Method Statement - Sound Test (Recovered)
Method Statement - Sound Test (Recovered)
Statement
for Sound
Testing
of HVAC
System
BVLGARI
Hotel &
Residence
1.1 AJB Hightech shall perform Sound Testing of all rooms and spaces with maximum noise levels
as indicated in Section 230548 (Vibration and Seismic Controls for HVAC) and Section 230813
(Air and Water Systems Balancing) of the project specification.
2.1.2 A check should be made to determine that all building construction equipment
and activities are either removed from the building or are not operating.
2.1.3 Exterior noise, such as traffic, aircraft, etc., and interior construction noise will
substantially affect the measurements; therefore, sound level measurements shall
be made when these noise sources are not audible or noted as an exception.
2.1.4 The interior surfaces of the spaces must be reason- ably complete: suspended
acoustical ceilings in- stalled and all carpeting in place. These are sound
absorptive surfaces and will have a significant effect on the sound measurements.
On the other hand, work that does not substantially change the acoustical
characteristics of the room, such as painting of walls, installation of vinyl tile,
installation of desks and thinly upholstered chairs need not be completed before
starting sound tests.
2.2.2 Before making exterior sound measurements, all construction activities must
stop; noise from construction equipment, hoists, etc., will affect the
Rev. 2
3.1 SOUND LEVEL METER. Shall meet the Type 1 or Type 2 requirements specified in the
most current version of ANSI S1.4 American National Standard Specification for Sound Level
Meters.
3.2 FULL OCTAVE FILTERS. Shall meet the requirements specified in the most current version
of ANSI S1.11 American National Standard Specification for Octave- Band and Fractional-
Octave-Band Analog and Digital Filters.
3.3 ACOUSTIC CALIBRATORS. Shall meet the requirements specified in the most current
version of ANSI S1.40 American National Standard Specification for Acoustical Calibrators.
3.4 ANNUAL CALIBRATION. Sound Level instrumentation annual calibration is required for
both the sound level meter/ real time analyzer and the acoustic sound level calibrator.
3.5 FIELD CALIBRATION. All sound instrumentation shall be field calibrated with an acoustic
calibrator meeting the minimum requirements set forth in 3.1 to 3.3 of this section, at the
beginning and the end of each day of use. Field calibration shall be performed in accordance
with the manufacturer’s procedure for calibration or calibration check of instrumentation and
MUST include both the sound level meter and the matching acoustic sound level calibrator.
SECTION – 4 : SOUND LEVEL METER ORIENTATION
Rev. 2
4.2 Take sound measurements at a height approximately 48 inches (1.2meters) above the floor and
at least 36 inches (1 meter) from a wall, column, or any other large surface capable of altering
the measurements.
4.3 During all measurements sound level meter operator, shall not stand between noise source and
sound level meter or be positioned in such a manner to interfere with sound level
measurements.
4.4 The sound level meter should be on a tripod, although holding the sound level meter, at arm’s
length, is sufficient.
4.5 The sound level meter should be pointed towards the noise source at an angle of 45 degrees
from the vertical.
4.6 Refer to attached mark-up drawings at Section 10 of this method statement for the location of
test.
Perform sound measurements when other building systems/conditions and exterior sound sources
are at a minimum level and will not influence measurements of equipment being tested. In order to
minimize other sound sources, the following should be implemented:
6.1 Take sound measurements with the building systems “OFF” to establish the background levels
and take sound measurements with the building systems operating.
6.2 Calculate the difference between measurements. Apply a correction factor depending on the
difference and adjust measurements.
6.3 In certain situations, it may be impossible to shut down building systems in order to obtain
background sound levels. Under these conditions, background sound levels cannot be
measured. In all situations, the AJB shall contact the appropriate personnel before shutting
down any building systems.
7.1 NC data shall be dB (Linear), 1/1(Full) octave band, from 31.5 to 8,000 Hz and Fast Time
Constant.
7.3 Minimum sampling time, per measurement location, when using a Real-Time Analyzer shall be
minute (60-seconds) or sufficient time for sound level sample averaging to stabilize.
7.4 Depending on interference from outside noise sources multiple samples may be required in
order to obtain true and accurate data.
Sound measurements shall be recorded on appropriate test forms, indicating the decibel levels
measured for both background and operating building system readings. Each tested location shall
be recorded on appropriate NC, and/ or overall dB(A) forms. The following information shall also
be recorded: