Grundfosliterature 1191206
Grundfosliterature 1191206
Grundfosliterature 1191206
S pumps, range 62
15 to 50 kW
50 Hz
S pumps, range 62
1. Introduction 4
Table of contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Main constructional features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Performance range 5
Performance range overview, S pumps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Performance range, S pumps, range 62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
List of pump curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. Identification 7
Type key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Pump nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ex approval plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable entry approval plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. Selection of product 9
Ordering the product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. Product range 10
Standard pumps - cast iron, 3 x 400/690 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Explosion-proof pumps - cast iron, 3 x 400/690 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6. Variants 17
List of variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7. Construction 18
Sectional drawings, motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Components and material specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8. Product description 26
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Motor range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Explosion-proof pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Level controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11. Accessories 64
Accessories (for installation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Other accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2
S pumps, range 62
12. Dimensions 67
Table of contents
Recommendation for pump foundations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Basic pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Installation on auto-coupling system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Dry, vertical installation on base stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
13. Weights 76
3
1 S pumps, range 62
1. Introduction
Introduction
Introduction Applications
This data booklet deals with Grundfos heavy-duty S pumps are designed for applications such as these:
sewage pumps type S, range 62. • raw-water intake
• wastewater treatment plants
• municipal pumping stations
• public buildings
• blocks of flats
• industries
• garages
• underground car parks
• car-wash areas
• restaurants and hotels.
The pumps are suitable for both temporary and
permanent installation. The lifting bracket fitted on the
pumps facilitates easy transportation as well as
installation at the installation site.
TM07 0218 4517
4
S pumps, range 62
2
2. Performance range
Performance range
Performance range overview, S pumps
+
>P@
+]
5
2 S pumps, range 62
H
[m]
80 S Pumps
Range 62
60 50 Hz
50
40
S1.80.125 S1.100.125
30
S2.100.200
25
20
15
S2.100.300
10
S2.145.300
8
6
S3.120.300
5
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Q [m³/h]
6
S pumps, range 62
3
3. Identification
Identification
Type key 1
The power output (P2) indicated in the type key, which is used to
indicate the motor size, can deviate from the actual power output.
Please note that the pump type described in this Please refer to the nameplate or the chapter Performance curves
and technical data for the exact power output
booklet is not necessarily available in all variants. 2 PTC sensor are connected directly to IO 113 or other PTC relay.
Example: S1.100.100.55.4.50M.S.205.G.N.D.511.Z
Code Explanation Designation Pump nameplate
Grundfos sewage and wastewater
S
pump 1
Pump type
Multi-channel impeller pump installed
ST
in a column pipe 2 23
1 Single-channel impeller
3 12
2 Two-channel impeller
Impeller type
3 Three-channel impeller 4 13
V SuperVortex impeller 14
100 Maximum solid size [mm] Pump passage 5
15
Nominal diameter of pump outlet port Pump outlet, 6
[mm] S-type 16
100
Nominal diameter of column pipe Pump outlet, 7 17
[mm] ST-type
8 18
P2 = Code number from type
55 Power output [kW] 1
7
3 S pumps, range 62
yyww/no yyww/no
CE CE-mark
Warnings: Warnings: 1180 Number of quality assurance notified body
Do not open when energized. Do not open when energized or when
Cable temperature may exceed 70ºC. explosive gas atmosphere is present.
Cable temperature may exceed 70°C.
EU ex-symbol
Cable gland size and installation:see
installation and operating instructions.
Cable gland size and installation:see
installation and operation manual.
II Equipment group (II = non-mining)
Tamb=-5°C–+40°C Tamb=-5°C–+40°C
98488084 98488082
2 Equipment category (high protection)
G Type of explosive atmosphere
Fig. 3 Approval plate of Ex pumps, T3 and T4 Ex Explosion-proof motor according to European standard
classification b Control of ignition sources
db Flameproof
The approval plate gives the following details:
IIB Gas group (Ethylene)
Pos. Description Tamb Ambient temperature
8
S pumps, range 62
4
4. Selection of product
Selection of product
Ordering the product Accessories
When ordering the product, you need to take the Depending on the installation type, you may need to
following four aspects into consideration: order accessories. See Accessories, page 64 for
selection of the correct accessories.
1. pump
Note: Ordered accessories are not fitted from factory.
2. custom-built variation (option)
3. accessories Controller
4. controller.
Grundfos Dedicated Controls (DC) is available.
Pump
Use Product range starting on page 10 and Type key,
page 7 to identify the pump that best fulfils your needs.
The list below is a detailed description of the product
you get if you order the following pump:
Pump Product no
S1.80.125.300.4.62H.S.338.G.N.D 95113209
• Pump as specified in the type key
• 10 m cable
• Paint: black, NCS 9000N/RAL 9005, gloss 30,
thickness 150 µm
• Three thermal switches (Klixon) or three thermal
sensors (PTC) in stator windings
• One moisture switch below the motor top cover (two
moisture switches in explosion-proof versions: one
9
5 S pumps, range 62
5. Product range
Product range
10
S pumps, range 62
5
Cast iron, 3 x 415 V
Product range
Accessories
11
5 S pumps, range 62
Note: Pumps with 15 m cable are installed with PTC thermal protection.
Accessories
1 Pumps of installation type H include the standard horizontal stand. Pumps with material code G or Q include a painted-steel stand. If another
horizontal stand is required, order a pump of installation type D together with the required stand.
2
Installation type S and C pumps with outlet flange size DN 250 and higher are supplied with a guide claw mounted on the flange.
12
S pumps, range 62
5
Stainless steel impeller, 3 x 400/690 V
Product range
Accessories
13
5 S pumps, range 62
Accessories
14
S pumps, range 62
5
Cast iron, 3 x 415 V
Product range
Accessories
15
5 S pumps, range 62
Accessories
16
S pumps, range 62
6
6. Variants
Variants
List of variants
Motor
15 m
Various cable lengths 25 m
50 m
10 m
15 m
EMC power cables Screened power cables for variable-speed drives
25 m
50 m
Insulation class H
Special motor
Special voltage
PTC thermistors in windings
Special oil Non-toxic Shell Ondina X420 1
Motor protection
Pt100 on lower bearing + Pt100 on upper bearing + Pt100
Sensor set 2
on windings
Pt100 on lower bearing + Pt100 on upper bearing + Pt100
Sensor set 3
on windings + PVS3 vibration sensor
External water-in-oil sensor WIO
Coating
300 µm (painted twice)
Special paint thickness
450 µm (painted three times)
Epoxy coating (NCS 900N/RAL 9005 gloss 30, black)
Impeller (external surface)
Belzona 1321 coating (brush painted, blue)
Impeller (internal surface) Chesterton ARC 855 ceramic coating (grey)
Epoxy coating (NCS 900N/RAL 9005 gloss 30, black)
Pump housing (internal) Belzona 1321 coating (brush painted, blue)
Chesterton ARC 855 ceramic coating (grey)
Epoxy coating (NCS 900N/RAL 9005 gloss 30, black)
Inlet cover Belzona 1321 coating (brush painted, blue)
Chesterton ARC 855 ceramic coating (grey)
Zinc anodes (outside of inlet cover / pump housing) 3 pcs.
