QP Fire and Safety Philosophy - QP-PHL-S-0001 Rev.03 2013 16-30
QP Fire and Safety Philosophy - QP-PHL-S-0001 Rev.03 2013 16-30
QP Fire and Safety Philosophy - QP-PHL-S-0001 Rev.03 2013 16-30
6.6.3 The safety studies/reviews shall identify possible areas of equipment failure and
process upset and ensures that levels of protection are provided in accordance with
appropriate Codes and Standards. The safety studies/reviews place emphasis on the
consequences of change to operating variables; i.e. of high and low pressure,
temperatures, flow rates, level and leakage both between systems and into the
environment. The provision of protection systems to eliminate or minimise incidents
shall be studied to determine their adequacy.
6.6.4 Engineering shall undertake Hazops/ Safety studies/ reviews with representation from
Operations, Maintenance, and Engineering Loss Prevention Engineer.
6.6.5 The aim of the safety studies/reviews is to establish that an adequate level of safety is
achieved against the risk of fire or explosion and other design accident events.
6.6.6 Specific project fire and safety philosophy shall be detailed for each project.
6.6.7 For safety studies through out the project phases, refer to; Philosophy for Health and
Safety Activities In Projects (QP-PHL-S-038).
6.7 HAZARDOUS AREA CLASSIFICATION
6.7.1 The reasons for classifying the installation into hazardous areas are as follows:
a) To allow for appropriate material/ equipment selection.
b) To ensure that sources of ignition are segregated from potential sources of
flammable gas.
c) To assist in the location of clean air inlets (taken from non-hazardous area) for
ventilation systems or combustion equipment.
d) To assist in the location of flammable gas detectors.
6.7.2 The overall design philosophy should be to make the installation as safe as possible by
minimising the sources of release of flammable gas/liquid to the atmosphere.
6.7.3 The area classification will be in accordance with the IP Model Code of Safe Practice:
Part 15; latest edition.
6.7.4 The above Code involves classifying the various areas of the installation into zones
and grades the source of releases. Refer to IP 15 for definitions.
6.7.5 The extent of the hazardous zones is defined by the above mentioned code and is
dependent on the source of the hazard, the physical properties of the material released
and the ventilation of the area. These points are discussed below.
6.7.6 The various sources of release are determined from the PFD‟s and P&ID‟s and their
location on the installation from the equipment layout drawings. Continuous grades of
release giving rise to a Zone 0 area should be eliminated from installations.
6.7.7 The number of primary sources of hazard should be strictly limited. These are restricted
to continuous or frequent operations and to poorly ventilated areas where gas may
accumulate. The hazards of venting flammable gas must be appreciated and the vent
designed accordingly. The accumulation of pockets of gas should be eliminated by
efficient ventilation whether natural or mechanical.
6.7.8 Secondary sources of release occur infrequently and are typically caused by the failure
of a flanged joint or the infrequent venting of equipment to atmosphere. A fully welded
section of pipeline would not normally be considered to be a source of release. Further
items, which give rise to a secondary source of release, include filter covers and sphere
launcher doors, which are infrequently opened.
6.7.9 The extent of the hazardous area resulting from a source of release is governed by the
physical properties of the material. For most sources (except large vents) the distance
is defined in the IP Code.
6.7.10 A liquid will only give rise to a flammable vapour if it is at a temperature above its flash
point. Fluids with a flash point below 55°C or at a temperature above their flash point
are considered to be hazardous.
6.7.11 Sumps and pits shall be avoided or eleminated. If not possible then they shall be
classified for Zone 1.
6.7.12 Many items of equipment are potential sources of ignition. Electrical systems which
could produce a spark of sufficient energy to ignite the flammable gas must be
protected in accordance with recognised standards such as IEC 60079. Surface
temperatures of other equipment should be treated in the same way and may be
reduced by insulation or by cooling the contents of the system.
6.7.13 The temperature classification of electrical equipment shall be “T3” (IEC 60079),
corresponding to surface temperature not exceeding 200°C.
