Siprotec Multi-Functional Protectiv Relays 7SJ61... 7SJ64 Overcurrent Protection 7SJ80 Motor Protection 7SK80
Siprotec Multi-Functional Protectiv Relays 7SJ61... 7SJ64 Overcurrent Protection 7SJ80 Motor Protection 7SK80
Siprotec Multi-Functional Protectiv Relays 7SJ61... 7SJ64 Overcurrent Protection 7SJ80 Motor Protection 7SK80
Applications 1
SIPROTEC Basics 2
Mapping 3
Multi-Functional Protectiv
Relays Literature, Index
7SJ61...7SJ64
Overcurrent Protection
7SJ80
Motor Protection
7SK80
IEC 61850
PIXIT
C53000-G1140-C211-4
Disclaimer of Liability Copyright
We have checked the text of this manual against the hardware and Copyright © Siemens AG 2010
software described. However, deviations from the description can- Dissemination or reproduction of this document, or evaluation and
not be completely ruled out, so that no liability can be accepted for communication of its contents, is not authorized except where ex-
any errors or omissions contained in the information given. pressly permitted. Violations are liable for damages. All rights re-
The information given in this document is reviewed regularly and served, particularly for the purposes of patent application or
any necessary corrections will be included in subsequent editions. trademark registration.
We appreciate any suggestions for improvement.
We reserve the right to make technical improvements without no- Registered Trademarks
tice. SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks
of Siemens AG. Other designations in this manual might be trade-
Document Release V04.20.00 marks whose use by third parties for their own purposes would in-
Edition 03.2010 fringe the rights of the owner.
General information about the effects of configuration of your device to the different Logical
Nodes and DOIs
Mapping of device relevant information to Logical Nodes as part of protocol IEC61850
Target audience
This manual is intended mainly for all persons who configure, parameterize and operate a
SIPROTEC Devices 7SJ61, 7SJ62, 7SJ63, 7SJ64, 7SJ80, 7SK80.
Standards
This document has been created according to the ISO 9001 quality standards.
Further Support
If you have questions about SIPROTEC IEC 61850 interface, please contact your Siemens sales
representative.
1 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Association model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3 Server model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.4 Data set model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.5 Substitution model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.6 Setting group control model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.7 Reporting model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.7.1 Unbuffered Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.7.2 Buffered Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.8 Logging model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.9 Generic substation model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.10 Transmission of sample values model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.11 Control model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1.12 Time and time synchronisation model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.13 File transfer model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.14 General items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.15 TISSUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.2 Effects of Configuration on the Logical Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2.1 Function parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2.2 Function parameters SIPROTEC 7SJ61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.2.3 Function parameters SIPROTEC 7SJ62/63/64 . . . . . . . . . . . . . . . . . . . . . . . . . 38
2.2.4 Function parameters SIPROTEC 7SJ80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.2.5 Function parameters SIPROTEC 7SK80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.3 Allocation of Logical Nodes to Logical Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
2.4 Logical Node LLN0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.4.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.4.2 Logical Devices MEAS, DR and EXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2.4.3 Logical Device CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.5 DOI Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2.5.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2.5.2 Logical Devices MEAS, CTRL, DR and EXT. . . . . . . . . . . . . . . . . . . . . . . . . . . 59
3 Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Literature
Index
Contents
This chapter specifies the protocol implementation extra information for testing (PIXIT) of the
IEC 61850 interface in SIPROTEC 7SJ6, 7SJ80, 7SK80.
1.1 General 10
1.15 TISSUES 28
1.1 General
This chapter specifies the protocol implementation extra information for testing (PIXIT) of the
IEC 61850 interface in SIPROTEC 7SJ6, 7SJ80, 7SK80.
It is based on the service subset definition given in the protocol implementation conformance
statement (PICS), which is specified within the user manual SIPROTEC 4 Ethernet Module
EN 100 IEC 61850 Electrical Interface 100 MBit, Manual /1/“.
The following applicable ACSI service models are specified:
Association model
Server model
Substitution model
Reporting model
Logging model
Control model
Time and time synchronisation model
General items
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test
according to IEC 61850-10.
The mapping between the IEC 61850 server data model and the SIPROTEC specific data is
specified in Chapter 3.
