FDC 003 K

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

nt r

ra a
y
ar e
W Y
2

Downloaded from www.Manualslib.com manuals search engine


Table of contents

1. Introduction
1-1. Transportation
1-2. Preliminary Steps
1-3. Initial Setup
1-4. Important Safety Instructions
1-5. Maintenance, Service and Faults

2. Operation
2.1 Unpacking and inspection
2.2 UPS front and rear panel views
2.3 Installation Procedure
2.4 Forza Tracker monitoring software

3. Advanced operation

3.1 Description of buttons and functions


3.2 LCD Panel
3.3 Audible alarm
3.4 Abreviations on the LCD display
3.5 UPS parameter settings
3.6 Operating mode description
3.7 Fault codes
3.8 Warning indicators

4. Troubleshooting
5. Storage and maintenance
6. Technical specifications

Downloaded from www.Manualslib.com manuals search engine


1. Introduction
Thank you for purchasing the Forza Atlas 3000 Online UPS. To enjoy all the features and benefits of this unit, please read
and follow all installation and operation instructions thoroughly before unpacking, installing or operating this device. After
you have read this manual, keep it in a safe place for future reference.
The information contained in this manual covers the 3000 VA uninterruptible power system, its basic functions, operating
procedures, options available and troubleshooting guide. It also includes information on how to ship, store, handle, and
install the equipment.

1-1. Transportation
• Make sure to transport the UPS system only in the original package to protect it against shock and impact.

1-2. Preliminary steps


• Water condensation may occur if the UPS is unpacked in a very cold environment and then moved to a warmer location.
• The UPS must be thoroughly dry before being installed. Failure to do so may increase the risk of electric shock.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or near a heater or heating vent.
• Do not block ventilation holes in the UPS housing.

1-3. Initial setup


• Do not connect appliances or equipment that may overload the UPS system (such as a laser printer) to the output
sockets.
• Place cables in such a way that no one can step on or trip over them.
• Do not connect domestic appliances, such as hair dryers, to the UPS output sockets.
• Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS
system.
• Use CE-marked cables for connections between mains, the UPS and equipment (shockproof outlet).
• Use CE-marked power cables to connect the loads to the UPS system.
• During the installation of this equipment, make sure that the sum of the leakage currents of the UPS and the connected
loads shall not exceed 3.5 mA.

1-4. Important safety instructions

• Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) at any time,
since this would cancel the protective earth of the UPS system and of all connected loads.
• Connect the UPS only to a grounded socket that meets electrical safety guidelines.
Locate the UPS near a wall socket. Do not use an extension cord between the UPS and the socket.
• In the event of an emergency, press the OFF/Enter button and disconnect the power cord from the AC mains to properly
disable the UPS. Do not allow any kind of liquid or foreign object to enter this UPS unit.
• Do not place beverages or any other containers with liquid on or nearby the unit.
• The UPS can be operated by any individuals with no previous experience.

Downloaded from www.Manualslib.com manuals search engine


1-5. Maintenance, service and faults

• The voltage used by this UPS may be hazardous. The unit contains no user serviceable parts; do not attempt to
disassemble the unit. Only qualified service technicians can perform maintenance on the unit. Failure to adhere to this
could cause personal injury or equipment malfunction and void the warranty.
• Caution - risk of electric shock. Even after the unit is disconnected from the mains, components inside the UPS system
are still connected to the battery packs which are potentially dangerous.
• Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is
present and no hazardous voltage exists in the terminals of high capacity capacitors, such as BUS-capacitors. Servicing
of batteries should be performed or supervised by experts who possess the knowledge to closely follow all required
precautions.
• Caution: potentially hazardous voltages from the battery can still be present even after disconnecting the UPS from the
AC mains. Therefore, the positive and negative terminals of the battery shall de disconnected prior to performing any
maintenance or repair inside the unit.
• A battery can present the risk of short-circuit current and electrical shock. The following precautions should be taken:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
• When replacing the battery, make sure to use the same type and number of sealed lead-acid batteries specified.
• Do not dispose of batteries in a fire. Batteries may explode if exposed to high temperatures.
• Never try to open a battery. The cell contains a toxic electrolyte which is harmful to the skin and eyes.
• Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
• Do not dismantle the UPS system.

