Psa Lab Manual
Psa Lab Manual
2K15-ELE-111
Lab Manual
Power System Analysis
Submitted by:
Section: P2
Saira Javed
2K15-ELE-111
Table of Contents
Experiment 1: To model 5 bus power system using PWS19.
Experiment 7: To solve power system using Guass Seidel method using PWS19.
Experiment 9: To solve power system using fast decoupled method using PWS19.
Experiment 10: To model integration of solar wind hybrid renewable based power
with distribution grid using ETAP 12.6.
Experiment 11: To study and perform 3-phase balanced fault analysis on the power
system using PWS 19.
Experiment 12: To perform single line to ground fault analysis on the power
system using PWS 19.
Experiment 13: To perform analysis of line to line fault analysis on power system
using PWS19.
Experiment 1
Objective:
Apparatus:
Theory
A bus in a power system is defined as the vertical line at which the several
components of the power system like generators, loads, and feeders, etc., are
connected. The buses in a power system are associated with four quantities. These
quantities are the magnitude of the voltage, the phase angle of the voltage, active
or true power and the reactive power.
Saira Javed
2K15-ELE-111
Slack Bus:
Slack bus in a power system absorb or emit the active or reactive power from the
power system. The slack bus does not carry any load. At this bus, the magnitude
and phase angle of the voltage are specified. The phase angle of the voltage is
usually set equal to zero. The active and reactive power of this bus is usually
determined through the solution of equations.
This bus is also called the P-V bus, and on this bus, the voltage magnitude
corresponding to generate voltage and true or active power P corresponding to its
rating are specified. Voltage magnitude is maintained constant at a specified value
by injection of reactive power. The reactive power generation Q and phase angle δ
of the voltage are to be computed.
Load Bus:
This is also called the P-Q bus and at this bus, the active and reactive power is
injected into the network. Magnitude and phase angle of the voltage are to be
Saira Javed
2K15-ELE-111
computed. Here the active power P and reactive power Q are specified. The phase
angle of the voltage , i.e. δ is not very important for the load.
A classic load flow analysis consists of calculating voltage magnitude, phase angle,
active power and reactive power. Four variables are associated with each bus viz-
voltage (V), phase angle (δ), real power (P) and reactive power (Q).
P Q V δ
Slack Bus unknown unknown known known
PV Bus known unknown known Unknown
Load Bus known known unknown unknown
Saira Javed
2K15-ELE-111
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Transformer R X
Transmission Line R X B
Saira Javed
2K15-ELE-111
Branch element Real power flow Reactive power flow Real power loss
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
_______________
Saira Javed
2K15-ELE-111
Experiment 2
Objective:
Apparatus:
Theory
Shunt Switch:
Saira Javed
2K15-ELE-111
A device designed to switch the power circuit breaker ON or OFF. A capacitor can
be used as shunt switch.
Shunt Capacitor:
Applications:
Edit mode:
Saira Javed
2K15-ELE-111
Run mode:
Edit mode:
Saira Javed
2K15-ELE-111
Run mode:
Analysis
PV Bus
Load Bus
Transformer R X
Transmission Line R X B
Branch element Real power Reactive power Voltage drop Real power loss
flow flow
Branch element Real power Reactive power Voltage drop Real power loss
flow flow
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________
Saira Javed
2K15-ELE-111
Experiment 3
Objective:
Apparatus:
Theory
The amount of current present in the bus can be calculated with the help of
formation of the Admittance matrix. It is expressed as shown above.
In the simplest form, the above matrix can be written as shown below.
Where,
From the above figure, the (3×3) admittance matrix is formed as shown below.
The diagonal elements of the Bus Admittance matrix are known as self-
admittances and the off-diagonal elements are known as mutual admittances.
Edit mode:
Saira Javed
2K15-ELE-111
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Transmission Line R X B
Conclusion:
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
Saira Javed
2K15-ELE-111
Experiment 4
Objective:
Apparatus:
Theory
1. Slack bus
2. Voltage regulated bus
3. Load bus
Saira Javed
2K15-ELE-111
Edit mode:
Saira Javed
2K15-ELE-111
Run mode:
Saira Javed
2K15-ELE-111
_________________________________________________________________
2-Write the name of the bus having Highest per unit (p.u) voltage and Highest Per
Unit Value ?
