with large amounts of water for at least 15 minutes while holding the eyelids open. Get prompt
medical attention.
• SKIN: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
• INHALATION: Move victim to fresh air and restore breathing necessary. Stay with victim until arrival of emergency
personnel.
• INGESTION: Do not induce vomiting. Contact a local poison control center or physician immediately.
Microprocessor Service
Precautions must be taken to prevent electrostatic discharge when servicing the microprocessor controller and related
components. Potential differences considerably lower than those which produce a small spark from a finger to a door knob can
severely damage or destroy solid-state integrated circuit components.
The following procedures must be rigidly adhered to when servicing units to avoid microprocessor damage or destruction.
1. Disconnect all power to the unit.
2. Avoid wearing clothing that generates static electricity (wool, nylon, polyester, etc.).
3. Do wear a static discharge wrist strap (TK P/N 204-622) with the lead end connected to the microprocessor’s ground terminal.
These straps are available at most electronic equipment distributors. DO NOT wear these straps with power applied to the unit.
4. Avoid contacting the electronic components on the circuit boards of the unit being serviced.
5. Leave the circuit boards in their static proof packing materials until ready for installation.
6. If a defective controller is to be returned for repair, it should be returned in the same static protective packing materials from
which the replacement component was removed.
7. After servicing the controller or any other circuits, the wiring should be checked for possible errors before restoring power.
High Voltage
When servicing or repairing a temperature control unit, the possibility of serious or even fatal injury from electrical shock exists.
Extreme care must be used when working with a refrigeration unit that is connected to a source of operating power, even if the
unit is not operating. Lethal voltage potentials can exist at the unit power cord, inside the control box, at the motors and within
the wiring harnesses.
Low Voltage
Control circuits used in the temperature control unit are low voltage (24 volts ac and 12 volts dc). This voltage potential is not
considered dangerous, but the large amount of current available (over 30 amperes) can cause severe burns if shorted or grounded.
Do not wear jewelry, watch or rings. These items can short out electrical circuits and cause severe burns to the wearer.
Warning: Care must be taken because all external panels are heavier on the SLX/SLXe Whisper than on standard SLX/SLXe
Units.
First Aid
IMMEDIATE action must be initiated after a person has received an electrical shock. Obtain immediate medical assistance if
available.
The source of shock must be immediately removed by either shutting down the power or removing the victim from the source.
If it is not possible to shut off the power, the wire should be cut with either an insulated instrument (e.g., a wooden handled axe
or cable cutters with heavy insulated handles) or by a rescuer wearing electrically insulated gloves and safety glasses. Whichever
method is used, do not look at the wire while it is being cut. The ensuing flash can cause burns and blindness.
If the victim has to be removed from a live circuit, pull the victim off with a non-conductive material. Use the victim’s coat,
a rope, wood, or loop your belt around the victim’s leg or arm and pull the victim off. DO NOT TOUCH the victim. You can
receive a shock from current flowing through the victim’s body. After separating the victim from power source, check
immediately for the presence of a pulse and respiration. If a pulse is not present, start cardiopulmonary resuscitation and call for
emergency medical assistance. If a pulse is present, respiration may be restored by using mouth-to-mouth resuscitation, but call
for emergency medical assistance.
UNIT DECALS
Serial number decals, refrigerant type decals and warning decals appear on all Thermo King equipment. These decals provide
information that may be needed to service or repair the unit. Service technicians should especially read and follow the instructions
on all warning decals.
Refrigerant Decals
Information Decals
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Electrical Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Heat/Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Electrical Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Evaporator Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Electric Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Electric Drive Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Standby Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Remote Evaporator Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
ENGINE
Diesel Engine Model:
SL-100 and SL-200 TK 482
SL-100e, SL-200e, SL-300, SL-400, SL-400e,
SL TCI and SPECTRUM SL TK 486 and TK 486V (starting in August 2006)
SLX/SLXe-100, SLX/SLXe-200, SLX/SLXe-300, SLX/ TK 486 V
SLXe-400, SLX/SLXe SPECTRUM, SLX/SLXe Whisper
Fuel Type:
All models Diesel fuel must conform to EN590
Oil Capacity:
Crankcase: Fill to full mark on dipstick
TK 482, TK 486 and TK 486V 12.3 litre
Oil Type (All Engines):
Petroleum Multi-grade Oil: API Type CI-4, ACEA Class E3
Synthetic Multi-grade Oil: API Type CI-4, ACEA Class E3 (after first 500 hours)
Oil Viscosity (All Engines):
-30°C to +0°C SAE 5W-30
-25°C to +30°C SAE 10W-30
-25°C to +40°C SAE 10W-40
-15°C to +40°C (or -10°C to +50°C) SAE 15W-40
Engine Oil Pressure:
TK 482, TK 486 and TK 486V 1.0 to 3.8 bar, 15 to 55 psi
Engine RPM*:
SB-III 2200 +/- 25 RPM High Speed
1450 +/- 25 RPM Low Speed
SL-100, SL-100e 1600 +/- 25 RPM High Speed
1200 +/- 25 RPM Low Speed
SL-200 and SL-200e 1900 +/- 25 RPM High Speed
1450 +/- 25 RPM Low Speed
SL-300, SL-400 and SL-400e 2200 +/- 25 RPM High Speed
1450 +/- 25 RPM Low Speed
SL TCI, SPECTRUM SL 2200 +/- 25 RPM High Speed
1450 +/- 25 RPM Low Speed
SLX/SLXe-100, SLX/SLXe Whisper 1450 +/- 25 RPM High Speed
1250 +/- 25 RPM Low Speed
SLX/SLXe 200, SLX/SLXe-300 1550 +/- 25 RPM High Speed
1250 +/- 25 RPM Low Speed
SLX/SLXe-400/SLXe- 300 Whisper Pro, SLX/SLXe 2000 +/- 25 RPM High Speed
SPECTRUM/SPECTRUM Whisper Pro 1250 +/- 25 RPM Low Speed (PIEK speed)
* CAUTION: Do NOT operate the engine in ANY unit more than 100 RPM over the high speed setting shown to avoid blower
overspeed and/or damage.
Valve Clearance:
TK 482, TK 486 and TK 486V 0.15 to 0.25 mm on intake valve
0.15 to 0.25 mm on exhaust valve
Valve Setting Temperature 21 C (Room temperature)
ENGINE (CONTINUED)
Timing Injection Pump:
TK 482, TK 486 and TK 486V 12o +/- 1o BTDC (timed on No. 1 cylinder, fly wheel side)
Low Oil Pressure Switch (Normally Closed):
TK 482, TK 486 and TK 486V 0.69 +/- 0.21 bar, 10 +/- 3 psi
High Coolant Temperature Switch*:
TK 482, TK 486 and TK 486V Sensor*
Engine Thermostat:
All engines (except TK 486V) 82 C
TK 486V 71 C
Coolant System Capacity:
TK 482, TK 486, TK 486V, se 2.2 and di 2.2:
All models in the SL Range 7.1 litre with overflow tank
All Models in the SLX/SLXe Range 7.1 litre with overflow tank
All Models in the SLX/SLXe Range with Microchannel
Coil 6.6 litre with overflow tank
Engine Coolant Type (All engines):
ELC (Extended Life Coolant) Use a 50/50 concentration of any of the following
equivalents:
Texaco ELC (7997, 7998, 16445, 16447),
Havoline Dex-Cool® (7994, 7995),
Havoline XLC for Europe (30379, 33013),
Shell Dexcool® (94040), Shell Rotella (94041),
Saturn/General Motors Dex-Cool®, Caterpillar ELC,
Detroit Diesel POWERCOOL® Plus
Clutch:
Engagement 400 +/- 100 rpm
Dynamic Torque 79 N•m minimum at 900 rpm
SL/ SLe
Model: ALL
P/N 107-299 6-Pin Coupling with Small Compressor Shaft
P/N 107-340 6-Pin Coupling with Large Compressor Shaft
P/N 107-342 8-Pin Coupling with Small Compressor Shaft
P/N 107-343 8-Pin Coupling with Large Compressor Shaft
SLX/SLXe
Model: ALL
P/N 107-364 8-Pin Coupling with Large Compressor Shaft
Specifications 3-3
DRIVE SYSTEM
NOTE: Use belt tension gauge TK P/N 204-427 whenever possible to check belt tension. However, on some
unit models, and on some belts, it is difficult to use the gauge. Adjust these belts to allow 12 mm of deflection
at the centre of the longest span. New belts should be tensioned cold and tensioned cold again after 10 hours
of unit operation.
Tension Number on TK Gauge
Belt 204-427 New TK Gauge 204-1903
Field Reset Field Reset
SL: Direct Drive to Compressor (Model 30)
Electric Motor/Compressor Drive—Double 80
V Belt (Model 50)
37 Ampere, 12 Vdc Alternator 30
65 or 120 Ampere, 12 Vdc Alternator 45
Water Pump 40
Upper Fan (Fan to Jackshaft) 75
Lower Fan (Engine to Jackshaft) w/37 80
Ampere Alternator
Lower Fan (Engine to Jackshaft) w/65 or 120 85
Ampere Alternator
SLe and SPECTRUM SL**: Direct Drive to Compressor (Model 30) Tension Frequency
Electric Motor/Compressor Drive— 80–85
Upper Fan (Fan to Jackshaft) 85–90
Lower Fan (Engine to Jackshaft) w/37 85–90
Ampere Alternator
SLX/SLXe and SLX/SLXe SPECTRUM **: Direct Drive to Compressor (Model 30)
Electric Motor/Compressor Drive 80–85 700-800 67-72
Fan Drive Belt (Model 50) 350-450 95-108
Water Pump 40
** SLe, SPECTRUM SL, SLX, SLXe and SLX/SLXe SPECTRUM units have one/two automatic tensioning fan drive belt
systems, in order to drive the compressor and the evaporator fanshaft. SLX/SLXe only has one, SL has two (Upper and Lower).
The lower polygroove belt runs from the engine/compressor to the intermediate jackshaft (or electric motor, depending on the
unit model).
The upper polygroove belt links the intermediate jackshaft to the evaporator fanshaft, incorporating other belt driven components
such as the condenser blowers and the alternator.
Specifications 3-4
REFRIGERATION SYSTEM
Caution: Fluorinated Refrigerant gases should not be ventilated to atmosphere.
SLXe units from January 2015 are available with R-404A or R-452A Refrigerants. Both of which comply with F-Gas
legislation revision 2014 (Regulation (EC) No 517/2014)
NOTE: Please take note of your refrigerant type (label on outside of unit), and make sure not to cross-contaminate.
Refrigerant GWP
R-404A 3922
R-452A 2140
R-404A/ R452A*
Compressor Model:
SL-100, SL-100e, SL-200 and SL-200e X426
SL-300, SL-400, SL-400e, SL TCI and X430
SPECTRUM SL
SLX/SLXe-100 X426LSC5
SLX/SLXe-200, SLX/SLXe-300, SLX/ X430LSC5
SLXe-400, SLX/SLXe SPECTRUM,
SLX/SLXe Whisper
Refrigerant Charge:
SL-100 and SL-100e 5.00 kg
SL-200, SL-200e and SL-300 6.35 kg
SL-400, SL-400e 6.35 kg
SL TCI-2 and SPECTRUM SL-2 7.40 kg
SL TCI-3 and SPECTRUM SL-3 8.20 kg
SLX-100 7.00 kg
SLX-200, SLX-300, and SLX-400 7.50 kg
SLX SPECTRUM & SLXe Spectrum 6.5 kg approx. (For correct charge procedure for a SPECTRUM system, see
section in Trailer Install manual).
SLXe-100 4.00 kg
SLXe-400 5.70 kg
SLX/SLXe Whisper (and all remaining 5.00 kg
ST SLX/SLXe with Microchannel
condenser coil)
Compressor Oil Charge:
X426LSC5 or X430LSC5 4.10 litre**
6.62 litre (deep sump)**
TCI and SPECTRUM models Add 0.7 litre for remote evaporator system tubing
(with shallow sump)
Compressor Oil Type:
All models TK P/N 203-413 (Polyol Ester)
Suction Pressure Regulator Setting:
Throttling Valve Setting:
SL-100 and SL-100e 1.65 to 1.79 bar, 24 to 26 psi
SL-200, SL-200e, SLX/SLXe-100 and 2.28 to 2.35 bar, 33 to 34 psi
SLX/SLXe-200
SL-300 1.38 to 1.52 bar, 20 to 22 psi
SL TCI 1.38 to 1.52 bar, 20 to 22 psi
SPECTRUM SL
SLX/SLXe SPECTRUM Model 30 1.86 to 2 bar, 27 to 29 psi
SLX/SLXe SPECTRUM Model 50 1.59 to 1.73 bar, 23 to 25 psi
* From January 2015, See referigerant decal on your unit to confirm refrigerant type of the particular unit.
** When the compressor or compressor oil filter is removed from the unit, oil level should be noted or the oil removed from
the compressor should be measured so that the same amount of oil can be added before placing the replacement compressor
in the unit.
Specifications 3-5
R-404A/ R452A*
High Pressure Cutout:
SL, SLe, SLX, SLXe and SPECTRUM Opens: 32.41 +/- 0.48 bar, 470 +/-7 psi
Closes: Automatic reset @ 25.86 +/- 2.62 bar, 375 +/- 38 psi
High Pressure Control Switch (Receiver Tank):
SL TCI and SLe SPECTRUM models Opens: 20.68 +1.72/-0 bar, 300 +25/-0 psi
Closes: 13.79 +/- 0.69 bar, 200 +/- 20 psi
High Pressure Relief Valve:
All models Opens: 34.48 +/- 3.45 bar, 500 +/- 50 psi
Reset: 27.58 bar, 400 psi
HEAT/DEFROST SYSTEM
Heat/Defrost Method*:
All models:
Engine Operation Hot gas
Electric Operation Hot gas & electric heater strips** (Model 50)
Electronic Defrost Termination Switch:
All models with TG-VI, µP-IV, µP-V, µP-VI, SR-2 or Coil must be below 7 C for defrost initiation
SR-3 Coil must be above 14 C for defrost termination
Defrost Timer:
All models with TG-VI 4 hours (Out-of-range)
Setting adjustable through guarded access in controller
software
Terminates defrost 30 to 45 minutes after initiation
All models with µP-IV, µP-V, µP-VI or SR-2 4 hours (Out-of-range)
6 hours (In-range)
Setting adjustable through guarded access in controller
software
Terminates defrost 30 to 45 minutes after initiation
CONTROLLER
Type:
SL-100, SL-100e, SL-200, SL-200e, and SMX-II Thermoguard VI controller (TG-VI)
SL TCI and SPECTRUM SL Thermoguard μP-IV multi-temp controller (μP-IV
Multi-Temp)
SL-300 Thermoguard μP-V controller (μP-V)
SL-400 and SL-400e Thermoguard μP-VI controller (μP-VI)
or Smart Reefer 2 (SR-2) on SL-400e
SLX/SLXe, SLX/SLXe SPECTRUM, SLX/SLXe Smart Reefer 2 (SR-2) or Smart Reefer 3(SR-3)
Whisper
Setpoint Range:
TG-VI, μP-IV, μP-V, μP-VI and SR-2 -28.0 to +28.0 C (optional range to -32.0 C)
Digital Temperature Display:
μP-IV, μP-V, μP-VI and SR-2 -40.0 to +40.0 C
Fresh/Frozen (FRFZ) Temperature Setting (TG-VI, µP-IV, µP-V and µP-VI Only):
TG-VI Factory Setting High Speed Heat (or all Heat) locked out below -4 C
μP-IV, μP-V, μP-VI and SR-2 Factory Setting High Speed Heat (or all Heat) locked out below -4 C,
programmable for -4 C or -9 C
Specifications 3-6
ELECTRICAL CONTROL SYSTEM (CONTINUED)
TG-VI, µP-IV, µP-V, µP-VI and SR-2 Controllers:
2 Circuit:
SL, SLe models 40 ampere fuse
High Speed Solenoid Circuit:
SL/ SLe models 15 ampere fuse
8 or 8F Circuit:
SL/ SLe (except SL-400 and SL-400e) 15 ampere fuse
SL-400 and SL-400e models 25 ampere fuse
Damper Circuit:
SL/ SLe models 15 ampere fuse
Remote Evaporator Fan (RFM) Circuit:
TCI and SPECTRUM models 25 ampere fuse
Other Circuits*:
SL/ SLe 2 or 3 ampere fuses
Fusible Link:
All models 16 gauge wire (100 to 110 amperes)
Evaporator Fan Circuit Breaker:
SL TCI and SPECTRUM SL 30 ampere auto reset
Battery Charging Alternator:
All models (Except TCI and SPECTRUM models) 37 ampere brush type (optional: 65 ampere brush type)
SL TCI and SPECTRUM 120 ampere brush type
Voltage Regulator Setting:
All models 13.8 to 14.2 @ 25 C
Alternator/Regulator LED Diode
Used when replacing “Old Style” Integral Regulator 4.7 mFd 50 Vdc
Alternators with “New Style” Remote Regulator
Alternators
Alternator/Output Capacitor
Used to Filter Electrical Interference on “Old Style” 0.5 mFd 100 Vdc
Integral Regulator Alternators
* The alternator field fuse (F15 or F7) must be removed from the relay board for the Bosch alternator.
SLX/SLXe/SL-400 SR-2/SR-3 Controller
Fuse Size Function
F2 15A 2AB Power
F3 40A Fuel Sol Pull-In/Starter Circuit
F4 None No Fuse - all Bosch Alternators
F5 60A Preheat Circuit (Slow Burn Fuse)
F6 15A High Speed Circuit
F7 2A 8FP Circuit - CAN Bus
F8 5A CAN Connector J12
F9 5A CAN Connector J14
F10 10A 8X Power (Install Fuse in Upper Position)
F11 10A Zone 1 LLS (SPECTRUM)
F12 5A CAN Connector J13
F13 2A 8FC Circuit (Remote Lights)
F15 p/s On/Off Relay
F20 2A Alternator Sense
F25 7.5A HPCO Switch Circuit
Specifications 3-7
ELECTRICAL COMPONENTS
Disconnect components from unit circuit to check resistance.
Current Draw
(Amperes) Resistance
at 12.5 Vdc (Ohms)
Starter Motor:
TK 482, TK 486, se 2.2 and di 2.2* 250 to 375 (cranking)
80 (bench test)
TK 486V 350 to 475 (cranking)
Air Heater:
TK 482, TK 486 and TK One 89 0.14
486V
Glow Plug:
se 2.2 and di 2.2 One 7.1 1.8
All Plugs 28.4
Fuel Solenoid:
TK 482, TK 486 and TK Pull-in 35 to 45 0.2 to 0.3
486V
Hold-in 0.5 or 1.0 24 to 29
se 2.2 and di 2.2 Hold-in 1.4 8.8
Throttle Solenoid:
All engines 2.9 4.3
Pilot Solenoid:
All models 0.7 17
Damper Motor:
SL, SLX, SLXe 2.1 6.0
Damper Gear Motor
SL and SLe (beginning August 2000) 3.1 to 4.2 3.0 to 4.0
SLX, SLXe 2.5 to 3.1 4.0 to 5.0
Receiver Tank Pressure Solenoid:
TCI and SPECTRUM models 0.7 17
Liquid Line Solenoid (Front and Rear):
TCI and SPECTRUM models 1.3 9.6
Hot Gas Bypass Solenoid:
TCI and SPECTRUM models 1.3 9.6
Remote Hot Gas Solenoid:
TCI and SPECTRUM models 1.3 9.6
Suction Line Solenoid (Front and Rear):
TCI and SPECTRUM models 1.3 9.6
Condenser Inlet Solenoid:
TCI and SPECTRUM models 1.3 9.6
Purge Valve Solenoid:
TCI and SPECTRUM models 0.9 17.0
Modulation Valve (Option):
All models (Except TCI and SPECTRUM models) 1.7 7.6
Hot Gas Bypass Valve (Option):
All models (including SLXe Spectrum) (Except SL TCI and 1.1 11.1
SL/SLX SPECTRUM models)
*Gear reduction type starter.
Specifications 3-8
EVAPORATOR FAN MOTORS
TLE Fan Motor
Number 2 or 3
Voltage 12 Vdc
Full Load Amps 7 amperes
SPECTRUM Remote Evaporator Fan Motor
Number 2 or 3
Voltage 12 Vdc
Full Load Amps 7 amperes
SPECTRUM Remote Evaporator Fan Motor (S-2 after Jan 2012)
Number 2
Voltage 12 Vdc
Full Load Amps 6 amperes
Specifications 3-9
ELECTRIC STANDBY
(Model 50 only)
Electric Heater Strips (optional):
SL-300, SL-400, SL-400e, SLX, SLXe, SMX and SMX-II)
Number 3
Watts (each) 1000
Resistance (cold and disconnected) 122 ohms
*Electric heater strips are standard on SLXe, SLX, SL-400 and SL-400e models, and not available on SL-100, SL-100e, SL-200 and SL-200e
models.
**Models with a TG-VI, µP-IV, µP-V or µP-VI controller use the evaporator coil sensor to provide evaporator high temperature protection.
Electrical
Specifications 3-10
Electrical
Specifications 3-11
Specifications 3-12
4 Maintenance Inspection
Schedule
SL and SLe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Remote Evaporators: ECT, ELT, EW, SPECTRUM and TLE. . . . . . . . . . . . . . . . . . . . 4-4
All SLX, SLXe and Spectrum Models Host Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
SLX/SLXe SPECTRUM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
SLX/SLXe WHISPER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
All SLX, SLXe and Spectrum Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
SL and SLe
Every 1,500*
Every or 3000* Annual/ Inspect/Service These Items
Pre-Trip 500 Hours Hours 4,500 Hours
Microprocessor/Thermostat
• • Perform Unit Self Check (units with TG-VI microprocessor) or Unit
Pre-Trip (units with µP-IV, µP-V, µP-VI or SR-2 microprocessor).
See appropriate Microprocessor Controller Operation and Diagnosis
manual.
• • • • Check thermostat cycle sequence (units with TG-IV or TG-V
thermostat) on Electric, Continuous Run and CYCLE-SENTRY
operation.
Engine
• Check fuel supply.
• • Check engine oil level.
• • • • Check engine coolant level light. (CAUTION: Do not remove
radiator cap while coolant is hot.)
• • • • Inspect belts for condition and proper tension.
• • • • Check engine oil pressure hot, on high speed. Minimum 276 kPa,
2.76 bar, 40 psi.
• • • • Listen for unusual noises, vibrations, etc.
• • • Check air cleaner indicator (if equipped).
Replace dry type element when indicator reaches 635 mm (25 in.)
H2O vacuum (381 mm [15 in.] H2O vacuum on SMX models before
1/93).
Replace Cyclonic air filter element at 3,000 hours or two years
(whichever comes first) if air clean indicator has not reached 635
mm (25 in.) H20 vacuum.
If not equipped with an air restriction indicator, replace air filter
element at 3,000 hours or one year (whichever occurs first).
• • Check and adjust engine speeds (high and low speed).
• • Change engine oil* (hot) and dual element oil filter**.
• • Clean and service crankcase breather. Check air cleaner hose for
damage.
• • Drain water from fuel tank and check vent.
• • Inspect/clean fuel transfer pump inlet strainer.
• • Separate fuel and water separator elements: Change fuel filter every
1,500 hours and water separator filter every 3,000 hours. Single
element fuel/water separator: Change fuel/water separator filter
every 3,000 hours.
• • Check condition of drive coupling bushings***.
• Check condition of engine mounts.
• Change green or blue-green engine coolant.
Maintain anti-freeze protection at -34 C.
Change ELC (red) engine coolant every 5 years or 12,000 hours
(whichever comes first).
Test fuel injection nozzles at least every 10,000 hours.
* Every 3,000 hours or two years (whichever comes first) on units equipped with EMI 3,000 oil filter and oil with ACEA Rating E2-96 (API
Rating CG-4) or better. EMI 3,000 filters are black with gold lettering. Every 3,000 hours on units equipped with synthetic engine oil, but
oil filter must still be changed at 1,500 hour intervals. On units equipped with synthetic oil and a bypass oil filter, oil filter change interval
can be extended to 3,000 hours.
** Single element oil filters require oil and filter change at 1,000 hours.
*** With unit OFF, rotate coupling backward and forward by hand. Any movement indicates the bushings need replacement.
**** Check controller for alarms.
MULTI-TEMPERATURE SYSTEMS
DE, TC, TCI and SPECTRUM model systems are designed to control the temperatures in separate compartments. Each system
consists of a host unit that mounts on the front of the trailer.
• DE model systems consist of a host unit with a split evaporator to control two longitudinal compartments. An optional remote
evaporator is available to control temperature in a third compartment.
• TC, TCI and Spectrum model systems consist of a host unit with a single evaporator and one (or two) remote evaporator units.
The host unit contains the diesel engine, compressor, system controls and an evaporator. Refrigerant lines and wire harnesses
connect the host unit to the remote evaporators.
