Private: Total Demand Calculation: Al Muna Gardens For Each Villa Fixtures Type
Private: Total Demand Calculation: Al Muna Gardens For Each Villa Fixtures Type
The mean demand 18.0 gpm (mean demand = peak demand / peak factor )
Overhead tank size 540 gallon ( Overhead tank size = (peak demand - mean demand) x duration }
2.04 m3
Transfer pump capacity 18.0 gpm ( Transfer pump capacity = mean demand , Assuming one pump
4.09 m3/h running & one standby)
1.14 l/s
PROJECT NAME- AL MUNA GARDENS 122 VILLAS
MEP CONTRACTOR - SEMEC SPECIALIZED PROJECTS LLC
DATE - 22/DEC/2021
TYPE OF LOAD TOTAL NOS OF PERSON LITERS/DAY/PERSON
OCCUPANTS 5 400
OCCUPANTS /
FACILITY 20 400
BUILDING
TOTAL WATER DEMAND FOR 1 DAY (LITRE) FOR EACH VILLA
TOTAL GALLONS FOR DAY FOR EACH VILLA
TOTAL WATER DEMAND FOR ONE DAY (LITRE) FOR ALL 122 VILLA +
FB
TOTAL GALLONS FOR DAY FOR ALL 122 VILLA + FB
ASSUMED OVERHEAD WATER TANK FOR EACH VILLA - 600GALLONS
WATER DEMAND (LITRE)
2000
8000
2000
530
252000
66579 66578.5997358