Maximum number of clients that can set-up 5 with IEC 61850 Protocol Update
an association simultaneously Version EN100 V04.02 and lower
Is authentication supported N
Where
Y means: as defined within the ICD-File
ANY means: any value accepted
What is the maximum and minimum MMS Max MMS PDU size 32768
PDU size ? Min MMS PDU size
<additional items>
Source:
Y Process
N Substituted
Y Test
Y OperatorBlocked
Source:
Y Process
Y Substituted
Y Test
Y OperatorBlocked
What is the maximum number of data Not restricted; depends on the max. MMS PDU size given
values in one GetDataValues request ? above.
What is the maximum number of data Not restricted; depends on the max. MMS PDU size given
values in one SetDataValues request ? above. No Data Attribute within our object directory is
writable with the service SetDataValues.
<additional items>
Maximum number of data elements in one Not limited by an internal configuration parameter. It
data set depends on the available memory.
How many persistent data sets can be 64 data sets for each LD. It depends on the available
created by one or more clients ? memory.
How many non-persistent data sets can be 10 data sets. It depends on the available memory.
created by one or more clients ?
additional items:
Maximum number of data sets Could not be defined, it depends on the available memory
space. In principle, this information it not necessary from
type conformance testing standpoint.
This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850
Electrical Interface 100 MBit, Manual /1/).
What is the number of supported setting Setting groups available for LLN0 only in LD PROT. The
groups for each logical device ? number of supported setting groups is 1 or 4, it depends
on the given configuration. Specified in the ICD-File.
What is the effect of when and how the Just SelectActiveSG service will supported according to
non-volatile storage is updated ? PICS.
(compare IEC 61850-8-1 $16.2.4)
<additional items>
Multi client URCB approach All clients can access all URCB’s
(Compare IEC 61850-7-2 $14.2.1)
additional items:
Dynamic URCB reservation after an abort Reservation of the URCB is lost. After a re-establishment
of the client/server association of the association the URCB reservation has to be done
by the client before. This behavior is implemented to
avoid unnecessary memory residuals if temporarily client
associations (e.g. for maintenance) are established.
Multi client BRCB approach All clients can access all BRCB’s
(Compare IEC 61850-7-2 $14.2.1)
What is the buffer size for each BRCB or About 1 MB are available for the buffering.
how many reports can be buffered ? Each BRCB has an extension attribute Memory that
display the percentage of those 1 MB that have been
reserved/forseen for its own entries.
Default amount 1 MB/(2*Number of logical devices)
additional items:
Dynamic BRCB reservation after an abort Reservation of the BRCB has been fixed with TISSUE
of the client/server association 453.
The value of the attribute ResvTms delivers the time
interval during which the reservation is still active after the
connection has been lost. In case a BRCB is still
reserved, and a client connects with the same IP address
as the one used during the reservation, then the BRCB
attribute can be written by this client without prior setting
the ResvTms attribute as long as the reservation timer
has not expired.
Configured BRCB reservation after an Reservation of the BRCB is not lost for BRCBs that have
abort of the client/server association been pre-associated to a specific client (pre-association
defined with means of the CLientLN element with the
BRCB instantiation in the SCD file).
Reservation of a BRCB is lost for BRCBs, that have not
been pre-associated to a specific client, after the
expiration of the reservation timer set with the ResvTms
attribute. In case ResvTms is not set (backward
compatibility), ResvTms will get a default value for all
preconfigured BRCBs that are not pre-associated to a
specific client.
Optional use of a flow control for As specified in the IEC61850-7-2, transmission of entries
transmitting history of a BRCB may required some times, depending of the amount of
entries that have to be transmitted.
Therefore, the SIPROTEC has an optional flow control
feature to accelerate the transmission of the entries: each
BRCB has an extended attribute MaxOutReports that can
be set from the associated-client to change the
transmmision strategy of the entries. The number ordered
will then be transmitted as long as they exist in the buffer;
the server then reset the attribute to 0 and wait for the
client to set it again in order to continue the history
transmission with MaxOutReports entries. The attribute
only influences the flow control of entries while dealing
with the history, and not after the history transmission has
completed.
This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850
Electrical Interface 100 MBit, Manual /1/).