Several compartment configurations are possible. The temperature in each compartment is maintained by a separate controller
(except when the unit is set to control at a single temperature). The systems are flexible enough to allow each compartment to be
set at any temperature. There are two basic models:
• Model 30: Cooling, heating (hot gas) and defrost (hot gas) on engine operation.
TCI and SPECTRUM Multi-Temp Systems with TLE or SPECTRUM Remote Evaporators
– Typical Compartment Configurations
1. TCI Host Unit Evaporator
2. **TLE or SPECTRUM Remote Evaporator
3. Adjustable Compartments
A. Zone 1 Compartment
B. Zone 2 Compartment
C. Zone 3 Compartment (TCI-3 System)
** TLE and SPECTRUM remote evaporators are available in 2 models with 2 or 3 evaporator blowers.
UNIT FEATURES
Compressors
• SL-300, SL-400, SL-400e, SLX, SLXe, SL-TCI, SPECTRUM SL/SLX/SLXe, models feature a X430, four-cylinder
compressor with 491 cm3 displacement.
• SL-100, SL-100e, SL-200 and SL-200e models feature a X426CSLS, four-cylinder compressor with 424 cm3 displacement.
Engines
• SL-100 and SL-200 and models feature a TK 482, four-cylinder, diesel engine rated at 21.3 kW at 1900 rpm.
• SL-100e, SL-200e, SL-300, SL-400, SL-400e, SL TCI, SPECTRUM models feature a TK 486, four-cylinder, diesel engine
rated at 25.3 kW at 2200 rpm.
• SL-100e, SL-200e, SL-400e, SLX/SLXe 100/200/300/400 and SPECTRUM models feature a TK 486V (starting in August
2006), four-cylinder, diesel engine rated at 25.3 kW at 2200 rpm.
Controllers
Thermoguard VI Microprocessor (TG-VI)
The TG-VI controller is used on SL-100, SL-100e, SL-200, SL-200e and SMX-II models. The TG-VI is a one-piece,
programmable microprocessor that uses external relays to control unit functions to maintain the cargo at the proper temperature.
The TG-VI integrates the following functions: thermostat, digital thermometer, defrost timer, hourmeters, oil pressure gauge,
coolant temperature gauge, voltmeter, tachometer, mode indicator, refrigeration system controller and diagnostic system.
SLX/SLXe Spectrum ETV Modulation is only available when using Zone 1 flat.
Data Logging Option (µP-IV, µP-V, µP-VI, SR-2 and SR-3 Controllers)
µP-VI controllers are available with an optional data logging system. SR-2 and SR-3 controllers have them as standard. The data
logging system records operating events, alarm codes and compartment temperatures. This trip data can be retrieved (but not
erased) from the controller memory using an IBM compatible laptop or desktop microcomputer and Thermo King Wintrac or
TracPac™ software. Detailed graph or table trip reports can then be created and printed.
WARNING: With the On/Off/Sleep switch in the SLEEP position, the unit may start at any time without prior warning.
NOTE: Sleep mode operation does NOT maintain temperature inside the trailer.
CAUTION: Operation in confined spaces. Diesel operation should be avoided in areas or circumstances where fumes from
the engine could become trapped and cause serious injury or death.
WARNING: With the CYCLE-SENTRY switch in the CYCLE position (or CYCLE-SENTRY icon ON in TG-VI and SR-2
display) and the unit On/Off switch in the ON position, the unit may start at any time without prior warning.
OptiSet™ Option
µP-VI and SR-2 control systems include the OptiSet feature as standard. OptiSet allows each customer to program a set of unit
operating details for a specific setpoint or setpoint temperature range. When the unit setpoint falls within a programmed setpoint
range, all unit operation is automatically determined by the OptiSet settings for that setpoint range. Unit operating features that
can be programmed using the OptiSet feature include:
• Setpoint limit high
• Setpoint limit low
• Fresh to Frozen range switch point (-4 C or -9 C)
• Range (0 to 9)
• Economy mode
• Cycle-Sentry mode
• Cycle-Sentry Null Range
• Fuel Saver II (for CYCLE-SENTRY)
• High Speed Pulldown (for CYCLE-SENTRY)
• Maximum Null Time Limit
• Minimum Off Time Limit
• Continuous mode
• Fuel Saver II (for Continuous Run)
• High Speed Pull-down (for Continuous Run)
• Low Speed Switch Point
• Modulation mode.
Remote Control Options (TG-V, µP-IV Multi-Temp, µP-V and µP-VI Controllers)
Remote controls are available for TG-V, µP-IV Multi-Temp, µP-V and µP-VI Controllers. Remote controls are used to operate
the unit from inside the trailer or the truck cab. The flush mount remote control is usually mounted in a wall inside the trailer.
The in-cab remote control is usually mounted in the dash of the truck cab.
Sequence of Operation
Engine Operation
Continuous Mode
• High Speed Cool
• Low Speed Cool
• Low Speed Heat
• High Speed Heat2, 3
• Defrost
Note: Tables shown are for basic operation and can be used for basic diagnostic’s. However, these may change from this
owing the the basic programmable features configurations and/or optiset configurations.
NOTE: If the controller calls for the Null mode (CYCLE-SENTRY or Electric Standby operation) while the unit is defrosting,
the unit will continue to operate until defrosting is complete. Then the unit will stop.
Engine Operation
Continuous Mode without Modulation
• High Speed Cool
• Low Speed Cool
• Low Speed Heat
• High Speed Heat1
• Defrost
1
High Speed Heat is locked out if controller setpoint is below -9 C.
Defrost
Defrost can be manually initiated, or automatically initiated by the air switch, controller defrost timer or controller Demand
Defrost algorithm. A demand defrost occurs when the difference between the return air temperature, discharge air temperature
and evaporator coil temperature becomes excessive.
NOTE: An air switch is not available on SL, Sle and SLX models.
Defrost can be initiated any time the evaporator coil temperature is below 7 C. If the unit is in Null (on CYCLE-SENTRY Engine
operation only), initiating defrost will cause the unit to start and operate. When a Defrost cycle is initiated, the controller energises
the damper motor or solenoid, pilot solenoid, heater contactor and Defrost icon. The controller maintains the In-range signal
during defrost.
The unit remains in defrost until the evaporator coil temperature increases to 14 C. If the evaporator coil temperature does not
rise to 14 C within the defrost duration time limit (30 or 45 minutes), the controller terminates defrost. The evaporator then returns
to operation based on controller demand.
Electric Operation
Continuous Mode without Modulation
• Cool
• Null1
• Hot Gas Heat2
• Full Heat2 (hot gas and electric heaters)
• Defrost (hot gas and electric heaters)
1
Null mode ONLY when the setpoint is BELOW the Fresh/Frozen temperature setting. Exceptions: SB-III SR and SMX SR
with software versions 102, 103 and 201 have Null mode at setpoints above the Fresh/Frozen temperature setting.
2
Null mode if controller setpoint is below the Fresh/Frozen temperature setting.
Continuous Mode with Modulation
• Cool
• Modulated Cool1
• Null2
• Modulated Heat1, 3
• Hot Gas Heat4
• Full Heat4 (hot gas and electric heaters)
• Defrost (hot gas and electric heaters)
1
Modulation valve operation is locked out if controller setpoint is below Fresh/Frozen temperature setting.
2
Null mode ONLY when the setpoint is BELOW the Fresh/Frozen temperature setting. Exceptions: SB-III SR and SMX SR
with software versions 102, 103 and 201 have Null mode at setpoints above the Fresh/Frozen temperature setting.
3
Modulated Heat mode ONLY available on SB-III SR and SMX SR with software versions 102, 103 and 201. Controller
setpoint must be above Fresh/Frozen temperature setting.
4
Null mode if controller setpoint is below the Fresh/Frozen temperature setting.
Modulation
The modulation temperature range is factory set at -9 C to 27 C. The lower limit (-9 C) is adjustable through the keypad to -4C.
However, the upper limit (27 C) can be field adjusted from 27 C down to -4 C or -9 C depending on setting. If the upper limit is
set to -4 C or -9 C, the modulation mode is completely disabled.
The Modulation mode is disabled when the controller setpoint is above or below the modulation temperature range, when the unit
is in Defrost, and when the CYCLE-SENTRY switch is in the CYCLE-SENTRY position (except in CYCLE-SENTRY Fresh
range).
Defrost
Defrost can be manually initiated through the controller keypad, or automatically initiated by the controller defrost timer or
controller Demand Defrost algorithm. A demand defrost occurs when the difference between the return air temperature, discharge
air temperature and evaporator coil temperature becomes excessive.
Defrost can be initiated any time the evaporator coil temperature is below 7 C. If the unit is in Null (on Engine or Electric Standby
Operation), initiating defrost will cause the unit to start and operate. When a defrost cycle is initiated, the controller energises the
damper motor, pilot solenoid, heater contactor and Defrost icon. The controller maintains the In-range signal during defrost.
The unit remains in defrost until the evaporator coil temperature increases to 14 C. If the evaporator coil temperature does not
rise to 14 C within the defrost duration time limit (30 or 45 minutes), the controller terminates defrost. The evaporator then returns
to operation based on controller demand.
SL-400, SLX/SLXe and SLX/SLXe Spectrum (µP-VI, SR-2 and SR-3 Controller)
Operating Characteristics of µP-VI, SR-2 and SR-3 Software
• µP-VI, SR-2, and SR-3 software use complex algorithms to determine the unit operating mode. Therefore you can NOT
predict the unit mode of operation by comparing the setpoint to the return air temperature.
• Different versions of software may provide different control sequences and operating mode switch points.
• The unit always starts in Low Speed. Low speed operation continuous for a minimum of 2 minutes, or until the engine coolant
temperature increases to 10 C.
• The High Speed Pull-Down (HSPD) feature controls unit operation on initial start-up. If HSPD is set to [YES], the unit
operates in High Speed (after engine warm-up) until setpoint is reached on initial unit start-up. The unit them operates in low
speed or high speed as required by the controller. Factory HSPD setting is YES.
• When the setpoint is below the Fresh/Frozen (FRFZ) temperature, High Speed Heat (or all Heat) is locked out. The Fresh/
Frozen temperature is factory set at -4 C, but may be field programmed to -4 C or -9 C.
• The Economy mode feature controls the CYCLE-SENTRY Null Range setting during CYCLE-SENTRY operation; or the
Low Speed Switch Point during Continuous Run operation. The CYCLE-SENTRY Null Range default setting is 5.6 C, but
may be field programmed from 2.8 C to 11.2 C. The Low Speed Switch Point default setting is 5.6 C, but may be field
programmed from 1.7 C to 8.4 C.
• OptiSet™ settings will determine all variable operating features for each setpoint or setpoint range programmed in
the controller.
• All units feature an electronic throttling valve (ETV) that provides a modulation cool mode as standard when the controller
setpoint is above the Fresh/Frozen temperature setting.
• When the return air temperature is within several degrees of setpoint, an In-range icon will appear in the LED display.
• During Defrost mode, unit operates in Low Speed Heat only.
• When the unit is in Null on electric standby operation, the drive motor and compressor do NOT operate.
• Controller defrost timer intervals are factory set for 4 hours when compartment temperature is out-of-range; and for 6 hours
when compartment temperature is in-range.
CYCLE-SENTRY Mode1, 2
• High Speed Cool3
• Low Speed Cool3
• Null4
• Low Speed Heat5
• High Speed Heat5
• Defrost
1
ETV operation is locked out during CYCLE-SENTRY operation.
2
If engine temperature, battery condition or defrost initiation requires unit start-up during Null mode, unit starts and operates
in Low Speed Heat or Low Speed Cool.
3
After initial unit start-up and unit pull-down to setpoint, the controller limits Low Speed Cool operation when the controller
setpoint is below Fresh/Frozen temperature setting. On increasing compartment temperature, the unit operates in Low Speed
Cool for a maximum of 8 minutes in an attempt to reach setpoint. If setpoint is not reached within 8 minutes, the unit will
operate in High Speed Cool until setpoint is reached.
4
Unit mode is Null when the engine temperature and battery are satisfied.
5
Null mode if setpoint is below Fresh/Frozen temperature setting.
Modulation
The modulation temperature range is factory set at -9 C to 27 C. The lower limit (-9 C) is adjustable through the keypad to -4C.
The upper limit (27 C) can be field adjusted from 27 C down to -9 C. Ito -4 C or -9 C depending on setting. If the upper limit is
set to -4 C or -9 C, the modulation mode is completely disabled.
The Modulation mode is disabled when the controller setpoint is above or below the modulation temperature range, when the
unit is in Defrost, and when the CYCLE-SENTRY switch is in the CYCLE-SENTRY position (except in Cycle-Sentry Fresh
range).
Defrost
Defrost can be manually initiated through the controller keypad, or automatically initiated controller defrost timer or
controller Demand Defrost algorithm. A demand defrost occurs when the difference between the return air temperature,
discharge air temperature and evaporator coil temperature becomes excessive.
Defrost can be initiated any time the evaporator coil temperature is below 7 C. If the unit is in Null (on Engine or Electric
Standby Operation), initiating defrost will cause the unit to start and operate. When a defrost cycle is initiated, the controller
energises the damper motor or solenoid, pilot solenoid, heater contactor and Defrost icon. The controller maintains the
In-range signal during defrost.
The unit remains in defrost until the evaporator coil temperature increases to 14 C. If the evaporator coil temperature does not
rise to 14 C within the defrost duration time limit (30 or 45 minutes), the controller terminates defrost. The evaporator then
returns to operation based on controller demand. In this case the unit will generate an alarm.
This description is to be used in conjunction with the Diesel Mode block flow chart.
When the unit requires initial start-up in Diesel mode, power is provided through the On/Off switch and On key. The
Microprocessor will review the inputs from the Setpoint, and the Engine temperature.
If in a Null mode then the microprocessor will re-start based on Setpoint, Engine temperature, battery voltage and defrost input.
To allow the unit to enter Null the Setpoint must be satisfied, Engine temperature must be above the predetermined level, Battery
must be fully charged and the unit not in defrost.
The below description of operation is a guide to understand the basic operational sequence of the automatic start sequence and
Cycle Sentry operation.
Note: Because Thermo King Microprocessors are programmable some functionality may change as a result of this
programming, therefore this is a guide to units that are set at factory default settings.
Operation
When the unit requires start up power the Microprocessor activates the components as follows.
1. The Pre-Heat relay is energised to power the Intake heater or glow plugs for the pre-determined time based on engine
temperature. The colder the engine the longer the Pre-Heat time, but this should not exceed 2 minutes.
2. After the proper Pre-Heat time has elapsed, approximately 3 seconds before engine cranking occurs, the Run Relay is
energised. The Run relay energises and feeds power to the hold in coil of the Fuel Solenoid. The Run Relay also makes ready
other unit circuits for operation.
3. After proper Pre-Heat time and approximately 3 seconds after the Run Relay energised the Starter Relay is energised. The
Starter Relay feeds power to the Starter Solenoid and the starter is engaged, the engine starts cranking. As soon as the starter
relay is energised the Microprocessor initiates a 30 second maximum cranking timer, so if the engine fails to start the starter
is disengaged.
4. When the starter cranks the engine, the RPM Sensor produces a signal indicating cranking or running has occurred.
5. The cranking signal must be above 50 RPM within 4 seconds. If not an alarm code 17 is generated indicating that the engine
failed to crank.
6. The running signal must be above 600 RPM for Trailer and 800 RPM for Truck. If not, after the 30 seconds cranking time,
and providing a cranking signal (50 RPM) was recognised by the Micrprocessor, an alarm code 20 is generated indicating that
the engine failed to start.
7. Once the running signal is above the required RPM the Microprocessor de-energises the Pre-Heat and Starter Relays.
The engine remains running. If the unit is in Cycle Sentry mode it will continue to run until all of the following has occurred.
1. Box temperature is satisfied
2. Engine temperature is above 32 C for Trailer and 49 C for Truck
3. Unit is not in defrost
4. The battery is above the setting of CSBV (Cycle Sentry Battery Voltage) and the charge rate is at the CSA (Cycle Sentry
Amps) setting.
Note: The Unit will remain running in Cycle Sentry until the following occurs:
This description is to be used in conjunction with the Standby Mode block flow chart.
When the unit requires initial start-up in Standby mode, power is provided through the On/Off switch and On key. The
Microprocessor will review the inputs from the Setpoint, and the PSM [Phase Selection Module].
If in a Null mode then the microprocessor will re-start based on Setpoint, battery voltage and defrost input.
To allow the unit to enter Null the Setpoint must be satisfied, Battery must be fully charged and the unit not in defrost.
The below description of operation is a guide to understand the basic operational sequence of the automatic start sequence and
Cycle Sentry operation.
Note: Because Thermo King Microprocessors are programmable some functionality may change as a result of this
programming, therefore this is a guide to units that are set at factory default settings.
Operation
When the unit requires start up power the Microprocessor activates the components as follows.
1. The PSM receives an On signal from the Microprocessor
2. The PSM at this time must see 180 VAC on all three phases for a minimum of 2 to 4 seconds. A signal is then sent from the
PSM to the Microprocessor on the ER circuit.
3. If not an alarm code 91 will be generated indicating that the electric ready input was not initiated.
4. Once the ER signal is received by the Microprocessor the Pre-Heat Buzzer is energised to warn the operator the Electric motor
is about to start.
5. After the Buzzer time has elapsed and approximately 3 seconds before the K5 Diesel/Electric Relay is energised, the Run
Relay is energised. The Run relay energises and feeds power to the hold in coil of the Fuel Solenoid. The Run Relay also
makes ready other unit circuits for operation.
6. After proper Pre-Heat time, and approximately 3 seconds after the Run Relay energised, K5 Diesel/Electric Relay is
energised. The K5 Diesel/Electric Relay provides a 12vdc signal to the PSM for Motor Contactor power.
7. The PSM decides which Motor Contactor to energise (MC1 or MC2) based on the input sequence of L1, L2 and L3.
8. Once the Motor Contact is energised and the Electric Motor is running the Microprocessor checks the output signal from the
Alternator. The alternator provides a frequency (Hz) signal to the Microprocessor on the W wire. This signal allows the
Microprocessor to determine that the electric motor is running.
9. Approximately 3 seconds after the signal is received from the Alternator on the W wire the Buzzer is de-energised.
The Electric Motor remains running. If the unit is in Cycle Sentry mode it will continue to run until all of the following has
occurred.
1. Box temperature is satisfied
2. Unit is not in defrost
3. The battery is above the setting of CSBV (Cycle Sentry Battery Voltage) and the charge rate is at the CSA (Cycle Sentry
Amps) setting.
Note: The unit will remain running in Cycle Sentry until the following occurs:
NOTE: The following example shows a TCI-3 or SPECTRUM-3 Multi-Temp system for a 3 compartment trailer. The
operation of a, TCI-2 or SPECTRUM-2 system for a 2 compartment trailer is similar.
See refrigeration system diagram on the following page. High pressure refrigerant vapor leaves the compressor and flows through
the open condenser inlet solenoid to the condenser where the refrigerant condenses into high pressure liquid. The liquid
refrigerant flows through the receiver tank into the liquid line.
The LLS liquid line solenoid is open so some of the refrigerant flows through the Zone 1 expansion valve into the Zone 1
evaporator. There liquid refrigerant cools the evaporator as it evaporates into low pressure vapor. The refrigerant returns to the
compressor through the SLCV suction line check valve and the accumulator.
The LLS2 liquid line solenoid is also open so some of the refrigerant flows through the Zone 2 expansion valve into the Zone 2
evaporator. There liquid refrigerant cools the evaporator as it evaporates into low pressure vapor. The refrigerant returns to the
compressor through the SLS2 suction line solenoid, the suction line, the SLCV2 suction line check valve and the accumulator.
The LLS3 liquid line solenoid is also open so some of the refrigerant flows through the Zone 3 expansion valve into the Zone 3
evaporator. There liquid refrigerant cools the evaporator as it evaporates into low pressure vapor. The refrigerant returns to the
compressor through the SLS3 suction line solenoid, the suction line, the SLCV3 suction line check valve and the accumulator.
NOTE: The following example shows a DE-3, TCI-3 or SPECTRUM-3 Multi-Temp system for a 3 compartment trailer. The
operation of a DE-2, TCI-2 or SPECTRUM-2 system for a 2 compartment trailer is similar.
See refrigeration system diagram on the previous page. The condenser inlet solenoid is closed so high pressure refrigerant vapor
leaves the compressor and flows through the hot gas line and the open HGS3 hot gas solenoid to the Zone 3 evaporator. There
the refrigerant heats the evaporator and condenses into high pressure liquid. Because the SLS3 suction line solenoid is closed,
the liquid refrigerant flows through the LRCV3 liquid return check valve and liquid line to the LLS and LLS2 liquid line
solenoids.
The LLS liquid line solenoid is open so the refrigerant flows through the Zone 1 expansion valve into the Zone 1 evaporator.
There the liquid refrigerant cools the evaporator as it evaporates into low pressure vapor. The refrigerant returns to the compressor
through the SLCV suction line check valve and the accumulator.
The LLS2 liquid line solenoid is open so the refrigerant flows through the Zone 2 expansion valve into the Zone 2 evaporator.
There the liquid refrigerant cools the evaporator as it evaporates into low pressure vapor. The refrigerant returns to the compressor
through the SLS2 suction line solenoid, the suction line, the SLCV2 suction line check valve and the accumulator.
Defrost
Defrost can be manually initiated, or automatically by the controller defrost timer or controller Demand Defrost algorithm. A
demand defrost occurs when the difference between the return air temperature, discharge air temperature and evaporator coil
temperature becomes excessive.
Defrost can be initiated any time the evaporator coil temperature is below 7 C. When a defrost cycle is initiated, the controller
energises the damper motor or solenoid, or turns the remote evaporator fan off. The host unit operates in low speed when a zone
is in Defrost.
The unit remains in defrost until the evaporator coil temperature increases to 14 C. If the evaporator coil temperature does not
rise to 14 C within the defrost duration time limit (30 or 45 minutes), the controller terminates defrost. The evaporator then returns
to operation based on controller demand.
Use this sight glass to check the level of refrigerant in the receiver tank. See the Refrigeration Maintenance
Chapter for the correct procedure.
9
1
2
10
3
4
11
5
6
12
7
13
14
8
15
1. Coil Temperature Sensor (Ungraded) 6. Variable Blower (12 V) 11. Terminal Board Markstrip
2. Hot Gas Solenoid 7. Blower Housing 12. Drain Heater (Resistance Wire)
3. Liquid Solenoid 8. Blower Cover 13. Return Air Sensor (Graded)
4. Suction Line Solenoid 9. Terminal Board Bracket 14. Sensor Clamp
5. Discharge Air Sensor (Graded) 10. Terminal Board 15. Coil Sensor Delay Pad
SPECTRUM S-3 Evaporator Components
UNIT OPERATION
The remote evaporator cycles between cool, null and heat to maintain the trailer’s compartment(s) at the setpoint. The
operating modes include Cool, Null, Heat, and Defrost.
Power to run the direct current fan motors is supplied by the alternator in the host unit.
When cooling is required, the SR-2 MT Control System energizes the remote liquid line solenoid valve. Refrigerant flows
through the evaporator coil to provide cooling.
When the compartment temperature is near setpoint, the SR-2 MT Control System de-energizes the remote liquid line solenoid
valve and switches the remote evaporator to null.
The SR-2 MT Control System energizes the remote hot gas solenoid when the remote compartment requires heat or defrost.
Defrost
The Defrost mode can be initiated any time the evaporator coil temperature is below 45 F (7 C). Defrost is initiated
automatically by the controller or manually by selecting defrost from the Defrost Prompt Screen for the desired zone.
The evaporator fan stops during defrost. The Defrost mode will continue until the evaporator coil temperature rises to 58 F
(14.5 C), causing the controller to terminate defrost. After Defrost, the evaporator may shift back to Cool, Null or Heat.
Operating Modes
Remote evaporator operating modes are:
• Cool
• Null
• Heat
• Defrost
Unit Features
• Direct Expansion Evaporator Coil
• SR-2 MT Control System with Expansion Module
• 12 Vdc Fan Motor (with low speed start feature)
• Aluminum Housing
• Liquid Line Solenoid
• Hot Gas Solenoid
• Suction Line Solenoid
• Liquid Return Check Valve
Unit Nameplate
SL, Sle, SLX and SLXe: Nameplate is located inside the front access doors on front of unit frame below compressor.
Engine Nameplate
TK 482 and TK 486: Nameplate on rocker arm cover.
Compressor Nameplate
X426 and X430 Compressors: Stamped on end above oil pump.
NOTE: With the On/Off switch (or Zone 1 On/Off switch) in ON position, the following units may start at any time without
prior warning:
• OFF position. The electric control system is de-energised and the unit will not operate.
• SLEEP position (optional with MT µP-IV, µP-V and µP-VI). The unit starts and stops as required to keep the engine warm
and the battery charged.
NOTE: The unit will NOT control temperature in the trailer during Sleep mode operation.
TC, TCI and SPECTRUM MODEL NOTE: A separate ON/OFF switch is provided to energise and de-energise each remote
evaporator.