2. OPERATION
2-1. Unpacking and inspection
Remove the UPS from its package and make sure that all the following items are included:
• One UPS unit
• One user manual
• One monitoring software CD (ForzaTracker)
• One USB cable
• Warranty certificate
Carefully inspect the UPS to check for any damages that may have occurred during shipping. Should any evidence of
damage be found or if some parts are missing, do not turn the UPS on; you must immediately notify the carrier or dealer
where you purchased the unit.
2-2. UPS front and rear panel views
UPS front view picture

Downloaded from www.Manualslib.com manuals search engine


Rear panel view

1. Programmable outlets: connect to non-critical loads.


2. Output receptacles: connect to high critical loads.
3. AC input
4. Input circuit breaker
5. Network/Fax/Modem surge protection
6. Emergency power off (EPO) connector
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
10. Output terminal
11. Output circuit breaker
12. Input terminal

2.3. Installation procedure


Choose location
Install the UPS unit in any protected environment that provides adequate airflow around the unit, and free from excessive
dust, corrosive fumes and conductive contaminants. Do not operate your UPS in an environment where the ambient
temperature or humidity is high. For best performance, keep the indoor temperature between 0° C and 40° C. Place the
UPS unit at least 20 cm away from monitors to avoid interference.
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
• For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.
• For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA L5-130P.
Note: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when the UPS is plugged into an
improperly wired utility power outlet (refer to the troubleshooting section). A circuit breaker (40A) must also be provided
between the mains and AC input.
Step 2: UPS output connection
• For socket-type outputs, there two kinds of outputs: programmable outlets and general outlets. Connect non-critical
devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend
the backup time to critical devices by setting shorter backup time for non-critical devices.
• For terminal-type input or outputs, please follow the steps below for the wiring configuration:
a) Remove the terminal block cover by unscrewing the two screws.
b) We recommend using an AWG 14 or 2.1mm2 power cord, a AWG12-10 or 3.3mm2-5.3mm2 power cord for
the NEMA type.
c) Once the wiring configuration is complete, verify that the wires are securely attached.
d) Finally, replace the terminal cover and secure it using the screws.

Downloaded from www.Manualslib.com manuals search engine


Step 3: Communication connection
Communication port:
USB port RS-232 port Intelligent slot

To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to
the USB/RS-232 port, and the other end to the communication port of your PC. With the monitoring software installed, you
can schedule UPS shutdown/start-up and monitor UPS status through PC.

The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400
card in the UPS, it will provide advanced communication and monitoring options.
Note: The USB port and RS-232 port cannot be used at the same time.

Step 4: Connect the network surge protection


The UPS has two network cable jacks for network lines

Network/Fax/Phone port

Entrada Salida

• Connect a single line modem/phone/fax cable into the network surge-protection “IN” jack on the rear panel of the UPS.
• Connect a network cable from the OUT jack on the rear of the UPS to a port on a PC or network device such as a route.

Step 5: Disabling and enabling the EPO function


Keep pins 1 and 2 closed for UPS normal operation. To activate EPO feature, remove the wire between pin 1 and 2.

Closed for UPS normal


operation.

Step 6: Turning on the UPS


Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during
this initial charge period.
2-4. ForzaTracker monitoring software
ForzaTracker is a new generation of UPS monitoring software, which provides user-friendly interface to monitor and control
your UPS system. This unique software provides safe auto-shutdown for multi-computer systems during power failures. With
this software, users can monitor and control any UPS on the same LAN no matter how far they might be from the UPS.

Downloaded from www.Manualslib.com manuals search engine


Installation procedure for Windows users:
1. Use the supplied CD or go to the website: http://www.forzaups.com.
2. After clicking the software icon, choose the required operation system.
3. Follow the on-screen instructions to install the software.
4. When you finished downloading all required files, enter the serial No (installation password): 5242-87f6-64re-di8d-986u
to install the software (include the hyphens).
5. In order to access as Administrator, input the password: 111296.
6. When your computer restarts, the management software will appear as a light blue round icon located in the system
tray, near the clock.
For Mac users, please refer to the ForzaTracker QIG inside the Mac folder.
3. Advanced operation

3-1. Description of buttons and functions

Button Function

Turn on the UPS: Press and hold the ON/Mute button for at least 2 seconds
to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this
button for at least 5 seconds to disable or enable the alarm system.
ON/Mute Button This command would not apply when warnings or errors occur.
Up key: Press this button to display previous selection in the UPS
configuration menu.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds
to perform the self-test in AC mode, ECO mode, or converter mode.
Turn off the UPS: Press and hold this button for at least 2 seconds to turn
off the UPS in battery mode. The UPS will remain in standby mode under
normal power conditions or transfer to Bypass mode provided it has been
OFF/Enter Button
enabled previously by pressing this button.
Confirm selection key: Press this button to confirm the selection in the
UPS configuration menu.
Switch LCD message: Press this button to change the LCD message for
input voltage, input frequency, battery voltage, output voltage and output
frequency. The default display will be restored when pausing for 10 seconds.
Select Button Setting mode: Press and hold this button for 5 seconds to enter the UPS
configuration menu while UPS is in standby or bypass mode.
Down key: Press this button to display the next selection in the UPS
configuration menu.
Switch to bypass mode: When the utility power is normal, press ON/Mute
ON/Mute + and Select buttons simultaneously for 5 seconds to transfer the UPS to
Select Button bypass mode. This action will be ineffective if the input voltage is not within
an acceptable range.