What is the behavior when one subscribed The telegram will be discarded (i.e not forwarded to the
GOOSE message isn’t received or application) since it is corrupt or syntactically incorrect
syntactically incorrect ? and therefore not readable. The data objects will be
declared as invalid after a timeout detection since no
telegram have been received by the application.
What is the behavior when a subscribed Error message will be stored into the error buffer (could
GOOSE message is out-of-order ? be accessed by EN100 web-server).
All expected data objects will be declared as invalid.
What is the behavior when a subscribed The sequence number given in the GOOSE-message is
GOOSE message is duplicated ? out-of-order. Error message will be stored into the error
buffer (could be accessed by EN100 web-server).
All expected data objects will be declared as invalid.
additional items:
Maximum number of GOOSE messages <= 128 ; It depends on the available memory.
which could be received
GOOSE subscriber behavior in case of After a GOOSE multicast application association has
missing GOOSE messages been interrupted, the reception of the second consecutive
GOOSE telegram is required to validate the state of this
GOOSE association again.
However, the IED tolerates a missing telegram as long as
the next telegram (expected n, received n+1) is received
within the time allowed to live time out detection (the time
allowed to live timeout detection occurs after 2*TAL).
GOOSE subscriber behaviour in case of If a message is received twice or more, the IED already
multiple GOOSE messages reports an error after the second reception. Therefore,
network configuration error can be more easily tracked.
What is the behavior when a GOOSE Error message will be stored into the error buffer (could
header parameter is mismatching with the be accessed by EN100 web-server).
expected one? All expected data objects will be declared as invalid.
(datSet, goID, confRev, numDatSetEntries,
number of allData)
What is the behavior when a Error message will be stored into the error buffer (could
timeAllowedToLive is 0? be accessed by EN100 web-server) since the
timeAllowedToLive expired.
All expected data objects will be declared as invalid.
What is the behavior when there is an out- The confRev attribute in the header guarantees that the
of-order entry in the allData? allData entries are in the correct order. Therefore, it’s
necessary to check the confRev attribute. There is no
chance to detect such an out-of-order.
What is the behavior when no telegram is To avoid an incorrect timeout detection, the subscriber
received within a TAL timeout? detects a timeout after a period of 2×TAL.
The information is then declared as questionable,
oldData.
What is the behavior when a GOOSE Since the goCBRef shall be unique stationwide, the
header parameter goCBRef is mismatching received telegram with the mismatched goCBRef will be
with the expected one? discarted: it has not been published. In that case only the
timeout detection will set the data to invalid.
What is the behavior when a GOOSE The APPID is a link layer parameter. It is used as a filter
header parameter APPID is mismatching on link layer. If the APPID is mismatching, the tellegram
with the expected one? will therefore be discarded on link layer without notifying
the application. Only the timeout detection will set the
data to invalid.
What is the behavior when a GOOSE The t parameter is not checked. Therefore it doesn't lead
header parameter t is not increasing? to any error detection.
What is the behavior when The telegram is discarded since it is corrupt (not well
numDatSetEntries and number of allData formed). After the timeout detection (no telegram
are inconsistent? forwarded to the application) the data objects are
declared invalid.
Compare the “Implementation Guidelines for Electrical Current and Voltage Transducers
according to IEC 60044-7/8 with Digital Output according to IEC 61850-9-2; Version 1.0; as
specified by ABB, Areva, Landis+Gyr, OMICRON and SIEMENS
This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850
Electrical Interface 100 MBit, Manual /1/).
What is the behavior when the test attribute Will be acknowledged with negative response. The
is set in the SelectWithValue and/or AddCause attribute will be set to “not supported”
Operate request ?
What are the conditions for the time (T) Time attribute is not relevant.
attribute in the SelectWithValue and/or
Operate request ?
Is “operate-many” supported ? N
additional items:
Inconsistency between Select and (Oper or Oper or cancel will be acknowledged with negative
cancel) response if inconsistencies to the select request are
detected.
The following attributes will not be checked in this case:
T (Time)
What is the behavior when the time The quality attribute “ClockFailure” will be set to TRUE
synchronization signal/messages are lost ? after a configured time period.
What is the behaviour when the time A stratum with a value greater than 3 with the SNTP time
synchronisation messages indicate that the synchronization messages indicates that the time server
stratum is greater than 3? has a questionable synchronisation.