Materials
Stainless steel lifting bracket AISI 316
Stainless steel shaft AISI 329
Impeller Stainless steel
Tests
Test at specified duty on standard impeller curve
Trimmed impeller for specified duty test
Additional test of entire QH curve (including report) 5-10 pointsbase plate from pump performance curve
ISO 9906:2012 grade 1E
tolerances
ISO 9906:2012 grade 1B/1U
Different test standard Efficiency guaranteed by Grundfos
tolerances
ISO 9906:2012 grade 2B/2U
tolerances
Vibration test (including report) According to Grundfos factory quality standard
Performance test on dry test stand Contact Grundfos
NPSHr test Contact Grundfos
String test Contact Grundfos
Witness test Contact Grundfos
Miscellaneous
Special packaging Contact Grundfos
Special nameplate Contact Grundfos
Old UK-guide shoe Contact Grundfos / order guide shoe installation kit
Other variants Contact Grundfos
1
For pumps with WIO sensor Shell Ondina is not an option.
17
7 S pumps, range 62
7. Construction
Construction
B
520
520a
176a
176b
A A
25
100
178
B
248 252
A-A 250a
B-B
181 181a 250
168 250b
180
E E
198
164a
D D
190
157
177a 190b
61c
59b
154
48 157b
150
55
172
150c
60
182b 187
155 187a
72a
184
37a
72
153 193
58 194
109
59
182a
TM04 2306 0917
271
105b 270
26a
77 105 107
18
S pumps, range 62
7
Construction
176d 176c 173b 173
E-E
B D-D
520
193 520a
194
176a
A A
176b
25
100
178
B
A-A B-B 248 252
250a
181a
181 250
168 250b
180
E E
198
164a
D D
190
157
177a 190b
61c 59b
154
48
150
55
172
60
182b 187
155 187a
72a
184
72
153
58
109
59
182a
TM04 2307 0917
271
105b 270
26a
77 105 107
19
7 S pumps, range 62
Construction
G-G
520
D-D
E-E
B 176d 176c 193 194 173b 173
173f 520
173e
173d 520a
176a
A A
25
100
25a 176b
178
168 250a
180 250b
E E
180a
198
164a
D D
190
157
177a 190b
61c 59b
154
157b
48
150
55
172
150c
60
182b 187
155 187a
72a
184 G G
72 37a
153 193
58 194
109
59
182a
271
TM04 2309 0917
105b 270
26a
107
77 105
20
S pumps, range 62
7
Construction
G-G
520
E-E D-D
B 176c 176d 173b 173
173f
173e
173d 193 520
194 520a
H H
176a
A A
176b
25
100
25a
178
E E
180a
198
164a
D D
157
190
61c
177a
154 190b 59b
48
150
55
172
60
182b 187
155 187a
72a 184
G G
72
153
58
109
59
271
TM04 2308 0917
182a
270
105b
26a
77 105 107
21
7 S pumps, range 62
22
S pumps, range 62
7
Construction
702
703
701
23
7 S pumps, range 62
Construction
24
S pumps, range 62
7
Components and material specification
Construction
Motor
DIN W.Nr./ DIN W.Nr./
AISI/ AISI/
Pos. Component Material EN Pos. Component Material EN
ASTM ASTM
standard standard
7a Rivet Stainless steel 1.4436 316 250 Cable clamp PA or cast iron
25 Pressure-test plug Stainless steel 1.4436 316 250a Cable entry PA or cast iron
150 Stator complete 12c Adjusting screw Stainless steel 1.4436 316
150c Cooling jacket Galvanized steel 26 Screw Stainless steel 1.4436 316
155 Lower bearing bracket Cast iron 1 35a Screw Stainless steel
172 Shaft with rotor Stainless steel 1.4436 316 49 Impeller Cast iron1 EN-JL-1050
173 Screw Stainless steel 1.4436 316 50 Pump housing Cast iron 1 EN-JL-1050
25
8 S pumps, range 62
8. Product description
Product description
9
Cables
The pumps have H07RN-F AT power cables as
12
TM04 2391 2508
For pumps with DN 250 outlet and larger, the Grundfos Motor power
Voltage
Cable size
[kW] [power + control]
SmartSeal auto-coupling sealing mounted on the
pump outlet flange provides a completely leak-proof 15
2 x 4 x 6 mm2 +
20
connection between the pump and the base unit of the 1 x 7 x 1.5 mm 2
28
auto-coupling system. This optimises the efficiency of
30 3 x 415 V
the entire pumping system and keeps operating costs 41 3 x 400/690 V 2 x 4 x 10 mm2 +
at a minimum. 1 x 7 x 1.5 mm 2
43
Bearings 2 x 4 x 16 mm2 +
50
1 x 7 x 1.5 mm 2
The bearings are greased for life.
Main bearings: Double-row angular contact ball
bearing. Single or pair-mounted angular contact ball
bearings for axial forces and cylindrical roller bearing
for radial forces.
Support bearings: Single-row deep-groove ball
bearing.
26
S pumps, range 62
8
Power cable 2. PVS3 (pump vibration sensor)
Product description
The vibration sensor monitors the vibration level of
Outer cable the pump by using measurements of three axes and
Cable type Weight Bending radius
diameter
[mm2] [kg/m] [cm] combining them into a single measurement
[mm]
4x6 15.7 - 17.2 0.44 10 outputted in an analog current signal. The sensor
4 x 10 20.9 - 23.4 0.38 14 acts only as a general indicator of changes in the
4 x 16 23.8 - 26.3 1.26 16 vibration levels. PVS3 is to be connected to the
Grundfos IO 113 and SM 113 modules. A
Control cable
substantial increase in vibration will trigger a
Outer cable warning or an alarm.
Cable type Weight Bending radius
[mm2]
diameter
[kg/m] [cm]
An increase in vibrations can be caused by a
[mm] clogged impeller, worn bearings, closed force main
7 x 1.5 14.4 - 16.4 0.35 10 valves etc. indicating that service inspection must
Cable entry be carried out quickly in order to protect the pump
or the pipe system from being damaged.
Watertight PA or cast iron cable entry with soft shape
and sealing rings to prevent damage of the cable or 3. Bearing temperature sensor (Pt100).
leaks. Pt100 bearing temperature sensor installed within
the motor housing. Sensors to be connected using
Sensors a SM 113 and IO 113.
A standard pump is equipped with these switches and Testing
sensors:
All pumps are tested before leaving the factory. The
• Three thermal switches (Klixon) or three thermal
factory test report is based on ISO 9906:2012; grade
protectors in the stator housing
3B. Test reports can be ordered directly with the pump
• One moisture switch under the motor top cover. or can be ordered separately based on the pump serial
An explosion-proof pump is equipped with these number.
switches: Other tests or third-party inspection certificates are
• Three thermal switches (Klixon) or three thermal available on request. See List of variants, page 17.
protectors in the stator housing
• One moisture switch under the motor top cover and
one in the stator housing in the dry end of the motor.