Downloaded from www.Manualslib.com manuals search engine


3-2. LCD panel

Downloaded from www.Manualslib.com manuals search engine


Display Function
Backup time information
Indicates the remaining backup time in pie chart.

Indicates the remaining backup time in numbers.


H: hour, M: minute, S: second
Fault information
Indicates that the warning and fault occurs

Warning and fault code indicators. The meaning of the codes is listed
in the section below.
Mute operation
Indicates that the UPS alarm is disabled.

Output & battery voltage information

Output voltage, frequency or battery voltage.


VAC: output voltage VDC: battery voltage Hz: frequency
Load information

Load level indicator at 0-25%, 26-50%, 51-75%, and 76-100%


of its capacity

Overload indicator

Indicates the load or the UPS output is short circuited.

Programmable outlet information

Indicates that programmable management outlets are working

Mode operation information

Indicates the UPS is connected to the mains

Indicates the battery is working

Indicates the bypass circuit is working

Indicates the ECO mode is enabled

Indicates the Inverter circuit is working

Indicates the output receptacle is working

Battery information

Battery level indicator at 0-25%, 26-50%, 51-75%, and 76-100%


of its capacity

Battery fault indicator

Low battery level and low voltage indicator

Input & Battery voltage information

Input voltage or frequency or battery voltage indicator.


VAC: Input voltage, VDC: battery voltage, Hz: input frequency

Downloaded from www.Manualslib.com manuals search engine


3-3. Audible alarm

Battery mode Beeps once every 4 seconds

Low battery Beeps once every second

Overload Beeps twice every second

Fault Beeps continuously

Bypass mode Beeps every 10 seconds

3-4. Abbreviations on the LCD display

Abbreviation Display content Meaning


ENA Enable
DIS Disable
ESC Escape
HLS High line transfer
LLS Low line transfer
BAT Battery
CF Converter
EP EPO
TP Temperature
CH Charger

3-5. UPS parameter settings

Parameter 1
Three parameters need to be configured
in order to set up the UPS. Refer to
following diagram.
Parameter 1: it is used for the different
configuration options. There are 10
programs to set up. Refer to the table
below.
Parameter 2 and parameter 3: they
represent the setting options or values of
each program.
Parameter 2 Parameter 3

Downloaded from www.Manualslib.com manuals search engine


01: Output voltage settings

Interface Setting
Parameter 3: Output voltage
For 200/208/220/230/240 VAC, you may choose any of the
following output voltages in parameter 3:
200: The output voltage is 200VAC
208: The output voltage is 208VAC
220: The output voltage is 220VAC
230: The output voltage is 230VAC
240: The output voltage is 240VAC
For 100/110/150/120/127 VAC, you may choose any of the
following output voltages :
100: The output voltage is 100VAC
110: The output voltage is 110VAC
115: The output voltage is 115VAC
120: The output voltage is 120VAC
127: The output voltage is 127VAC

02: Frequency Converter enable/disable

Interface Setting

Parameter 2 & 3: Activates or cancels the converter mode


CF ENA: Enable converter mode
CF DIS: Disable converter mode

03: Output frequency settings

Interface Setting
Parameter 2 & 3: Output frequency setting.
Use this menu to define the initial frequency on battery mode:
BAT 50: The output frequency is set to 50Hz
BAT 60: The output frequency is set to 60Hz
If the converter mode is enabled, the following options
will be available:
CF 50: The output frequency is set to 50Hz
CF 60: The output frequency is set to 60Hz

04: ECO enable/disable

Interface Setting

Parameter 3: Activates or cancels the ECO mode:


ENA: ECO mode enabled
DIS: ECO mode disabled

Downloaded from www.Manualslib.com manuals search engine


05: ECO voltage range settings

Interface Setting
Parameter 2 & 3: Press the UP or Down key to choose the
acceptable high and low voltage values for the ECO mode.
HLS: High line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC, the setting in parameter
3 ranges between +7V and +24V of the nominal voltage.
For 100/110/115/120/127 VAC, the setting in parameter 3
ranges between+3V and +12V of the nominal voltage.
LLS: Low line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC, the setting in parameter
3 ranges between-7V and -24V of the nominal voltage.
For 100/110/115/120/127 VAC, the setting in parameter
3 ranges from -3V to -12V of the nominal voltage.

