Flo-Tronic Plus: User Manual Revision 03
Flo-Tronic Plus: User Manual Revision 03
Rev No: 03
Date: 4/15/2013
COPYRIGHT
DISCLAIMER:
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 11
1. WARNING
Thank you for purchasing control equipment from Waukee Engineering a member of United
Process Controls. We want your new control equipment to operate safely. Anyone who uses
this equipment should read this publication (and any other relevant publications) before
installing or operating the equipment.
To minimize the risk of potential safety problems, you should follow all applicable local and
national codes that regulate the installation and operation of your equipment. These codes
vary from area to area and usually change with time. It is your responsibility to determine
which codes should be followed, and to verify that the equipment, installation, and operation
are in compliance with the latest version of these codes.
At a minimum, you should follow all applicable sections of the National Fire Code, National
Electrical Code, and codes of the National Electrical Manufacture’s Association (NEMA). There
may be local regulatory or government offices that can also help determine which codes and
standards are necessary for safe installation and operation.
Equipment damage or serious injury to personnel can result from failure to follow all applicable
codes and standards. We do not guarantee the products described in this publication are
suitable for your particular application, nor do we assume any responsibility for you product
design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you
need additional information, please call us at 414-462-8200.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 12
2. TABLE OF CONTENTS
1. WARNING ............................................................................................................................................................. 11
2. TABLE OF CONTENTS............................................................................................................................................. 12
5. SPECIFICATIONS .................................................................................................................................................... 15
8. MAINTENANCE ..................................................................................................................................................... 21
9. CALCULATIONS ..................................................................................................................................................... 22
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 13
3. MANUAL OVERVIEW
Supplemental Manuals
The Installation and Operation of Waukee Flo-Meters manual contain technical
information as well as precautions about Waukee Flo-Meters.
Technical Support
We strive to make our manuals the best in the industry. We rely on your feedback to let
us know if we are reaching our goal. If you cannot find the solution to your particular
application, or, if for any reason you need technical assistance, please call us at:
+1-414-462-8200 Toll free North America: +1-800-438-3347
Our technical support group will work with you to answer your questions. They are
available Monday through Friday from 8:00 A.M. to 4:30 P.M. Central Standard Time.
We also encourage you to visit our web site where you can find technical and non-
technical information about our products and company.
http://www.waukeemeters.com
http://www.group-upc.com
If you have a comment, question or suggestion about any of our products, services, or
manuals, please e-mail or contact us by phone.
Conventions Used
When you see the exclamation point icon in the left-hand margin, the
paragraph to its immediate right will be a warning. This information could
prevent injury, loss of property, or even death in extreme cases. Any
warning in this manual should be regarded as critical information that should
be read in its entirety. The word WARNING or CAUTION in boldface will
mark the beginning of the text.
When you see the “notepad” icon in the left-hand margin, the paragraph to
its immediate right will be a special note.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 14
4. FLOW SENSOR INTRODUCTION
The Waukee Flo-Tronic™ utilizes a sensor to read the position of the float rod indicator on a
Waukee Flo-Meter™. The unit provides both electrical and mechanical indication of flow. The
unit is factory calibrated to provide linear and accurate flow measurement. If necessary, the
Flo-Tronic may be “field calibrated”.
How it works
Magnet assembly attached to float rod of the Waukee Flo-Meter interacts with a
magnetostrictive linear position sensor installed in Flo-Meter sensing head. A strain
pulse is induced in a specially designed waveguide by the momentary interaction of two
magnetic fields. One field comes from a moving magnet, which passes along the
outside of the sensing tube, the other field from a current pulse launched along a wire
inside the waveguide. The interaction between these two magnetic fields produces a
strain pulse which travels at sonic speed along the waveguide, until the pulse is detected
at the head of the transducer. The position of the moving magnet is precisely
determined by measuring the elapsed time between the launching of the electronic pulse
and the arrival of the strain pulse. As a result, accurate non-contact sensing of the Flo-
Meter’s indicator is achieved. The indicator position is directly related to the Flo-Meter’s
flow rate and is represented by a proportional analog electrical signal.