__________________________________________________________________
3- Which transmission line has the highest % MVA Loading and Actual Value Of
MVA Fill the following table in support of your answer?
4- Which transmission line has the Lowest % MVA Loading and Actual Value Of
MVA Fill the following table in support of your answer?
5- Which transmission line has the highest % MW Loading and Actual Value Of
MW Fill the following table in support of your answer?
6- Which transmission line has the highest % Line Amp and Actual Value of Line
Amp Fill the following table in support of your answer?
__________________________________________________________________
__________________________________________________________________
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
Saira Javed
2K15-ELE-111
Experiment 5
Objective:
Apparatus:
Theory
Cost optimization:
Cost optimization is a business-focused, continuous discipline to drive spending
and cost reduction, while maximizing business value.
Shunt compensation:
In shunt compensation, switches are connected in parallel with the power system
transmission line. It works as a controllable current source. A reactive current is
injected into the line to maintain constant voltage magnitude by varying shunt
impedance. Therefore, the transmittable active power is increased but at the
expense of increasing the reactive power demand.
Edit mode:
Saira Javed
2K15-ELE-111
Run mode:
When shunt switches are off:
Analysis
Branch element Real power flow Reactive power flow Real power loss
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
Saira Javed
2K15-ELE-111
Experiment 6
Objective:
Apparatus:
Theory
Edit mode:
Run Mode:
Saira Javed
2K15-ELE-111
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
_______________
Saira Javed
2K15-ELE-111
Experiment 7
Objective:
Apparatus:
Theory
It is an iterative method in which at the beginning a set of values for the unknown
quantities are chosen. These are then updated at each iteration. The process
continues till errors between all the known and actual quantities reduce below a
pre-specified value. In the Gauss-Seidel load flow we denote the initial voltage of
the ith bus by Vi(0) , i = 2, ... , n . This should read as the voltage of the i th bus at
the 0th iteration, or initial guess. Similarly this voltage after the first iteration will
be denoted by Vi(1) .
Saira Javed
2K15-ELE-111
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Saira Javed
2K15-ELE-111
Analysis
No of P1 Q2 P2 V2 𝛿2 Q2
iteration
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
_______________
Saira Javed
2K15-ELE-111
Experiment 8
Objective:
Apparatus:
Theory
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
No of P1 Q2 P2 V2 𝛿2 Q2
iteration
Saira Javed
2K15-ELE-111
Conclusion:
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________
Saira Javed
2K15-ELE-111
Experiment 9
Objective:
Apparatus:
Theory
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Saira Javed
2K15-ELE-111
Analysis
No of P1 Q2 P2 V2 𝛿2 Q2
iteration
Conclusion:
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________________________________________________________
__________
Saira Javed
2K15-ELE-111
Experiment 10
Objective:
To model integration of solar wind hybrid renewable based power with distribution
grid using ETAP 12.6.
Apparatus:
Theory
The block diagram of solar wind hybrid system is shown in the figure in which the
solar panels and wind turbine are used for power generation.
Saira Javed
2K15-ELE-111
Advantages:
1. Continuous power supply – The hybrid solar systems provide power
continuously, without any interruption, as the batteries connected to them store the
energy.
2. Utilize the renewable sources in best way – Because the batteries are connected
to the system to store the energy, there is no waste of the excess energy generated
on bright sunny days. So, these systems make use of the renewable energy in best
way, storing energy on a good day and utilize the stored power on a bad day. The
balance is maintained.
3. Low maintenance cost – The maintenance cost of the hybrid solar energy
systems is low as compared to the traditional generators which use diesel as fuel. No
fuel is used and they do not require frequent servicing.
4. High efficiency – The hybrid solar energy systems work more efficiently than
your traditional generators which waste the fuel under certain conditions. Hybrid
solar systems work efficiently in all types of conditions without wasting the fuel.
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Solar panels
Power generation
Wind turbines
Power generation
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________
Saira Javed
2K15-ELE-111
Experiment 11
Objective:
To study and perform 3-phase balanced fault analysis on the power system using
PWS 19.