Operating conditions
Customised sensor options Pumps without cooling jacket in submerged
installation (type S):
1. WIO (water-in-oil) sensor
The WIO sensor measures the water content in the • Continuous operation when the pump is fully
oil and converts the value into an analog current submerged to the top of motor.
signal. The two sensor conductors are for power • Intermittent operation with maximum 20 starts per
supply as well as for carrying the signal to the hour when the pump is submerged to the middle of
measuring device or controller. The sensor the motor and with short periods of operation down
measures the water content from 0 to 20 %. It also to the top of the pump housing.
sends a signal if the water content is outside the Warning: A motor protection device must be used
normal range (warning), or if there is air in the oil to cut off power supply in case of overheating.
chamber (alarm). The sensor is fitted in a stainless Note: Explosion-proof pumps must always be fully
steel tube for mechanical protection. submerged.
The sensor is either built-in with the motor (Ex) or
Pumps with cooling jacket in submerged and dry
installed as an accessory. If the sensor is installed
installation (types C, D and H):
externally, it is fitted in a plastic hose for mechanical
protection. The WIO sensor is connected to • Continuous and intermittent operation with
Grundfos IO 113. maximum 20 starts per hour with the water level
down to the top of the pump housing.
27
8 S pumps, range 62
Motor range
Motor power [kW] Number of poles
15 12
20 8
28 8
30 4
41 4
43 4
50 4
Explosion-proof pumps
Use explosion-proof pumps in potentially explosive
environments.
Gr-1016086
Note: All installations must be approved by the local
authorities.
Relevant standards/regulations Fig. 15 Grundfos Dedicated Controls control cabinet
• EN ISO 80079-36
Grundfos Dedicated Controls (DC) is a control system
• EN ISO 80079-37 designed for installation in municipal wastewater
• EN 60079-0 transportation, commercial buildings or network
• EN 60079-1 pumping stations with up to six wastewater pumps and
• IEC 60079-0 an optional mixer or a flush valve.
• IEC 60079-1 Advanced control and data communication are also
possible with the Grundfos Dedicated Controls system.
Explosion protection classification (IECEx & ATEX) The control cabinets are delivered with a built-in main
• Group II, Category 2, Gas or vapor environment switch and thermal magnetic circuit breaker.
• Ex db eb h mb IIB T3 or T4 Gb (Tamb = -5 °C to +40 Features and benefits:
°C) • Advanced Flow Calculation
Operation with frequency converter • Automatic energy optimisation
Only temperature class T3. • Easy installation and configuration
Notified body • Configuration wizard
• Electrical overview
SGS Baseefa
• Advanced data communication
• Advanced alarm and warning priority
• Supports several languages
• Daily emptying
• Mixer control or flush valve
• User-defined functions
• Anti-blocking
• Start level variation
• Advanced pump alternation with pump groups
• SMS scheduling
• Communication to SCADA, BMS, GRM or cell
phone.
Dedicated Controls is ordered either with or without a
built-in communication interface module (CIM).
28
S pumps, range 62
8
The communication module enables the possibility for IO 113
Product description
fieldbus protocol (e.g. PROFIBUS DP, Modbus RTU
The IO 113 module is a protection module for Grundfos
and PROFINET IO/Modbus TCP) and the
wastewater pumps.
communication line.
IO 113 has inputs for digital and analog pump sensors
For further information about Grundfos Dedicated
and can stop the pump if a sensor indicates a pump
Controls, please see Grundfos Product Center:
fault.
• Grundfos Dedicated Controls, brochure http://
IO 113 can be connected to the Grundfos Dedicated
net.grundfos.com/qr/i/96925597
Controls system and allows advanced monitoring
• Grundfos iSolutions, brochure http:// functions:
net.grundfos.com/qr/i/99249771
• motor temperature
• Grundfos Controls Guide, product guide http://
• moisture in motor
net.grundfos.com/qr/i/97954965
• water in oil
Additional features, CUE or VFD • insulation resistance.
The CUE/VFD (optional), which is either a Grundfos
variable frequency drive or a general variable SM 113
frequency drive, offers better pump protection and a The SM 113 module is used for collection and transfer
more steady flow through the pipe system. of sensor data in pumps and includes a large number
In addition, Grundfos CUE,VFD offers these features of sensors.
and benefits: SM 113 can be placed either inside the pump (allowing
• Anti-blocking fewer sensor conductors out of the pump) or in the
• Automatic energy optimisation control cabinet next to the pump installation.
• Specific-energy test SM 113 works together with IO 113 through a power-
• Output frequency line communication using the Grundfos GENIbus
• Monitoring of: protocol.
– voltage* SM 113 can collect data from:
– current* • 3 current sensors, 4-20 mA
– phase sequence* • 3 Pt100 thermal sensors or 3 Pt1000 thermal
sensors
– power*
• 1 PTC thermal sensor
– energy*
• 1 digital input.
– torque*
• Reverse start**
• Run flushing MP 204
• Stop flushing The MP 204 control cabinet can be used as a stand-
• PID control. alone motor protector. MP 204 may also be
* These functions are only available with a Grundfos incorporated in a Grundfos Dedicated Controls system
CUE. in which it functions as a motor protector. The pump is
** We do not recommend reversing at full speed at protected secondarily by measuring the temperature
any time. When reduced reverse operation settings with a Pt100 sensor and a PTC sensor or thermal
are set, make sure constant torque is enabled in switch.
Variable Frequency Drive (VFD) (i.e. Grundfos
CUE, Siemens Simatic, ABB, Schneider Electric
etc.) to have maximum torque available when
reversing.
Grundfos LC controllers
The LC 231 pump controller is designed for level
control, monitoring and protection of Grundfos
pumping stations featuring one pump or two pumps,
starting direct-on-line. The LC 231 controller is
integrated in a polymer cabinet.
The LC 241 is a modular pump controller that has a
metal or polymer cabinet and can be customised
according to your needs.
It is designed for level control, monitoring and
protection of Grundfos pumping stations featuring one
pump or two pumps, starting direct-on-line with 0-23 A,
star-delta with 0-59 A or soft starter with 0-72 A.