6.7.14 For exhausts and air intakes the following shall be obtained:
Sparks from the exhausts from combustion equipment may also provide a source
of ignition. These are caused by glowing particles of carbon and to eliminate this
problem, all exhausts are to be taken to the edge of a Non-Hazardous area and
extended into this Non-Hazardous area by minimum of three metres.
The air intakes for combustion engines, air compressors and the ventilation
systems shall be located in non-hazardous areas and as remote from the process
areas and other sources of gas release as practical.
The air exhausts from non-hazardous areas and combustion engines shall be
terminated in non-hazardous areas at a minimum of 4.5 m from the air intakes to
avoid cross flow between extract and intake. All combustion exhausts shall be
fitted with a spark arrestor
6.7.15 Other ignition sources may comprise fixed equipment such as fired heaters or mobile
equipment such as plant traffic.
6.7.16 Fired equipment shall be located in non-hazardous areas. Within a hazardous area, the
maximum external surface temperature of equipment and piping systems will be limited
to 200°C. Plant roads that are around the perimeter of plots will be in non-hazardous
areas and only authorised traffic will be allowed to enter the plant location.
6.7.17 Other potential sources of ignition which may be present in hazardous areas during
operations or maintenance, such as welding or gas cutting, will be controlled by the
permit to work system. The plant area will be a “no-smoking” zone, and will be noted
as such by work instructions and by safety signs.
6.7.18 Where non-hazardous areas are located within hazardous areas, airlocks or gas tight,
self-closing doors shall be provided as necessary together with sufficient mechanical
ventilation to achieve a minimum level of pressurisation of 50 Pa above the adjacent
hazardous area.
6.7.19 The HVAC system where provided to maintain pressure differential within the lower
hazard rated area should be capable of ensuring a continuous air flow from the lower
hazard rated area to the higher hazard area when doors are open. This may be
achieved by the provision of a standby system capable of maintaining the required
pressure differential.
6.7.20 Construction of enclosures required to be pressurised shall ensure low leakage of
pressurisation air; adequate pipe or cable seals and airtight construction are essential.
6.7.21 Access openings between hazardous and non-hazardous enclosures shall be avoided;
where this is not possible the opening shall be protected by an airlock or gas tight door.
6.7.22 Access openings into or between Zone 1 or Zone 2 hazardous areas shall be protected
by an appropriate airlock(s) or gas tight door(s). Three alternative situations are
possible:
(i) Zone 1 area opening into a Zone 2 area;
(ii) Zone 2 area opening into a non-hazardous area;
(iii) Zone I area opening into a non-hazardous area.
6.7.23 Preference shall be given to using an airlock for each of the three alternative situations
referred to above. However, when an airlock is not practicable, gas-tight self-closing
doors may be used for situations (i) and (ii).Situation (iii) should be fitted with a double
door airlock whenever possible, but if this is not practicable the HVAC system provided
to maintain pressure differential should be upgraded. from a single fan normally used
for arrangements (i) and (ii), to include two 100% duty fans, one running and one
standby. Controls should automatically start the standby fan on failure of the duty fan or
upon prolonged loss of pressure differential, when both would run simultaneously.
6.7.24 Where practicable doors shall be positioned so that they do not face a source of
hazard.
6.7.25 The area of lower hazard rating shall be maintained at a minimum pressure differential
of 50 Pa above that of the connected higher hazard rated area.
6.7.26 Loss of pressure differential shall initiate an audible/visual alarm at a normally manned
station after a delay period not exceeding 30 seconds.
6.7.27 Loss of pressure differential in a non-hazardous space coincident with the detection of
gas at any location, shall initiate automatic disconnection and de-energising of all
electrical equipment that is not certified for operation in a hazardous atmosphere.
6.7.28 All electric equipment located within an airlock shall be certified as suitable for use in a
hazardous area of equal or greater hazard rating than that external to the airlock.
6.7.29 Should pressurisation be lost, an alarm shall annunciate in the Control Rooms. If gas is
simultaneously detected on the platform then executive action (electrical isolation) shall
be taken.