06: Bypass enable/disable when UPS is off

Interface Setting

Parameter 3: Use it to activate or cancel the Bypass mode.


ENA: Bypass enabled
DIS: Bypass disabled

07: Bypass voltage range setting

Interface Setting
Parameter 2 & 3: Press the UP or Down key to choose the
acceptable high and low voltage values for Bypass operation
HLS: High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264: High voltage setting from 230VAC to 264VAC
as set in parameter 3.
For 100/110/115/120/127 VAC:
120-132: High voltage setting from 120VAC to 132VAC
as set in parameter 3.
LLS: Low voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
170-220: Low voltage setting from 170VAC to 220VAC
as set in parameter 3.
For 100/110/115/120/127 VAC:
85-115: Low voltage setting from 85VAC to 115VAC
as set in parameter 3

Downloaded from www.Manualslib.com manuals search engine


08: Enable/Disable programmable outlets

Interface Setting
Parameter 3: Activates or cancels the programmable
outlet feature.
ENA: Programmable outlets enabled
DIS: Programmable outlets disabled

09: Backup time setting for programmable outlets

Interface Setting
Parameter 3: Sets the backup time limits for the
programmable outlets.
0-999: Use this setting to define the programmable outlets
backup time in minutes, from 0-999, in order to connect
non-critical devices on battery mode.

10: Backup time setting for outlets

Interface Setting
Parameter 3: Sets up backup interval on battery mode
for default outlets.
0-999: Use this setting to define the default outlets backup
interval in minutes, from 0-999, to operate on battery mode.
0: When this parameter is set to “0”, the backup interval will
only last 10 seconds.
999: When this parameter is set to “999”, the backup interval
will be disabled.

00: Exit setting

Downloaded from www.Manualslib.com manuals search engine


3-6. Operation mode description

Operating mode Description LCD display

When the input voltage is within acceptable range, the UPS


Online mode will supply pure and stable AC power to connected loads.
The UPS will also charge the battery in online mode.

Energy saving mode:


ECO mode When the input voltage is within the voltage regulation range,
the UPS will bypass voltage to loads for energy saving.

When input frequency is between 40 Hz and 70 Hz,


Frequency the UPS can be set at a constant output frequency,
Converter mode 50 Hz or 60 Hz. The UPS will still charge the battery when
operating in this mode.

When the input voltage exceeds the acceptable range or


Battery mode during a power failure, the UPS will start supplying power
from the battery while the alarm will beep every 4 seconds.

When input is within acceptable voltage range but the UPS


is overloaded, the UPS will transfer to bypass mode or it can
Bypass mode be manually changed to bypass mode using the front panel
controls. The alarm will sound once every 10 seconds
in this case.

The UPS is powered off and there is no power supplied to


Standby mode
the loads, but batteries can still be charged.

3-7. Fault codes

Fault event Fault Fault event Fault Icon


code code
Bus start failure 01 Low inverter voltage 13 X
Bus over 02 Inverter output is short circuited 14
Bus under 03 Battery voltage too high 27
Bus unbalance 04 Battery voltage too low 28
Inverter soft start failure 11 Excessive temperature 41 X
High inverter voltage 12 Overload 43