It might also indicate that no GPS connection are
available.
Therefore the time quality attribute
“ClockNotSynchronized” will be set to TRUE as long as
the stratum content is greater than 3.
additional items:
What is the behavior at start up time when The “ClockNotSynchronized” attribute is set to TRUE as
a time synchronization via SNTP is long as no time synchronization is established.
configured ?
What is the resulting behavior if no file If no file specification is present in the directory request,
specification is present in the file directory all files are returned - not only the files in the root
request? directory.
additional items:
IED behavior when the Logical Device Unlike the definition of the Data Objects “Mod/Beh” in IEC
is blocked : LLN0.Mod.stVal = blocked 61850-7-4, outputs to the process will be generated.
Details to this behavior are specified in SIPROTEC 4
Ethernet Module EN 100 IEC 61850 Electrical Interface
100 MBit, Manual /1/
additional items:
What is the type of the attribute actVal in The type is integer 32 (INT32).
the BCR (Binary Counter Reading) CDC?
1.15 TISSUES
1.15 TISSUES
Contents
This chapter contains general information about the effects of device configuration on Logical
Nodes and DOIs.
2.1 General 32
2.1 General
The protocol IEC 61850 was developed to define a standard that can be internationally
employed for the transmission of power automation system data.
This cross national standard enables an interoperability between automation systems and
devices made by different manufacturers.
The devices and high voltage bay control units of the SIPROTEC 4 series can be equipped with
an Ethernet module EN100 via which the protocol IEC 61850 is interpreted.
The configuration of the protocol and the integration of the device with redundant IEC 61850
interfaces in your network are performed via the configuration system DIGSI.
For details please refer to the manuals:
SIPROTEC 4 Ethernet Module EN 100 IEC 61850 Electrical Interface 100 MBit, Manual /1/
and
SIPROTEC 4 System Description /2/.
Note
The following definitions are taken mainly from standard IEC 61850, Technical Specification
IEC TS 61850-2.
Logical Devices
LD Logical Devices represent a functional structuring of the LN Logical Nodes of a SIPROTEC
device.
The following Logical Devices are present:
Logical Device Protection PROT
2.1 General
Logical Node LN
Smallest part of a function that exchanges data. A logical node is an object defined by its data
and methods.
Depending on the configuration of the function parameters the functions of the SIPROTEC are
enabled or disabled. If a function is disabled, the corresponding Logical Node is not available.
The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.
Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes
Enabled RDRE1
Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes (Forts.)
Enabled PMSS1
Enabled PMRI1
Enabled PMLJ1
Enabled RBRF1
Enabled RREC1
Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes (Forts.)
The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.
Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes
Enabled RDRE1
Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)
130 (sens.) Ground fault dir. characteristic cos ϕ / sin ϕ see Parameter 131
Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)
Enabled PMSS1
Enabled PMRI1
Enabled PMLJ1
Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)
SYNCHROCHECK RSYN1
SYNCHROCHECK RSYN2
SYNCHROCHECK RSYN3
SYNCHROCHECK RSYN4
Enabled RBRF1
Enabled RREC1
Enabled RFLO1
Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)
The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.
Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes
Enabled RDRE1
Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes (Forts.)
130 (sens.) Ground fault dir. characteristic cos ϕ / sin ϕ see Parameter 131
Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes (Forts.)
Enabled RBRF1
Enabled RREC1
Enabled RFLO1
The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.
Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes
Enabled RDRE1
Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes (Forts.)
130 (sens.) Ground fault dir. characteristic cos ϕ / sin ϕ see Parameter 131
Enabled PMSS1
Enabled PMRI1
Enabled PMLJ1
Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes (Forts.)
Enabled RBRF1
All Logical Nodes (LN) are allocated to Logical Devices (LD). The following tables show this
allocation and the DOIs available for each LN.
