FDC 003 K
FDC 003 K
FDC 003 K
ra a
y
ar e
W Y
2
1. Introduction
1-1. Transportation
1-2. Preliminary Steps
1-3. Initial Setup
1-4. Important Safety Instructions
1-5. Maintenance, Service and Faults
2. Operation
2.1 Unpacking and inspection
2.2 UPS front and rear panel views
2.3 Installation Procedure
2.4 Forza Tracker monitoring software
3. Advanced operation
4. Troubleshooting
5. Storage and maintenance
6. Technical specifications
1-1. Transportation
• Make sure to transport the UPS system only in the original package to protect it against shock and impact.
• Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) at any time,
since this would cancel the protective earth of the UPS system and of all connected loads.
• Connect the UPS only to a grounded socket that meets electrical safety guidelines.
Locate the UPS near a wall socket. Do not use an extension cord between the UPS and the socket.
• In the event of an emergency, press the OFF/Enter button and disconnect the power cord from the AC mains to properly
disable the UPS. Do not allow any kind of liquid or foreign object to enter this UPS unit.
• Do not place beverages or any other containers with liquid on or nearby the unit.
• The UPS can be operated by any individuals with no previous experience.
• The voltage used by this UPS may be hazardous. The unit contains no user serviceable parts; do not attempt to
disassemble the unit. Only qualified service technicians can perform maintenance on the unit. Failure to adhere to this
could cause personal injury or equipment malfunction and void the warranty.
• Caution - risk of electric shock. Even after the unit is disconnected from the mains, components inside the UPS system
are still connected to the battery packs which are potentially dangerous.
• Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is
present and no hazardous voltage exists in the terminals of high capacity capacitors, such as BUS-capacitors. Servicing
of batteries should be performed or supervised by experts who possess the knowledge to closely follow all required
precautions.
• Caution: potentially hazardous voltages from the battery can still be present even after disconnecting the UPS from the
AC mains. Therefore, the positive and negative terminals of the battery shall de disconnected prior to performing any
maintenance or repair inside the unit.
• A battery can present the risk of short-circuit current and electrical shock. The following precautions should be taken:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
• When replacing the battery, make sure to use the same type and number of sealed lead-acid batteries specified.
• Do not dispose of batteries in a fire. Batteries may explode if exposed to high temperatures.
• Never try to open a battery. The cell contains a toxic electrolyte which is harmful to the skin and eyes.
• Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
• Do not dismantle the UPS system.
2. OPERATION
2-1. Unpacking and inspection
Remove the UPS from its package and make sure that all the following items are included:
• One UPS unit
• One user manual
• One monitoring software CD (ForzaTracker)
• One USB cable
• Warranty certificate
Carefully inspect the UPS to check for any damages that may have occurred during shipping. Should any evidence of
damage be found or if some parts are missing, do not turn the UPS on; you must immediately notify the carrier or dealer
where you purchased the unit.
2-2. UPS front and rear panel views
UPS front view picture
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to
the USB/RS-232 port, and the other end to the communication port of your PC. With the monitoring software installed, you
can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400
card in the UPS, it will provide advanced communication and monitoring options.
Note: The USB port and RS-232 port cannot be used at the same time.
Network/Fax/Phone port
Entrada Salida
• Connect a single line modem/phone/fax cable into the network surge-protection “IN” jack on the rear panel of the UPS.
• Connect a network cable from the OUT jack on the rear of the UPS to a port on a PC or network device such as a route.
Button Function
Turn on the UPS: Press and hold the ON/Mute button for at least 2 seconds
to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this
button for at least 5 seconds to disable or enable the alarm system.
ON/Mute Button This command would not apply when warnings or errors occur.
Up key: Press this button to display previous selection in the UPS
configuration menu.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds
to perform the self-test in AC mode, ECO mode, or converter mode.
Turn off the UPS: Press and hold this button for at least 2 seconds to turn
off the UPS in battery mode. The UPS will remain in standby mode under
normal power conditions or transfer to Bypass mode provided it has been
OFF/Enter Button
enabled previously by pressing this button.