29
8 S pumps, range 62
Product description
Control cabinet
IO 113 SM 113
T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE
D1 D2 D3 D4 D5 D6 D7 D8 A Y B
Reset
ON DIP
1 2 3 4 5 6 7 8 9 10
P1 P2 P3 P4 P5 I1 I2 I3 1 2 3 4 5 6 7 8 9 1011 1213 14
Level sensor
SM 113, optional
1 2 3 4 5 6 7 8 9 1011 1213 14
3 3 3
4
Pt100 in lower bearing
4 4
9 1
8 2 5 5 5
7 3 Pt100 in stator
6 6 6
6 4 +t
5
Pt100 in upper bearing
7 7 7
+t
TM06 8753 1117
8 8 8
Oil indicator
4 to 20 mA
9 9 9
30
S pumps, range 62
8
Product description
MP 204
MP 204
Control cabinet
IO 113 SM 113
T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE
D1 D2 D3 D4 D5 D6 D7 D8 A Y B
Reset
ON DIP
1 2 3 4 5 6 7 8 9 10
P1 P2 P3 P4 P5 I1 I2 I3 1 2 3 4 5 6 7 8 9 1011 1213 14
Level sensor
SM 113, optional
1 2 3 4 5 6 7 8 9 1011 1213 14
3 3 3
Pt100 in lower bearing
4 4 4
9 1
8 2 5 5 5
7 3 Pt100 in stator
6 6 6
6 4 +t
5
Pt100 in upper bearing
7 7 7
+t
TM06 8754 1117
8 Oil indicator
8 8
4 to 20 mA
9 9 9
31
8 S pumps, range 62
Wiring diagrams
Product description
Motor
Read clockwise
from GND
Pt100 in stator
Thermistor
176c
520d
176a
Stator conductors
TM04 3729 5008
Optional equipment
Item Description
1 Female push-on connector
2 Wire pin
3 Butt splice
4 Ring connector
176a Terminal block (power cable connections)
176c Terminal block (sensor connections)
520d Moisture sensor
32
S pumps, range 62
8
Product description
Thermal switch Moisture switch and thermal protectors
Read clockwise
from GND
In Ex pumps 2 moisture switches Motor
Pt100 in stator
Thermistor
176c
520d
176a
Stator conductors
TM043274 4008
Optional equipment
Item Description
1 Female push-on connector
2 Wire pin
3 Butt splice
4 Ring connector
176a Terminal block (power cable connections)
176c Terminal block (sensor connections)
520d Moisture sensor
33
9 S pumps, range 62
p H
[kPa] [m]
14
62E.S
S2 50 Hz
.14
5.3
120 00. ISO 9906:2012 3B
12 28 0.8
421 .( QH curve for each individual pump
S2. )
100 145
10 .30
0.2
00.
8.(3
38)
80 8 NPSH
[m]
60 6 6
S2.145.300.280.8.(421)
40 4 4
NPSH curve for all variants shown.
When sizing the pumps, add a
20 2 S2.145.300.200.8.(338) 2 safety margin of at least 0.5 m
0 0 0
0 50 100 150 200 250 300 350 400 450 Q [l/s]
8
0 50 100 150 200 250 300 350 400 450 Q [l/s]
Note: The pumps are tested according to ISO 9906:2012 grade 3B tolerance. Testing equipment and measuring
instruments are designed and calibrated according to the standards mentioned. The pumps are approved according to
tolerances for entire curves, specified in grade 3B.
34
S pumps, range 62
9
Curve conditions These tolerance grades can be used in the contract
10
Pump performance testing 8
Q: Flow rate
H: Head
P1: Total consumed power
Eta-tot: Total efficiency
35
9 S pumps, range 62
– Q and H; or 50
Mandatory Optional
Acceptance measurements measurements 10
grade
Q H P1 Eta-tot 0
0 200 400 600 800 1000 1200
3B Standard On request Q [m3/h]
2B
On request On request Fig. 23 Measured values for total efficiency
2U
1B
1E On request On request
1U
36
S pumps, range 62
9
2. Q, H and P1 tested and verified In fig. 26 tolerance crosses according to Grade 3B
grade 3B tolerances: Q = ± 9 %, H = ± 7 %. 10 20
5 10
0 0
H [m] 0 100 200 300 Q [l/s]
Fig. 27 Measured values for tested pump
/RZHUOLPLW
TM07 1515 1618
8SSHUOLPLW
6WDQGDUGFXUYH
Q [m3/h]
37
9 S pumps, range 62
H P1
[m] [kW] checked, individual measurements must be made,
75 150
70 140
which is not part of the performance curve test.
65 130
Static high pressure test
60 120
55 110 All produced pumps undergo a static high pressure
50 100
test of 1.5 x PN (nominal pressure of the pump).
45 90
40 80
35
30
70
60
Specifying acceptance grades
25 50
The graphs in the table on page 39 show the
15 30 tolerance on efficiency.
10 20
5 10 Acceptance grade U
0 0
0 100 200 300 Q [l/s]
This acceptance grade refers to a grade with a
unilateral tolerance on flow rate and head. For the 2U
Fig. 29 Measured values for tested pump grade there is a tolerance on efficiency. For the 1U
grade there is no tolerance on efficiency.
H P1 Note that if the acceptance grade changes from Grade
[m] [kW]
75 150 1B to 1U, the customer does not necessarily get a
70 140 better pump with a higher efficiency. More likely, he
65 130
gets a pump where the performance is always to the
60 120
55 110
positive side of the guarantee point.
50 100
45 90
40 80
35 70
30 60
25 50
TM07 1693 2018
20 40
15 30
10 20
5 10
0 0
0 100 200 300 Q [l/s]
38
S pumps, range 62
9
Q: ±9%
Grade 3
Ș Ș: í7%
H H
H: ±5% H: +10%
Q: ±8% Q: +16%
Q Q
Grade 2
Ș Ș: í5% Ș Ș: í5%
Q Q
H H H
H: ±3% H: ±3% H: +6%
Q Q Q
Grade 1
Ș: í3% Ș: 0% Ș: 0%
Ș Ș Ș
Q Q Q
39
10
Performance curves and technical data
p H
[kPa] [m]
8 S3.120.300.150.12.(449)
62F.S
50 Hz
70 7 ISO 9906:2012 3B
60 6
50 5
40 4
30 3 NPSH
[m]
20 2 4
10 1 S3.120.300.150.12.(449) 2
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Q [m³/h]
P2
[kW]
14
S3.120.300.150.12.(449)
13
12
11
9
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
40
10
60 6
50 5
40 4
30 3 NPSH
[m]
20 2 4
10 1 S3.120.300.150.12.(449) 2
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Q [m³/h]
P2
[kW]
14
S3.120.300.150.12.(449)
13
12
11
9
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
Motor data
Pump data
41
10
Performance curves and technical data
p H
[kPa] [m]
8 S3.120.300.150.12.(449)
62F.S
50 Hz
70 7 ISO 9906:2012 3B
60 6
50 5
40 4
30 3 NPSH
[m]
20 2 4
10 1 S3.120.300.150.12.(449) 2
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Q [m³/h]
P2
[kW]
14
S3.120.300.150.12.(449)
13
12
11
9
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
42
10
60 6
50 5
40 4
30 3 NPSH
[m]
20 2 4
10 1 S3.120.300.150.12.(449) 2
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Q [m³/h]
P2
[kW]
14
S3.120.300.150.12.(449)
13
12
11
9
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 Q [l/s]
Motor data
Pump data
43
10
Performance curves and technical data
p H
[kPa] [m]
14
62E.S
S2 50 Hz
.14
5.3
120 00. ISO 9906:2012 3B
12 28 0.8
421 .(
S2. )
100 145
10 .30
0.2
00.
8.(3
38)
80 8 NPSH
[m]
60 6 6
S2.145.300.280.8.(421)
40 4 4
20 2 S2.145.300.200.8.(338) 2
0 0 0
0 50 100 150 200 250 300 350 400 450 Q [l/s]
20
16 S2.145.300.200.8.(338)
8
0 50 100 150 200 250 300 350 400 450 Q [l/s]
44
10
40 4 4
20 2 S2.145.300.200.8.(338) 2
0 0 0
0 50 100 150 200 250 300 350 400 450 Q [l/s]
20
S2.145.300.200.8.(338)
16
12
Motor data
Pump data
45
10
Performance curves and technical data
p H
[kPa] [m]
14
62E.S
S2 50 Hz
.14
5.3
120 00. ISO 9906:2012 3B
12 28 0.8
421 .(
S2. )
100 145
10 .30
0.2
00.