LD PROT
The Logical Device PROT (Protection) contains the following LNs:
LN Function DOI
PTOC6 50/51 (Charac. Phase) Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC7
PTOC1
PTOC18
PTRC2
PTOC8 50N/51N (Charac. Ground) Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC9
PTOC2
PRTC2
PTOC10 67, 67-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC11
PTOC3
PTRC3
PTOC12 67N, 67N-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC13
PTOC4
PRTC2
LN Function DOI
PMRI1 66 Startup Counter for Motors Mod, Beh, Health, NamPlt, Op, StrInhTmm
PMLJ1 Load Jam Protection Mod, Beh, Health, NamPlt, Str, Op, LDJamAlm,
ChgSet
PTUF1 81 Underfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV
PTUF2
PTUF3
PTUF4
PTOF1 81 Overfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV
PTOF2
PTOF3
PTOF4
PTTR1 49 Thermal Overload Protection Mod, Beh, Health, NamPlt, Str, Op, AlmThm
RFLO1 Fault Locator Mod, Beh, Health, NamPlt, FltZ, FltDiskm, FltDisPrc
RBRF1 50BF Breaker Failure Protection Mod, Beh, Health, NamPlt, Str, OpEx, OpIn
LD MEAS
The Logical Device MEAS (Measurement) contains the following LNs:
LN Function DOIs
MSQI1 Measured values, symmetrical Mod, Beh, Health, NamPlt, SeqA, SeqV
components
LD DR
The Logical Device DR (Disturbance Recorder) contains the following LNs:
LN Function DOIs
RDRE1 Oscillographic Fault Records Mod, Beh, Health, NamPlt, RcdMade, RcdStr
FltNum, GriFltNum
LD CTRL
The Logical Device CTRL (Control) contains the following LNs:
LN Function DOIs
CALH1 Error with a summary alarm and Mod, Beh, Health, NamPlt, GrAlm, GrWrn,
Alarm summary event ErrBoard1, ErrBoard2, ErrBoard3, ErrBoard4,
ErrBoard5, ErrBoard6, ErrBoard7
LD EXT
The Logical Device EXT (Extended) contains the following LNs:
LN Function DOIs
The Logical Nodes of the switching (and userdefined) objects will be created by DIGSI during
the parameterization of your SIPROTEC device.
MICS, Model Implementation Conformance Statement, shows the assignment of the DOIs;
you can use DIGSI to print the MICS.
LLN0.Mod
No. Information
LLN0.Mod.stVal 5 1 2 3 4
LLN0.Beh
No. Information
LLN0.Beh.stVal 5 1 2 3 4
LLN0.Health
No. Information
LLN0.Health.stVal 3 1
LLN0.OpTmh
1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)
LLN0.Mod
No. Information
LLN0.Mod.stVal 4 3 2 1
LLN0.Beh
No. Information
LLN0.Beh.stVal 5 1 2 3 4
LLN0.Health
No. Information
LLN0.Health.stVal 3 1
LLN0.OpTmh
1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)
LLN0.Mod
No. Information
LLN0.Mod.stVal 4 3 2 1 5
LLN0.Beh
No. Information
LLN0.Beh.stVal 4 3 2 1 5
LLN0.Health
No. Information
LLN0.Health.stVal 3 1
LLN0.OpTmh
1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)
For the Logical Nodes of the PROT Logical Device, LNx.Beh.stVal is formed from
LNx.Mod.stVal of the Logical Node and the status of the following device messages:
Test mode (Test mode),
No. Information
LNx .Mod.stVal 5 1 1 1 1 2 2 x
LNx.Beh.stVal 5 1 3 2 4 2 4 5
For the Logical Nodes of the MEAS, CTRL, DR and EXT Logical Devices, LNx.Beh.stVal is
formed from LNx.Mod.stVal of the Logical Node and the status of the following device
messages:
Test mode (Test mode),
No. Information
LNx .Mod.stVal 5 1 1 1 1 2 2
LNx.Beh.stVal 5 1 3 2 4 2 4
Contents
This chapter shows the mapping of the information relevant to the device on the Logical Node of
protocol IEC61850. It is structured according to function. In Chapter 2 you can find what
consequences non-configured functions have on the Logical Nodes as well as general
information about IEC 61850 mapping of information.