Downloaded from www.Manualslib.com manuals search engine


3-8. Warning indicators

Warning Icon (flashing) Alarm


Low battery Beeps once every second

Overload Beeps twice every second

Battery not connected Beeps once every second

Overcharge Beeps once every second

Site wiring fault Beeps once every second

EPO enable Beeps once every second

Over temperature Beeps once every second

Charger failure Beeps once every second

Out of bypass voltage range Beeps once every second

Downloaded from www.Manualslib.com manuals search engine


4. Troubleshooting guide
If the UPS system does not operate correctly, use the table below to troubleshoot the problem.

Symptom Possible cause Remedy


The AC input cable is not Check to make sure the power cord is
Even though the mains supply properly connected. firmly connected to a AC wall socket
is normal, there are no status
indicators or alarms. The AC input is connected
Plug the power cord to a wall socket.
to the UPS outlet.
The icon and the warning code
become illuminated on the Set the circuit in its closed position
EPO function is enabled
LCD display, and the alarm starts to disable the EPO function
beeping once every second.
The and the icons become Live and neutral
illuminated on the LCD display, Rotate mains power socket by 180°
conductors of UPS input
and the alarm starts beeping once are reversed. and then connect to UPS system
every second.
The and icons become
The external or internal
illuminated on the LCD display Check if all batteries are
battery connection
and the alarm starts beeping properly connected.
is incorrect.
once every second.
Fault code 27 and the
become illuminated on the LCD Battery voltage is too high
Contact your dealer or service center
display and alarm starts or the charger is fault
beeping continuously.
Fault code 28 and the
icon become illuminated on the Battery voltage is too low Please contact the dealer
LCD display and the alarm starts or the charger fails or service center
beeping continuously.
UPS is overloaded Remove excess loads from UPS output
UPS is overloaded.
Devices connected to the Remove excess loads from the
UPS are fed directly from UPS output
The and icons become
utility power via the Bypass
illuminated on the LCD display and
the alarm starts beeping twice After repetitive overloads, Remove excess loads from the UPS
every second the UPS is locked in output first. Shut down the UPS
Bypass mode. Connected completely before restarting the unit
devices are fed directly once again
from utility power.
Fault code 43 becomes illuminated The UPS shuts down
along with the icon on the automatically upon Remove excess loads from the UPS
LCD display, and the alarm starts detecting the overload output and restart the unit once again
beeping continuously condition in the output

Downloaded from www.Manualslib.com manuals search engine


Symptom Possible cause Remedy

Fault code 14 becomes illuminated The UPS shuts down


Check the output wiring and
along with the icon on the automatically upon
if connected devices are
LCD display, and the alarm starts detecting the overload
short-circuited.
beeping continuously. condition in the output.
A UPS internal fault has
occurred. There are two
possible causes:
Fault code 1, 2, 3, 4, 11, 12, 13
1. Power is continued to
and 41 become illuminated on Please contact the dealer or
be supplied to the load,
the LCD display, and alarm starts service center.
but is done directly from
beeping continuously.
the AC grid via a bypass.
2. Power is no longer
supplied to the load.
Charge the batteries for at least
Batteries are not fully 5 hours and then check their
Battery backup time is shorter
charged. capacity. If the problem persists,
than its nominal value.
consult your dealer.
Contact your dealer for
Defective batteries.
a replacement.

5. Storage and maintenance


The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient
temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer or
service center.

Batteries must not be discarded as regular household waste! As part of the


company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.

Storage

Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:

Storage temperature Recharge frequency Runtime


-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours

Downloaded from www.Manualslib.com manuals search engine


6. Specifications
Model FDC-003K
CAPACITY* 3000 VA / 2400 W
INPUT
160VAC / 140VAC / 120VAC / 110VAC ± 5 % or
80VAC / 70VAC / 60VAC / 50VAC ± 5 %
Low line transfer
(based on load percentage
100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Voltage range
Low line comeback High line transfer voltage - 10V
High line transfer 300 VAC ± 5 % or 150 VAC ± 5 %
High line comeback 290 VAC ± 5 % or 145 VAC ± 5 %
Frequency range 40Hz ~ 70 Hz
Phase Single phase with ground
Power factor ≥ 0.99 @ 220-230 VAC (input voltage)
OUTPUT
Output voltage 200/208/220/230/240VAC or 100/110/115/120/127 VAC
AC voltage regulation ± 3% (batt. mode)
Frequency range (synchronized range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency range (batt. mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
100%~110%: audible warning
110%-130%: UPS shuts down in 30 seconds in battery mode
Overload or transfers to bypass mode when utility power is normal.
>130%: UPS shuts down immediately in battery mode
or transfer to bypass mode when utility power is normal
Current crest ratio 3:1
≤3 % THD (linear load) ≤ 4 % THD (linear load)
Harmonic distortion
≤6 % THD (non-linear load) ≤ 7 % THD (non-linear load)
AC mode Zero
Transfer time to batt. mode
Inverter to bypass 4 ms (typical)
Waveform (batt. mode) Pure sine wave
EFFICIENCY
AC mode ~ 85% ~ 88%
Battery mode ~ 83%
BATTERY
Battery type 12 V / 9 Ah
Quantity 6
Recharge time 4 hours to 90% capacity (typical)
Charging current 1.0 A (max.)
Charging voltage 82.1 VDC ±1%
PHYSICAL
Dimensions (mm) 421 X 190 X 318
Tower case
Net weight (kg) 28
ENVIRONMENT
Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise level Less than 45dBA @ 1 meter
MANAGEMENT
Supports Windows® 2000/2003/XP/Vista/2008/7,
Smart RS-232 or USB Linux, Unix and MAC
Optional SNMP Power management from SNMP manager
and web browser

* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage
is adjusted to 208VAC.

Downloaded from www.Manualslib.com manuals search engine

You might also like