COOL CYCLE
SENTRY
HEAT
ALARM
DEFROST MODULATION
SETPOINT
A
+
C
▲ ▲
▲ !
SELECT SETPOINT ENTER CODE CLEAR
ALARM
The Unit will start automatically on both Continuous Run and CYCLE-SENTRY operation when the On/Off switch is turned
to ON.
DIESEL/ELECTRIC Switch (Model 50 only). This switch selects diesel or electric operation. To operate the unit with the
switch in the ELECTRIC position, the unit must be connected to an electric power source that has the correct voltage and
frequency.
MANUAL DEFROST Switch. Pressing this switch initiates a defrost cycle. The evaporator coil temperature must be below 7 C
(6 C on units with TG-V controller; 3 C on units with TG-IV controller) before the unit will defrost.
WARNING: With the CYCLE-SENTRY icon ON in controller display and the unit On/Off switch in the ON position, the unit
may start at any time without prior warning.
Diesel Operation:
• CONTINUOUS RUN: Modulation Cool (option) is activated at setpoints above -5 C (-9 C or -4 C on some units). The unit
operates on Cool, Modulation Cool and Null.
• After start-up, the unit operates continuously until the unit On/Off switch is turned off, or a malfunction occurs that causes
a unit shutdown.
THERMOGUARD VI
TEMPERATURE
COOL
CYCLE
1
SENTRY
HEAT ! ALARM
DEFROST ELECTRIC
SETPOINT
▲ ▲ 2
▲
TG-VI Controller
1. LCD Display
2. Keypad
NOTE: Units equipped with a µP-VI controller include the CYCLE-SENTRY mode as standard in the software menu display.
Scroll to the CYCLS screen in the menu display. Then press ARROWS key to select CYCLS YES (CYCLE-SENTRY
operation) or CYCLS NO (Continuous Run operation). Then press the ENTER key to load desired operating mode. The
display will briefly show “LOAD” or “Lod”. The CYCLE-SENTRY icon will appear in the controller display when
CYCLE-SENTRY operation is selected.
NOTE: Units with a MT µP-IV (Except Multi-Temp MT µP-IV), µP-V, µP-VI controller include a CYCLE-SENTRY
Fresh (CSFR) feature. If CSFR is active and the setpoint is within the programmed lockout range, the CYCLE-SENTRY
symbol will flash while the unit is automatically starting. After the unit starts, the CYCLE-SENTRY symbol will disappear
and the unit will operate in Continuous Run.
The engine starts automatically whenever the controller calls for cooling or heating; the engine block temperature decreases to
-1 C; the manual defrost switch, air switch or defrost timer initiates defrost; or the battery voltage drops below the
CYCLE-SENTRY setting (TG-VI, MT µP-IV, µP-V, µP-VI controllers only).
The engine operates until the controller reaches setpoint; the block temperature reaches 32 C; and the battery is sufficiently
charged.
Electric Operation:
• CONTINUOUS RUN. Modulation Cool (option) is activated at setpoints above -5 C (-9 C or -4 C on some units). The unit
operates on Cool, Modulation Cool and Null.
• CYCLE-SENTRY (Auto Start-Stop) (CYCLE-SENTRY icon appears in TG-VI, Multi-Temp MT µP-IV, µP-V or µP-VI
controller). Modulation (option) is disabled unless the CYCLE-SENTRY Fresh (CSFR) feature is active and the setpoint
is within the programmed lockout range. The unit operates on Cool and Null (except when CSFR is active).
CONTROLLER
Set the controller at the required temperature. Adjusting the setpoint lower than required will not make the unit cool faster.
The TG-VI controller is a solid-state, programmable microprocessor that controls all unit functions to maintain the cargo at the
proper temperature. A keypad controls the operation of the microprocessor while operating information appears on a liquid
crystal display (LCD). The TG-VI integrates the following functions: temperature sensors, hourmeters, oil pressure gauge, water
temperature gauge, voltmeter, tachometer, operating mode indicator, and refrigeration system controls.
The MT µP-IV, Multi-Temp MT µP-IV, µP-V and µP-VI controllers are solid-state, programmable microprocessors that control
all unit functions to maintain the cargo at the proper temperature. The Multi-Temp MT µP-IV also controls each remote
evaporator. A keypad controls the operation of the microprocessor while operating information appears on a liquid crystal display
(LCD). The controllers integrate the following functions: temperature sensors, hourmeters, oil pressure gauge, water temperature
gauge, ammeter, voltmeter, tachometer, operating mode indicator, refrigeration system thermostat, diagnostic system, data logger
(optional) and Tracker (optional).
The SR-2/SR-3 controller is a programmable microprocessor that controls all unit functions to maintain the cargo at the proper
temperature. The SR-2/SR-3 integrates the following functions: changing setpoint and operating mode, viewing gauge/sensor and
hourmeter readings, initiating Defrost cycles, viewing and clearing alarms.
1 4
2 5
4
3
Pressing the soft key under each zone allows the setpoint for that zone to be changed. In addition, the soft keys under Zone 2
and Zone 3 are used to turn those zones on and off. Pressing the soft key under MENU accesses the MAIN MENU.
2 4
1 5
NOTE: Zone 1 is always on when the control system is powered up. Zone 1 cannot be turned off using the HMI control panel
menu.
Off Key
Press this key to turn the host unit and Zone 1 off. First the display will briefly show “System is Powering Down -
Please Wait. Press On to Resume”, and then “Off” will appear momentarily. When the power-down sequence is
complete the display will be blank. For more information .
Defrost Key
Press this key to initiate a Manual Defrost cycle. For more information .
Mode Key
Press this key to select CYCLE-SENTRY Mode or Continuous Mode operation if allowed by OptiSet. For more
information .
The four “soft” keys under the display (see Figure ) are multi-purpose keys. Their function changes depending on
the operation being performed. If a soft key is active, the key function is shown in the display directly above the
key. The keys are numbered from left to right, with Key 1 on the far left and Key 4 on the far right.
Typical soft key functions:
•• Zone On/Off and Setpoint Change
•• Menu
•• Next/Back
•• Yes/No
•• +/–
•• Select/Exit
•• Clear/Help
•• Hour Meters/Sensors
•• Gauges
Engine Oil
The engine oil level should be at the FULL mark with the dipstick turned (threaded) into oil pan. Never overfill.
Coolant
The engine coolant must have antifreeze protection to -34 C(-30 F). Alarm Code 37 indicates low coolant. Add coolant in the
expansion tank.
Note: If the cooling system is low and Extended Life coolant (ELC) has been used previously. The system can only be topped
up with ELC, or de-ionised water.
CAUTION: Do not add “GREEN” or “BLUE-GREEN” conventional coolant to cooling systems using
“RED” Extended Life Coolant, except in an emergency. If conventional coolant is added to Extended Life
Coolant, the cooling system will get contaminated and sludge will form, also crutially, the engine could
overheat.
Battery
The terminals must be clean and tight.
Belts
The belts must be in good condition and adjusted to the proper tensions.
Electrical
The electrical connections should be securely fastened. The wires and terminals should be free of corrosion, cracks or
moisture.
Structural
Visually inspect the unit for leaks, loose or broken parts and other damage. The condenser and evaporator coils should be clean
and free of debris. Check the defrost drain hoses and fittings to make sure they are open. Make sure all the doors are latched
securely.
NOTE: With SPECTRUM Multi-Temp applications, Zone 1 is turned on any time the host unit is turned on. Zone 1 is turned
off when the host unit is turned off.
2
1
Press On Key
1. On Key
2. Display
2. The display briefly shows a Thermo King Logo as the display initializes.
NOTE: With extremely cold ambient temperatures it may take up to 15 seconds for the first display to appear.
ARA797
2 1 8
5 6 7
1. Continuous Mode
2. Box Temperature (Zone 1)
3. Setpoint (Zone 1)
4. Cooling (Zone 1)
5. Zone 1 Soft Key
6. Zone 2 Soft Key
7. Menu Soft Key
8. Zone 2 Display
Method 1:
The unit may be operated with each Zone individually set to the same setpoint temperature. For example, each Zone could be
individually set to 35 C. The evaporator in each compartment will then control the temperature in that compartment to the same
35 C setpoint.
NOTE: Using Method 1, it is recommended that the bulkheads that separate each compartment be in place to isolate the
compartments.
Method 2:
If Single Zone Control Mode has been has been enabled in the Guarded Access/Main Menu Configuration menu, the following
will apply.
• Single Zone Control Mode will appear in the Mode Menu only if the Single Zone Control feature has been enabled in the
Guarded Access/Main Menu Configuration menu. IF the feature is enabled then Single Zone Control will appear in the Main
Menu/Mode Menu.
• If Single Zone Control operation is selected then all zones will be forced on and will control to the same setpoint. The Zone
1 sensors are used to determine box temperature.
NOTE: Using Method 2, it is recommended that all bulkheads should be taken down to create one large compartment.
• With the exception of defrost, the operating mode of each zone evaporator(s) will be same when in this mode. Unit control is
based on the temperature sensors of Zone 1.
• If Single Zone Control operation is selected the Single Zone Standard Display provides one soft key labeled Setpoint as shown
in Figure . This allows the setpoint for all zones to be changed simultaneously.
• If Single Zone Control operation is selected the individual zones cannot be turned off. The unit and all zones are turned On
and Off simultaneously using the On and Off hard keys at the left side of the display.
NOTE: If Single Zone Control Mode has been enabled in the Guarded Access/Main Menu Configuration menu, either Single
Zone or Multi Zone control can be selected in the Main Menu/Mode menu. For example, to return to Multi Zone Control
from Single Zone Control, select Multi Zone Control in the Main Menu/Mode menu.
NOTE: When using Single Zone Control Mode on SLX units equipped with ETV (SLX Spectrum ETV and SLXe Spectrum)
the modulation function is disabled.
1 2
Alarm Display
If a unit alarm condition occurs the large Alarm Icon will appear on the Standard Display as shown below.
If an alarm specific to a zone occurs, then a small zone alarm icon will appear next to the affected zone as well. Both Alarm
Icons will be present. Below in Figure the small zone Alarm Icon indicates that an alarm exists specific to Zone 2.
NOTE: If the large alarm icon only appears, then the active alarm(s) are unit level alarm(s). If a zone alarm icon and the
large alarm icon are displayed there is a zone level alarm or a combination of zone level and unit level alarms present.
If an alarm condition (other than a log alarm) is present the Temperature Watch Display will not appear. If an alarm condition
occurs while the Temperature Watch Display is present the display will return to the Standard Display. If the Defrost or Cycle
Sentry keys are pressed the display will return to the Temperature Watch Display after defrost is initiated or the operating mode
is changed.
In the Three Zone Temperature Watch Display the Menu soft key label covers the Zone 3 label as shown below.
If the unit is operating in Cycle-Sentry Mode, the Cycle-Sentry icon will appear near Zone 2 as shown below. If the unit is
operating in Continuous Mode the Cycle-Sentry icon will not be present.
1 2
1. Cycle-Sentry Icon
2. Menu Soft Key Label
NOTE: On early µP-VI controllers, disconnect jumper J13 on the relay board in the control box to service the microprocessor
or disconnect or connect the battery.
DEFROST TERMINATION . Units equipped with a SR-2 or SR-3 controller, defrost initiation and termination are controlled
by an evaporator coil sensor and the controller.
THROTTLING VALVE. This valve is located in the suction line and limits the suction pressure at the compressor. See
“Refrigeration Systems” in the Specifications chapter for normal pressure setting for your specific unit.
NOTE: Refer to the unit wiring diagram or the appropriate Controller Operation and Diagnosis Manual for additional fuse
number and size information.
LOW OIL PRESSURE SWITCH. The low oil pressure switch confirms that the engine oil pressure is within tolerance. If low,
the oil switch will close and the unit will record an alarm.
LOW OIL LEVEL SWITCH. The low oil level switch closes if the crankcase oil level becomes too low. If the switch stays
closed for more than 30 seconds, the controller will shut the unit down and record an alarm.
HIGH PRESSURE CUTOUTS. One or two high pressure cutouts (HPCO) are located in the compressor discharge manifold.
The HPCOs are pressure sensitive switches that open if the discharge pressure becomes excessive.
One switch (HPCO1) opens the circuit to the fuel solenoid which stops the engine during engine operation.
The other switch (HPCO2) (Model 50 Units Only) opens the circuit to the electric motor contactor, stopping the electric motor
during electric operation.
If either switch opens, the unit will shutdown and record an alarm.
HIGH PRESSURE RELIEF VALVE. The high pressure relief valve is designed to relieve excess pressure within the
refrigeration system. The valve is a spring-loaded piston that lifts off its seat when refrigerant pressure exceeds 34.48 +/- 3.45
bar, 500 +/- 50 psi. The valve will reset when the pressure drops to 27.58 bar, 400 psi. The valve could possibly leak refrigerant
after it has relieved excess pressure. Tapping the valve lightly may help the valve reseat and SEAL PROPERLY. The valve is
non-repairable and requires no adjustment. If the valve fails to reseat properly, remove the refrigerant charge and replace the
valve.
The high pressure relief valve is located on a high pressure line near the condenser. The location of the valve directs refrigerant
away from anyone servicing the unit if pressure is expelled from the valve.
OVERLOAD RELAY (MODEL 50). An overload relay protects the standby electric motor. The overload relay opens the
circuit from the motor contactor to the electric motor if the motor overloads (e.g., low line voltage or improper power supply)
while the unit is on electric standby operation. Press the Motor Reset switch to manually reset the overload relay.
EVAPORATOR HIGH TEMPERATURE PROTECTION (Model 50). Units equipped with a TG-VI, MT µP-IV, µP-V,
µP-VI, SR-2or SR-3 controller use the controller and the evaporator coil sensor to provide evaporator high temperature
protection.
PREHEAT BUZZER. The preheat buzzer sounds whenever the unit is starting in either diesel or electric mode operation.This
should warn anyone near the unit that the unit is about to start the diesel engine.
WARNING: The glow plugs (or air heater) do not always preheat before the engine starts.
Unit Operation
ENGINE OIL. The engine oil level should be at the FULL mark with the dipstick NOT threaded into the oil pan. Never overfill.
WARNING: Do not remove the expansion tank cap while coolant is hot.
CAUTION: Do not add “GREEN” or “BLUE-GREEN” conventional coolant to cooling systems using “RED” Extended Life
Coolant, except in an emergency. If conventional coolant is added to Extended Life Coolant, the cooling system will get
contaminated and sludge will form, also crutially, the engine could overheat.
BATTERY. The terminals must be clean and tight and that the battery is mounted securely.
BELTS. The belts must be in good condition and adjusted to proper tension.
ELECTRICAL. The electrical connections should be securely fastened. The wires and terminals should be free of corrosion,
cracks or moisture.
STRUCTURAL. Visually inspect the unit for leaks, loose or broken parts and other damage. The exhaust rain cap (if
fitted)should move freely. The condenser and evaporator coils should be clean and free of debris. Check the defrost drain hoses
and fittings to make sure they are open. The damper in the evaporator outlet must move freely with no sticking or binding. Make
sure all doors are latched securely.
WARNING: With the selector switch in CYCLE-SENTRY (Auto Start Stop) operation (or CYCLE-SENTRY icon ON in
TG-VI, Multi-Temp MT µP-IV, µP-V, µP-VI , SR-2 and SR-3 display) and the unit On/Off switch in the ON position, the unit
may start at any time without prior warning.
NOTE: Fully charged batteries in good condition are essential for reliable unit operation. This is especially true on
CYCLE-SENTRY equipped units in cold weather.
WARNING: After 10 seconds, the units start automatically when On/Off switch is turned to ON:
TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 and SR-3 NOTE: If the controller displays the cool or heat icon but the engine does
not start within 15 seconds, turn the unit On/Off switch to OFF. Check and correct any alarm code conditions. Also check
and correct the engine control circuit and engine for the cause of the failure. Then repeat start procedure.
NOTE: Place each rear compartment (Zone 2, Zone 3) On/Off switch in the ON position to start the remote evaporators
NOTE: Units with a µP-V, µP-VI(Except Multi-Temp MT µP-IV), SR-2 or SR-3 controller include a CYCLE-SENTRY Fresh
(CSFR) feature. If CSFR is active and the setpoint is within the programmed lockout range, the CYCLE-SENTRY symbol will
flash while the unit is automatically starting. After the unit starts, the CYCLE-SENTRY symbol will disappear and the unit
will operate in Continuous Run as long as the setpoint is within the programmed lockout range. The CYCLE-SENTRY light
on the optional remote indicator light assembly will remain on, indicating that the CYCLE-SENTRY switch is in the
CYCLE-SENTRY position.
7. If the engine fails to start, place the unit switch in the OFF position. Determine and correct the cause of the starting failure.
TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 and SR-3 NOTE: If the controller displays the cool or heat icon but the engine does
not start within 15 seconds, turn the unit On/Off switch to OFF. Check and correct any alarm code conditions. Also check
and correct the engine control circuit and engine for the cause of the failure. Then repeat start procedure.
NOTE: Place each remote compartment (Zone 2, Zone 3) On/Off switch in the ON position to start the remote evaporators.
Then set remote compartment setpoint at desired temperature.
1. With the On/Off switch in the OFF position and the high voltage power supply OFF, connect the power receptacle to the
power supply. Make sure the power supply is the proper voltage, amperage and phase.
NOTE: Always turn the electric power supply OFF when handling, connecting, or disconnecting high voltage power cords.
NOTE: Units equipped with an Auto Phase Correction System will automatically adjust to the phase of the power supply.
NOTE: On units equipped with a phase indicator light, check the phase indicator light on control panel (or power receptacle).
If the phase indicator light is ON, the phase of the power supply is WRONG and must be corrected. Use a qualified electrical
repair technician to reverse the power leads on the power plug. First turn OFF the power to the cable. Then remove the socket
and reverse the position of any two power leads on the socket. DO NOT disturb the green ground wire.
CAUTION: Do not start the electric motor until the diesel engine has come to a complete stop, disengaging the clutch.
NOTE: If the controller setpoint is well above or below the compartment temperature, check the overload relay reset button
on the unit to make sure the overload relay has not opened.
TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 and SR-3 NOTE: If the controller displays the cool or heat icon but the electric motor
does not start within 15 seconds, turn the unit On/Off switch to OFF. Check and correct any alarm code conditions. Also check
and correct the electric motor control circuit and electric motor for the cause of the failure. Then repeat start procedure.
NOTE: Place each remote compartment (Zone 2, Zone 3) On/Off switch in the ON position to start the remote evaporators.
Then set remote compartment setpoint at desired temperature.
NOTE: Press OIL PRESS key on MT µP-IV or µP-V controller. Press GAUGES key on µP-VI , SR-2 and SR-3 controller
and scroll to oIL.P. Scroll to oIL screen in the TG-VI menu display.The display will show OK.
Press AMPS key on MT µP-IV, uPV and mPVI controller to display amp reading. Press GAUGES key on SR-2 and SR-3
controller and scroll to AMPS display. The TG-VI controller do NOT include an AMPS menu display.
COMPRESSOR OIL. Compressor oil level should be visible in the sight glass.
REFRIGERANT. Check the refrigerant charge. See Refrigerant Charge in the Refrigeration Maintenance chapter.
OPERATING MODES. Check unit operating modes.
TCI and SPECTRUM MODEL NOTE: Only the zones with the On/Off switch ON will be tested.
c. Press and hold the TK LOGO key for at least 3 seconds (or PRETRIP key on µP-VI). PRE TRIP then appears on the MT
µP-IV, or µP-V or µP-VI display (USC appears on the TG-VI display).
MT µP-IV, µP-V and µP-VI NOTE: Press the TK LOGO key (or PRETRIP key on µP-VI) before the engine starts to perform
a Full Pretrip Test. After the ENTER key is pressed, PRE AMPS appears on the MT µP-IV display, indicating the amps check
is being performed. The amps check continues for several minutes. Then the unit starts automatically and the controller
performs the operating tests.
d. Press the ENTER key while PRE TRIP or USC is displayed. PRE LOAD appears on the MT µP-IV, µP-V or µP-VI display
(Lod appears on the TG-VI display) and the Full Pre-trip/Unit Self Check test starts.
e. When the Pre-trip/Unit Self Check test is complete, the controller displays PASS, CHECK (CHEC) or FAIL. If CHECK
(CHEC) or FAIL occurs, view alarm codes and correct all conditions. Then repeat the Full Pre-trip Test/Unit Self Check
test. The unit should PASS before being released for service.
PRE-COOLING. Adjust the controller to the required temperature setpoint. Allow the unit to operate for one-half to one hour
(longer if possible) before loading the trailer. Pre-cooling removes residual body heat and moisture from the trailer interior and
provides a good test of the refrigeration system.
DEFROST. When the unit has finished pre-cooling the trailer interior, manually initiate a Defrost cycle. This will remove the
frost that builds up while operating the unit to pre-cool the trailer. Defrost cycle should terminate automatically.
TG-VI, µP-V, µP-VI , SR-2 and SR-3 NOTE: A manual defrost function is built into the controller. Press SELECT key
(MODE key on µP-VI) (Manual Defrost key on SR-2/SR-3) to scroll to the dEF screen in the menu display. Then press the
ENTER key to initiate Defrost. The display will briefly show Lod (load) and enter Defrost.
Loading Procedure
1. To minimise frost accumulation on the evaporator coil and heat gain in the trailer, make sure the unit is OFF before opening
the doors. (Unit may be operating when loading the trailer from a warehouse with door seals.)
2. Spot check and record load temperature while loading. Especially note any off-temperature product.
3. Load product so that there is adequate space for air circulation completely around the load. DO NOT block the evaporator
inlet or outlet.
4. Products should be pre-cooled before loading. Transport temperature control units are designed to maintain loads at the
temperature at which they were loaded. Temperature control units are not designed to pull hot loads down to temperature.
TG-VI, MT µP-V AND µP-VI NOTE: A manual defrost function is built into the controller. Press SELECT key (MODE key
on µP-VI) (MANUAL DEFROST key on SR-2/SR-3) to scroll to the dEF screen in the menu display. Then press the ENTER
key to initiate Defrost. The display will briefly show Lod (load) and enter Defrost.
WARNING: Make sure to turn the On/Off switch OFF before opening unit doors or inspecting or working on any part of the
unit.
• • Multi-Temp MT µP-IV or µP-V Controller: The unit may START automatically AT ANY TIME when the On/Off switch
is in the ON position.
CAUTION: The microprocessor On/Off switch (or circuit breaker CB3) MUST be in the OFF position before disconnecting
or connecting the unit battery.
NOTE: Refer to the appropriate Controller Operation and Diagnosis Manual for complete operation and diagnosis
information.
Unit operational information appears on liquid crystal display (LCD). During normal operation, the Standard Display appears on
the screen. Return air temperature (upper display) and setpoint temperature (lower display) is the factory set Standard Display
(this may be changed). Check the symbols (icons) that appear on the display. These symbols identify the operating information
that currently appears.
Multi-Temp MT µP-IV: The Standard Display for each zone automatically alternates on the screen every 10 seconds.
A keypad allows the operator to select information to display and programme unit features including the setpoint temperature. If
no key is pressed for about 10 seconds, the display will return to the Standard Display.
1
14
13
2
12
3
4 11
5
6 8 9 10
1. With the Standard Display on the controller, press and release the SELECT key until CYCLS appears in the upper display.
2. Press the UP or DOWN arrow key until the desired setting shows in the lower display.
• Yes = CYCLE-SENTRY mode
• No = Continuous Run mode
3. When the correct setting shows in the lower display, press the ENTER key to load the new setting in the controller memory.
• “LOAD” will appear in the lower display for a few seconds.
• CYCLE-SENTRY icon appears in the display when CYCLE-SENTRY mode is selected.
• If the ENTER key is not pressed, the operating mode will NOT change and the display will return to the standard display
in about 10 seconds.
NOTE: The Zone On/Off switch must be ON and the evaporator coil temperature must be below 7 C to initiate a Defrost cycle
in the zone you select.
A
+
C
▲ ▲
▲ !
SELECT SETPOINT ENTER CODE CLEAR
ALARM
6 7 8 9 10 11
MT µP-IV, Multi-Temp MT µP-IV and µP-V Keypad
1. HOURS Key
2. OIL PRESSURE Key
3. WATER TEMPERATURE Key
4. AMPS Key
5. TK Key
6. SELECT Key
7. UP Key
8. DOWN Key
9. ENTER Key
10. ALARM Key
11. ALARM CLEAR Key
NOTE: The information and organization of screens displayed by a controller depend on the controller type, software version,
unit model and optional equipment. See the appropriate Controller Operation and Diagnosis Manual for more specific
information.
Prompt Display
dEF1 Zone 1 Defrost mode
CYCLS Continuous Run or CYCLE-SENTRY mode
screen:
Yes = Cycle-Sentry, No = Continuous Run
Zone 2 Zone 2 Standard Display
DEF2 Zone 2 Defrost mode
Zone 3 Zone 3 Standard Display
DEF3 Zone 3 Defrost mode
AMB.T Ambient temperature display
BAT.V Battery voltage display
RPM Diesel Engine RPM
HED.P Discharge (Head) Pressure
TCI and SPECTRUM MODEL NOTE: A remote evaporator must be operating to view information for a specific zone.