3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) 131
LPHD1.DevStr
No. Information
67 Resume (Resume) 0 1 0 1
LPHD1.DevStr.stVal T 2 1 T
LPHD1.Proxy
No. Information
LPHD1.Proxy.stVal 1 0
LPHD1.PhyHealth
No. Information
LPHD1.PhyHealth.stVal 3 1
CALH1.Mod
No. Information
CALH1.Mod.stVal 1 5
CALH1.Health
No. Information
CALH1.Health.stVal 3 1
CALH1.GrAlm
No. Information
CALH1.GrAlm.stVal 1 0
CALH1.GrWrn
No. Information
CALH1.GrWrn.stVal 1 0
CALH1.ErrBoard1
No. Information
CALH1.ErrBoard1.stVal 1 0
CALH1.ErrBoard2
No. Information
CALH1.ErrBoard2.stVal 1 0
CALH1.ErrBoard3
No. Information
CALH1.ErrBoard3.stVal 1 0
CALH1.ErrBoard4
No. Information
CALH1.ErrBoard4.stVal 1 0
CALH1.ErrBoard5
No. Information
CALH1.ErrBoard5.stVal 1 0
CALH1.ErrBoard6
No. Information
CALH1.ErrBoard6.stVal 1 0
CALH1.ErrBoard7
No. Information
CALH1.ErrBoard7.stVal 1 0
RDRE1.Mod
No. Information
RDRE1.Mod.stVal 1
RDRE1.Health
No. Information
RDRE1.Health.stVal 3 1
RDRE1.RcdMade
No. Information
RDRE1.RcdMade.stVal 1 0
RDRE1.FltNum
RDRE1.GriFltNum
RDRE1.RcdStr
No. Information
RDRE1.RcdStr.stVal 0 1
PTOC6.Mod
No. Information
PTOC6.Mod.stVal 5 5 2 2 1
PTOC6.Health
No. Information
PTOC6.Health.stVal 3 1
PTOC6.Str
No. Information
PTOC6.Str.general 0 1
PTOC6.Op
No. Information
PTOC6.Op.general 0 1
PTOC6.ChgSet
No. Information
PTOC6.ChgSet.stVal 0 1
PTOC7.Mod
No. Information
PTOC7.Mod.stVal 5 5 2 2 1
PTOC7.Health
No. Information
PTOC7.Health.stVal 3 1
PTOC7.Str
No. Information
PTOC7.Str.general 0 1
PTOC7.Op
No. Information
PTOC7.Op.general 0 1
PTOC7.ChgSet
No. Information
PTOC7.ChgSet.stVal 0 1
PTOC1.Mod
No. Information
51 PICKUP (P1207) = ∞ x 1 0 0 0
PTOC1.Mod.stVal 5 5 2 2 1
PTOC1.Health
No. Information
PTOC1.Health.stVal 3 1
PTOC1.Str
No. Information
PTOC1.Str.general 0 1
PTOC1.Op
No. Information
PTOC1.Op.general 0 1
PTOC1.ChgSet
No. Information
PTOC1.ChgSet.stVal 0 1
PTOC18.Mod
No. Information
50-3 PICKUP(P1217) = ∞ x 1 0 0 0
PTOC18.Mod.stVal 5 5 2 2 1
PTOC18.Health
No. Information
PTOC18.Health.stVal 3 1
PTOC18.Str
No. Information
PTOC18.Str.general 0 1
PTOC18.Op
No. Information
PTOC18.Op.general 0 1
PTOC18.ChgSet
No. Information
PTOC18.ChgSet.stVal 0 1
PTOC8.Mod
No. Information
PTOC8.Mod.stVal 5 5 2 2 1
PTOC8.Health
No. Information
PTOC8.Health.stVal 3 1
PTOC8.Str
No. Information
PTOC8.Str.general 0 1
PTOC8.Op
No. Information
PTOC8.Op.general 0 1
PTOC8.ChgSet
No. Information
PTOC8.ChgSet.stVal 0 1
PTOC9.Mod
No. Information
PTOC9.Mod.stVal 5 5 2 2 1
PTOC9.Health
No. Information
PTOC9.Health.stVal 3 1
PTOC9.Str
No. Information
PTOC9.Str.general 0 1
PTOC9.Op
No. Information
PTOC9.Op.general 0 1
PTOC9.ChgSet
No. Information
PTOC9.ChgSet.stVal 0 1
PTOC2.Mod