Model Explanation
FT M17
Size L13: L1-3 (9” Scale)
S17: S Gas (3” Scale)
L46: L4-6 (9” Scale)
SF17: SF Liquid (3” Scale)
L79: L7-9 (9” Scale)
M17: M1-7 (6” Scale)
L10: L10 (9” Scale)
M811: M8-11 (6” Scale)
Model
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 15
5. SPECIFICATIONS
General Specifications
Operation Specification
Accuracy ± 0.4% FS + 1.6% Rd
Measurement Repeatability < 0.5% FS
Turndown Ratio 1:40 (2.5 … 100%)
Operating Voltage 24VDC ± 10%
Electrical Power
Power Consumption 75mA
Current: 4-20mA or 0-20mA
Ranges Selectable
Voltage: 0-10VDC or 2-10VDC
Voltage Output
Short Circuit Protection YES
Analog Output Short Circuit Current 0.875mA
Min Load Impedance 1k Ohm
Current Output
Open Circuit Voltage 24VDC
Max Load Impedance 500 Ohm
Type SPST
Relay Output Contact Rating 0.5A @ 30VDC
Alarm Logic No power or alarm condition de-energize relay
Operating Temp 0°C to 65°C (32°F to 150°F)
Humidity 20 to 90% RH (non-condensing)
Environment Storage Temp -20°C to 65°C (-4°F to 150°F)
Enclosure Rating IP 65
Installation Location Keep from corrosive gas and liquid
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 16
achieve this lay the unit on its side on a work bench or table. Then
hold the Flo-Tronic unit with one hand, while unscrewing the union
nut counters clockwise with the other hand to loosen it. FLOAT STOP
BODY O-RING
Remove the Float Rod Assembly and store it in a safe location until
Flo-Meter body is installed and mounted. Once the Flo-Meter is
installed, remove the red tape from the float rod and insert the float
rod assembly into the Flo-Meter body. Fill the sight glass tube with FLO-TRONIC
Waukee Flo-Meter oil so that the level of oil is approximately one SENSOR
(1) inch from the top. Then carefully install the Flo-Tronic on to the
Flo-Meter.
Do not put oil in the sight glass tube of meters used for
oxygen or methanol service. Oxygen Flo-Meters should be
run dry, or with distilled water. Flo-Meters for Methanol
service will automatically fill the sight glass tube with
Methanol when in service.
WARNING: Do not fill the sight glass tube with Flo-Meter oil on
meters used for oxygen service. Use of oil may cause fire or
explosion. Serious personal injury may result from fire or
explosion.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 17
Wiring Guidelines
Your company may have guidelines for wiring installation. If so, you should check those
before you begin the installation. Here are some general things to consider:
• Use the shortest wiring route whenever possible.
• Use shielded wiring for all signal wiring and ground the shield at the Field Device
end. DO NOT ground the shield at both the Flo-Tronic Sensor and Field Device.
• Do not run the signal wiring next to large motors, high current switches, or
transformers. This may cause noise problems.
• Route the wiring through an approved cable housing to minimize the risk of
accidental damage. Check local and national codes to choose the correct
method for your application.
• Be sure to leave enough slack in the cables to allow easy removal of the Flo-
Tronic from the Flo-Meter for maintenance. If seal tight or similar conduit is used,
be sure to provide an adequate loop of conduit for maintenance access.
Wiring Connections
All wiring connections are located inside the main box. To access the wiring terminals
remove the (4) four screws located on the front of the box and remove the cover.
Circuit Protection
The Flo-Tronic is equipped with built-in over-voltage and short circuit protection. The
unit may require recycling of power to reset once the fault condition is removed.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 18
Wiring Terminals
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 19
CAUTION: Relay is for use with 30VDC or less ONLY!!! Use of any other
voltage may result in damage to unit and poses a potential fire risk.