6.7.30 Hinged doors for normal access between hazardous and non-hazardous areas shall
open into the non-hazardous area: emergency hinged doors shall open in the direction
of escape. The exception to this guidance is sliding doors when fitted.
6.7.31 By design, the following areas shall be defined as “non-hazardous” by location:
a) Control rooms
b) Living quarters / offices
c) UPS Switch room/instrumentation/electrical equipment rooms
d) Telecommunications equipment room
e) Fire pump rooms
f) Emergency power generation areas
6.7.32 Battery rooms (Special considerations shall apply owing to battery venting and possible
H2 generation). If mechanical pressurisation is adopted then the room should be
negatively pressurised with respect to adjoining non-hazardous areas but positively
pressurised with respect to the external environment.).
6.7.33 All outdoor field equipment that may be required to operate under emergency
conditions shall be suitable for use within a Zone 1 area. This equipment includes all
items from the following list :-
a) Emergency shutdown system
b) Fire and gas detection system
6.8.27 The minimum width of access ways and roads will be as follows:
7.3.10 All information from sub-systems shall be available to the operator in the master CCR.
Any sub-system providing information at other plant locations shall be for indication only.
Thus while the master CCR maintains the control functions, slave information systems
on the same plant provide information only with no executive control features on
associated distributed plants (e.g. gas distribution system) with designated secondary
control centres, control facilities may be enabled either by cascade or password control.
7.3.11 The following essential aspects of Human Machine Interface (HMI) for control systems
shall be considered in design:
a) Construction and hierarchy of graphics
b) Definition and operation of major graphics
c) Adopted colour representations
d) Alarm processing and reporting
e) Matrix and Mimic panels including indications and controls
7.3.12 The system shall be self-monitoring to detect faults that may affect the operation of the
system. Detection of a fault shall register an appropriate signal at the alarm panel and
any annunciation panels or system displays.
7.3.13 Signals from the fire and gas detection system may be used to initiate operation of fire
fighting equipment or systems, and initiate plant shutdown and blowdown systems.
7.3.14 The alarm system shall be supplied power from the essential power supply and shall
include battery back-up with a dedicated battery charger. The back-up battery capacity
shall not be less than 60 minutes maximum load.
7.3.15 The fire and gas system shall be based on the provision of suitable field detector
devices, which alarm to the fire and gas control panel.
7.3.16 The fire and gas detection system shall be physically arranged so that a single failure in
it is unlikely to cause critical impairment of the system‟s safety function.
7.3.17 Cables to field detectors shall be fire resistant to IEC 60331.
7.3.18 Detection modes that are arranged to cause plant shutdown shall be generally on a two
out of N voting arrangement to reduce the possibility of spurious shutdowns; where N is
a minimum of three detectors.
A revealed fault condition shall be arranged to vote as an alarm condition; in the other
hand, it shall not cause tripping the plant. For example, one detector in fault mode and
another detector in confirmed mode shall trip the plant; but, two detectors in fault
condition shall not trip the plant.
Nevertheless, any one pneumatic detection system will each operate as a single loop.
7.3.19 Field detector types shall be selected on the basis of the following:
a) The type which gives the earliest detection of the event
b) Freedom from spurious operation
c) Suitability for the ambient environmental conditions
d) An optimum design and limitation of the number of detectors
e) Proven operation in similar situations
f) Inherent reliability
g) Low maintenance requirements
Electrical and instrument equipment and cabling such as that contained in the switch
room or local equipment room: OR
Other combustible material such as paper, rag, lubricating oil and grease that may
be contained in a workshop or materials store.
7.6.2 Detector types shall be selected to detect the predominant characteristics of the fire
behaviour, and shall be provided in sufficient numbers and suitably located to provide
effective monitoring.
7.6.3 Due consideration shall be given to the specification and design of fire detection systems
to minimise the incidence of false or spurious alarms.
7.6.4 Fire detector selection shall be from the following types (Depending upon the area being
protected):
a) Smoke detection - Ionisation, Optical and Air sampling (HSSD)
b) Heat detection - Pneumatic (frangible bulb / fusible plug / fusible tube)
Electrical (rate of rise / rate compensated / fixed temp).
c) Flame detection - IR.