No. Information
PTOC2.Mod.stVal 5 5 2 2 1
PTOC2.Health
No. Information
PTOC2.Health.stVal 3 1
PTOC2.Str
No. Information
PTOC2.Str.general 0 1
PTOC2.Op
No. Information
PTOC2.Op.general 0 1
PTOC2.ChgSet
No. Information
PTOC2.ChgSet.stVal 0 1
PTRC2.Mod
No. Information
PTRC2.Mod.stVal 5 2 2 1
PTRC2.Health
No. Information
PTRC2.Health.stVal 3 1
PTRC2.Str
No. Information
PTRC2.Str.general 0 1
PTRC2.Str.dirGeneral
No. Information
PTRC2.Str.dirGeneral 0
PTRC2.Str.phsA
No. Information
PTRC2.Str.phsA 0 1
PTRC2.Str.dirPhsA
No. Information
PTRC2.Str.dirPhsA 0
PTRC2.Str.phsB
No. Information
PTRC2.Str.phsB 0 1
PTRC2.Str.dirPhsB
No. Information
PTRC2.Str.dirPhsB 0
PTRC2.Str.phsC
No. Information
PTRC2.Str.phsC 0 1
PTRC2.Str.dirPhsC
No. Information
PTRC2.Str.dirPhsC 0
PTRC2.Str.neut
No. Information
PTRC2.Str.neut 0 1
PTRC2.Str.dirNeut
No. Information
PTRC2.Str.dirNeut 0
PTRC2.Op
No. Information
PTRC2.Op.general 0 1
PTOC10.Mod
No. Information
PTOC10.Mod.stVal 5 5 2 2 1
PTOC10.Health
No. Information
PTOC10.Health.stVal 3 1
PTOC10.Str
No. Information
PTOC10.Str.general 0 1
PTOC10.Op
No. Information
PTOC10.Op.general 0 1
PTOC10.ChgSet
No. Information
PTOC10.ChgSet.stVal 0 1
PTOC11.Mod
No. Information
PTOC11.Mod.stVal 5 5 2 2 1
PTOC11.Health
No. Information
PTOC11.Health.stVal 3 1
PTOC11.Str
No. Information
PTOC11.Str.general 0 1
PTOC11.Op
No. Information
PTOC11.Op.general 0 1
PTOC11.ChgSet
No. Information
PTOC11.ChgSet.stVal 0 1
PTOC3.Mod
No. Information
PTOC3.Mod.stVal 5 5 2 2 1
PTOC3.Health
No. Information
PTOC3.Health.stVal 3 1
PTOC3.Str
No. Information
PTOC3.Str.general 0 1
PTOC3.Op
No. Information
PTOC3.Op.general 0 1
PTOC3.ChgSet
No. Information
PTOC3.ChgSet.stVal 0 1
PTOC12.Mod
No. Information
PTOC12.Mod.stVal 5 5 2 2 1
PTOC12.Health
No. Information
PTOC12.Health.stVal 3 1
PTOC12.Str
No. Information
PTOC12.Str.general 0 1
PTOC12.Op
No. Information
PTOC12.Op.general 0 1
PTOC12.ChgSet
No. Information
PTOC12.ChgSet.stVal 0 1
PTOC13.Mod
No. Information
PTOC13.Mod.stVal 5 5 2 2 1
PTOC13.Health
No. Information
PTOC13.Health.stVal 3 1
PTOC13.Str
No. Information
PTOC13.Str.general 0 1
PTOC13.Op
No. Information
PTOC13.Op.general 0 1
PTOC13.ChgSet
No. Information
PTOC13.ChgSet.stVal 0 1
PTOC4.Mod
No. Information
M.of PU TD (P1630) = ∞ x 1 0 0 0
PTOC4.Mod.stVal 5 5 2 2 1
PTOC4.Health
No. Information
PTOC4.Health.stVal 3 1
PTOC4.Str
No. Information
PTOC4.Str.general 0 1
PTOC4.Op
No. Information
PTOC4.Op.general 0 1
PTOC4.ChgSet
No. Information
PTOC4.ChgSet.stVal 0 1
PTRC3.Mod
No. Information
PTRC3.Mod.stVal 5 2 2 1
PTRC3.Health
No. Information
PTRC3.Health.stVal 3 1
PTRC3.Str
No. Information
PTRC3.Str.general 0 1
PTRC3.Str.dirGeneral
No. Information