1. With the unit operating, press and hold the TK LOGO key until “PrE TRIP” appears in upper display.
2. Press the SELECT key to display “REU” and the software version code.
2. Write down each alarm code that appears. Then correct the cause of each alarm.
NOTE: Turn the Unit On/Off switch OFF to stop unit before inspecting or servicing the unit. Turn the unit Microprocessor
On/Off switch to OFF to service the microprocessor module or disconnect the unit battery. Finally, disconnect the battery to
completely remove 12 Vdc power to the unit for service of the microprocessor relay board and unit controls.
3. To clear the alarms after all problems have been corrected, start the unit. Then press the CODE key to display the alarm again.
4. While the alarm screen is showing, press the CLEAR key. The alarm will clear and the standard display will appear on the
screen. If more than one alarm code is present, repeatedly press the CLEAR key to clear each alarm code individually.
NOTE: Alarms may continue to appear as the unit operates if the alarm condition is not corrected.
WARNING: Units equipped with a Multi-Temp MT µP-IV or µP-V controller start automatically 10 seconds after the Unit
(Zone 1) On/Off switch is turned ON.
NOTE: Press the TK LOGO key before the engine starts to perform a Full CYCLE-SENTRY Pre-trip Test. After the ENTER
key is pressed, PRE AMPS appears on the MT µP-IV display, indicating the amps check is being performed. The amps check
continues for several minutes. Then the unit starts automatically and the controller performs the operating tests.
4. With PrE TRIP in the display, press the ENTER key to start the test.
• “LOAD” will appear in the display for a few seconds.
• The controller then performs a series of unit tests.
• If the ENTER key is not pressed, the operating mode will NOT change and the display will return to the Standard Display
in about 10 seconds.
5. When the Pre-trip Test is complete, the controller displays PASS, CHEC or FAIL. Press any key to clear test results display
from controller.
NOTE: If CHEC or FAIL occurs, view alarm codes and correct all conditions. Then repeat the Unit Self-Check Test. The unit
should PASS before being released for service.
Pre-trip Tests
The controller performs the following checks. Operator attention is not required after the programmable settings have been
displayed.
• Preheat and Start Test: Engine preheats and starts. On Multi-Temp MT µP-IV and µP-V controllers, the TK LOGO key must
be pressed before engine starts to perform Full Pretrip test.
• Display Test: All display segments light at the same time.
• Show Programmable Settings: Controller displays all programmable settings for operator verification.
• RPM Check: Check engine rpm in high and low speed.
• Low Speed Cooling Check: Checks unit cooling performance in low speed.
• Heating Check: Checks unit heating performance.
• Defrost Damper Check: Check damper door operation.
• Low Speed Cooling Check: Second cooling test ensures that unit can cycle between Heat and Cool modes.
• Modulation Check: Checks ability of modulation valve to open and close.
WARNING: Units equipped with THERMOGUARD VI and THERMOGUARD VIb controllers may START automatically
AT ANY TIME when the On/Off switch is in the ON position and the CYCLE-SENTRY icon APPEARS in the TG-VI display
(CYCLS screen in menu display set to YES). Make sure to turn the On/Off switch OFF before opening unit doors or inspecting
or working on any part of the unit.
CAUTION: The Unit On/Off switch MUST be in the OFF position before disconnecting or connecting the unit battery.
NOTE: Refer to the appropriate Controller Operation and Diagnosis Manual for complete operation and diagnosis
information.
Unit operational information appears on liquid crystal display (LCD). During normal operation, the Standard Display appears on
the screen. The Standard Display shows the return air temperature (upper display) and the setpoint temperature (lower display).
A keypad allows the operator to select information to display and programme unit features including the setpoint temperature. If
no key is pressed for about 10 seconds, the display will return to the Standard Display. Check the symbols (icons) that appear on
the display. These symbols identify the operating information that currently appears.
2
9
3 8
4 7
5 6
1 2 3 4 5
TG-VI Keypad
1. SELECT Key
2. UP Key
3. DOWN Key
4. ENTER Key
5. TK Key
NOTE: The coil temperature must be below 7°C and the unit must be operating to initiate a defrost cycle.
• “LOd” (abbreviation for LOAD) will appear in the lower display for a few seconds.
• The defrost symbol will appear in the display when the unit starts the defrost cycle.
• Defrost will terminate automatically.
• If the ENTER key is not pressed, the operating mode will NOT change and the display will return to the standard display
in about 10 seconds.
1. With the unit operating, press and hold the TK LOGO key until “USC” appears in upper display.
2. Press the SELECT key to display “rEU” and the software version code.
1. To display the alarm code, press and release the SELECT key until the alarm screen is displayed.
NOTE: If more than one alarm has been sensed, all alarm codes present will automatically alternate on the screen.
2. Write down each alarm code that appears. Then correct the cause of each alarm.
NOTE: Press the OFF key to stop unit before inspecting or servicing the unit. Turn the unit On/Off switch to OFF to service
the TG-VI microprocessor module or disconnect the unit battery. Finally, disconnect the battery to completely remove 12 Vdc
power to the unit for service of the microprocessor relay board and unit controls.
3. To clear the alarms after all problems have been corrected, start the unit. Then press and release the SELECT key until the
alarm screen is displayed again.
4. While the alarm screen is showing, press the ENTER key. The alarm will clear and the Standard Display will appear on the
screen. If more than one alarm code is present, repeatedly press the ENTER key to clear each alarm code individually.
NOTE: Alarms may continue to appear as the unit operates if the alarm condition is not corrected.
NOTE: Each screen will remain on the display for about 10 seconds. If no other key is pressed, the controller display returns
to the Standard Display.
*These screens can be locked on the display by pressing the ENTER key within 10 seconds. Press any key to unlock the
display.
NOTE: If CHEC or FAIL occurs, view alarm codes and correct all conditions. Then repeat the Unit Self-Check Test. The unit
should PASS before being released for service.
Self-Check Tests
The controller performs the following checks. Operator attention is not required after the programmable settings have been
displayed.
• Preheat and Start Test: Engine preheats and starts.
• Display Test: All display segments light at the same time.
• Show Programmable Settings: Controller displays all programmable settings for operator verification.
• RPM Check: Check engine rpm in high and low speed.
• Defrost Damper Check: Check damper door operation.
• Low Speed Cooling Check: Checks unit cooling performance in low speed.
• Heating Check: Checks unit heating performance.
WARNING: The unit may START automatically AT ANY TIME when the CYCLE-SENTRY symbol is visible in the control
panel display. Make sure to press the ZONE 1 OFF key before opening unit doors or inspecting any part of the unit.
NOTE: Refer to the Multi-Temp MT µP-IV Controller Operation and Diagnosis Manual for complete operation and
diagnosis information on Multi-Temp remote control panel.
NOTE: The Standard Display for each zone automatically alternates on the screen every 10 seconds.
A keypad allows the operator to program the setpoint temperature for each zone.
WARNING: Make sure to turn the On/Off switch OFF before opening unit doors or inspecting or working on any part of the
unit. The unit may START automatically AT ANY TIME when the On/Off switch is in the ON position.
CAUTION: The Controller On/Off switch MUST be in the OFF position before disconnecting or connecting the unit battery.
NOTE: Refer to the appropriate Controller Operation and Diagnosis Manual for complete operation and diagnosis
information.
1
14
13
2
12
3
4 11
5
6 8 9 10
NOTE: If OptiSet has been programmed for CYCLE-SENTRY or Continuous Run, the arrow keys will not change the screen
setting.
3. When the correct setting shows in the lower display, press the ENTER key to load the new setting in the controller memory.
• “LOAD” will appear in the lower display for a few seconds.
• CYCLE-SENTRY icon appears in the display when CYCLE-SENTRY mode is selected.
• If the ENTER key is not pressed, the operating mode will NOT change and the display will return to the standard display
in about 10 seconds.
P
MODE HOURS GAUGES PRETRIP
C
▲ ▲
▲ !
SELECT SETPOINT ENTER CODE CLEAR
ALARM
6 7 8 9 10 11
µP-VI Keypad
1. MODE Key
2. HOURS Key
3. GAUGES Key
4. PRETRIP Key
5. TK Key
6. SELECT Key
7. UP Key
8. DOWN Key
9. ENTER Key
10. ALARM Key
11. ALARM CLEAR Key
The Economy mode can be turned ON or OFF for both CYCLE-SENTRY and Continuous Run operation.
Economy mode extends the length of the Null mode on CYCLE-SENTRY operation. The CYCLE-SENTRY Null Range changes
from 2.8 C to 5.6 C (default setting) when the Economy mode is ON. The CYCLE-SENTRY Null Range can also be adjusted
from 2.8 C to 11.2 C.
The Economy mode extends the Low Speed Cool mode on Continuous Run operation. The Low Speed Switch Point changes
from 2.0 C to 5.6 C (default setting) when the Economy mode is ON. The Low Speed Switch Point can also be adjusted from
1.7 C to 8.4 C.
1. With the Standard Display on the controller, press and release the MODE key until ECOn appears in the upper display.
2. Press the UP or DOWN arrow key until the desired setting shows in the lower display.
• Yes = CYCLE-SENTRY mode
• No = Continuous Run mode
NOTE: If OptiSet has been programmed to determine the Economy mode setting, the arrow keys will not change the screen
setting.
3. When the correct setting shows in the lower display, press the ENTER key to load the new setting in the controller memory.
• “LOAD” will appear in the lower display for a few seconds.
• CYCLE-SENTRY icon appears in the display when CYCLE-SENTRY mode is selected.
• If the ENTER key is not pressed, the operating mode will NOT change and the display will return to the standard display
in about 10 seconds.
NOTE: Each screen will show for 10 seconds if no other key is pressed. These screens can be locked on the display by pressing
the ENTER key within 10 seconds. Press any key to unlock the display.
Prompt Display
TLHR Total Hours
ENHR Engine Hours
ELHR Electric Hours
HRM4 Programmable Hours
HRM5 Programmable Hours
HRM6 Programmable Hours
View GAUGES Display Screens:
1. With the unit operating, press the GAUGES key to display information screens. If no alarms exist, the first screen to appear
will be the WAT.T screen.
2. Repeatedly press the GAUGES key to display additional information screens.
Prompt Display
WAT.T Engine Water Temperature
OIL.P Engine oil Pressure Status
AMPS Battery Current Flow
BATV Battery Voltage
RPM Engine speed
SUC.P Suction Pressure
DIS.P Discharge Pressure
ETV.P ETV Position
View SELECT Display Screens:
1. With the unit operating, press the SELECT key to display information screens. If no alarms exist, the first screen to appear
will be the DIS.A screen.
2. Repeatedly press the SELECT key to display additional information screens.
Prompt Display
DIS.A Discharge Air Temperature
TPDF Temperature Differential
COIL Coil Temperature
AMB.T Ambient Temperature
SPR.1 Spare 1 Sensor Temperature
SPR.2 Spare 2 Sensor Temperature
DAS1 DAS Sensor 1 Temperature
DAS2 DAS Sensor 2 Temperature
DAS3 DAS Sensor 3 Temperature
DAS4 DAS Sensor 4 Temperature
DAS5 DAS Sensor 5 Temperature
DAS6 DAS Sensor 6 Temperature
NOTE: Each display screen will show for 3 minutes if no other key is pressed.
Prompt Display
PrETRIP Pre-trip Prompt Screen
PRNT Print Prompt Screen
REV Software Revision Display
YEAR Current Year
MNTH Current Month
dAY Current Day
DATE Current Day of Month
HOUR Current Time (24 Hours)
MIN Current Time (Minutes)
SOT Start of Trip
1. With the unit operating, press and hold the TK LOGO key until “PrE TRIP” appears in upper display.
2. Press the SELECT key to display “REV” and the software version code.
NOTE: Turn the Unit On/Off switch OFF to stop unit before inspecting or servicing the unit. Turn the unit Microprocessor
On/Off switch to OFF to service the microprocessor module or disconnect the unit battery. Finally, disconnect the battery to
completely remove 12 Vdc power to the unit for service of the microprocessor relay board and unit controls.
3. To clear the alarms after all problems have been corrected, turn the Unit On/Off switch ON. Then press the CODE key to
display the alarm again.
4. While the alarm screen is showing, press the CLEAR key. The alarm will clear and the standard display will appear on the
screen. If more than one alarm code is present, repeatedly press the CLEAR key to clear each alarm code individually.
NOTE: Alarms may continue to appear as the unit operates if the alarm condition is not corrected.
NOTE: The controller automatically starts the unit 10 seconds after the Unit On/Off switch is turned ON.
NOTE: If CHEC or FAIL occurs, view alarm codes and correct all conditions. Then repeat the Full Pre-trip Test. The unit
should PASS before being released for service.
Pre-trip Tests
The controller performs the following checks. Operator attention is not required after the programmable settings have been
displayed.
• Control Component Amps Test: Each electrical control component energizes for a current draw measurement.
• Preheat and Start Test: Engine preheats and starts.
• ETV Check: The electronic throttling valve is checked for correct operation.
• Display Test: All display segments light at the same time.
• Show Programmable Settings: Controller displays all programmable settings for operator verification.
• RPM Check: Check engine rpm in high and low speed.
• Low Speed Cooling Check: Checks unit cooling performance in low speed.
• Heating Check: Checks unit heating performance.
• Defrost Damper Check: Check damper door operation.
• Low Speed Cooling Check: Second cooling test ensures that unit can cycle between Heat and Cool modes.
WARNING: This unit is capable of automatic operation and could start at any time.
The microprocessor On/Off switch must be placed in the Off position ("0") before:
• any inspection, maintenance or service operation is performed on the unit
• the unit is placed in a location where a start-up would be undesirable (for example, a confined area).
The microprocessor on/off switch supplies or removes electrical power to the microprocessor. It is located between the
communication ports on the left side of the Smart Reefer 2 control panel.
WARNING: Make sure to turn the On/Off switch OFF before opening unit doors or inspecting or working on any part of the
unit. The unit may START automatically AT ANY TIME when the On/Off switch is in the ON position.
CAUTION: The Controller On/Off switch MUST be in the OFF position before disconnecting or connecting the unit battery.
NOTE: Refer to the appropriate Controller Operation and Diagnosis Manual for complete operation and diagnosis
information.
1
2 4
5
6
SR-2/SR-3 Controller
1. On Key (Dedicated Key)
2. Off Key (Dedicated Key)
3. Display
4. Defrost Key (Dedicated Key)
5. Mode Key (Dedicated Key)
6. Soft Keys
Off Key
Press this key to turn the unit off.
Defrost Key
Press this key to initiate a Manual Defrost cycle.
The four “soft” keys under the display are multi-purpose keys. Their function changes depending on the operation
being performed. If a soft key is active, it’s function will be shown in the display directly above the key.
NOTE: If the alarm occurred during a Unit Self-Check, it will be preceded by a dash (-).
CAUTION: Full-fielding alternators with the integral regulator is accomplished by installing a jumper from terminal F2 to
ground. Attempting to full-field the alternator by applying battery voltage to terminal F2 will cause voltage regulator failure.
Complete the following checkout procedure before replacing the voltage regulator or the alternator.
• When testing alternators use accurate equipment such as a Thermo King P/N 204-615 (FLUKE 23) digital multimeter and a
Thermo King P/N 204-613 amp clamp or an equivalent.
• Make sure the drive belts and pulleys of the charging system are in good condition and are adjusted properly before testing
the alternator. Worn belts and pulleys or loose belts will lower the output of the alternator.
• The battery must be well charged, the battery cable connections must be clean and tight, and the 2A and excitation circuits
must be connected properly.
NOTE: All voltage readings should be taken between the negative battery terminal, or a good chassis ground, and the
terminals indicated, unless stated otherwise.
CAUTION: Check to make sure the alternator field fuse (F15 on uP-VI and TG-VI, F7 on uP-IV and F4 on SR-2/SR-3) has
been removed from the relay board. If the fuse has not been removed, the voltage regulator has probably been damaged.
1. Set the unit for CONTINUOUS operation and place the main On-Off switch in the OFF position.
2. Check the battery voltage. If the battery voltage is less than 12 volts, the battery must be charged or tested to determine if it
should be replaced.
3. Check the voltage at the B+ terminal on the alternator. Battery voltage must be present. If not, check the 2A circuit.
4. Disconnect the alternator harness from the voltage regulator by carefully pushing on the spring clip to release the plug lock.
5. Set the unit for CONTINUOUS operation and place the main On-Off switch in the ON position.
6. Check the voltage at pin A and pin B in the two pin connector on the alternator harness.
a. The A pin is the battery sense circuit and should be at battery voltage. If not, check the sense circuit (2 or equivalent) in the
alternator harness and in the main wire harness.
b. The B pin is the excitation circuit and should be at 10 volts or higher. If not, check the excitation circuit (7K or equivalent)
in the alternator harness and in the main wire harness.
7. If battery voltage is present on the sense and excitation circuits, connect the alternator harness to the voltage regulator and
check the voltage on the B pin in the two pin connector on alternator harness. The voltage should be 1 to 3 volts.
a. No voltage or a voltage reading below 1 volt indicates that the rotor or the voltage regulator may be shorted. Perform the
field current test to further isolate the problem.
b. A voltage reading above 3 volts indicates that the field circuit may be open or have high resistance. The brushes or the rotor
are probably defective.
CAUTION: DO NOT full field the alternator for more than seven seconds while checking the meter readings, or the electrical
system may be damaged.
12. Check the amperage in the 2A wire and record the reading. Check the voltage at the B+ terminal and continue to observe this
voltage for a few seconds to see if it increases, decreases, or stays the same. Note the change in voltage and record the voltage
reading.
Amperage in the 2A wire =____amps.
Voltage at the B+ terminals =___volts.
The voltage at the B+ terminal should be 13 to 18 volts and the amperage in the 2A wire should be at least as high as the rated
output of the alternator.
NOTE: This assumes that the alternator did not charge properly prior to the full field test.
Alternator Disassembly
1. Remove the pulley and the fan. Remove the nut, lock washer, pulley, fan and the spacer from the rotor shaft.
2. Remove the capacitor.
a. Unplug the wire from the capacitor to the + terminal.
b. Loosen the capacitor mounting screw and remove the capacitor.
3. Remove the brush-regulator assembly.
a. Remove the field (green) wire from the terminal on the alternator.
b. Remove the brush-regulator assembly by removing the two mounting screws.
4. Remove the front housing.
a. Remove the nut, lock washer, flat washer, and isolation washer from the B+ terminal on the alternator.
b. Remove the four screws on the front of the alternator that surround the rotor shaft.
c. Remove the nut, lock washer, and flat washer from the longest of the four through bolts on the alternator.
d. Mark the rear housing, front housing, stator, and the longest through bolt to aid in assembly later.
e. Remove the four through bolts from the alternator.
f. Remove the front housing. (Front housing should slide off the front rotor shaft bearing with minimal force.)
5. Remove the rotor. Support the rear housing and stator. Slide the rotor shaft assembly toward the front of the alternator. This
can be done by hand, but considerable force is needed.
NOTE: The nut can be screwed on the rotor shaft to aid in pulling on the rotor shaft.
CAUTION: Note the position of the isolation washer and the isolation spacer on the B+ terminal.
7. Separate stator windings from the diode plate (only if necessary). Unsolder the three leads of the stator winding from the diode
plate.
Brush Test
1. Remove and replace the O-ring in the bearing bore of the rear housing if needed.
2. Inspect the rear housing for a cracked or broken casting, stripped threads, or evidence of severe wear in the bearing bore due
to a worn rear bearing.
Front Housing
1. Inspect the front housing for cracks. Check the condition of the threads of the adjusting boss.
2. Check the bore in the mounting boss. Discard housing if bore shows signs of elongation (oval or out of roundness).
Brush Test
Continuity:
From A to B
From C to D
No Continuity:
From A or B to C or D
Rotor
1. Place 15 volts dc across the slip rings on the rotor.
CAUTION: Turn off the dc power source before installing or removing test leads on slip rings to prevent arcing and damage
to the slip ring surface.
2. Check the current draw. The draw should be near the appropriate value shown in the following chart.
Strator
The stator assembly consists of three individual windings terminated in the delta-type connections. Using an ohmmeter or test
lamp, check for winding continuity between leads A, B, and C. There should be no continuity from any lead to point D
(laminations). Also, stators showing signs of winding discolouration should be discarded
Alternator Assembly
1. Connect the stator windings to the diode plate.
Solder the three leads of the stator windings to the diode plate if either is to be replaced.
Brush Installation
1. Brush Contacts (Spring Loaded)
CAUTION: Care must be used during installation of brushes to prevent damage to slip rings or brushes.
Alternator Installation
1. Mount the alternator on the bracket. Do not tighten the bolts.
2. Install the alternator drive belt, tension it correctly and tighten the mounting bolts.
3. Install the wires on the alternator terminals and secure them with the nuts.
4. Connect the battery power to the unit.
CAUTION: “Full Fielding” Unlike other alternators a Thermo King alternator it is accomplished by installing a jumper from
terminal F2 to Positive Battery Voltage (+12V). Attempting to full-field the alternator by connecting Ground pin to terminal
F2 will cause regulator failure.
Complete the following checkout procedure before replacing the voltage regulator or the alternator.
• When testing alternators use accurate equipment such as a Thermo King P/N 204-615 (FLUKE 23) digital multimeter and a
Thermo King P/N 204-613 amp clamp or an equivalent.
• Make sure the drive belts and pulleys of the charging system are in good condition and are adjusted properly before testing
the alternator. Worn belts and pulleys or loose belts will lower the output of the alternator.
• The battery must be well charged, the battery cable connections must be clean and tight, and the 2A and excitation circuits
must be connected properly.
NOTE: All voltage readings should be taken between the negative battery terminal, or a good chassis ground, and the
terminals indicated, unless stated otherwise.
NOTE: The alternator field fuse (F15 on uP-VI and TG-VI, F7 on uP-IV and F4 on SR-2/SR-3) must be removed on the relay
board on units equipped with the Prestolite alternator. If this fuse is inserted in the relay board, the alternator will not function
properly.
1. Set the unit for CONTINUOUS operation and place the main On-Off switch in the OFF position.
2. Check the battery voltage. If the battery voltage is less than 12 volts, the battery must be charged or tested to determine if it
should be replaced.
3. Check the voltage at the B+ terminal on the alternator. Battery voltage must be present. If not, check the 2A circuit.
4. Disconnect the alternator harness from the voltage regulator by carefully pushing on the spring clip to release the plug lock.
5. Set the unit for CONTINUOUS operation and place the main On-Off switch in the ON position. If possible, enter Service
Test Mode High Speed Cool (HSC) before the Unit starts. Refer to the appropriate Diagnostic’s Manual for specific
Information on Service Test Mode.
6. Check the voltage at pin A and pin B in the two pin connector on the alternator harness.
a. The A pin is the battery sense circuit and should be at battery voltage. If not, check the sense circuit (2 or equivalent) in the
alternator harness and in the main wire harness.
b. The B pin is the excitation circuit and should be at 10 volts or higher. If not, check the excitation circuit (7K or equivalent)
in the alternator harness and in the main wire harness.
7. If battery voltage is present on the sense and excitation circuits, connect the alternator harness to the voltage regulator.
Note:The Current through the L Terminal must be limited through a 300ohm resistor in the EXC or 7-circuit. (Like the bosch
Alternator). The Alternator will be damaged if +12V is connected directly to the L Terminal.
The Nominal Voltage regulator setting for Thermo King Alternators is 14.15 +/- 0.20 @ 25’C)
Alternator Removal
1. Disconnect the battery power from the unit.
2. Remove the wires from the alternator terminals.
3. Remove the mounting bolts and remove the alternator.
Battery
CAUTION: Before connecting or disconnecting the unit battery:
CAUTION: When Connecting the Battery - connect the positive Battery cable first and then the negative.
CAUTION: When Disconnecting the Battery - disconnect the negative battery cable first and then the positive.
A dead or low battery can be the cause of an ammeter indicating discharge due to lack of initial excitation of the alternator.
NOTE: If the battery was discharged enough that a boost was needed, the alternator may not recharge the battery because
there may not be adequate current to excite the alternator field.
NOTE: Units with TK 486V engines use 0-gauge battery cables to ensure reliable starting in extremely cold weather.
UNIT WIRING
Inspect the unit wiring and the wire harnesses during scheduled maintenance inspections for loose, chaffed or broken wires to
protect against unit malfunctions due to open or short circuits.
FUSE LINK
The fuse link is located in the engine compartment near the battery. The fuse link protects the electric system from a short in the
2 (2P or 2A) circuit. It also protects the electrical system should a circuit breaker fail to open. If the fuse link burns out, check for
a grounded 2 (2P or 2A) wire or a short in the glow plug or alternator circuits. Also check for any condition that would cause a
circuit breaker to open. If a circuit breaker is defective, replace it before replacing the fuse link.