8.(3
38)
80 8 NPSH
[m]
60 6 6
S2.145.300.280.8.(421)
40 4 4
20 2 S2.145.300.200.8.(338) 2
0 0 0
0 50 100 150 200 250 300 350 400 450 Q [l/s]
20
16 S2.145.300.200.8.(338)
12
46
10
40 4 4
20 2 S2.145.300.200.8.(338) 2
0 0 0
0 50 100 150 200 250 300 350 400 450 Q [l/s]
20
S2.145.300.200.8.(338)
16
12
Motor data
Pump data
47
10
Performance curves and technical data
p H
[kPa] [m] S2.100.300.500.4.(289) 62E.S
180 18 50 Hz
S2.100.300.400.4.(281)
ISO 9906:2012 3B
160 16
140 14
120 12
S2.100.300.300.4.(253)
100 10
80 8
NPSH
[m]
S2.100.300.500.4.(289)
60 6 12
40 4 8
20 2 S2.100.300.300.4.(253) 4
S2.100.300.400.4.(281)
0 0 0
80 120 160 200 240 280 320 360 400 Q [l/s]
48
10
120 12
S2
.10
100 0 .30
10 0 .30
0 .4.(
80 8 253 NPSH
)
[m]
S2.100.300.500.4.(289)
60 6 12
40 4 8
20 2 S2.100.300.300.4.(253) 4
S2.100.300.400.4.(281)
0 0 0
80 120 160 200 240 280 320 360 400 Q [l/s]
TM04 06641914
20
15
80 120 160 200 240 280 320 360 400 Q [l/s]
Motor data
Pump data
49
10
Performance curves and technical data
p H
[kPa] [m] S2.100.300.500.4.(289) 62E.S
180 18 50 Hz
S2.100.300.400.4.(281)
ISO 9906:2012 3B
160 16
140 14
120 12
S2.100.300.300.4.(253)
100 10
80 8
NPSH
[m]
S2.100.300.500.4.(289)
60 6 12
40 4 8
20 2 S2.100.300.300.4.(253) 4
S2.100.300.400.4.(281)
0 0 0
80 120 160 200 240 280 320 360 400 Q [l/s]
50
10
120 12
S2
.10
100 0 .30
10 0 .30
0 .4.(
80 8 253 NPSH
)
[m]
S2.100.300.500.4.(289)
60 6 12
40 4 8
20 2 S2.100.300.300.4.(253) 4
S2.100.300.400.4.(281)
0 0 0
80 120 160 200 240 280 320 360 400 Q [l/s]
Motor data
Pump data
51
10
Performance curves and technical data
p H
[kPa] [m]
62L.S
S2.1
00.2 50 Hz
320 32 00.5
00.4
.(29 ISO 9906:2012 3B
0 )
280 S2.1
28 00.2
00.4
00.4
.(28
240 24 5)
200 20
160 16 NPSH
[m]
120 12 12
80 8 S2.100.200.500.4.(290) 8
40 4 S2.100.200.400.4.(285) 4
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]
P2
[kW]
50 S2.100.200.500.4.(290)
40
30 S2.100.200.400.4.(285)
10
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [l/s]
52
10
200 20
160 16 NPSH
[m]
120 12 12
80 8 S2.100.200.500.4.(290) 8
40 4 S2.100.200.400.4.(285) 4
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]
P2
[kW]
50 S2.100.200.500.4.(290)
40 S2.100.200.400.4.(285)
30
20
Motor data
Pump data
53
10
Performance curves and technical data
p H
[kPa] [m]
62L.S
S2.1
00.2 50 Hz
320 32 00.5
00.4
.(29 ISO 9906:2012 3B
0 )
280 S2.1
28 00.2
00.4
00.4
.(28
240 24 5)
200 20
160 16 NPSH
[m]
120 12 12
80 8 S2.100.200.500.4.(290) 8
40 4 S2.100.200.400.4.(285) 4
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]
P2
[kW]
50 S2.100.200.500.4.(290)
40
30 S2.100.200.400.4.(285)
20
54
10
200 20
160 16 NPSH
[m]
120 12 12
80 8 S2.100.200.500.4.(290) 8
40 4 S2.100.200.400.4.(285) 4
0 0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [l/s]
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]
P2
[kW]
50 S2.100.200.500.4.(290)
40 S2.100.200.400.4.(285)
30
10
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [l/s]
Motor data
Pump data
55
10
Performance curves and technical data
p H
[kPa] [m] S1.1
0 0.12
5.5
00.4
.(367
62M.S
500 )
50 S1.1
00.1 50 Hz
25.4
450 00.4 ISO 9906:2012 3B
45 .(345
)
S1.1
400 00.1
40 25.3
00.4
.(314
)
350 35
300 30
250 25
200
NPSH
20
[m]
150 15 12
S1.100.125.300.4.(314)
100 10 8
S1.100.125.400.4.(345)
50 5 4
S1.100.125.500.4.(367)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
40 S1.100.125.400.4.(345)
30 S1.100.125.300.4.(314)
20
56
10
100 10 S1.100.125.300.4.(314) 8
50 5 S1.100.125.500.4.(367) 4
S1.100.125.400.4.(345)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
40 S1.100.125.400.4.(345)
S1.100.125.300.4.(314)
30
10
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
Motor data
Pump data
57
10
Performance curves and technical data
p H
[kPa] [m] S1.1
0 0.12
5.5 00.4
.(367
62M.S
500 )
50 S1.1
00.1 50 Hz
25.4
450 00.4 ISO 9906:2012 3B
45 .(345
)
S1.1
400 00.1
40 25.3
00.4
.(314
)
350 35
300 30
250 25
200
NPSH
20
[m]
150 15 12
S1.100.125.300.4.(314)
100 10 8
S1.100.125.400.4.(345)
50 5 4
S1.100.125.500.4.(367)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
40 S1.100.125.400.4.(345)
30 S1.100.125.300.4.(314)
10
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
58
10
100 10 S1.100.125.300.4.(314) 8
50 5 S1.100.125.500.4.(367) 4
S1.100.125.400.4.(345)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
40 S1.100.125.400.4.(345)
S1.100.125.300.4.(314)
30
10
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [l/s]
Motor data
Pump data
59
10
Performance curves and technical data
p H
[kPa] [m]
70
62H.S
S1.8
0.12 50 Hz
5 .500
.4.(3
600 98 ) ISO 9906:2012 3B
60 S1.8
0.125
.400.4
.( 374)
500 50 S1.8
0.125
.300.4
.( 338)
400 40 NPSH
[m]
300 30 S1.80.125.300.4.(338) 12
200 20 8
S1.80.125.400.4.(374)
100 10 4
S1.80.125.500.4.(398)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
40 S1.80.125.400.4.(374)
30 S1.80.125.300.4.(338)
20
0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
60
10
200 20 8
S1.80.125.400.4.(374)
100 10 4
S1.80.125.500.4.(398)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
30 S1.80.125.300.4.(338)
20
0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
Motor data
Pump data
61
10
Performance curves and technical data
p H
[kPa] [m]
70
62H.S
S1.8
0.12 50 Hz
5 .500
.4.(3
600 98 ) ISO 9906:2012 3B
60 S1.8
0.125
.400.4
.( 374)
500 50 S1.8
0.125
.300.4
.( 338)
400 40 NPSH
[m]
300 30 S1.80.125.300.4.(338) 12
200 20 8
S1.80.125.400.4.(374)
100 10 4
S1.80.125.500.4.(398)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
40 S1.80.125.400.4.(374)
30 S1.80.125.300.4.(338)
20
0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
62
10
200 20 8
S1.80.125.400.4.(374)
100 10 4
S1.80.125.500.4.(398)
0 0 0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
30 S1.80.125.300.4.(338)
20
0
0 10 20 30 40 50 60 70 80 90 100 110 Q [l/s]
Motor data
Pump data
63
11 S pumps, range 62
11. Accessories
Accessories
Weight Product
Pictures Description Size PN
[kg] number
Cast iron, epoxy-coated auto-coupling system complete DN 150/DN 125 104 96782145
with:
• guide claw 1
Outlet flange
• base unit
• upper guide rail bracket
• gaskets and bolts. DN 200 250 10 96641489
TM06 9868 3417
• flange seal
• bolts. DN 300/DN 300 - 3" 120 10 97908892
DN 150 51 96308238
Inlet flange
DN 150 50 96787496
Steel. DN 200 50 96787497
Base stand for horizontal, dry installation with:
TM04 4156 0909
DN 300 73 96787500
1
Pumps with L-hydraulic.