7.6.5 Linear Heat Detector Cable for fire detection in the cable trenches and cable cellars shall
be provided
7.7 SMOKE DETECTION
7.7.1 Smoke detectors sense combustion products and should be used within enclosed
spaces that are not subject to extremes of temperature, humidity, dust or wind.
7.7.2 Detection is achieved in the smouldering stage before flames and high temperature
occurs. Areas of selection include accommodation, ceiling void spaces, auxiliary and
switch gear rooms with false floors and ceilings, where high density of electrical cables
are installed.
7.7.3 Where detection is required in false floors and ceilings, remote indicating lamps shall be
provided.
7.7.4 Detection in areas of electrical risk, where historically gaseous fire protection systems
have been employed, and detection in not normally manned buildings on remote not
normally manned plants shall be by HSSD which is likely to give an alarm of a fire at an
early stage.
7.7.5 Consideration should also be given to using HSSD systems in not normally manned
buildings on manned plants; where the risk and consequential loss deems it appropriate.
7.7.6 Point type, optical smoke detectors may only be used in accommodation type risk areas
where there is minimal air movement.
7.7.7 Point type, ionisation smoke detectors may be installed, if the Authority having
jurisdiction, permits their use in any appropriate enclosed space that does not require to
be provided with an HSSD system.
7.8 HEAT AND FLAME DETECTION
7.8.1 Heat detection shall be used when it is not practical to utilise smoke detection i.e. high
temperature, high humidity, dust etc.
7.8.2 In areas protected by sprinkler or deluge system fusible plugs or frangible quartzoid will
generally be chosen for heat detection/activation with the system being designed in
accordance with NFPA Code 13 for sprinkler system and NFPA 15 for deluge system. In
certain areas protected such as floating tank roofs, plastic tube may be considered as an
option.
7.8.3 In open areas, such as process area, fires may show heat radiation and flames.
Therefore appropriate detector types shall be selected using a case by case examination
of the plant equipment and plant layout. This will be detailed in the specific plant project.
3D model review to be used for location of flame detectors in order to identify possible
obstruction and to ensure clear line of sight.
Note: Operating efficiency of the detection system shall remain at a maximum at all
times. Prevailing environmental conditions shall be taken into account in establishing the
locations of detectors with attention paid to detrimental vibration effects and moist salt-
laden air. The detectors shall be protected against accidental damage or tampering
where necessary.
7.9 MANUAL ALARM CALL POINTS
7.9.1 Onshore plants shall be provided with a manual alarm call point system throughout the
plant area. At the entry/exit points to buildings and along escape routes such that the
distance from any part of the process or utilities plant areas to the nearest call point shall
not exceed 30 metres.
7.9.2 Offshore plants shall be provided with a manual emergency alarm call point system
throughout the plant area and at the entry/exit points, at bridge access points and
stairways.
7.9.3 Call points shall be double action type e.g. lift flap “break-glass”.
7.9.4 Manual alarm call points shall activate audible and visual alarms on the central and local
fire and gas panels, start the firewater pumps and operate the general plant alarm and
plant status lights.
7.10 PRE-DISCHARGE AUDIBLE ALARMS
Enclosed areas protected by fixed gaseous fire protection shall be provided with a pre-
discharge alarm within the protected space, operating in conjunction with the status light.
This is to warn personnel of the imminent discharge of gaseous extinguishant into the
area. Duration of the alarm shall be 30 seconds.
7.11 EXECUTIVE ACTION
7.11.1 Executive action of the fire and gas systems shall be determined on a case by case
basis and shall be detailed in the cause and effect of the specific plant project.
However, in general, the executive action philosophy is as outlined below.
7.11.2 The fire and gas detection system shall automatically initiate executive actions as
follows:
a) FIRE DETECTED
Air sampling type high sensitivity smoke detection
Fire detected (level 1) ALERT 1
Alarm to Control Room
Initiate local panel alarm
Fire detected (level 2) ALERT 2
Alarm to Control Room
Initiate local panel alarm