The Flo-Tronic Plus output signal is calibrated at the factory and should be received calibrated,
but in some cases the unit may require field calibration of the electronics. If you find that the
analog output signal is not correct in relation to the indicated flow, you can recalibrate the
output by the adjustment of the “Zero” and “Span” potentiometers located inside the sensor
box.
CAUTION: Do not turn
potentiometers
excessively as
these adjustments
ZERO
are sensitive.
SPAN
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 20
The best way to measure the output signal is to disconnect the unit from the field device and
connect a multi-meter across terminals 3&4. Set the multi-meter to measure the correct signal
the unit is setup for.
If you are unsure what the output signal is, refer to “Analog output configuration”
located on page 8.
Method 1
Remove the Flo-Tronic and float rod assembly from the Flo-Meter and
manually move the float rod assembly to the required position for calibration.
Refer to page 6 of this manual for removal and installation. This is the
preferred method of Calibration of the Flo-Tronic.
Method 2
If the equipment and process allows this, the float rod assembly can be moved
to the required position for calibration by shutting off the fluid valve for zero
flow and opening the fluid valve to full open for full flow.
To adjust the Zero (0%), the float rod should be at the bottom or zero flow position.
Then adjust the “Zero” pot until the signal is correct for the selected analog output. This
will be 4mA for 4-20mA, 0mA for 0-20mA, 2V for 2-10VDC and 0V for 0-10VDC
To adjust the Span “Full Scale Flow”, the float rod will now need to be adjusted to Full
scale (100%). Then adjust the “Span” pot until the signal is correct for the selected
analog output. This will be 20mA for a current output or 10VDC for a voltage output.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 21
8. MAINTENANCE
The Flo-Tronic is a magnetic based sensor which is unaffected by dirt. The dampening oil can
be soiled to the point that it is not possible to visually read the flow on the Flo-Meter and the
unit will still accurately determine the position of the float rod assembly.
The Flo-Meter is a mechanical device that requires regular maintenance in order to maintain
accuracy. All Flow Meters are susceptible to dirt affecting its accuracy. Although not all
manufactures have a means to gauge when the Flo-Meter requires maintenance. Waukee Flo-
Meters on the other hand have a built in indication when the Flo-
Meter requires maintenance, which is the dampening oil. When the oil becomes soiled it is
indication maintenance on the Flo-Meter is needed. The frequency of maintenance intervals will
vary depending on the cleanliness of the gas being used. To replace the oil will require the
removal of the Flo-Tronic; refer to the installation section of this manual for instructions. Also
during these maintenance intervals it is recommended that all gaskets and o-rings are
inspected for signs of wear or damage. Replace worn or damaged seals. Gasket kit sets are
available from Waukee if needed.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 22
9. CALCULATIONS
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 23
10. TROUBLESHOOTING
Diagnostic Lights
The Flo-Tronic has a comprehensive diagnostic system. The diagnostic lights are
displayed on the front panel of the unit.
TEMP – The TEMP LED indicates when unit electronics (IC) temperature is in excess of
185°F; unit will not function until temperature is below 185°F
Diagnostics
Description Corrective Actions
1. Check for 24VDC power at terminals 1 and 2
PWR LED not Illuminated
2. Make sure power supply is not over loaded
1. Check wiring at terminals 1,2,3 of sensor TB
SENSOR LED Illuminated
2. Check for cut or damaged sensor cable
1. Check wiring at terminals 3 & 4
OUTPUT LED Illuminated 2. Check wiring at Field device 3.
Ensure unit is configured for correct output signal
TEMP LED Illuminated 1. Shield device from sources of heat
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 24
On Demand
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved
Flo-Tronic Plus Rev 03 Page 25
Reach us at www.group-upc.com
United Process Controls brings together leading
brands to the heat treating industry including
Waukee Engineering, Furnace Control, Marathon
Monitors and Process-Electronic.
We provide prime control solutions through our
worldwide sales and services network with easy-to-
access local support.
Copyright © 2013, Waukee Engineering., a member of United Process Controls. All rights to copy, reproduce and transmit are reserved