SL, SLe, SLX, SLXe NOTE: Beginning in August 2000 the fuse link is located in the positive battery cable.
NOTE: Refer to the unit wiring diagram or the appropriate Controller Operation and Diagnosis Manual for additional fuse
number and size information.
NOTE: Refer to the appropriate Controller Operation and Diagnosis Manual for more specific relay board information for
your unit.
TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 and SR-3 NOTE: This switch alerts the microprocessor that engine oil level is low.
Shutdown Code 66 occurs after 5 minutes.
Switch Test
1. Make sure that the unit is turned off.
2. Disconnect the switch wires from the main wire harness.
3. Connect a continuity tester to the switch wires at the switch wire connector.
4. Check the oil level with the dipstick and make sure that it is between the low mark and the full mark. Add oil if necessary.
5. The switch should be open and there should be no continuity between the switch wires with the oil level between the low mark
and the full mark on the dipstick.
Bench test the switch if there is continuity between the 20A and CH wires and there are no short circuits in the wires.
2. Remove the push-in style switch by carefully prying it out of the oil pan with a pry bar. The neoprene seal may stay in the oil
pan.
3. To install the push-in style switch, first lubricate the neoprene seal and install it in the oil pan. Then press the switch into the
neoprene seal. No tools are required.
4. Connect the switch wires to the main wire harness after installing it.
Bench Test
1. Disconnect the switch wires from the main wire harness. Remove the switch from the oil pan.
2. Use a small container partially filled with engine oil to check the float. Make sure that it floats in engine oil and that it slides
freely between the upper and lower stops.
3. Slide the float up to the upper stop and check the continuity through the switch (between wire 20A and wire CH). The switch
should be open.
4. Slide the float down to the lower stop and check the continuity through the switch (between wire 20A and wire CH). The
switch should be closed.
5. Replace the switch if the float sinks or does not slide freely, or if the switch does not open and close properly.
The high water temperature switch will close and open the reset switch if the coolant temperature is greater than 104 C. Use a
continuity tester to check the switch. Use a coolant temperature gauge to check the coolant system temperature.
Switch Test
1. Remove wire 20A from the high water temperature switch.
2. Operate the unit until it reaches normal operating temperature of 82 C. There should be no continuity from the switch to
ground.
3. If the engine becomes overheated and reaches 104 C, the switch should have continuity to ground.
4. Replace a defective switch.
Electrical Contacts
Inspect all relay contacts for pitting or corrosion during scheduled maintenance inspections and repair or replace as necessary.
Test the contact points of the contactor by checking the voltage drop across each set of points when the contactor is energised
and the system is operating. If the voltage drop is more than 15 Vac, replace the contact points as a set.
Test the contactor coil by checking the voltage across the coil. The contactor coil should be energised by a minimum of 10 Vdc.
Overload Relay
The overload relay should open if the motor circuit current draw is more than 20 amperes at 380-460 Vac. The overload relay
should open the motor circuit if the current draw is more than 40 amperes at 200-230 Vac.
Phase Indicator
Standard TG-VI model 50 units are equipped with a phase indicator light. This light comes on when the phase of the power supply
is incorrect. Incorrect phase causes the electric motor to spin backwards, which causes the unit’s fans to spin backwards. (MT
µP-IV, µP-V, µP-VI , SR-2 and SR-3 have automatic phase correction).
If the phase indicator light comes on when the unit is connected to an electric power supply, the phase of the power supply must
be corrected. Turn the power off and switch the positions of any two of the power leads in the power cable plug. DO NOT disturb
the green ground wire. This procedure should be performed by a qualified electrical technician.
If the electric motor spins backwards (unit airflow incorrect), but the phase indicator light does not come on:
1. Turn the electric power supply off and check the unit wiring.
a. Wires from the phase indicator module should be connected to the heater contactor terminals as follows: BRN to L1, BLU
to L2, and RED to L3.
b. Wires L1, L2, and L3 should be connected respectively to terminals L1, L2, and L3 on the heater contactor and the motor
contactor.
c. Wires L1, L2, and L3 should be connected respectively to terminals X, Y, and Z in the power receptacle.
2. Disconnect the BLK wires from the phase indicator light, turn the power supply ON, and check the voltage between the two
BLK wires coming from the phase indicator module.
Voltage of approximately 120 volts ac indicates that phase indicator module is acceptable and that the light is probably
defective.
No voltage indicates that the phase indicator module is probably defective if the wiring is correct and the power supply phase
is incorrect.
Defrost Cycle
NOTE: The unit will not defrost during normal unit operation unless the evaporator temperature is below 3 C (TG-IV), 6 C
(TG-V) or 7 C (TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 or SR-3).
TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 or SR-3 NOTE: Defrost initiation and termination is controlled by the microprocessor
using an evaporator coil sensor.
Engine Operation
The Defrost cycle can be initiated by the manual defrost switch, the defrost air switch or the automatic defrost timer when the
defrost termination thermostat is closed.
The initiation of the Defrost cycle energises the defrost relay, pilot solenoid, damper solenoid (or damper motor) and defrost
indicator light.
NOTE: Units with a TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 or SR-3 controller do hot have a defrost relay. The microprocessor
controls the pilot solenoid, damper solenoid (or motor) and the defrost indicator.
The pilot solenoid allows the three-way valve to shift and divert heated refrigerant vapor to the evaporator coil, melting frost. The
damper solenoid (or damper motor) closes the damper in the discharge opening of the evaporator housing to hold the heat within
the evaporator and prevent warm air from passing over the load.
The unit will stay in Defrost until the frost has melted and the evaporator temperature rises above 9 C (TG-IV), 11 C (TG-V) or
14 C (TG-VI, MT µP-IV, µP-V, µP-VI , SR-2 or SR-3).
Internal Defrost Timer (Units with TG-VI, MT µP-IV, µP-V, µP-VI, SR-2or SR-3)
The standard factory settings are 6 hours for in-range defrost intervals and 4 hours for pull down intervals. See the appropriate
Controller Operations and Diagnostic manual for more specific information about programmable defrost intervals.
TG-VI NOTE: The in-range defrost interval is automatically determined by the controller based on the time required to
complete the previous Defrost cycle.
NOTE: See Specifications chapter for unit oil capacity and correct type of oil to use.
3. Operate the unit. Then recheck the oil level. Add oil as necessary to reach the full mark.
CRANKCASE BREATHER
The crankcase breather system ducts crankcase gases formed in the crankcase directly to the intake elbow. Harmful vapours that
would otherwise collect in the crankcase and contaminate the oil or escape to the outside, are now drawn back into the engine
and burned. The breather hose should be inspected to make sure it is not plugged during scheduled maintenance inspections.
,
1 2
7 6 5
Dry Type
A dry element air cleaner filters all of the air entering the engine. Excessive restriction of the air intake system affects horsepower,
fuel consumption and engine life.
SL Units
Replace the dry type element after every 3,000 hours of operation or one year (whichever occurs first).
a. Pour clear water into radiator and allow it to drain out of the block until it is clear.
b. Close the block drain and install a commercially available radiator and block flushing agent. Operate the unit in accordance
with instructions of the flushing agent manufacturer.
c. Open the engine block drain to drain water and flushing solution.
3. Pour clear water into the radiator. Allow it to drain out of the block (and accumulator) until it is clear.
4. Inspect all the hoses for deterioration and the hose clamp for tightness. Replace if necessary.
5. Loosen the water pump belt. Check the water pump bearing for looseness and retighten the belt.
6. Inspect the radiator cap. Replace the cap if the gasket shows any signs of deterioration.
7. Mix 4 litres of permanent type antifreeze and 4 litres clean water in a container to make a 50/50 mixture. (Do not add
antifreeze and then add water to the unit. This procedure may not give a true 50/50 mixture because the exact cooling system
capacity may not always be known.)
8. Close all drains and refill the radiator with the 50/50 antifreeze mixture. Make sure all air is bled from the cooling system.
CAUTION: IF YOU SUSPECT THAT AIR IS TRAPPED IN THE BLOCK, DO NOT START THE ENGINE WITHOUT
BLEEDING THE AIR OUT OF THE BLOCK.
NOTE: If an engine operates with air trapped in the block, the engine may be damaged. The high water temperature switch
may not protect an engine that has air trapped in the block.
Engine Thermostat
For best engine operation, always use a 82.0°C thermostat.
For TK 486V engine operation, always use a 71.0°C thermostat.
Engine Thermostat
1. Jiggle Pin
2. Install This End Toward Engine
TK 486 Engine
1. In-Line Injection Pump
TK 486V Engine
1. Mono- Plunger and Distributor Injection Pump
The injection pump camshaft is driven at one end by the engine timing gears. The cam lobes actuate the plungers, forcing fuel
through the injection nozzles. A governor assembly is connected to the other end of the injection pump camshaft. The governor
meters the amount of fuel delivered to the injection nozzles by controlling the position of the plungers.
NOTE: The injection nozzles should be tested every 9,000 when only clean fuel is used and the fuel system is maintained
according to the Maintenance Inspection Schedule. Refer to the appropriate Engine Overhaul Manual for injection nozzle
testing and repair.
Whenever the fuel system is opened, take the following precautions to prevent dirt from entering the system:
• Cap all fuel lines.
• Work in a relatively clean area whenever possible.
• Complete the work in the shortest possible time.
Any major injection pump or nozzle repairs should be done by a quality diesel injection service shop. The necessary service
equipment and facilities are not found in most engine rebuild shops because of the large investment required.
The following procedures can be done under field conditions:
• Bleeding air from the fuel system
• Fuel tank and filter system maintenance.
• Prime pump (hand) replacement or repair ( TK 482, TK 486 and TK 486V engines)*
• Transfer pump replacement or repair ( TK 482, TK 486 and TK 486V engines)*
• Injection line replacement*
• Pump and governor adjustments ( TK 482, TK 486 and TK 486V engines)*
• Pump timing
• Nozzle spray pattern testing and adjustment*
• Minor rebuilding of nozzles*
*TK 482, TK 486 and TK 486V Overhaul Manual TK 8312.
NOTE: MAKE SURE to keep the fuel tank vent open. If the vent becomes clogged, a partial vacuum develops in the tank. This
increases the tendency for air to enter the system.
3
4
7 5
A single element fuel filter/water separator is used on all engines. Two orifices in the filter head control the pressure in the fuel
system by allowing a certain amount of fuel to return to the tank. One orifice is located in the center of the filter head bleeds off
water and returns it to the fuel tank. The other orifice is located off-center on the filter head and bleeds off air. Replace the single
element fuel/water separator filter every 3,000 hours.
1. Unscrew the filter using a strap wrench. Drain filter and properly dispose of fuel and filter.
2. Fill the new filter with clean fuel through one of the small openings in the top of the filter body. Do not use the center hole to
add fuel to the filter or unfiltered fuel may reach the injection pump. Filling the filter with fuel purges air from the filter.
3. Clean the filter head seal surface. Lubricate filter seal with clean fuel.
4. Install and tighten the filter until it is hand-tight. Then tighten 1/4 turn more using a strap wrench.
High Speed
1. Start the unit and check the high speed rpm.
2. Shut the unit off.
3. Remove the ball joint from the eye bolt in the high speed solenoid.
4. Remove the boot from the high speed solenoid.
5. Pull the plunger out of the solenoid enough to loosen the jam nut. An Allen wrench placed in the hex opening in the face of
the plunger will keep the plunger from turning. Turn the plunger eye bolt clockwise to increase the speed and counter
clockwise to decrease the speed.
6. Replace the ball joint, start the unit and check the speed. When the speed is correct, tighten the jam nut and replace the
solenoid boot.
NOTE: If the correct speed cannot be set close enough with half turns of the eye bolt, use the Allen wrench to turn the
plunger in smaller increments.
Low Speed
1. Loosen the jam nut on the low speed adjustment screw.
2. Operate the unit in low speed. Adjust the screw to obtain the correct speed.
3. Tighten the jam nut and recheck the speed.
NOTE: On units with a TK482, TK 486 or TK 486V engine, the unit may be restarted immediately.
If you suspect that the engine does not operate because the fuel solenoid is not operating correctly, use the following procedure:
1. Disconnect wire 8S from the starter solenoid.
2. Disconnect the fuel solenoid wire connector from the main wire harness.
NOTE: For SL-400, SL-400e and all SLX/SLXe modeks, refer to the relevant operation and diagnostic’s manual.
NOTE: The pull-in coil may draw 35 to 45 amperes so do not leave the jumper connected to pin 8DP for more than a few
seconds.
a. If the pull-in coil does not energise, check the resistance of the pull-in coil by placing an ohmmeter between 8DP circuit
and the CH circuit in the connector on the fuel solenoid. The resistance of the pull-in coil should be 0.2 to 0.3 ohms. If the
resistance of the pull-in coil is not in this range, replace the fuel solenoid.
NOTE: If the pull-in coil fails, make sure to replace the fuel solenoid relay with the correct relay (Potter-Brumfield relay P/N
44-9111 on older models). Refer to unit parts manual.
c. De-energise the hold-in coil by removing the jumper from the 8D circuit and terminal 2. The fuel solenoid should make a
definite click when the hold-in coil is de-energised.
d. If the hold-in coil does not function properly, check the resistance of the hold-in coil by placing an ohmmeter between the
8D circuit and the CH circuit in the connector to the fuel solenoid. The resistance of the hold-in coil should be 24 to 29
ohms. If the resistance of the hold-in coil is not in this range, replace the fuel solenoid.
e. If the hold-in coil does function properly, go to step 10.
9. Reconnect the main wire harness connector to the fuel solenoid connector.
10. Remove the fuel solenoid relay from its socket and make sure the unit On-Off switch is in the ON position.
11. Check the voltage on the 8D circuit at terminal 85 in the fuel solenoid relay socket.
a. If battery voltage is not present on the 8D circuit, check the 8D circuit and related components for a fault.
b. If battery voltage is present on the 8D circuit, go to step 13.
NOTE: The fuel solenoid must be energised when it is being installed. If it is not, the plunger and the linkage may not line up
correctly. Then the fuel solenoid will not function properly.
4. Place the O-ring in the groove in the end of the fuel injection pump. Make sure that the O-ring is positioned correctly during
installation to avoid damage and leaks.
5. Install the new fuel solenoid.
6. Turn the unit OFF.
NOTE: The injection timing mark is a line scribed in the flywheel approximately 35 mm from the TC mark. The injection
timing mark has no identification markings.
The engine now has the No. 1 cylinder at the fuel injection mark of its compression stroke.
2. Before installing the pump, rotate the gear until the “O” marked on the gear is approximately in the 10 o’clock position as
you face the gear end of the pump.
3. Remove the access cover from the timing gear cover.
4. Install the pump in the engine, lining up the “O” with the timing mark cast into the access hole
5. Install and torque the injection pump mounting bolts.
6. Remove the 8 mm bolt located at the back of the injection pump in the middle of the injection lines. Install the special dial
indicator, P/N 204-589 in its place. Make sure the adapter bottoms out tightly on the pump housing. Insert the dial indicator
into the adapter until the dial indicator contacts the pump plunger. Preload the dial indicator at least 2.0 mm and lock the dial
indicator in place by tightening the locking collar.
7. Rotate the engine backwards, counter clockwise from the front, to approximately 89 mm from the TC mark on the flywheel.
8. Adjust the dial indicator to zero. The pump plunger should be at the bottom of its stroke. To check this, rotate the engine back
and forth no more than 13 mm. The dial indicator should stay at zero.
NOTE: The injection timing mark is a line scribed in the flywheel approximately 35 mm from the TC mark. The injection
timing mark has no identification markings.
10. The dial indicator should now show the pump plunger is at 0.5 mm from the bottom of its stroke and ready to inject fuel.
11. If the timing position is not correct, loosen the 3 (or 2) bolts on the front flange of the pump.
12. If the dial indicator shows a figure larger than 0.5 mm, rotate the top of the pump away from the engine until the dial indicator
reads the correct value. A figure less than 0.5 mm requires the pump be turned in towards the engine until the correct value
is reached. Tighten the three bolts and lock the pump in position.
13. Perform a final check by turning the engine backwards, counter clockwise from the front, beyond the injection timing mark
and then clockwise back to the injection timing mark. The dial indicator should now read 0.5 mm. Slight adjustments may be
necessary.
14. Remove the dial indicator and replace the 8 mm timing bolt.
WARNING: Loosen all of the injection lines at the injection nozzles to prevent the possibility of the engine firing while it is
being rotated.
3. Remove the injection line for the number one cylinder from the injection nozzle and from the delivery valve on the injection
pump.
NOTE: The number one cylinder is the cylinder at the flywheel end of the engine.
NOTE: Disconnect the 8S wire from the starter solenoid to prevent the engine from cranking. Otherwise, units with
Cycle-Sentry or MT µP-IV, µP-V, µP-VI, SR-2 and SR-3 controllers may start at any time when the unit On/Off switch is ON.
b. If the engine is not in the unit, use jumper wires to energise the fuel solenoid at the three pin fuel solenoid connector. Place
a jumper between the black wire (CH wire, pin C) and the negative terminal of a 12 Vdc power source. Place a jumper
between the red wire (8D wire, pin A) and the positive terminal of a 12 Vdc power source. Then momentarily place a jumper
between the white wire (8DP wire, pin B) and the positive terminal of a 12 Vdc power source.
CAUTION: Do not leave the jumper on the white wire (8DP wire, pin B) more than a few seconds or the fuel solenoid will be
damaged.
7. Rotate the engine backwards (counter clockwise viewed from the water pump end) until the injection timing mark is
positioned in the bottom of the timing mark access hole. The injection timing mark is a horizontal line stamped on the flywheel
approximately 30 mm (1.2 in.) before the top dead center mark.
8. Pump the priming pump by hand a few times, or energise the electric fuel pump if an electric fuel is being used.
9. Use a clean towel to remove the fuel from the top end of the delivery valve holder.
10. Slowly turn the engine in the normal direction of rotation until you see the fuel rise in the end of the delivery valve holder.
Stop as soon as you see the fuel rise.
11. Check position of the timing marks. The injection timing mark on the flywheel should be aligned with the index mark on the
side of the timing mark access hole. Repeat steps 8 and 12 to recheck the timing.
12. If the timing is off by more than 1 degree (2.5 mm), loosen the mounting nuts on the studs that fasten the injection pump to
the engine and rotate the injection pump to change the timing.
a. Pull the top of the injection pump away from the engine to advance the timing.
b. Push the top of the injection pump toward the engine to retard the timing.
13. Tighten the injection pump mounting nuts and recheck the timing. Repeat steps 8 through 14 until the timing is correct.
14. Install the cover in the timing mark access hole, install the injection line for the number one cylinder, install the rocker arm
cover, and tighten the other injection lines when finished with the procedure.
2. Clean the area with brake cleaner or something similar. Place an injection angle sticker on the gear case so the center line on
the sticker is aligned with the index mark on the injection pump. An injection angle sticker is provided with the new injection
pump.
3. Remove the old injection pump. Use the injection pump gear tool P/N 204-1011 to remove injection pump gear without
removing timing gear cover.
NOTE: Remove the injection pump gear by removing the nut and lock washer that secure the injection pump gear assembly
to the injection pump shaft. The injection pump gear assembly is made of three pieces; the flange, the gear, and the transfer
pump cam. Do not loosen or remove the four bolts that fasten the gear to the flange because that changes factory-set timing
and the EPA certification would void.
4. Record the injection angle marked on the old injection pump. The injection angle mark is located on the side of the pump
facing the engine. The injection angle mark on the pump does not use a decimal point. Add a decimal point before the last
digit of the injection angle mark. (sample: number 67 equals an injection angle of 6.7 degrees.
5. Record the injection angle marked on the side of the new injection pump.
6. Calculate the injection angle difference by subtracting the injection angle of the old from the new injection pump.
Examples
Injection Angle of New Injection
Pump (Degrees) 8.5 6.1
- Injection Angle of Old Injection
Pump (Degrees) -6.7 -6.7
= Injection Angle Difference
(Degrees) =+1.8 =-0.6
7. Install the new injection pump on the gear case and position it so the index mark on the injection pump is aligned with the
mark equal to the injection angle difference on the injection angle sticker. Tighten the injection pump mounting nuts when
the index mark is aligned as necessary with the injection angle sticker.
8. Install the injection pump gear, lock washer, and nut. torque the nut to 78 to 88 Nm.
NOTE: If the timing gear cover was removed to remove the injection pump gear, make sure the timing marks on the timing
gears are aligned. It helps to install the idler gear last when aligning the timing marks.
CAUTION: Loosen all of the injection lines at the injection nozzles to prevent the possibility of the engine firing while it is
being rotated.
3. Place the engine at top dead center of the compression stroke for the number one cylinder.
a. Rotate the engine in the normal direction of rotation (clockwise viewed from the water pump end). Rotate the engine until
the 1-4 timing mark on the flywheel lines up with the index mark in access hole.
b. Check the rocker arms on the number one cylinder.
c. If the rocker arms are loose, the engine is at top dead center of the compression stroke for the number one cylinder.
d. If the rocker arms are tight, the engine is at top dead center of the exhaust stroke for the number one cylinder. Rotate the
engine 360 degrees to place the engine at top dead center of the compression stroke for the number one cylinder.
4. Check the valve clearance of both valves for the number one cylinder with a feeler gauge. The clearance for both the intake
and exhaust valve should be 0.15 to 0.25 mm.
NOTE: Check to make sure that the valve stem cap is in good condition and is positioned squarely on the top of the valve stem.
Replace the valve stem cap if it shows significant wear.
5. Loosen the lock nut and adjust the valves as required by turning the adjustment screw.
6. Hold the adjustment screw while tightening the lock nut.
7. Recheck the valve clearance.
8. Place the engine at top dead center of the compression stroke for the number three cylinder.
a. Rotate the engine again in the normal direction of rotation until the 2-3 timing mark on the flywheel lines up with the index
mark in the access hole.
b. Check the rocker arms on the number three cylinder.
c. If the rocker arms are loose, the engine is at top dead center of the compression stroke for the number three cylinder.
d. If the rocker arms are tight, the engine is at top dead center of the exhaust stroke for the number three cylinder. Rotate the
engine 360 degrees to place the engine at top dead center of the compression stroke for the number three cylinder.
9. Check and adjust both valves for the number three cylinder.
Belts should be regularly inspected during unit pre-trip for wear, scuffing or cracking and correct tension.
Correct belt tension is critical for correct unit operation. Belts that are too loose will slip, squeal or whip causing excessive
vibration levels and poor unit performance. Belts that are too tight will put too much strain on the belt fibres and bearings, causing
premature belt and bearing failures.
New belts should be tensioned cold and re-tensioned cold after 10 hours of unit operation.
NOTE: DO NOT attempt to remove or install belts without loosening adjustments. Belts that are installed by prying will fail
prematurely due to internal cord damage.
WARNING: DO NOT jump belts on by cranking the engine. Personal injury may result.
WARNING: CYCLE-SENTRY Equipped Units with the CYCLE-SENTRY switch in the CYCLE position and unit On/Off
switch in ON position, the unit may start operation at any time without prior warning. Switch unit On/Off switch to OFF
position before performing maintenance or repair procedures.
NOTE: On model 30 units, the lower fan belt must be removed to remove the water pump belt.
SL:
1. Remove the bolts on the water pump pulley.
2. Remove the pulley sliding section and remove the belt.
3. Install new belt on the stationary pulley.
4. Replace the sliding pulley section on the pulley. Add or remove shims to adjust the belt tension.
5. Tighten the mounting bolts on the water pump pulley. The belt tension should read 35 on the belt gauge
NOTE: Do not remove or install the belts without loosening the components correctly. Belts that are installed by prying them
over the pulleys are likely to fail.
NOTE: The alternator belt must be removed to remove the upper belt.
1. Loosen the alternator adjustment arm bolts and the alternator pivot bolt. Remove the alternator belt.
2. Loosen the jackshaft adjustment arm bolts and the jackshaft angle pivot bolts.
3. Push on the jackshaft adjustment arm and move the jackshaft toward the back of the unit as far as it will go.
4. Loosen the two bolts that fasten the jackshaft to the jackshaft angle until the threaded ends of these bolts are flush with the
nuts welded on the jackshaft angle. These bolts must be loosened so the jackshaft can be moved enough to remove the belts.
5. Loosen the idler and move it toward the front of the unit as far as possible.
6. Remove the lower belt from the jackshaft pulley, the idler pulleys (if equipped) and from the engine (or electric motor) pulley.
7. Remove the upper belt from the jackshaft pulley, the idler, and the blower pulley.
NOTE: On model 30 units, the lower fan belt must be removed to remove the water pump belt. (SLe and Spectrum SL units
only)
1. Remove the bolts on the water pump pulley. Refer to “Belt Arrangement – SL 30 Models”, or “Belt Arrangement – SL 50
Models” for illustrations of the adjustable water pump pulley.