2 Pumps with E-hydraulic.
TM06 4971 3415
64
S pumps, range 62
11
Accessories
Weight Product
Pictures Description Size PN
[kg] number
Bend
Pipe/pump inlet
Cast iron, epoxy-coated
Reducing bend
Pipe/pump inlet
Cast iron, epoxy-coated
65
11 S pumps, range 62
Other accessories
Accessories
Product
Pictures Description Size
number
4m 98425788
Galvanised lifting chain with lifting link and safety hook. 6m 98425789
Certified.
Maximum lifting capacity 3200 kg. 8m 98425790
10 m 98425791
Contact
TM06 4974 3415
10 m cable 96003332
Float switch
20 m cable 96003695
TM02 0670 5000 TM01 6982 3999
10 m cable 96003421
Float switch for use in potentially explosive environments.
20 m cable 96003536
For 38 mm
Bracket for level electrodes 91713196
mounting pipe
66
S pumps, range 62
12
12. Dimensions
Dimensions
Recommendation for pump Pull-out strengths for anchor bolts
foundations Submerged installation on auto coupling (type S and
C):
Note: This applies only to pumps above 15 kW.
All rotating equipment generates vibrations as a mass, Auto-coupling base Pull-out resistance
Bolts
unit [kN]
such as an impeller or rotor, is turning at high speeds.
DN 100 5
Proper installation and anchorage of Grundfos pumps 4 x M16
DN 125/DN 150 1 8
and installation accessories is critical to limit vibrations
DN 200 16
and achieve reliable, trouble-free installation. It is
DN 250 4 x M24 30
important to note that all mechanically connected DN 300 40
pipes, fittings and supports of the pump are part of a DN 500 40
single system. 6 x M30
DN 600 40
The rotating mass of the entire pump, together with the 1 Pump outlet DN 125 and base plate outlet DN 150.
forces from the motor and hydraulics, will generate
disturbances related to the speed of the motor. Dry installation (type H and D):
Unbalance and impeller vane pass in hydraulics are Pull-out resistance
Dry installation Anchor bolts
the two most important frequencies affecting vibration. [kN]
When these frequencies coincide with the natural DN 100 3 x M20 18
frequency of the entire mechanical system, the DN 150 18
6 x M20
DN 200 18
vibration level will increase substantially.
DN 250 25
Pumps from Grundfos are designed and produced DN 300 25
according to the highest quality standards. The method DN 500/DN 400 1
6 x M24
25
and grade of balancing is specified by the DN 500 25
manufacturer in order to achieve acceptable vibration
1
levels. Although the pump itself can withstand rather Base plate inlet DN 500 and pump inlet DN 400.
high vibration levels under operating conditions without
considerable lifetime reduction, the pipes and
supportive structure might suffer and crack if vibration
levels are too high. Furthermore, noticeable noise
levels might be generated.
The likelihood of high vibration levels occurring is
increased in variable-speed applications where the
pump is operated over a range of speeds rather than
at a single constant speed. Most variable-speed drives
provide the possibility to exclude certain frequency
ranges to avoid operating areas with high vibrations.
To ensure acceptable vibration levels in the field, all
parts of the system must be sufficiently stiff and firmly
anchored to minimise vibrations:
• The foundation and concrete must be of adequate
strength to support the weight of the pump including
accessories, the weight of the liquid passing
through the pump and the forces generated by the
pump.
• As a rule of thumb, the mass of the concrete
foundation must be a minimum of three to five times
the mass of the supported equipment and must
have sufficient rigidity to withstand the axial,
transverse and torsional loadings generated by the
equipment.
• The foundation must be 15 cm wider than the base
plate for pumps up to 350 kW and 25 cm wider for
larger pumps.
• The concrete used in the foundation must have a
minimum tensile strength of 250 N/cm2. Epoxy grout
must always be used to secure the pump base plate
to the foundation.
67
12 S pumps, range 62
Basic pump
Dimensions
DT2
E DC02
D01 x D1N
DC10
MOT_H
!A
DT2
TM04 6361 2018 - TM04 6360 2118
DN2
D02 x D2N
HYDR_H
H
E DC02 DN1
C
68
S pumps, range 62
12
Note: Dimensions D01, D1N, DC10 and DN1 are equal to zero for installation types C and S because of the inlet type.