Confirm selection key: Press this button to confirm the selection in the
UPS configuration menu.
Switch LCD message: Press this button to change the LCD message for
input voltage, input frequency, battery voltage, output voltage and output
frequency. The default display will be restored when pausing for 10 seconds.
Select Button Setting mode: Press and hold this button for 5 seconds to enter the UPS
configuration menu while UPS is in standby or bypass mode.
Down key: Press this button to display the next selection in the UPS
configuration menu.
Switch to bypass mode: When the utility power is normal, press ON/Mute
ON/Mute + and Select buttons simultaneously for 5 seconds to transfer the UPS to
Select Button bypass mode. This action will be ineffective if the input voltage is not within
an acceptable range.
Warning and fault code indicators. The meaning of the codes is listed
in the section below.
Mute operation
Indicates that the UPS alarm is disabled.
Overload indicator
Battery information
Parameter 1
Three parameters need to be configured
in order to set up the UPS. Refer to
following diagram.
Parameter 1: it is used for the different
configuration options. There are 10
programs to set up. Refer to the table
below.
Parameter 2 and parameter 3: they
represent the setting options or values of
each program.
Parameter 2 Parameter 3
Interface Setting
Parameter 3: Output voltage
For 200/208/220/230/240 VAC, you may choose any of the
following output voltages in parameter 3:
200: The output voltage is 200VAC
208: The output voltage is 208VAC
220: The output voltage is 220VAC
230: The output voltage is 230VAC
240: The output voltage is 240VAC
For 100/110/150/120/127 VAC, you may choose any of the
following output voltages :
100: The output voltage is 100VAC
110: The output voltage is 110VAC
115: The output voltage is 115VAC
120: The output voltage is 120VAC
127: The output voltage is 127VAC
Interface Setting
Interface Setting
Parameter 2 & 3: Output frequency setting.
Use this menu to define the initial frequency on battery mode:
BAT 50: The output frequency is set to 50Hz
BAT 60: The output frequency is set to 60Hz
If the converter mode is enabled, the following options
will be available:
CF 50: The output frequency is set to 50Hz
CF 60: The output frequency is set to 60Hz
Interface Setting
Interface Setting
Parameter 2 & 3: Press the UP or Down key to choose the
acceptable high and low voltage values for the ECO mode.
HLS: High line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC, the setting in parameter
3 ranges between +7V and +24V of the nominal voltage.
For 100/110/115/120/127 VAC, the setting in parameter 3
ranges between+3V and +12V of the nominal voltage.
LLS: Low line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC, the setting in parameter
3 ranges between-7V and -24V of the nominal voltage.
For 100/110/115/120/127 VAC, the setting in parameter
3 ranges from -3V to -12V of the nominal voltage.
Interface Setting
Interface Setting
Parameter 2 & 3: Press the UP or Down key to choose the
acceptable high and low voltage values for Bypass operation
HLS: High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264: High voltage setting from 230VAC to 264VAC
as set in parameter 3.
For 100/110/115/120/127 VAC:
120-132: High voltage setting from 120VAC to 132VAC
as set in parameter 3.
LLS: Low voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
170-220: Low voltage setting from 170VAC to 220VAC
as set in parameter 3.
For 100/110/115/120/127 VAC:
85-115: Low voltage setting from 85VAC to 115VAC
as set in parameter 3
Interface Setting
Parameter 3: Activates or cancels the programmable
outlet feature.
ENA: Programmable outlets enabled
DIS: Programmable outlets disabled
Interface Setting
Parameter 3: Sets the backup time limits for the
programmable outlets.
0-999: Use this setting to define the programmable outlets
backup time in minutes, from 0-999, in order to connect
non-critical devices on battery mode.
Interface Setting
Parameter 3: Sets up backup interval on battery mode
for default outlets.
0-999: Use this setting to define the default outlets backup
interval in minutes, from 0-999, to operate on battery mode.
0: When this parameter is set to “0”, the backup interval will
only last 10 seconds.
999: When this parameter is set to “999”, the backup interval
will be disabled.
Storage
Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage
is adjusted to 208VAC.