2. Remove the pulley sliding section and remove the belt.
3. Install new belt on the stationary pulley.
4. Replace the sliding pulley section on the pulley. Add or remove shims to adjust the belt tension.
5. Tighten the mounting bolts on the water pump pulley. The belt tension should read 35 on the belt gauge.
7 8
9
6
10
5
4
3
11
1 2
12
13
204-1078
WARNING: Do not put fingers between the belt and the tensioner assembly.
3. Remove the old belt and install the new belt correctly on the pulleys - taking care over the belt routing
4. Use a 19mm wrench and the pawl release mechanism and carefully release the tensioner assembly checking the belt is
correctly set in the Poly-V Grooves
5. Remove the tensioner tool.
9
6
10
5
4
4
3
2 11
1
12
17
16
13
15 14
SLX, SLXe have both manual and automatic belt adjustment. Additionally it has special procedures to facilitate easy belt
changes.
WARNING: Do not put fingers between the belt and the tensioner assembly.
3. Loosen the sliding pulley centre bolt (5) and push sliding pulley to it’s furthest position.
6 5
1
2
7
4
5 8
6
Installation
1. Install the belt on the clutch pulley through the gap between the clutch and the flywheel.
2. Place the compressor in position and install the mounting bolts.
3. Place the compressor drive belt on the electric motor pulley.
4. Make sure that the belt is properly engaged in the pulley grooves on the clutch and on the electric motor pulley.
5. Turn the adjusting bolt counterclockwise to lower the motor until the target belt tension is achieved.
6. Turn the belt through five revolutions.
7. Measure the belt tension and readjust if necessary.
8. Tighten the adjusting bolt lock nut.
9. Reinstall the two lower electric motor mounting bolts and tighten all six (three each end) electric motor mounting bolts.
5 4
6 7
Set SLXe Engine Belt Tension by setting Centre to centre dimension between tensioning element screws & checking using
checking gauge Service P/N 2041964
Warning: Only use the screws provided with the tensioning system. Use appropriate tools and respect maximum torque to
tighten the screws. The tensioner element must not be cut by contact with any sharp object.
10 9 8
Warning: DO NOT tighten the plate screws (S2) and (S3) to keep the plate movable during the adjustment of the tensioning
system, just make sure the plate screws are in contact with the plate.
c
b d
e
f
a
a. Plate screws d. S4
b. Pivot screw : M14 l 100 mm Torque : 110 Ft.Lb ± 4 Ft.Lb e. S2
c. S3 f. S1
2.Put the electric engine pulley. Position pulley axially using block 2E13011H01
(Service P/N 2041963). (eccentric bkt to pulley 14.3mm or 42.3 from motor surface to
pulley) . Tighten pulley.
3.Move the eccentric plate to the higher position using the square hole of the plate. Fit
the belt on the pulleys and idler. Make sure all the ribs of the belt are in correct
position on the grooved pulleys.
4.Adjust the position of the tensioning system: by using the square hole of the plate, rotate
the arm slowly down and compress the tensioner element until you can fit the gauge tool on
the 2 screw heads of the tensioner.
Warning: The gauge tool must not be locked on the screw heads but must move freely on
and off the head screws. Centre to centre dimension between screws of 136.0mm on
Tensioning Element to be verified by using checking Gauge 2E13012H01 (Service P/N
2041964).
Note: 2E13012H01 is a checking gauge not a setting gauge & should not be used to hold
the dampener in position prior to tightening holding hardware.
5. Once the gauge tool fits perfectly and freely on the screw heads of the tensioner element, remove it and tighten the plate
screws (S2) and (S3) to lock the eccentric plate in that position.
After tightening of the plate screws, check the tensioner centre to centre distance again with the gauge tool and tighten the
screw (S4) to 22 Ft-lb ±2 Ft-lb (30 Nm±3Nm).
Warning: Do not use the tensioning system if the gauge tool does not fit correctly on the tensioner.
S3
S2
S4
NOTE: Do not allow the key to be pushed out of place behind the clutch during clutch installation.
9. Install and tighten the flat washers, lock washers and nuts on the studs.
NOTE: The 8-pin compressor drive hub will only slide onto the coupling pins in one of two positions that are 180 degrees
apart.
10. Reconnect the suction and discharge valves to the compressor if they were removed. Evacuate the compressor. Then backseat
the discharge service valve.
11. Reinstall the compressor drive belts on the electric motor pulley. Readjust the compressor drive belts.
1. Friction Shoe
2. Spring
3. Shoe Shaft
4. Bearings
NOTE: Unbolt the discharge and suction service valves from the compressor to allow more movement of the compressor for
better access to the clutch.
CAUTION: Do not allow the key to be pushed out of place behind the clutch during clutch installation.
19. Install the special washer and the clutch mounting bolt. Torque the clutch mounting bolt to 54 to 68 Nm.
20. Reinstall the compressor drive belts.
21. Reinstall the compressor on the bell housing studs.
NOTE: The 8-pin compressor drive hub will only slide onto the coupling pins in one of two positions that are 180 degrees
apart.
22. Install and tighten the flat washers, lock washers and nuts on the studs.
23. Reconnect the suction and discharge valves to the compressor if they were removed. Evacuate the compressor. Then backseat
the discharge service valve.
24. Reinstall the compressor drive belts on the electric motor pulley.
25. Readjust the compressor drive belts and lower fan belt (electric motor to jackshaft) as described in Belts (Removal,
Installation and Adjustment).
TG-VI, µP-IV, µP-V, µP-VI, SR-2 and SR-3 NOTE: A Service Test mode on these controllers allows technicians to operate
the unit under known conditions while performing diagnosis and service procedures. See the appropriate Controller
Operation and Diagnosis manual for instructions on how to use the Service Test mode.
SERVICE TOOLS
CAUTION: To prevent contamination, use only service tools certified for and dedicated to the refrigerant type and compressor
oil type used in the temperature control system you are servicing. Service tools (i.e., vacuum pump, gauge hoses and
refrigerant recovery equipment) should be dedicated for non-HFC or HFC refrigerants. Residual non-HFC refrigerants or
non-ester based oils will contaminate and damage HFC systems.
See Thermo King Truck and Trailer Diagnosing manual TK 60201-8-OD for additional information
Leak Detection
Leaks can be detected with the use of soap bubbles or a Halogen leak detector such as the GE H10G (P/N 204-712) or GE H10N
(portable model, P/N 204-756).
Compressor Oil
Synthetic compressor oil, P/N 67-404 is required with R-403B.
Polyolester oil (also called ester base oil), P/N 203-413, is required with R-134a , R-404A and R-452A. Because polyol ester oil
has an affinity for moisture, keep it in a closed container and add it as the last step in system repair. Wear rubber gloves when
handling polyol ester oil to prevent possible skin irritation.
Vacuum Pumps
A two-, three- or five-stage vacuum pump is recommended for evacuation. Purging the system with dry nitrogen is recommended
before evacuation.
Because residual refrigerants may remain in used vacuum pumps, a new vacuum pump should be used and dedicated strictly as
a HFC refrigerant pump. Use only recommended vacuum pump oils and change oil after every major evacuation. Because
vacuum pump oils are highly refined to obtain low vacuums, failure to follow these recommendations may result in acidic
conditions that will destroy the pump.
NOTE: Gauge hoses with self-sealing fittings may be removed and re-installed without additional purging if a slight positive
pressure remains in the lines when removed from the unit.
System Clean-up
Existing clean-up devices such as suction line filters and compressor oil filters may be used if they are properly cleaned and new
filters and cartridges are used. All standard petroleum and synthetic compressor oils must be removed from the clean-up devices
to prevent contamination of HFC systems. System failure from contamination will result if non-HFC refrigerants or non-ester
oils are introduced into a HFC system.
Refrigerant Recovery
When servicing an HFC refrigeration system, use only refrigerant recovery equipment approved for and dedicated to HFC
refrigerant recovery.
Additional Information Low Side Pump Down for TCI and SPECTRUM Models
1. Install a gauge manifold at the compressor.
2. Operate all compartments in COOL for 2 to 5 minutes. Then front seat the receiver tank outlet valve and bypass hand valve,
and pump down the low side to a -0.68 to -0.85 bar, 20 to 25 in. Hg vacuum. Turn all compartment On/Off switches OFF.
If the unit pumps down acceptably and then holds at least a , -0.51 bar, 15 in. Hg vacuum for 2 minutes or more, it can be
assumed that the receiver tank outlet valve, the compressor discharge valve plates, the hot gas solenoid, the rear (and center)
hot gas solenoid and the purge valve solenoid (TCI and SPECTRUM models) are sealing properly.
3. Prepare to perform service on the unit’s low side by equalizing the high side and low side pressures.
a. Disconnect the purge valve solenoid wires from the main wire harness (TCI and SPECTRUM models).
b. Keep Zone 1 setpoint adjusted to require COOL and turn the front compartment On/Off switch ON.
c. Adjust the Zone 2 setpoint to require HEAT. Then turn the rear compartment On/Off switch ON for 1/2 second and then
OFF again. The high pressure gauge will indicate a pressure decrease and the low pressure gauge will indicate a pressure
increase when the Zone 2 hot gas solenoid opens.
d. Adjust the Zone 3 setpoint (if so equipped) to require HEAT. Then turn the center compartment On/Off switch ON for 1/2
second and then OFF again. The high pressure gauge will indicate a pressure decrease and the low pressure gauge will
indicate a pressure increase when the Zone 3 hot gas solenoid opens.
e. Adjust the Zone 1 setpoint to require HEAT. Then turn the front compartment On/Off switch ON for 1/2 second and then
OFF again. The high pressure gauge will indicate a pressure decrease and the low pressure gauge will indicate a pressure
increase when the Zone 1 hot gas solenoid opens.
f. Adjust all zone setpoints to require HEAT. Then turn all compartment On/Off switches ON. Equalise the low side pressure
to 0.07 to 0.14 bar, 1 to 2 psi. Then turn all Zone On/Off switches OFF.
NOTE: If the compartment temperatures are high, the hot gas solenoids (Zones 1, 2 and 3) must be energised with a test lead.
If the reading on the gauge manifold’s high pressure gauge increases after the high and low side pressures have been
equalised, the condenser inlet check valve is leaking.
g. Remember to reconnect the purge valve solenoid wires (DE, TCI and SPECTRUM models) to the main wire harness when
the service procedures have been completed.
The compressor oil should be checked when there is evidence of oil loss (oil leaks) or when components in the refrigeration
system have been removed for service or replacement.
NOTE: Use refrigeration compressor oil ONLY. Special polyol ester oil, TK P/N 203-413 is required on R-404A and R-452A
systems.
NOTE: For additional information regarding category regarding category A, B & C for SLX/SLXe, see SLX/ SLXe charging
procedure later in this chapter. For SLXe Spectrum, use Category C.
Note: For Category B unit, close all doors on unit and ensure all unit panels and skins are securely attached.
4. Operate the unit (and all remote evaporators) on Cool until the air in the compartment indicates -18 C. By allowing the
compartment to leak a small amount, you can maintain -18 C.
5. The ball in the sight glass should be floating under the conditions below.
For category B SLX, open doors to view the sight glass and close again
• Discharge pressure reading:
R404A: The discharge pressure gauge should read 19.00 bar, 275 psi.
NOTE: If the discharge pressure is low, raise it by covering a portion of the condenser grille with a piece of cardboard. On
SL and SLe models, the condenser grille is located above the unit control panel. For SLX, SLXe, it is located on the side of
the unit, above the control panel.
NOTE: If there is any doubt about the accuracy of the discharge or compound gauge, check the calibration.
Note: For Category B unit, close all doors on unit and ensure all unit panels and skins are securely attached.
4. As the head pressure is rising, check the receiver tank sight glass.
NOTE: If the ball floats, there is sufficient refrigerant in the unit for that load at that particular compartment temperature.
This test does not determine if the unit contains a full charge of refrigerant.
NOTE: If the ball and liquid level in the sight glass decline during this step, the unit is not overcharged. You do not need to
continue this test.
5. Observe the receiver tank sight glass(es) and the unit’s discharge pressure.
When the discharge pressure decreases approximately 3.45 bar, 50 psi; the ball in the sight glass should move and the liquid
level should decline. When the discharge pressure stabilises, the ball and liquid level will rise to the previous level. If the
liquid level declines during this test, the refrigerant charge is correct.
If the ball does NOT move or liquid level does NOT decline, the unit has an overcharged of refrigerant. Remove refrigerant
to reduce the refrigerant charge.
To remove refrigerant:
1. Connect a gauge manifold set to the receiver tank outlet valve and an approved sealed container.
2. Operate the unit in high speed COOL (and the remote evaporators in COOL).
Note: For Category B unit, close all doors on unit and ensure all unit panels and skins are securely attached.
3. Use a gauge manifold set to pump refrigerant from the receiver tank into the approved sealed container.
4. When the liquid level begins to decline in the receiver tank sight glass (bottom sight glass on two sight glass receiver tank),
close the hand valve on the gauge manifold immediately. Allow the new liquid level in the sight glass to stabilise (1 to
2 minutes).
Note: For Category B unit, close all doors on unit and ensure all unit panels and skins are securely attached.
Note: For Category B unit, close all doors on unit and ensure all unit panels and skins are securely attached.
3. Operate the unit in high speed COOL (and the remote evaporators in COOL).
4. Open the valve on the refrigerant bottle and read the suction pressure on the gauge manifold.
5. Add liquid refrigerant through the suction service valve. Open the gauge manifold low pressure hand valve only enough to
permit suction pressure to increase 1.40 bar, 25 psi. This will meter liquid refrigerant slowly into the low side.
NOTE: For Category B unit, after the first additional 0.25kg is added, all doors should be closed and high speed cool should
be maintained. Proceed as per step 7. Wait 5 minutes. Check refrigerant level by opening doors momentarily.
6. Add refrigerant until the ball 1/4 to 1/3 of the sight glass (bottom sight glass on two sight glass receiver tank). Allow the level
to stabilise (1 to 2 minutes).
• If the refrigerant level is now high, remove refrigerant (see above).
• If the refrigerant level is still low, repeat steps 4 through 6.
• If the refrigerant level is ok, perform a complete refrigerant level check and repeat the overcharge test.
Note: Please take note of your refrigerant type (label on outside of unit), and make sure not to cross-contaminate.
A system has to operate for at least 15 minutes to change the colour of an indicator ring after the moisture content of the system
has been changed. For example, evacuating a system to remove the moisture will not change the colour of the indicator ring until
the system has been recharged and then operated for at least 15 minutes.
Green Dry
Chartreuse Caution
Yellow Wet
Note: Please take note of your refrigerant type (label on outside of unit), and make sure not to cross-contaminate.
The exact quantity of refrigerant charge required will depend on the layout of the refrigeration systemconcerned; therefore,
without this procedure it is difficult to pre-determine the correct charge.
Refrigerant charge levels should be checked by running all zones in high speed cool with all separation walls stowed in the
open position.
Note: Please take note of your refrigerant type (label on outside of unit), and make sure not to cross-contaminate.
5. For Category B unit, close all doors on unit and ensure all unit panels and skins are securely attached.
6. Run unit in high speed cool with a set point of ‐20°C in all zones and with any separation walls stowed in the open position.
Note: Carry out manual defrost of remote evaporators and then host unit evaporator at -15°C to ensure all ice is cleared from
all evaporators.
7. Maintain unit running in high speed cool and check refrigerant level. Cover condenser to raise discharge pressure to
approximately 325psig to 350psig (22 Bar to 23 Bar gauge). Ball in receiver sight glass should be between ⅓ and ½ full, if the
ball is not floating add charge at 0.25kg increments until the ball floats.
8. For Category B unit, after the first additional 0.25kg is added, all doors should be closed and high speed cool should be
maintained. Proceed as per step 7. Wait 5 minutes. Check refrigerant level by opening doors momentarily.
9. If ball is not floating, close doors, uncover condenser and proceed to add more refrigerant according to step 7 until the ball
floats.
10. If the recommended charge level is exceeded by 1kg, this indicates that the unit may now be overcharged and the installation
should be checked for possible problems.
11. Once system is charged and prior to placing the unit into service, ensure the correct refrigerant charge is entered into the
refrigerant charge decal on the frame near the serial plate. This must be filled in so the next technician knows the quantity
required for the system. Please ensure that the installed date information is also entered.
NOTE: It is normal for compressor shaft seals to have a slightly oily film.
Set-up Unit
The Multi-Temp microprocessor must be placed in the Evacuation Test to evacuate and charge the unit. When the microprocessor
is in the Evacuation Test it opens all the normally closed solenoid valves in the refrigeration system. This allows the refrigeration
system to be evacuated properly. Refer to the appropriate Diagnostic Manual for complete information about the microprocessor.
SYSTEM EVACUATION
NOTE: Use the Service Test mode to operate units with a TG-VI, µP-IV, µP-V, µP-VI, SR-2 or SR-3 controller. See the
appropriate Controller Operation and Diagnosis manual for instructions.
NOTE: It will be necessary to use a battery charger. Make sure that the battery voltage is sufficient to keep the solenoids
energised when in evacuation mode.
NOTE: The evacuation line to Evacuation pump should be larger than the other 3 lines => this will speed up the evacuation
time.
2. Prepare the unit for evacuation. Recover all refrigerant from the unit and reduce the unit pressure to -0.35 bar, 10 in. Hg
vacuum.
3. Break vacuum with dry nitrogen and equalise pressure to 0 bar, 0 psi. Replace the liquid line filter drier.
4. Connect a 2-stage vacuum pump equipped with a vacuum gauge to the suction service valve, the discharge service valve and
the receiver outlet valve.
5. Back seat the suction service valve and discharge service valve and the receiver outlet valve.
6. If connecting a refrigerant tank to the evacuation pump, close the gauge manifold and refrigerant tank valves to prevent
refrigerant from being drawn from the tank.
7. Open the vacuum valve at the vacuum pump and start the pump.
NOTE: Evacuation hose to the evacuation pump should be larger than the other three hoses to the unit. This will speed up
evacuation time.
NOTE: Dirty vacuum pump oil or a defective vacuum pump will prevent a low micron reading. Hoses and fittings can be
isolated individually to identify leaks.
Unit Evacuation
NOTE: Battery charger must be connected and system must be energised throughout this procedure.
NOTE: Do not attempt to evacuate the unit until the evacuation equipment has been tested and its performance has been
verified.
CAUTION: Do not attempt to evacuate a unit until you are sure the unit is leak free. A unit with less than a full refrigerant
charge should be thoroughly leak checked and all leaks must be repaired.
SPECTRUM AND TCI MODEL NOTE: Continue to evacuate for 1 hour after a 500 to 1000 micron vacuum has been
achieved.
NOTE: The presence of refrigerant in the compressor oil may prevent a low micron reading from being achieved. The oil can
continue to “outgas” for long periods of time. If the micron level appears to stall after 30 to 45 minutes between 1000 and
1500 microns, front seat the suction and discharge service valves and observe the micron gauge. A sharp drop in the micron
reading (1000 to 1500 microns) would indicate that refrigerant is present in the oil or a leak exists in the compressor area.
7. When the desired micron level has been achieved (500 to 1000 microns), close the vacuum valve at the vacuum pump. Turn
the vacuum pump OFF.
8. Observe the reading on the vacuum gauge for 5 minutes. The vacuum rise should not exceed 2000 microns. If the vacuum
level exceeds 2000 microns after 5 minutes, a leak is present, or additional evacuation time is required.
9. If the vacuum level is acceptable, start the pump and open the vacuum valve. Evacuate the system for 5 minutes to remove
the pressure rise.
10. Close the vacuum valve and stop the pump. Observe the vacuum gauge to confirm that the system remains in a deep vacuum.
11. Close the isolation valve at the manifold. The unit is now ready to charge.
Unit Charging
NOTE: The electrical system must be energised throughout this procedure.
NOTE: Please take note of your refrigerant type (label on outside of unit), and make sure not to cross-contaminate.
NOTE: Before charging the system, make sure that the refrigerant lines from the gauge manifold to the refrigerant supply
bottle have been evacuated or purged.
1. Mid seat the suction service valve, the discharge service valve and receiver outlet valve remain mid-seated.
2. Weigh the tank of refrigerant.
3. Check the unit data plate for the required weight of refrigerant charge. Then subtract the amount of the charge to be input to
your unit from the total weight of the tank of refrigerant. This provides the final tank weight after the unit receives a full
system charge.
4. Set the refrigerant supply bottle for liquid. Open the gauge manifold hand valve to receiver tank and charge liquid refrigerant
into receiver tank until the system has the proper charge or until the system will take no more liquid. The remainder of the
charge will be added through the suction service valve if more refrigerant is required.
NOTE: If you are charging a partially charged unit, make sure the liquid level does not rise above the top of the receiver tank
sight glass (top of the bottom receiver tank sight glass on two sight glass receiver tanks).
NOTE: SLXe Spectrum units have a seperate charge level label as shown. Charge the unit to the figure written on the label
NOTE: For charging TCI and Spectrum units where the correct charge weight is not knowen, refer to the Charge Procedure
On page10-8 of this chapter.
7. When the correct amount of charge has been added, close the gauge manifold hand valve.
Unit Charging
1. Isolation valve closed 5. Refrigerant
2. Vacuum valve closed 6. Valves to be in ‘cracked’ open position
3. Evacuate or purge hoses before charging
4. Scale
The condenser pressure bypass check valve is built into the three-way valve. This check valve controls the bypass flow of
refrigerant gas between the condenser inlet line and compressor discharge line.
The check valve is closed when the unit is operating on cool, or whenever the discharge pressure is higher than the condenser
pressure.
When the unit is operating on defrost or heat, or if the condenser pressure is higher than the discharge pressure, the check valve
opens and the condenser pressure is bled off until it decreases to the level of the discharge pressure. This improves
heating/defrosting performance and three-way valve response.
NOTE: Valve stem MUST be back seated during normal unit operation.
11. Back seat the receiver tank outlet valve, remove the gauges and return the unit to normal operation.
MODULATION VALVE
The modulation valve is normally open. As a controlled electrical signal is applied to the coil, the armature overcomes the spring
tension and the valve closes a precise amount. As the signal strength is increased, the valve closes more. This controls the flow
of suction gas to the compressor. The unit controller (TG-VI or µP-IV) controls the signal and the position of the modulation
valve.
Because of the valve and seat design, the pressure from the flow of fluid past the valve has no opening or closing force on the
valve spool. This allows the valve to provide very precise control of unit cooling capacity.
Service of the valve includes replacement of the coil or replacement of the complete valve.
TG-VI, µP-IV AND µP-V NOTE: See the appropriate Controller Operation and Diagnosis manual for instructions on testing
the modulation valve.
Modulation Valve
1. Outlet
2. Inlet
3. Enclosure Tube
4. Armature
5. Electric Coil
6. Piston
7. Closing Spring
8. Valve Seats
9. Opening Spring
Electronic Throttling Valve (ETV - Alco Valve) Electronic Throttling Valve (ETV - Danfross Valve)
1. Stepper Motor
2. Valve Body
3. Inlet
4. Outlet
TG-VI, µP-IV, µP-V, µP-VI, SR-2 and SR-3 NOTE: A Service Test mode on these controllers allows technicians to operate
the unit under known conditions while performing diagnosis and service procedures. See the appropriate Controller
Operation and Diagnosis manual for instructions on how to use the Service Test mode.
NOTE: If the purge valve solenoid wires are not disconnected from the main wire harness, the purge valve is energized when
the unit is placed in the Evacuation Test. This allows the refrigerant in the condenser to flow into the accumulator, undoing
the low side pump down.
b. Place the unit in the Evacuation Test. Refer to the appropriate Microprocessor Diagnostic Manual. The high and low side
pressures should equalize in the Evacuation Test.
NOTE: Repeat the pump down procedure if the pressures equalize above 20 psi (138 kPa). If suitably low pressures cannot
be achieved after the third pump down, the refrigerant must be recovered to perform service on the low side.
c. If the reading on the gauge manifold’s high pressure gauge increases after the high and low side pressures have been
equalized, the condenser inlet check valve is leaking.
NOTE: Remember to reconnect the purge valve solenoid wires to the main wire harness when the service procedures have
been completed.
Compressor
Removal
1. Pump down the compressor and equalise the pressure to 0 psig, (0 bar g).
2. Loosen and remove the compressor/electric motor belt from the Electric Motor pulley (SLe Model 50 and all SLX and SLXe
units).
3. Front seat the discharge and suction service valves. Recover remaining refrigerant pressure from compressor.
4. Unbolt and remove compressor oil filter bracket from flywheel housing (optional).
5. Unbolt the discharge valve and the suction valves from the compressor.
6. Keep the compressor ports covered to prevent dust, dirt, etc., from falling into the compressor.
7. Disconnect all high pressure cutout switch wires. Disconnect the pilot solenoid valve line. (SLX and SLXe - remove
compressor belt guard)
8. Support compressor and remove the compressor mounting bolts from flywheel housing.
9. Lift the service valves out of the way.
10. Slide the compressor to the left until coupling pins are clear.
11. Remove the compressor from the front of the unit.
NOTE: When the compressor is removed from the unit, note the oil level or measure the oil removed from the compressor.
Add the same amount of oil to the replacement compressor.