Dimensions
Pump type A C D D01 D02 D1N D2N DC02 DC10
S1.80.125.300.4.62H.C/S 1460 687 260 - 19 - 8 210 -
S1.80.125.300.4.62H.D/H 1502 690 260 M20 19 8 8 210 240
S1.80.125.400.4.62H.C/S 1460 687 260 - 19 - 8 210 -
S1.80.125.400.4.62H.D/H 1502 690 260 M20 19 8 8 210 240
S1.80.125.500.4.62H.C/S 1460 687 260 - 19 - 8 210 -
S1.80.125.500.4.62H.D/H 1502 690 260 M20 19 8 8 210 240
S1.100.125.300.4.62M.C/S 1488 690 276 - 19 - 8 210 -
S1.100.125.300.4.62M.D/H 1492 690 276 M20 19 8 8 210 295
S1.100.125.400.4.62M.C/S 1488 690 276 - 19 - 8 210 -
S1.100.125.400.4.62M.D/H 1492 690 276 M20 19 8 8 210 295
S1.100.125.500.4.62M.C/S 1488 690 276 - 19 - 8 210 -
S1.100.125.500.4.62M.D/H 1492 690 276 M20 19 8 8 210 295
S2.100.200.400.4.62L.C/S 1496 960 356 - 24 - 8 295 -
S2.100.200.400.4.62L.D/H 1519 960 356 M20 24 12 8 295 350
S2.100.200.500.4.62L.C/S 1496 960 356 - 24 - 8 295 -
S2.100.200.500.4.62L.D/H 1519 960 356 M20 24 12 8 295 350
S2.100.300.300.4.62E.C/S 1525 1235 484 - 24 - 12 400 -
S2.100.300.300.4.62E.D/H 1561 1235 484 M20 24 12 12 400 350
S2.100.300.400.4.62E.C/S 1525 1235 484 - 24 - 12 400 -
S2.100.300.400.4.62E.D/H 1561 1235 484 M20 24 12 12 400 350
S2.100.300.500.4.62E.C/S 1525 1235 484 - 24 - 12 400 -
S2.100.300.500.4.62E.D/H 1561 1235 484 M20 24 12 12 400 350
S2.145.300.200.8.62E.C/S 1515 1139 522 - 24 - 12 400 -
S2.145.300.200.8.62E.D/H 1569 1139 522 M20 24 12 12 400 400
S2.145.300.280.8.62E.C/S 1515 1139 522 - 24 - 12 400 -
S2.145.300.280.8.62E.D/H 1569 1139 522 M20 24 12 12 400 400
S3.120.300.150.12.62F.C/S 1515 1139 522 - 24 - 12 400 -
S3.120.300.150.12.62F.D/H 1569 1139 522 M20 24 12 12 400 400
HYDR MOT
Pump type DN1 DN2 DT2 E F H
H H
S1.80.125.300.4.62H.C/S - DN 125 22 440 523 230 315 1145
S1.80.125.300.4.62H.D/H DN 150 DN 125 22 440 523 272 357 1145
S1.80.125.400.4.62H.C/S - DN 125 22 440 523 230 315 1145
S1.80.125.400.4.62H.D/H DN 150 DN 125 22 440 523 272 357 1145
S1.80.125.500.4.62H.C/S - DN 125 22 440 523 230 315 1145
S1.80.125.500.4.62H.D/H DN 150 DN 125 22 440 523 272 357 1145
S1.100.125.300.4.62M.C/S - DN 125 22 440 552 245 343 1145
S1.100.125.300.4.62M.D/H DN 200 DN 125 22 440 552 249 347 1145
S1.100.125.400.4.62M.C/S - DN 125 22 440 552 245 343 1145
S1.100.125.400.4.62M.D/H DN 200 DN 125 22 440 552 249 347 1145
S1.100.125.500.4.62M.C/S - DN 125 22 440 552 245 343 1145
S1.100.125.500.4.62M.D/H DN 200 DN 125 22 440 552 249 347 1145
S2.100.200.400.4.62L.C/S - DN 200 26 660 646 240 351 1145
S2.100.200.400.4.62L.D/H DN 250 DN 200 26 660 646 263 374 1145
S2.100.200.500.4.62L.C/S - DN 200 26 660 646 240 351 1145
S2.100.200.500.4.62L.D/H DN 250 DN 200 26 660 646 263 374 1145
S2.100.300.300.4.62E.C/S - DN 300 33 800 869 266 380 1145
S2.100.300.300.4.62E.D/H DN 250 DN 300 33 800 869 302 416 1145
S2.100.300.400.4.62E.C/S - DN 300 33 800 869 266 380 1145
S2.100.300.400.4.62E.D/H DN 250 DN 300 33 800 869 302 416 1145
S2.100.300.500.4.62E.C/S - DN 300 33 800 869 266 380 1145
S2.100.300.500.4.62E.D/H DN 250 DN 300 33 800 869 302 416 1145
S2.145.300.200.8.62E.C/S - DN 300 33 700 907 225 370 1145
S2.145.300.200.8.62E.D/H DN 300 DN 300 33 700 907 279 424 1145
S2.145.300.280.8.62E.C/S - DN 300 33 700 907 225 370 1145
S2.145.300.280.8.62E.D/H DN 300 DN 300 33 700 907 279 424 1145
S3.120.300.150.12.62F.C/S - DN 300 33 700 907 225 370 1145
S3.120.300.150.12.62F.D/H DN 300 DN 300 33 700 907 279 424 1145
69
12 S pumps, range 62
Model A Model B
Auto coupling X
Product number Model Size [mm]
Auto-coupling dimensions
G C
A H I J
Dimensions [mm]
Product number Size
A B C D E F G H I J K
96782145 DN 125/DN 150 450 502 280 280 78 0 78 340 300 300 420
96641489 DN 200 485 710 365 535 89 86 175 500 430 430 710
96782484 DN 300 1050 1260 614 830/160 1 127 99 226 780 710 710 1230
1 Six-bolt installation: distance between the front bolt hole and the middle bolt hole / distance between the middle bolt hole and the back bolt hole.
70
S pumps, range 62
12
Pump installation dimensions
Dimensions
C Z6
Z7
Z8
Z9
F
Z10
Installation S
Ex pumps
Z17G
Z17S
Installation S
ZL1 Std. pumps Z1
ZDC1 ZDN1 Z15 Z11
Z23
ZDT1 ZL2
S3OPR
Z01
Installation C
Z2 Z3 Z16
Z12B
ZM Z12A
71
12 S pumps, range 62
Dimensions
C Z6
Z7
Z8
Z9
F Z10
Z17G
Z17S Installation S
Ex pumps
ZL1
Z15 Installation S
ZDT1 Std. pumps Z1
ZDC1 ZDN1 Z11
S3OPR Z23
Z01 Installation C
Z16
Z12B
Z13 Z 12A
Z4
Note: Z12A is the minimum recommended distance from pit bottom to bottom of pump inlet port.
Note: Z11 is the total height of the pump installed on Grundfos installation accessory in the pit.
Note: The pump in this figure might not be equal to Z12A + Z1.