Apparatus:
Theory
Power system:
An electric power system is a network of electrical components deployed to
supply, transfer, store and use electric power.
Fault:
In an electric power system, a fault or fault current is any abnormal electric
current. For example, a short circuit is a fault in which current bypasses the normal
load. An open-circuit fault occurs if a circuit is interrupted by some failure. In
three-phase systems, a fault may involve one or more phases and ground, or may
occur only between phases. In a "ground fault" or "earth fault", current flows into
the earth. The prospective short-circuit current of a predictable fault can be
calculated for most situations. In power systems, protective devices can detect fault
conditions and operate circuit breakers and other devices to limit the loss of service
due to a failure.
Saira Javed
2K15-ELE-111
Symmetrical faults:
These are very severe faults and occur infrequently in the power systems. These are
also called as balanced faults and are of two types namely line to line to line to
ground (L-L-L-G) and line to line to line (L-L-L).
Saira Javed
2K15-ELE-111
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________
Saira Javed
2K15-ELE-111
Experiment 12
Objective:
To perform single line to ground fault analysis on the power system using PWS 19.
Apparatus:
Theory
Electrical fault:
Electrical fault is the deviation of voltages and currents from nominal values or
states. Under normal operating conditions, power system equipment or lines carry
normal voltages and currents which results in a safer operation of the system.
But when fault occurs, it causes excessively high currents to flow which causes the
damage to equipments and devices. Fault detection and analysis is necessary to
select or design suitable switchgear equipments, electromechanical relays, circuit
breakers and other protection devices.
Types of fault:
There are mainly two types of faults in the electrical power system. Those are
symmetrical and unsymmetrical faults.
1. Symmetrical faults
These are very severe faults and occur infrequently in the power systems. These are
also called as balanced faults and are of two types namely line to line to line to
ground (L-L-L-G) and line to line to line (L-L-L).
Saira Javed
2K15-ELE-111
Symmetrical faults
Only 2-5 percent of system faults are symmetrical faults. If these faults occur, system
remains balanced but results in severe damage to the electrical power system
equipments.
2. Unsymmetrical faults
These are very common and less severe than symmetrical faults. There are mainly
three types namely line to ground (L-G), line to line (L-L) and double line to ground
(LL-G) faults.
Unsymmetrical faults
Line to ground fault (L-G) is most common fault and 65-70 percent of faults are of
this type.
Saira Javed
2K15-ELE-111
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________
Saira Javed
2K15-ELE-111
Experiment 13
Objective:
To perform analysis of line to line fault analysis on power system using PWS19.
Apparatus:
Theory
Power system:
An electric power system is a network of electrical components deployed to
supply, transfer, store and use electric power.
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
_______________
Saira Javed
2K15-ELE-111
Experiment 14
Objective:
To perform analysis of double line to ground fault analysis on power system using
PWS19.
Apparatus:
Theory
Power system:
An electric power system is a network of electrical components deployed to
supply, transfer, store and use electric power.
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________
Saira Javed
2K15-ELE-111
Experiment 15
Objective:
Apparatus:
Theory
Grid station:
An electrical grid is an interconnected network for delivering electricity from
producers to consumers. It consists of generating stations that produce electrical
power, high voltage transmission lines that carry power from distant sources to
demand centres, and distribution lines that connect individual customers. The bulk
power transmission network will move the power long distances, sometimes across
international boundaries, until it reaches its wholesale customer (usually the
company that owns the local electric power distribution network). On arrival at a
substation, the power will be stepped down from a transmission level voltage to a
distribution level voltage. As it exits the substation, it enters the distribution wiring.
Finally, upon arrival at the service location, the power is stepped down again from
the distribution voltage to the required service voltage(s).
Saira Javed
2K15-ELE-111
Edit mode:
Run mode:
Saira Javed
2K15-ELE-111
Analysis
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
____________
Experiment 16
Objective:
Apparatus:
Theory
Relay:
Saira Javed
2K15-ELE-111
Edit mode:
Saira Javed
2K15-ELE-111
Run mode:
Analysis
Saira Javed
2K15-ELE-111
Conclusion:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________