12. Remove clutch from compressor crankshaft on Model 50 units, from drive coupling on model 30 units.
Installation
1. Replace clutch from compressor crankshaft on Model 50 units, or on drive coupling on model 30 units.
2. Lift compressor into the unit and install the mounting bolts.
NOTE: The 8-pin compressor drive hub will only slide onto the coupling pins in one of two positions that are 180 degrees
apart.
3. Install suction and discharge service valves and torque to the correct value. Coat new o-ring or gasket with compressor oil.
Connect the high pressure cutout switch wires.
4. Reconnect the pilot solenoid valve and compound pressure gauge lines.
5. Pressurise the compressor and test for refrigerant leaks.
6. If no leaks are found, evacuate the compressor. Replace the compressor/electric motor belt and adjust the tension (SLe Model
50 and all SLX and SLXe units).
7. Refit the belt guard on SLX/ SLXe units
8. Back seat the suction and discharge service valves.
9. Operate the unit at least 30 minutes and then inspect the oil level in the compressor. Add or remove oil if necessary.
10. Check refrigerant charge and add refrigerant if needed.
NOTE: For Micro Channel Coil, please follow points 1, 2 and 4 above. (Radiator can be left in for this one)
Installation
1. Clean the refrigerant tubes for soldering.
2. Place the condenser coil in the unit and install the mounting hardware.
3. Solder the refrigerant line connections.
4. Change drier.
5. SLX copper tube and fin condenser - refit coolant hoses to radiator portion of coil.
6. Pressurise the refrigeration system and test for leaks. If no leaks are found, evacuate the system.
7. Fill tank half way with 50/50 antifreeze of correct specification for the system.
• SL and SLe: Install clamps on the condenser inlet line. Install engine coolant expansion tank. Solder tank breather tube.
8. After evacuation, charge the unit with refrigerant.
9. Operate unit and check compressor oil level and refrigerant charge.
• Check and add correct coolant solution to fill the cooling system to the top of the filler neck if required. Make sure there
are no low spots in the vent tube that will trap air in the expansion tank.
• SLX and SLXe, make sure that tank is half full
• SLX copper tube and fin: Refill coooling system (refer to correct system refill procedure in Engine MAintenance Chapter
of this manual)
Discharge Vibrasorber
Removal
1. Remove the refrigerant charge.
2. Heat the connections on the vibrasorber until the vibrasorber can be removed.
CAUTION: Use a heat sink or wrap the vibrasorber with wet rags to protect the vibrasorber.
Installation
1. Prepare the vibrasorber and tubing fittings by cleaning thoroughly.
2. Solder the vibrasorber connections.
3. Change drier
CAUTION: Use a heat sink or wrap the vibrasorber with wet rags to protect the vibrasorber.
4. Pressurise the system and test for leaks. If no leaks are found, evacuate the system.
5. Charge the unit with correct refrigerant and check the compressor oil level.
NOTE: SLX and SLXe => refer to correct refrigerant charging procedure
Suction Vibrasorber
NOTE: If there ia a possibility that the unit has been in a vacuum owing to a leak to the vibraabsorber, the refrigerant must
be recovered.
Removal
1. Pump down the low side and equalise pressure to 0 psig, (0 bar g).
2. Unsolder the suction vibrasorber from the suction service valve. Unsolder the connection to the accumulator and remove from
the unit.
CAUTION: Use a heat sink or wrap vibrasorber with wet rags to prevent damaging the vibrasorber.
Condenser Inlet Check Valve, Condenser Outlet Check Valve or Receiver Tank Outlet
Check Valve
Disassembly and Inspection
1.
• Condenser Inlet or Condenser Outlet Check Valve:
Remove the refrigerant charge.
2. Remove the bonnet nut (or cap) from the check valve.
NOTE: An in-line check valve (P/N 66-5722 or 66-5763) does not have a bonnet nut and is not repairable. An in-line check
valve must be replaced if it fails.
3. Inspect the seat in the check valve for damage or foreign particles which might adhere to the seat and would damage the new
seat. If damaged, replace the entire check valve assembly
Replacement
1. If the seat in the check valve is damaged, unsolder the inlet and outlet line connections. Remove the check valve.
2. Clean the tubes for soldering.
3. Place a new disassembled check valve in position. Arrow on the valve body indicates the direction of refrigerant flow through
the valve.
4. Solder the inlet and outlet connections. After the valve cools, reassemble the valve.
Repair/Assembly
1. Install the new seat and spring.
2. Place a new gasket on the cap and torque to 61 N•m.
3. Replace drier
4. Pressurise the refrigeration system and test for leaks.
5.
• Condenser Inlet or Condenser Outlet Check Valve: If no leaks are found, evacuate the system. Charge unit with correct
refrigerant and check the compressor oil level.
Receiver Tank
Removal
1. Remove the refrigerant charge.
2. Unsolder liquid inlet line from the receiver tank.
3. Disconnect the filter drier line from receiver tank.
4. SL and SLe: Disconnect bypass check valve line from receiver tank. Remove the bypass check valve from the receiver tank.
5. Unbolt the mounting brackets and remove the receiver tank from the unit.
Installation
1. SL and SLe: Coat the bypass check valve fittings with compressor oil. Install the check valve on the receiver tank. Tighten
securely, holding the hex on the receiver tank with a back-up wrench.
2. Place the receiver tank in the unit. Install the mounting bolts and nuts loosely. Position the receiver tank so the sight glass is
clearly visible (through viewing hole in mounting bracket) and the outlet tube lines up.
3. Solder the inlet tube to the receiver tank.
4. Connect filter drier outlet tube and bypass check valve line (SL and SLe) to receiver tank.
5. Tighten the receiver tank mounting hardware securely.
6. Replace drier
7. Pressurise the refrigeration system and check for leaks. If no leaks are found, evacuate the system.
8. Charge the unit with correct refrigerant.
Installation
1. Wrap the new By-pass Check Valve with a suitable heat sink to prevent damage to the valve whilst .soldering
2. Solder in new By-pass Check Valve.
3. Replace drier
4. Back seat the By-pass Hand Valve and place unit in service.
Installation
1. Apply compressor oil to the O-ring on the high pressure relief valve.
2. Apply a refrigerant locktite to the threads of the high pressure relief valve.
3. Install and tighten the high pressure relief valve.
4. Pressurise the refrigeration system and test for leaks. If no leaks are found, evacuate the system.
5. Recharge the unit with refrigerant and check the compressor oil level.
Dehydrator (Filter-Drier)
Removal
1. Pump down the low side and equalise the pressure to 0 psig, (0 bar g).
2. Disconnect the nuts at the end of the drier. Hold the drier with a back-up wrench on the hex behind the flare fitting.
3. Loosen the mounting hardware and remove the drier.
Installation
1. Apply a thin layer of compressor oil to new O-rings and install in the inlet and outlet nuts.
2. Install the new drier and tighten the mounting bracket screws and nuts.
3. Install and tighten the inlet nut to the receiver tank outlet valve line (inlet end of drier is labelled “IN”). Hold the drier with a
back-up wrench on the hex behind the Flare/ORS (depending on manufacture date of the unit) fitting .
4. Pressurise the system and inspect for leaks. If no leaks are found, evacuate low side (See the correct operation and diagnostic
manual for more information. Place the unit in operation.
5. Back seat the receiver outlet valve, check the refrigerant charge and compressor oil level.
NOTE: Do not use oil or grease once the surfaces are clean.
5. Replace Drier
6. Pressurise the low side and test for leaks. If no leaks are found, evacuate the low side.
7. Install evaporator access panels.
8. Open the receiver tank outlet valve. Place the unit in operation.
9. Test the unit to see that the expansion valve is correctly installed.
10. Check refrigerant charge
Evaporator Coil
Removal
1. Pump down the low side and equalise the pressure to 0 psig, (0 bar g).
2. Remove the evaporator access panels.
3. Unsolder the expansion valve from the distributor.
4. Remove thermostat and thermometer sensors.
5. Remove insulating tape and feeler bulb from suction line clamp. Note the position of the feeler bulb on the suction line.
6. Unsolder the suction line and hot gas line from the evaporator coil.
7. Disconnect the electric heaters and high temperature cutout switch (model 50 units).
8. Remove the mounting bolts and remove the coil from the evaporator housing.
Installation
1. Place the evaporator coil in the housing.
2. Install the mounting bolts and tighten.
3. Clean the tubes for soldering.
4. Solder the suction line and hot gas line connections to the evaporator coil.
5. Solder or connect the distributor to the expansion valve assembly.
6. Replace Drier
7. Pressurise the low side and test for leaks. If no leaks are found, evacuate the low side.
8. Clean the suction line to a bright polished condition. Install the feeler bulb clamps and the feeler bulb on the suction line.
Locate the bulb on the side of the suction line in its former position. The feeler bulb must make good contact with the suction
line or the operation will be faulty. Wrap it with correct insulating material.
9. Install thermostat and thermometer sensors. Install the high temperature cutout switch and electric heaters (Model 50 units).
10. Install evaporator access panels.
11. Back seatthe receiver tank outlet valve. Place the unit in operation. Check the refrigerant charge and compressor oil level and
add as required.
TLE and SPECTRUM REMOTE EVAPORATOR NOTE: Unsolder the inlet and outlet connections. Then go to step 8a.
Installation
1. Clean the tubes for soldering.
2. Place the heat exchanger assembly in the evaporator housing. Install the mounting hardware loosely.
TLE and SPECTRUM REMOTE EVAPORATOR NOTE: Tighten mounting hardware. Solder the inlet and outlet
connections. Then go to step 8.
3. Solder liquid inlet and suction outlet line connections on the condenser side of the bulkhead. Seal openings through bulkhead
with putty when refrigerant lines have cooled off.
4. Tighten the heat exchanger mounting hardware securely.
5. Solder suction line connection to the evaporator coil.
6. Solder the equaliser line to the suction line.
7. Solder liquid outlet line to expansion valve.
8. Replace Drier
9. Pressurise the low side and test for leaks. If no leaks are found, evacuate the unit.
10. Clean the suction tube to a bright polished condition. Install the feeler bulb clamps and feeler bulb on the side of the suction
line in its former position. The feeler bulb must make good contact with the suction line or operation will be faulty. Wrap with
correct insulating material.
NOTE: Do not use oil or grease once the surfaces are clean.
11. Open the receiver tank outlet valve. Place the unit in operation. Install refrigerant charge.
12. Check refrigerant charge and compressor oil level
Accumulator
Removal
1. Pump down the low side and equalise the pressure to 0 psig, (0 bar g).
2. Remove the mounting bolts from the accumulator tank mounting brackets.
3. Unsolder the inlet and outlet suction lines from the accumulator tank.
CAUTION: Use a heat sink or wrap vibrasorber with wet rags to prevent damage to the vibrasorber.
Installation
1. Place the accumulator in the unit and loosely install the mounting bolts.
2. Solder the inlet and outlet suction lines to the accumulator tank.
CAUTION: Use a heat sink or wrap vibrasorber with wet rags to prevent damage to the vibrasorber.
Pilot Solenoid
Removal
1. Remove the refrigerant.
2. Disconnect the wires and remove the coil from the valve.
3. Unsolder the refrigeration lines.
4. Remove the mounting bolts and remove the valve.
Installation
1. Remove the coil from the valve.
2. Place the valve in the unit and install the mounting bolts.
3. Solder the refrigeration lines to the valve.
4. Install the coil and connect the wires.
5. Replace Drier
6. Pressurise the refrigeration system and test for leaks. If no leaks are found, evacuate the system.
7. Recharge the unit with the proper refrigerant and check the compressor oil level.
CAUTION: Use a heat sink or wrap valve with wet rags to prevent damaging the valve.
Installation
1. Clean the tubes and elbows for soldering.
2. Remove the coil from the new valve. Correctly position the modulation valve and elbows between the evaporator outlet and
the heat exchanger inlet.
3. Solder the connections.
CAUTION: Use a heat sink or wrap valve with wet rags to prevent damaging the valve.
4. Allow the valve to cool. Install the coil on the modulation valve and connect the wires.
5. Replace Drier
6. Pressurise the low side and check for leaks. If no leaks are found, evacuate the low side.
7. Install the evaporator access panel.
8. Open the receiver tank outlet valve. Place the unit in operation.
9. Check refrigerant charge
Removal
1. Remove the refrigerant charge.
2. SLX/SLXe Spectrum: Remove the lower evaporator access panel.
3. Disconnect the wires and remove coil from the valve.
4. Unsolder the lines and remove the valve.
CAUTION: Use a heat sink or wrap valve with wet rags to prevent damaging the valve.
4. Allow the valve to cool. Install the coil on the valve and connect the wires.
5. Replace Drier
6. SLX/SLXe Spectrum: Refit the lower evaporator access panel.
7. Pressurise the refrigeration system and check for leaks. If no leaks are found, evacuate the system.
8. Charge the unit with correct refrigerant. Place the unit in operation and check compressor oil level.
NOTE: If the throttling valve joints are leaky and/or the rubber cap is detached or missing, the refrigerant may be
contaminated and should be recovered.
Disassembly/Repair
1. Remove the piston end cap (round end).
2. Remove cotter pin from the castle nut and remove nut.
3. Remove the spring and piston.
4. Loosen all the bolts on end cap.
Assembly
1. Install new bellows with O-ring into the housing.
2. Center the spring on bellows shoulder.
3. Coat the gasket with compressor oil. Install gasket on the valve body. Place shims in end cap (use same number as removed).
Tighten end cap in place with vent hole closest to outlet opening of the valve body.
4. Install the piston and spring. Tighten the castle nut until firmly seated against the bottom of the piston.
5. Back off the castle nut, one full turn only.
6. Insert the cotter pin.
7. Oil the gasket and install the end cap.
8. Throttling valve will have to be recalibrated on operating unit. (Refer to Specification section for setting.)
9. Adjust by adding or removing shims under the spring.
NOTE: Spring and valve are held in by the stem. While removing the stem, use care so the spring and valve are not lost.
Installation
1. Coat the O-ring with compressor oil and install it on the check valve stem.
2. Insert the spring into the hole in the check valve stem and then install the Teflon check valve on the other end of the spring
with the hole in the valve towards the spring.
3. Coat the entire assembly with compressor oil and install the assembly into the check valve seat in the three-way valve.
CAUTION: The Teflon valve must be inserted with the flat side against the valve seat to ensure correct sealing.
4. Screw the check valve stem into the three-way valve until the circlip can be installed.
5. Install the circlip.
6. Unscrew (back seat) the check valve stem against the circlip.
NOTE: Valve stem must be back seated during normal unit operation.
7. Coat sealing area in cap with compressor oil, install and tighten the cap on the three-way valve.
8. Pressurise the refrigeration system and test for leaks. If no leaks are found, evacuate the system.
9. Recharge the unit.
Removal
1. Remove the refrigerant charge.
2. Clean the exterior surface of the valve.
3. Unsolder the copper line from the three-way valve to the pilot solenoid.
4. Loosen the 4 Allen head screws (DO NOT remove). Use tool #204-424 to break the gasket at each side of the center section.
CAUTION: Do not force the tool into the brass or against the bolts.
NOTE: The valve body cannot be reconditioned. Seat positions change and incorrect sealing will result.
NOTE: The open side of the seal must face the stem and seat. The closed side of the seal must face the top cap.
NOTE: Make sure that the stem assembly is located correctly into the hole in the bottom cap.
8. Solder pilot solenoid line and pressurise system with refrigerant to check for leaks.
9. Replace Drier
10. If there are no leaks, evacuate the system and recharge with refrigerant.
11. Operate the unit to check for correct three-way valve operation.
CAUTION: Use a heat sink or wrap valve with wet rags to prevent damaging the valve.
Installation
1. Clean the tubes and elbows for soldering.
2. Remove the stepper motor and piston assembly from the new valve. Correctly position the valve body and elbows in the
evaporator.
3. Solder the connections.
NOTE: Use a heat sink or wrap valve with wet rags to prevent damaging the valve.
4. Allow the valve to cool. Install the stepper motor and piston assembly on the valve body and nut.
CAUTION: The stepper motor piston must be fully retracted (valve open position) prior to installing into valve body.
Installation
1. Apply a refrigerant locktite to the threads of sensor.
2. Hold the discharge tube adapter with a backup wrench. Screw the sensor into the adapter.
3. Install mounting clamp on sensor. Connect wire connector.
4. Pressurise the refrigeration system and test for leaks.
5. If no leaks are found, evacuate the system.
6. Charge the unit with the correct refrigerant. Operate the unit and check the compressor oil level.
Liquid Line Solenoid Valve (LLS, LLS2, LLS3, RLLS or CLLS) or Suction Line Solenoid
Valve (SLS, SLS2, SLS3, RSLS or CSLS)
NOTE: Valves that have nylon seats must be disassembled before soldering.
Removal
1. Pump down the low side and equalise the pressure to 0 psig, (0 bar g).
2. Remove evaporator access panels.
3. Remove the coil and disassemble the valve.
4. Unsolder the liquid lines from the valve. Remove the valve from the unit.
Installation
1. Clean the tubes for soldering.
2. Remove the coil and disassemble the valve. Place the valve in position in the unit.
3. Solder the inlet and outlet connections. After the valve cools, assemble the valve and install the coil.
4. Replace Drier
5. Pressurise the refrigeration system and test for leaks.
6. If no leaks are found, evacuate the system.
7. Install evaporator access panels.
8. Open the receiver tank outlet valve. Place the unit in operation.
9. Check refrigerant charge.
Removal
1. Remove the refrigerant charge.
2. Remove the coil and disassemble the valve.
3. Unsolder the hot gas lines form the valve, and remove the valve from the unit.
Installation
1. Clean the tubes for soldering.
2. Remove the coil, disassemble the valve, and place the valve in position.
3. Solder the inlet and outlet connections. After the valve cools, assemble the valve and install the coil.
4. Replace Drier.
5. Pressurise the refrigeration system and test for leaks.
6. If no leaks are found, evacuate the system.
7. Charge the unit with the correct refrigerant. Operate the unit and check the compressor oil level.
Suction Line Check Valve (SLCV, SLCV2, SLCV3, RSLCV or CSLCV), Purge Check Valve
(PCV) or Liquid Return Check Valve (LRCV, LRCV2, LRCV3, RLRCV or CLRCV)
Disassembly and Inspection
1. Pump down the low side and equalise the pressure to 0 psig, (0 bar g).
2. Remove the bonnet nut (or cap) from the check valve.
NOTE: An in-line check valve (P/N 66-5722 or 66-5763) does not have a bonnet nut and is not repairable. An in-line check
valve must be replaced if it fails. Place a heat sink on the valve before unsoldering the inlet and outlet connections to prevent
damage to the neoprene seal.
3. Inspect the seat in the check valve for damage or foreign particles which might adhere to the seat and would damage the new
seat. If damaged, replace the entire check valve assembly.
Replacement
1. If the seat in the check valve is damaged, unsolder the inlet and outlet line connections. Remove the check valve.
2. Clean the tubes for soldering.
3. Place a new disassembled check valve in position. Arrow on the valve body indicates the direction of refrigerant flow through
the valve.
4. Solder the inlet and outlet connections. After the valve cools, reassemble the valve.
Repair/Assembly
1. Install the new seat and spring.
2. Place the new gasket on the cap and torque to 61 N•m.
3. Replace Drier.
4. Pressurise the low side and test for leaks.
5. If no leaks are found, evacuate the system.
6. Open the receiver tank outlet valve. Place the unit in operation.
7. Check refrigerant charge and the compressor oil level.
CAUTION: Use a heat sink or wrap the valve with wet rags to prevent damage.
Installation
1. Clean the tubes for soldering.
2. Remove the coil from the valve. Place the valve in position in the unit.
3. Solder the inlet and outlet connections. After the valve cools, install the coil on the valve.
CAUTION: Use a heat sink or wrap the valve with wet rags to prevent damage.
4. Replace Drier.
5. Pressurise the refrigeration system and test for leaks.
6. If no leaks are found, evacuate the system.
7. Recharge unit with correct refrigerant. Check the compressor oil level.
Removal
1. Remove the refrigerant charge.
2. Remove the coil and disassemble the valve.
3. Unsolder the refrigeration lines from the valve, and remove the valve form the unit.
Installation
1. Clean the tubes for soldering.
2. Remove the coil and disassemble the valve. Place the valve in position in the unit.
3. Solder the inlet and outlet connections. After the valve cools, assemble the valve and install the coil.
4. Replace Drier.
5. Pressurise the refrigeration system and test for leaks.
6. If no leaks are found, evacuate the system.
7. Recharge the unit with the correct refrigerant.
DEFROST DRAINS
Clean the defrost drains during scheduled maintenance inspections to be sure the lines remain open.
CAUTION: Air or water pressure should not be high enough to damage coil fins.
Cleaning Intervals
• The coils should be cleaned a Minimum of once a year.
• It is recommended that any time the unit is in for service or maintenance that the coils be inspected and cleaned if needed.
• The coil should be cleaned if there are visible accumulations that obstruct the view of the fins or tubes of the coil.
• The coils should be cleaned if there is debris imbedded in the tubes and fins
The area and conditions in which the unit operates will dictate the cleaning intervals and method(s) needed.
NOTE:Chemicals to aid in cleaning WILL VOID WARRANTY and are NOT RECOMMENDED.
In some instances in may take a combination of two methods to result in a clean coil. Such as, first wiping the coil to clean the
surface and then using a vacuum, water or compressed air to clean down in the fins. This will depend on the type of debris that
needs to be cleaned from the coil.
Be sure not to contact the coil with any hard vacuum nozzle, air nozzle, or any other tool. This will damage the tubes of the coil.
NOTE: The nuts for mounting the unit should be elastic stop nuts (Nylock type)
NOTE to trailer manufacturer: Not all trailer configurations will permit adding the top center unit mounting bracket assembly
9154C10G01. The top center mounting bolt can be permanently mounted to the trailer structure as part of the trailer. Trailer
structure to support mounting bolt must fit within the limits of the evaporator assembly bolt pocket to avoid interference with
the unit during installation.
Note: For SLX Whisper, service access is provided through access points in the noise Insulation Foam.
DEFROST DAMPER
Check the damper during scheduled maintenance inspections for shaft wear, end play and the ability to stop the airflow. The
damper should close and seal so the airflow is stopped on the top and bottom edges with the solenoid plunger bottomed out. If
the damper does not seal properly, adjust the damper assembly.
Theory of Operation
Micro Switch Logic
Each micro switch is a double-pole, single-throw switch that is activated through a lever. The lever is also called a follower. One
set of contacts in the switch are normally closed and one set are normally open.
When a switch is in the normal position, the yellow wire (pole 1) is connected to the red wire (throw) and the blue wire (pole 2)
is open.
NOTE: The damper motor is sensitive to polarity. If the motor leads are reversed, the motor will rotate in the opposite
direction. This will damage the micro switches and cause erratic operation of the defrost damper.
When it stops, the flat should be on the left side of the output shaft and approximately parallel with the vertical sides of the
gear case. In this position the damper would be open. The output shaft must be in this position (damper open) when the damper
motor is being installed in the unit.
NOTE: If the damper motor assembly does not function properly, it should not be installed.
NOTE: The damper link MUST be installed correctly. If the damper link is not installed correctly, the damper will not operate
properly. The damper will move between half open and half closed and it will be impossible to adjust the damper properly.
4. Attach the damper motor bracket to the evaporator blower housing. Tighten the mounting hardware enough to hold the
damper motor bracket in place, but do not completely tighten the mounting hardware.
5. Push the damper motor and bracket assembly up so it is positioned as high as possible in the evaporator blower housing.
6. Assemble the ball joint link. Set the length between the ball joint centers at 57 mm and make sure that the centers are
approximately parallel.
7. Attach one end of the ball joint link to the damper door bracket with a stainless steel screw, spacer washers, and a Nylock nut.
Use the spacer washers as required to center the ball joint link in the damper door bracket.
WARNING: This damper system can cause serious injuries. Make sure to keep your hands away from the damper door and
the moving parts of the damper system while the damper motor is energised. It is necessary to change the position of the
damper by energizing the damper motor during the adjustment procedure. It may also be desirable to energise the damper
motor while installing some of the components.
The damper system must be adjusted properly. The damper motor assembly has enough power to damage some of the damper
system components if the damper is not adjusted correctly. Two different adjustments are needed to adjust the damper properly.
First, the damper motor and bracket assembly must be positioned vertically so the rubber strip on the damper door barely makes
contact with the non-freeze strip on the bottom of the damper door opening when the damper is open. Second, the damper door
bracket must be positioned on the damper door so the damper door closes completely when the damper is closed.
1. Make sure that the damper motor and bracket assembly is positioned as high as possible in the evaporator blower housing and
that the damper is in the open position.
2. Move the damper motor and bracket assembly down until the rubber strip on the damper door barely makes contact with the
non-freeze strip on the bottom of the damper door opening.
NOTE: Make sure that the metal edge of the damper door does not contact the non-freeze strip on the bottom of the damper
door opening when the damper door is open. Such contact will damage the components of the damper system.