72
S pumps, range 62
12
Dry, vertical installation on base stand
Dimensions
B A
DN2 XDC3
DC02 X03
D2N x D02
X10
DT2
X13
B X16
X131
X132
X17
F X15
X6
A
X05
0
12
Pump type C E F X03 X05 X6 X10 X13 X131 X132 X14 X15
S1.80.125.300.4.62H.D 690 440 523 24 24 621 DN 150 450 150 120 290 520
S1.80.125.400.4.62H.D 690 440 523 24 24 621 DN 150 450 150 120 290 520
S1.80.125.500.4.62H.D 690 440 523 24 24 621 DN 150 450 150 120 290 520
S1.100.125.300.4.62M.D 690 440 552 24 24 719 DN 200 520 170 120 350 344
S1.100.125.400.4.62M.D 690 440 552 24 24 719 DN 200 520 170 120 350 344
S1.100.125.500.4.62M.D 690 440 552 24 24 719 DN 200 520 170 120 350 344
S2.100.200.400.4.62L.D 960 660 646 24 28 854 DN 250 600 200 150 460 692
S2.100.200.500.4.62L.D 960 660 646 24 28 854 DN 250 600 200 150 460 692
S2.100.300.300.4.62E.D 1235 800 646 24 28 854 DN 250 600 200 150 460 692
S2.100.300.400.4.62E.D 1235 800 646 24 28 854 DN 250 600 200 150 460 692
S2.100.300.500.4.62E.D 1235 800 646 24 28 854 DN 250 600 200 150 460 692
S2.145.300.200.8.62E.D 1139 700 907 24 28 882 DN 300 675 225 150 475 780
S2.145.300.280.8.62E.D 1139 700 907 24 28 882 DN 300 675 225 150 475 780
S3.120.300.150.12.62F.D 1139 700 907 24 28 882 DN 300 675 225 150 475 780
Pump type X16 X17 XDC3 DN2 DC02 D02 D2N DT2 XM1
S1.80.125.300.4.62H.D 2098 893 240 DN 125 210 19 8 24 6 x M24
S1.80.125.400.4.62H.D 2098 893 240 DN 125 210 19 8 24 6 x M24
S1.80.125.500.4.62H.D 2098 893 240 DN 125 210 19 8 24 6 x M24
S1.100.125.300.4.62M.D 2186 968 295 DN 125 210 19 8 26 6 x M24
S1.100.125.400.4.62M.D 2186 968 295 DN 125 210 19 8 26 6 x M24
S1.100.125.500.4.62M.D 2186 968 295 DN 125 210 19 8 26 6 x M24
S2.100.200.400.4.62L.D 2348 1117 350 DN 200 295 24 8 26 6 x M24
S2.100.200.500.4.62L.D 2348 1117 350 DN 200 295 24 8 26 6 x M24
S2.100.300.300.4.62E.D 2390 1117 350 DN 200 295 24 8 26 6 x M24
S2.100.300.400.4.62E.D 2390 1117 350 DN 200 295 24 8 26 6 x M24
S2.100.300.500.4.62E.D 2390 1117 350 DN 200 295 24 8 26 6 x M24
S2.145.300.200.8.62E.D 2426 1161 400 DN 300 400 24 12 33 6 x M24
S2.145.300.280.8.62E.D 2426 1161 400 DN 300 400 24 12 33 6 x M24
S3.120.300.150.12.62F.D 2426 1161 400 DN 300 400 24 12 33 6 x M24
73
12 S pumps, range 62
Dimensions
DC2 DN2
D2N x D02
Q2
DT2
QDC1 Q3
QDN1
D1N x D01
Q4
Q10
Q1
QZ1
Q5 Q6
Q8
TM04 2414 2018
Q03
74
S pumps, range 62
12
Dimensions
Pump type D F ∅ Q03 Q1 Q2 Q3 Q4 Q5 Q6 Q8 Q10 QDC1
S1.80.125.300.4.62H.H 260 523 18 1495 290 815 375 115 500 390 815 240
S1.80.125.400.4.62H.H 260 523 18 1495 290 815 375 115 500 390 815 240
S1.80.125.500.4.62H.H 260 523 18 1495 290 815 375 115 500 390 815 240
S1.100.125.300.4.62M.H 276 552 18 1485 267 815 375 115 500 390 815 295
S1.100.125.400.4.62M.H 276 552 18 1485 267 815 375 115 500 390 815 295
S1.100.125.500.4.62M.H 276 552 18 1485 267 815 375 115 500 390 815 295
S2.100.200.400.4.62L.H 356 646 18 1512 281 1035 375 115 500 390 1015 350
S2.100.200.500.4.62L.H 356 646 18 1512 281 1035 375 115 500 390 1015 350
S2.100.300.300.4.62E.H 484 869 19 1554 320 1350 550 115 500 390 865 350
S2.100.300.400.4.62E.H 484 869 19 1554 320 1350 550 115 500 390 865 350
S2.100.300.500.4.62E.H 484 869 19 1554 320 1350 550 115 500 390 865 350
S2.145.300.200.8.62E.H 522 907 19 1567 302 1250 550 120 500 500 870 400
S2.145.300.280.8.62E.H 522 907 19 1567 302 1250 550 120 500 500 870 400
S3.120.300.150.12.62F.H 522 907 19 1567 302 1250 550 120 500 500 870 400
Pump type DN1 Q01 D1N QZ1 DN2 D2N D02 DC2 DT2 QZ1
S1.80.125.300.4.62H.H DN 150 M20 8 18 125 8 19 210 22 18
S1.80.125.400.4.62H.H DN 150 M20 8 18 125 8 19 210 22 18
S1.80.125.500.4.62H.H DN 150 M20 8 18 125 8 19 210 22 18
S1.100.125.300.4.62M.H DN 200 M20 8 18 125 8 19 210 22 18
S1.100.125.400.4.62M.H DN 200 M20 8 18 125 8 19 210 22 18
S1.100.125.500.4.62M.H DN 200 M20 8 18 125 8 19 210 22 18
S2.100.200.400.4.62L.H DN 250 M20 12 18 200 8 24 295 26 18
S2.100.200.500.4.62L.H DN 250 M20 12 18 200 8 24 295 26 18
S2.100.300.300.4.62E.H DN 250 M20 12 18 300 12 24 400 33 18
S2.100.300.400.4.62E.H DN 250 M20 12 18 300 12 24 400 33 18
S2.100.300.500.4.62E.H DN 250 M20 12 18 300 12 24 400 33 18
S2.145.300.200.8.62E.H DN 300 M20 12 23 300 12 24 400 33 23
S2.145.300.280.8.62E.H DN 300 M20 12 23 300 12 24 400 33 23
S3.120.300.150.12.62F.H DN 300 M20 12 23 300 12 24 400 33 23
75
13 S pumps, range 62
13. Weights
Weights
76
S pumps, range 62
14
Flange forces
The flange forces and moments are according to EN
Horizontal installations
ISO 5199.
Z Forces can be found for both horizontal and vertical
installations in Table B.3 in EN ISO 5199 by selecting
the correct flange dimension. Forces cannot be used
Y directly for end-suction wastewater pumps without
using a coefficient which can be found in Table B.5 in
EN ISO 5199 by selecting the correct pump family.
Z For Grundfos wastewater pumps, the pump families
Y and coefficients are as stated below.
Horizontally installed pumps
Pump family A4 = Coefficient 0.35
X
Vertically installed pumps
Pump family 10A = Coefficient 0.30
Vertical installations
X
Base unit
Z
TM06 4901 3115 - TM06 4903 3115 - TM06 4902 3115
77
15 S pumps, range 62
Online search and sizing tool to help you make the right choice.
http://product-selection.grundfos.com
TM07 2384
instructions, data booklets, service instructions, etc. in PDF format.
2 3 4 5
TM07 2383
Pos. Description
1 This drop-down menu enables you to set the search function to "Products" or "Literature".
2 SIZING enables you to size a pump based on entered data and selection choices.
3 CATALOGUE gives you access to the Grundfos product catalogue.
REPLACEMENT enables you to find a replacement product.
Search results will include information on
4 the lowest purchase price
the lowest energy consumption
the lowest total life cycle cost.
5 LIQUIDS enables you to find pumps designed for aggressive, flammable or other special liquids.
78
79
ECM: 1307629
GRUNDFOS A/S
96805708 01.2021
www.grundfos.com
Telephone: +45 87 50 14 00
DK-8850 Bjerringbro . Denmark
Trademarks displayed in this material, including but not limited to Grundfos, the Grundfos logo and “be think innovate” are registered trademarks owned by The Grundfos Group. All rights reserved. © 2021 Grundfos Holding A/S, all rights reserved.