Diff Pressure Transmitter - Huba-699
Diff Pressure Transmitter - Huba-699
Pressure and flow Huba Control Type 699 | Technical data subject to change | Edition 09/2020 1/5
Technical overview
Pressure range
Relative and differential -1 ... 1 mbar / 0 ... 0.3 – 50 mbar
Operating conditions
Medium Air and neutral gases
Medium / ambient 0 ... +70 ºC
Temperature Storage -10 ... +70 ºC
No condensation
< 3 mbar P1 = 50 mbar P2 = 4 mbar
Application at over pressure range
> 3 mbar P1 = 100 mbar P2 = 4 mbar
Tolerable overload on one side < 3 mbar P1 = -4 mbar P2 = -50 mbar
Application at under pressure range
> 3 mbar P1 = -4 mbar P2 = -100 mbar
ambient temperature 2 x overload
Rupture pressure
70 ºC 1.5 x overload
Electrical overview
Output 1) Power supply 1) Load Current consumption 2)
2 wire 4 ... 20 mA 8.0 ... 33 VDC < supply voltage
0.02 A
-8V
[Ohm] < 20 mA
0 ... 10 V 13.5 ... 33 VDC / 24 VAC ±15% > 10 kOhm < 10 mA
0 ... 20 mA 13.5 ... 33 VDC / 24 VAC ±15% < 500 Ohm < 30 mA
3 wire 4 ... 20 mA 13.5 ... 33 VDC / 24 VAC ±15% < 500 Ohm < 30 mA
0 ... 5 V 3) 6.5 ... 33 VDC / 24 VAC ±15% > 10 kOhm < 10 mA
Filter Response time switchable by off / 0.2s / 1s / 5s / 20s
Polarity reversal protection Short circuit proof and protected against polarity reversal. Each connection is protected against crossover up to max. supply voltage.
Dynamic response
Response time < 20 ms
Load cycle < 10 Hz
Protection standard
Without cover IP 00
IP 54
With cover
IP 65
Display
Double spaced per 8 digit alphanumeric
LCD Display
At additional backlight LCD-Display 30 mA current consumption
Module MODBUS RTU RS-485
Ranges of adjustment
The zero piont is adjustable by reset button.
The Full scale is adjustable by DIP-Switch and additional by the turbopoti.
Adjustability
Optional version with self configurable parameters (see order code selection table)
Electrical connection
Screw terminals for wire and stranded conductors up to 1.5 mm2
Cable gland with built-in strain relief PG11
Pressure connection
Connection pipe Ø 6.2 mm
Mounting instructions
Installation arrangement Recommendation: Vertical, (Factory calibration) with pressure connections downwards
Mounting Mounting bracket (integrated in case)
Tests / Admissions
UL
Electromagnetic compatibility CE-conformity acc. EN 61326-2-3
Weight
Without display ~ 90 g
With display ~ 100 g
Packaging
Single packaging in cardboard
Multiple packaging 20 / 40 / 120
Accuracy
Parameter Unit ±0.5 mbar 0 ... 1 mbar 0 ... 3 mbar 0 ... 5 mbar 0 ... 10 - 50 mbar
Tolerance zero point max. % fs ±1.0 ±1.0 ±0.7 ±0.7 ±0.7
Tolerance zero full scale max. % fs ±1.0 ±1.0 ±0.7 ±0.7 ±0.7
Resolution % fs 0.2 0.2 0.1 0.1 0.1
Total of linearity, hysteresis and repeatability max. % fs ±1.0 ±1.0 ±1.0 ±1.0 ±0.6
Long therm stability acc. to DIN EN 60770 % fs ±1.0 ±1.0 ±1.0 ±1.0 ±1.0
TC zero point 4) typ. % fs/10K ±0.2 ±0.2 ±0.2 ±0.1 ±0.1
TC zero point 4) max. % fs/10K ±1.0 ±1.0 ±0.5 ±0.4 ±0.4
TC sensitivity 4) typ. % fs/10K ±0.3 ±0.3 ±0.2 ±0.1 ±0.1
TC sensitivity 4) max. % fs/10K ±0.6 ±0.6 ±0.5 ±0.5 ±0.2
- no additional root-extracted errors Test conditions: 25 ºC, 45% rF, Power supply 24 VDC
- For changing diaphragm position, compensable with zero point reset TC z.p. / TC z.p. 0 … 70 ºC
1) 2) 3)
Adjustable by DIP-Switch At nominal pressure Additional adjustable by software (with LCD-Display only)
4)
TC = Temperature coefficient
2/5 Pressure and flow Huba Control Type 699 | Technical data subject to change | Edition 09/2020
1 2 3 4 5 6 7 8 9 10
Zero @ 50%
Zero @ 10%
0%
0% Pressure 100% -10%1) Pressure 90% -100%1) 0% 100%
Pressure
Tenfold DIP-Switch Pressure ranges in grades; stepless adjustable with Turbo-Poti / output signals / filter (off / on) / response curve (linear / root extracted)
Tenfold DIP-Switch with Display Pressure ranges in grades; stepless adjustable with Turbo-Poti / pressure units / pressure range character / output signals; additional
0 ... 5 V / filter (off / 0.2s / 1s / 5s / 20s) / response curve (linear / root extracted) / backlight (off / 5min / on)
1) 2)
under pressure max. acc. order code selection table = -50 Pa/ 100 Pa Accessories supplied loose
Pressure and flow Huba Control Type 699 | Technical data subject to change | Edition 09/2020 3/5
Dimensions in mm / Electrical connections
92 4
6 11.6
51
35.2
28
97
EN 60 715-TH 35-7.5
4/5 Pressure and flow Huba Control Type 699 | Technical data subject to change | Edition 09/2020