NOTE: Do not overtighten the set screw or the threads in the cam may be stripped.
If the above items are satisfactory, disassemble the damper motor and check the following items:
1. Check the brushes to see if they are damaged or worn out.
2. Check the armature to see if it is damaged or if the windings are burned out.
SYMPTOM – When the unit goes into defrost, the damper door closes and opens a few times before closing properly:
1. Check the outer micro switch. It may be staying in the active position.
a. If the outer cam is loose, it may fail to rotate with the output shaft and hold the micro switch in the active position.
b. Something may be stuck on the switch that causes the switch to stay in the active position.
2. Check the inner micro switch. It may be staying in the normal position.
a. If the inner cam is loose, it may fail to rotate with the output shaft and fail to actuate the micro switch.
b. Something may be stuck on the switch that causes the switch to stay in the normal position.
4. Check the resistance wire by checking the resistance between the end of the resistance wire and CH (or pin 4). The resistance
should be approximately 12 ohms. If not, the resistance wire is defective.
5. Check the thermostat switch by checking the resistance between the switch wires (or switch and pin 3).
a. When the temperature of the thermostat switch is above 2 C, there should be no continuity through the switch. If there is
continuity, the thermostat switch is defective.
b. When the temperature of the thermostat switch is below -16 C, there should be continuity through the switch. If not, the
thermostat switch is defective.
Wiring
See the schematic below for gear motor and gear motor controller wiring.
Operation
Any time the gear motor is not required to run 12 Vdc power is supplied to both sides of the motor via the gear motor controller
X and Y terminals. When the motor is required to run, the gear motor controller supplies a chassis ground to either the X or Y
terminal to cause the motor to run in the desired direction.
Diagnostics
The only tool required is an accurate digital multi-meter such as a Fluke.
Refer to the electrical schematics and wiring diagrams for the specific unit.
Voltages are measured from the specified gear motor controller terminal to chassis ground. Proceed in the order shown below:
1. Disconnect the GM+ wire at the “X” terminal of the controller. Measure the resistance of the gear motor from the GM+ wire
to the “Y” terminal of the controller. If the motor resistance is not between 3.0 and 4.0 ohms the motor or motor harness is
defective and must be repaired or replaced.
2. Reconnect the GM+ wire to the “X” terminal of the controller.
3. Be sure a secure connection exists from the “-” terminal of the controller to chassis ground.
4. Start the unit and use Service Test mode to place the unit in Low Speed Cool. See Service Procedure in the relevant
microprocessor Diagnostic Manual for details of using Service Test mode.
5. Battery voltage should be present at the “B” terminal (29A wire) of the controller. If not, check the defrost relay K3 located
on the relay board.
6. Battery voltage should be present at the “+” terminal (HGP wire) of the controller. If not, check the unit 8F and HGP circuits.
7. Battery voltage should be present at both the “X” (GM+ wire) and “Y” (GM- wire) terminals of the controller. If not, the
controller is defective and must be replaced.
8. Place the unit in Defrost using Service Test mode. Battery voltage should be present at the “A” terminal (29 wire) of the
controller. If not, check the defrost relay K3 located on the relay board.
9. Place the unit in Low Speed Cool using Service Test mode.
10. Connect the voltmeter to the “Y” terminal (GM- wire) of the controller. Carefully monitor the meter and place the unit in
Defrost using Service Test mode. When the defrost relay is energized the voltage from the “Y” terminal to ground should fall
below 0.5-vdc for 3 to 10 seconds. If not, the controller is defective and must be replaced.
11. Connect the voltmeter to the “X” terminal (GM+ wire) of the controller. Carefully monitor the meter and place the unit in
Low Speed Cool using Service Test mode. When the defrost relay is energized the voltage from the “X” terminal to ground
should fall below 0.5-vdc for 3 to 10 seconds. If not, the controller is defective and must be replaced.
12. Check to be sure the linkage is connected correctly. Note that due to the gear reduction involved moving the defrost damper
door manually is impossible.
A Close Signal 29
+ Power 8F/HGP
- Chassis Ground CH
Figure 1
1. Limit Stop Bolts
Adjust the door to correctly open and close and set the limit stops as follows:
1. Loosen off the two 8 mm limit stop adjusting bolts.
2. Disconnect the “A”, “B” and “+” wires from the controller.
3. Jumper a #2 wire circuit (battery +) to terminal “B” on the controller.
4. The motor will operate and the door will open until the damper blade touches the air discharge housing. The motor bracket
and damper door will bend slightly until the controller senses a rise in motor current and will switch off.
5. Screw in the 8 mm open side limit stop bolt until it just touches the linkage crank arm; turn in a further 1 turn.
6. Operate the door to close and reopen and observe the operation.
7. The motor bracket should not noticeably move and the damper blade should lightly touch the air discharge anti-ice strip.
8. This will set the damper blade to touch the air discharge anti-ice strip and the limit stop bolt simultaneously.
9. Tighten the open side limit stop bolt lock nut and re-check the operation.
10. Jumper a #2 wire circuit (battery +) to terminal “A” on the controller.
11. The motor will operate and the damper door will move to the close position.
12. The damper blade neoprene air seal will press into the air discharge housing making a tight seal against the housing. The motor
bracket will bend slightly until the controller senses a rise in motor current and will switch off.
13. Screw in the 8 mm close side limit stop bolt until it just touches the linkage crank arm; turn in a further 1 turn.
14. Operate the door to open and close and observe the operation.
15. Adjust the 8 mm screw until the damper door blade neoprene seal makes a light but uniform contact with the air discharge
housing.
16. Tighten the close side limit stop bolt lock nut.
17. Repeat the opening and closing operation ensuring the damper blade seal neoprene and the limit stops make simultaneous
contact giving a light and uniform air seal.
Figure 2
1. Spacer Washers
2. Damper Bracket
3. Ball Joint Link
CLOSED POSITION
Figure 3
Figure 4
Note:Please refer to previous paragraphs on Damper Door Logic and Operation - this is the same principle on the SLXe/SLX.
1. Evaporator Grille
2. Damper Door
3. Evaporator Blower
4. Evaporator Blower Housing
5. Blower Hub
6. Scroll Pane
1. Evaporator Grille
2. Damper Door
3. Evaporator Blower
4. Evaporator Blower Housing
5. Blower Hub
6. Scroll Panel
SL and SLe
The SL and SLe are equipped with a one-piece fan shaft that is supported by separate compressor side and control box side
bearing assemblies. Check the bearing assemblies for leaky oil seals during pre-trip inspections. If a seal is leaking, remove and
repair that bearing assembly.
9. Tap one Woodruff key (item 17) into the keyway on the compressor side end of the fan shaft for the compressor side
condenser blower (item 3).
10. Tap one square key (item 18) into the keyway on the control box side end of the fan shaft for the control box side condenser
blower (item 4).
11. Slide the control box side bearing assembly (item 11) onto the control box side end of the fan shaft. Make sure to align the
tabs on the inner race of the bearing with the slots in the fan shaft collar. Orient the control box side bearing as shown in the
illustrations with the oil plug and the vent on the front side of the bearing assembly. Fasten the control box side bearing to the
mounting bracket, but do not completely tighten the mounting hardware
12. Slide the compressor side condenser blower (item 3) onto the compressor side end of the fan shaft and make sure to align the
Woodruff key.
13. Install an end shaft screw (item 14) in the compressor side end of the fan shaft. Torque the end shaft screw to 25 N•m. The
end shaft screw secures the inner race of the compressor side bearing between the compressor side condenser blower and the
shoulder on the fan shaft. This keeps the inner bearing race from turning on the fan shaft.
14. Torque the compressor side condenser blower mounting screws (item 15) to 17.5 N•m.
15. Tap the remaining Woodruff key (item 17) into the keyway on the control box side end of the fan shaft for the fan shaft pulley
(item 12).
16. Slide the fan shaft pulley (item 12) onto the control box side end of the fan shaft and make sure to align the Woodruff key.
17. Install an end shaft screw (item 14) in the control box side end of the fan shaft. Torque the end shaft screw to 25 N•m. The
end shaft screw secures the inner race of the control box side bearing between the fan shaft pulley and the shoulder on the fan
shaft. This keeps the inner bearing race from turning on the fan shaft.
18. Torque the two, M8, fan shaft pulley mounting screws to 25 N•m.
19. Torque the three, M10, control box side bearing assembly mounting screws to 44 N•m.
20. Position the seal plate (item 10) that is next to the evaporator blower so the hole in the seal plate is centered on the fan shaft.
Tighten the seal plate mounting hardware to hold the seal plate in this position.
21. Screw the condenser seal gauge pin (item 20) into one of the tapped holes in the control box side condenser blower. Screw
the seal gauge pin in until it is firmly finger tight. The thin tip of the tool should be sticking out of the compressor side of the
blower.
22. Slide the control box side condenser blower toward the bulkhead (compressor side of the unit) until the tip of the seal gauge
pin contacts the bulkhead and stops the blower from sliding any farther to the compressor side of the fan shaft.
23. Hold the control box side condenser blower firmly in this position against the bulkhead and torque the control box side
condenser blower mounting screws to 17.5 N•m.
24. Remove the condenser seal gauge pin from the control box side condenser blower after the mounting screws have been
tightened.
25. Position the seal plate (item 10) that is next to the control box side condenser blower so the hole in the seal plate is centered
on the fan shaft. Tighten the seal plate mounting hardware to hold the seal plate in this position.
NOTE: The fan shaft bearing assemblies require a special oil, TK P/N 203-0278.
NOTE: There is an O-ring on the outer bearing race. Be careful not to damage it during disassembly.
7. Inspect the roller bearing and the outer bearing race for scoring, wear, or other significant damage. Replace it necessary.
8. Inspect the wave washers, O-ring, and bearing seals for wear or other damage. Replace if any signs of wear or damage are
visible.
9. Clean the air vent hole.
10. Clean the parts thoroughly with clean solvent.
1. Coat the outer edge of the oil seal with gasket sealant and press the seal into the bearing housing.
2. Install the inner wave spring washer.
3. Install the O-ring on the outer bearing race and place the roller bearing assembly and the inner race in the housing. Be careful
not to damage the O-ring.
4. Install the outer wave spring washer.
5. Coat the outer edge of the oil seal with gasket sealant and press it into end cap.
6. Lubricate the gasket with light oil and position it on the bearing housing.
7. Install the bearing end cap on the bearing housing and tighten the six bolts in a star pattern.
8. Torque the housing bolts to 13.6 N•m.
9. Fill the oil reservoir.
CAUTION: Make sure to install the bearing assembly in the unit with the vent facing up.
NOTE: There are shims in the bearing housing end cap. These should be saved for possible use during reassembly.
5. Remove the end cap, O-ring, bearing seal, shims, inner race and roller bearings.
NOTE: There is an O-ring on bearing end cap. Be careful not to damage it during disassembly.
6. With a bearing splitter or similar tool, remove the roller bearings from the inner race.
7. With a hammer and punch remove the bearing races from the bearing housing.
8. Inspect the roller bearings and races for wear, scoring or other significant damage. Replace if necessary.
9. Inspect the O-ring and bearing seals for wear or other damage. Replace if any signs of wear or damage are visible.
10. Clean the air vent hole.
11. Clean the parts thoroughly with clean solvent.
Reassembly.
1. Coat the outer edges of the oil seals with gasket sealant and press them into the bearing housing and the bearing end cap.
2. Press the bearing races into the bearing housing and the bearing end cap.
3. Press the roller bearings on to the inner race and place the inner race in the bearing housing.
4. Place the O-ring on the end cap, and apply oil to the O-ring.
5. Install the original shims and the end cap.
6. Torque the four bolts in a criss-cross pattern in equal steps to 13.5 N•m.
7. Lock the assembly in a vise and set up a dial indicator to check the end-play. To measure the end-play, rotate the shaft while
pushing in one direction and set the dial indicator to ‘0’. Now rotate the shaft and pull in the opposite direction while reading
the dial indicator. The end-play should be 0.025 to 0.127 mm. If the end-play is incorrect, use different shims to obtain the
correct end-play. After the correct end-play is obtained, fill the oil reservoir.
8. Place the assembly on the work bench with the vent up. Rotate the shaft by hand. The shaft should be free enough to rotate
without having to hold the housing.
CAUTION: Make sure to install the bearing assembly in the unit with the vent facing up.
Assembly
1. Install the bearing on the shaft
2. Install the flat washers (x2) to Fanshaft
3. Install wave washer onto bearing ontop of the flatwasher
4. Add the second bearing onto wavewasher and flatwasher (i.e. the washers are in between the two bearings).
5. Place the narrow end on the Fanshaft housing over the two bearings.
6. Add the ring snap and place into slot provided (on the bearing).
7. Insert the second wavewwasher on the other end of the Fanshaft housing.
8. Install Bearing and then ring snap now over this wavewasher.
Note: See Chapter 9, Belt Arrangement SLXe, SLX for more details.
Removal
1. Remove the Upper Belt Drive
2. Loosen Orifice Mounting Screws (x3)
3. Remove Front mounting Bracket Bolts (x3) and Screw caps (x2)
4. With the Front mounting Plate removed, remove the remaining Cap screws (x2), holding the blower spindle onto the rear
mounting Bracket.
5. Loosen the Screws (7 below x 4) which hold the bearing Hub into the blower. Ensure that the screws do not come out of the
hub.
6. Allow the bearing and the spindle to slide into the blower.
7. Remove Blower.
7
6
5
1
7
6
5
11
4
2
09
10
4
08
SL
The SL are equipped with a one-piece jackshaft assembly that contains tapered roller bearings in a sealed oil reservoir. Check the
jackshaft during the pre-trip inspection for oil leakage. If there is any sign of leakage, remove the jackshaft assembly and repair it.
Removal
1. Loosen and remove the alternator, upper and lower belts (see Belt Removal and Replacement).
2. Loosen the alternator pivot bolt and remove the alternator adjustment bolt. Swing the alternator out of the way.
3. Remove the jackshaft adjustment bracket.
4. Remove the jackshaft pivot bolts.
5. Remove the jackshaft assembly from the unit.
Disassembly
With the jackshaft assembly removed from the unit:
1. Position the jackshaft in a vise with protective jaws or use two pieces of wood to protect the jackshaft housing from damage.
Vise jaws should be firm but not tight.
2. Remove the oil level and fill plugs and drain the oil reservoir.
3. Remove the pulleys from the jackshaft.
4. Remove the four hex-head screws and flat washers from the bearing housing cap.
NOTE: There are shims in the bearing housing. These should be saved for possible use during reassembly.
Jackshaft Assembly – SL
1. Oil Fill Plug
2. Vent
3. Oil Level Plug
Removal
1. Remove the polygroove belts.
2. Remove both tensioner assemblies.
3. Remove the plain and grooved idlers.
4. Remove the jackshaft mounting bolts.
5. Remove jackshaft assembly from the unit.
N.B. Complete removal of the belt will require the compressor to be removed
1
1
CAUTION: To prevent damage to the bearings, use bearing drivers (or other suitable tools) on the bearing races when
installing the bearings.
NOTE: Place a thin layer of grease (Mobil 28 or its equivalent) on the inner and outer bearing races before assembly.
1. Install the bearing on the small end (approximately 24 mm diameter) of the jackshaft.
2. Install the snap ring on the small end of the jackshaft.
3. Install the jackshaft and bearing in the jackshaft housing from the end opposite the lower mounting bolt tab.
4. Place the wave washers in lower mounting bolt tab end of the jackshaft housing.
5. Install the bearing on the large end (approximately 25 mm diameter) of the jackshaft and in lower mounting bolt tab end of
the jackshaft housing.
6. Install the snap ring on the large end of the jackshaft.
7. Install the key and pulley on the small end of the jackshaft. Make sure the pulley hub is up against the shoulder on the small
end of the jackshaft before tightening the pulley clamping bolts.
8. Install the key and pulley on the large end of the jackshaft. Position the pulley on the large end of the jackshaft so the distance
between the pulleys is 220 mm, and tighten the pulley clamping bolts.
Installation
1. Place the jackshaft assembly in position, and install and tighten the jackshaft mounting bolts. Install the lower mounting bolt
with the threaded end pointing towards the fan drive pulley (pulley on the small end of the jackshaft).
2. Install the grooved and plain idlers.
3. Install both tensioner assemblies.
4. Install the upper and lower polygroove belts.
220 mm
4 1
3
3 2
Unit Inspection
Inspect the unit during the unit pre-trip inspection and scheduled maintenance inspections. Look for loose or broken wires or
hardware, compressor oil leaks, or other physical damage that might affect unit performance and require repair or replacement
of parts.
Defrost Drains
Clean the defrost drains during scheduled maintenance inspections to make sure the lines remain open.
Evaporator Coil
Clean the evaporator coil during scheduled maintenance inspections by blowing compressed air from the top side of the coil down
toward the bottom (the direction opposite the normal airflow). Inspect the coil and fins for damage, and repair if necessary.
CAUTION: Air pressure should not be high enough to damage the coil fins.
NOTE: For diagnosis of units, see the appropriate Controller Operation and Diagnosis manual.
SYMPTOM
Unit not heating or defrosting
Unable to pump down system
Receiver sight glass empty
Unit operating in vacuum
Noisy compressor
No head pressure
POSSIBLE CAUSE
• • • • Overcharge of refrigerant
• • • • • • Shortage of refrigerant
• • • • • No refrigerant
• • Air through condenser too hot (ambient)
• • Air flow through condenser restricted
• • • • Air through condenser too cold (ambient)
• • • Air in refrigerant system
• • Condenser fan blades bent or broken
• Air short cycling around evaporator coil
• • Air through evaporator restricted
• • • • Evaporator needs defrosting
• • • Compressor discharge valves leaking
• • • • Compressor suction valves leaking
• Too much compressor oil in system
• Faulty oil pump in compressor
• Faulty compressor drive coupling
• Compressor bearing loose or worn out
• • • • • • Broken valve plate in compressor
• • Expansion valve power element lost its charge
• • Expansion valve feeler bulb improperly mounted
• • • Expansion valve feeler bulb making poor contact
• • Expansion valve open too much
• • Expansion valve closed too much
• • Expansion valve needle eroded or leaking
• • • Expansion valve partially closed by ice, dirt or wax
SYMPTOM
Unit not heating or defrosting
Unable to pump down system
Receiver sight glass empty
Unit operating in vacuum
Noisy compressor
No head pressure
POSSIBLE CAUSE
• • • • Liquid refrigerant entering compressor
• • • Restricted line on the low side
• • • • Restricted line on the high side
• • • • Restricted dehydrator
• Evaporator damper open
• • • Evaporator damper stuck closed
• Discharge service valve back seated
• Suction service valve back seated
• • • • • • • • Faulty three-way valve
• • • • Faulty pilot solenoid
• • • • • Controller or sensor out of calibration
Leaky receiver tank outlet valve
• • • *Leaky bypass check valve
• Leaky condenser check valve
Faulty three-way condenser pressure bypass check valve
• • • • • Modulation or ETV valve stuck closed
• • • • • Hot gas bypass valve stuck open or leaking
NOTE: *Unit would be able to ramp down if the unit had the BPCV valve front seated
SYMPTOM
High suction pressure
Noisy compressor
No head pressure
POSSIBLE CAUSE
• • • Faulty Condenser Inlet Solenoid (CIS)
• • • • • • Faulty hot gas solenoid (HGS)
• • • Leaky check valve
• • • • Faulty check valve
• Leaky receiver tank pressure solenoid (RTPS)
• • Closed receiver tank pressure solenoid (RTPS)
• • • • • Leaky front hot gas solenoid (HGS)
• • Closed front hot gas solenoid (HGS)
• Leaky front liquid line solenoid (LLS)
• • • • Closed front liquid line solenoid (LLS)
• Leaky suction line check valve (SLCV)
• • • Leaky rear hot gas solenoid (RHGS or HGS3)
• • Closed rear hot gas solenoid (RHGS or HGS3)
• Leaky rear liquid line solenoid (RLLS or LLS3)
• • • • Closed rear liquid line solenoid (RLLS or LLS3)
• • • Leaky rear liquid return check valve (RLRCV or LRCV3)
• Leaky front liquid return check valve (FLRCV or LRCV3)
• • Leaky rear suction line solenoid (RSLS or SLS3)
• • Leaky front suction line solenoid (FSLS or SLS3)
• • • • Leaky purge valve (PV)
• Leaky rear suction line check valve (RSLCV or SLCV3)
• Leaky front suction line check valve (FSLCV or SLCV3)
• • • Leaky center hot gas solenoid (CHGS or HGS2)
• • Closed center hot gas solenoid (CHGS or HGS2)
• Leaky center liquid line solenoid (CLLS or LLS2)
• • Closed center liquid line solenoid (CLLS or LLS2)
• Leaky center liquid return check valve (CLRCV or LRCV2)
• • Leaky center suction line solenoid (CSLS or SLS2)
• Leaky center suction line check valve (CSLCV or SLCV2)
SL/SLe 100, 200 and SLX/SLXe 100, 200 without modulation . . . . . . . . . . . . . . . . . . 15-2
Cooling Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Heat and Defrost Cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-5
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-5
SL, SLe 200 and 300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-5
SL-400 and SL-400e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-6
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-6
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-7
SLX 200 PPP, 300, 400 and SLXe 300, 400. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-8
Cooling Cycle with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-8
Heat and Defrost Cycles with Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-9
SL/SLe 100, 200 AND SLX/SLXe 100, 200 WITHOUT MODULATION
Cooling Cycle
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Throttling Valve
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Throttling Valve
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Throttling Valve
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
31. Modulation Valve
32. Hot Gas Bypass Valve
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Throttling Valve
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
31. Modulation Valve
32. Hot Gas Bypass Valve
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Suction Valve Adapter
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
31. Discharge Transducer
32. Hot Gas Bypass Valve
33. Suction Transducer
34. Electronic Throttling Valve (ETV)
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Suction Valve Adapter
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
31. Discharge Transducer
32. Hot Gas Bypass Valve
33. Suction Transducer
34. Electronic Throttling Valve (ETV)
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Suction Valve Adapter
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
31. Discharge Transducer
32. Hot Gas Bypass Valve
33. Suction Transducer
34. Electronic Throttling Valve (ETV - Danfoss
Valve)
1. Compressor
2. Discharge Service Valve
3. Discharge Line
4. Discharge Vibrasorber
5. Three-way Valve
6. Three-way Valve Bypass Check Valve
7. Condenser Coil
8. Condenser Check Valve
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass
12. Receiver Outlet Valve
13. Liquid Line
14. Drier
15. Heat Exchanger
16. Expansion Valve
17. Feeler Bulb
18. Equaliser Line
19. Distributor
20. Evaporator Coil
21. Accumulator
22. Suction Line
23. Suction Vibrasorber
24. Suction Service Valve
25. Suction Valve Adapter
26. Pilot Solenoid
27. Hot Gas Line
28. Defrost Pan Heater
29. Bypass Check Valve
30. Bypass Service Valve
31. Discharge Transducer
32. Hot Gas Bypass Valve
33. Suction Transducer
34. Electronic Throttling Valve (ETV - Danfoss
Valve))
Note: Early generation of SLX Spectrum units (until 04-2012) are fitted with MTV (not ETV). Therefore, please refer to
pages 15-4 and 15-4 for these Host unit diagrams
Wiring Wiring
Model
Diagram Schematic
SL
Single Temperature Systems
SL-100 30: 5D50976 5D50977
SL-100 50: 5D50481 5D50482
SL-200 30: 5D50976 5D50977
SL-200 50: 5D50481 5D50482
SL-300 30: 5D50978 5D50979
SL-300 50: 5D50465 5D50466
SL-400 30: 5D54368 5D54367
SL-400 50: 5D50737 5D50756
Multi-temperature Systems
SL-300 30 TCI-2/3: 5D50980 5D50981
SL-300 30 HC TCI-2/3: 5D50980 5D50981
SL-300 50 TCI-2/3: 5D50115 5D50114
SL-300 50 HC TCI-2/3: 5D50115 5D50114
SLe
Single Temperature Systems
SL-100e 30: 5D50976 5D50977
SL-100e 50: 5D51439 5D50482
SL-200e 30: 5D50976 5D50977
SL-200e 50: 5D51439 5D50482
SL-400e 30: 1E06785 1E06784
SL-400e 50: 1E08158 1E08157
SL-400e SR-2 30: 1E08158 1E08157
SL-400e SR-2 50: 1E08158 1E08157
Multi-temperature Systems
Spectrum SL 30-2: 5D50980 5D50981
Spectrum SL 30-3: 5D50980 5D50981
Spectrum SL 50-2: 5D50115 5D50114
Spectrum SL 50-3: 5D50115 5D50114
SLX/SLXe
Single Temperature Systems
SLX 30/50: 1E35058 1E35057
SLXe 30/50: 1E64644 1E64645
SLX
Multi-Temperature Systems
SLX Spectrum 30/50: 1E42258 1E42257
SLXe Spectrum 30/50: 1E42258 1E42257
Wiring Diagrams and Wiring Schematics 17-2