PTRC3.Str.dirGeneral 0 0 1 2 3
PTRC3.Str.phsA
No. Information
PTRC3.Str.phsA 0 1
PTRC3.Str.dirPhsA
No. Information
PTRC3.Str.dirPhsA 0 0 1 2 3
PTRC3.Str.phsB
No. Information
PTRC3.Str.phsB 0 1
PTRC3.Str.dirPhsB
No. Information
PTRC3.Str.dirPhsB 0 0 1 2 3
PTRC3.Str.phsC
No. Information
PTRC3.Str.phsC 0 1
PTRC3.Str.dirPhsC
No. Information
PTRC3.Str.dirPhsC 0 0 1 2 3
PTRC3.Str.neut
No. Information
PTRC3.Str.neut 0 1
PTRC3.Str.dirNeut
No. Information
PTRC3.Str.dirNeut 0 0 1 2 3
PTRC3.Op
No. Information
PTRC3.Op.general 0 1
PTOC16.Mod
No. Information
PTOC16.Mod.stVal 5 5 2 2 1
PTOC16.Health
No. Information
PTOC16.Health.stVal 3 1
PTOC16.Str
No. Information
PTOC16.Str.general 0 1
PTOC16.Op
No. Information
PTOC16.Op.general 0 1
PTOC17.Mod
No. Information
PTOC17.Mod.stVal 5 5 2 2 1
PTOC17.Health
No. Information
PTOC17.Health.stVal 3 1
PTOC17.Str
No. Information
PTOC17.Str.general 0 1
PTOC17.Op
No. Information
PTOC17.Op.general 0 1
PTUV1.Mod
No. Information
PTUV1.Mod.stVal 5 2 2 1
PTUV1.Health
No. Information
PTUV1.Health.stVal 3 1
PTUV1.Str
No. Information
PTUV1.Str.general 0 1 1
PTUV1.Op
No. Information
PTUV1.Op.general 0 1
PTUV2.Mod
No. Information
PTUV2.Mod.stVal 5 2 2 1
PTUV2.Health
No. Information
PTUV2.Health.stVal 3 1
PTUV2.Str
No. Information
PTUV2.Str.general 0 1 1
PTUV2.Op
No. Information
PTUV2.Op.general 0 1
PTOV1.Mod
No. Information
PTOV1.Mod.stVal 5 2 2 1
PTOV1.Health
No. Information
PTOV1.Health.stVal 3 1
PTOV1.Str
No. Information
PTOV1.Str.general 0 1
PTOV1.Op
No. Information
PTOV1.Op.general 0 1
PTOV2.Mod
No. Information
PTOV2.Mod.stVal 5 2 2 1
PTOV2.Health
No. Information
PTOV2.Health.stVal 3 1
PTOV2.Str
No. Information
PTOV2.Str.general 0 1
PTOV2.Op
No. Information
PTOV2.Op.general 0 1
PTOC14.Mod
No. Information
PTOC14.Mod.stVal 5 2 2 1
PTOC14.Health
No. Information
PTOC14.Health.stVal 3 1
PTOC14.Str
No. Information
PTOC14.Str.general 0 1
PTOC14.Op
No. Information
PTOC14.Op.general 0 1
PTOC15.Mod
No. Information
PTOC15.Mod.stVal 5 2 2 1
PTOC15.Health
No. Information
PTOC15.Health.stVal 3 1
PTOC15.Str
No. Information
PTOC15.Str.general 0 1
PTOC15.Op
No. Information
PTOC15.Op.general 0 1
PTOC5.Mod
No. Information
PTOC5.Mod.stVal 5 2 2 1
PTOC5.Health
No. Information
PTOC5.Health.stVal 3 1
PTOC5.Str
No. Information
PTOC5.Str.general 0 1
PTOC5.Op
No. Information
PTOC5.Op.general 0 1
PMSS1.Mod
No. Information
PMSS1.Mod.stVal 5 2 2 1
PMSS1.Health
No. Information
PMSS1.Health.stVal 3 1
PMSS1.Str
No. Information
PMSS1.Str.general 0 1
PMSS1.Op
No. Information
PMSS1.Op.general 0 1
PMRI1.Mod
No. Information
PMRI1.Mod.stVal 5 2 1
PMRI1.Health
No. Information
PMRI1.Health.stVal 3 1
PMRI1.Op
No. Information
PMRI1.Op.general 0 1
PMRI1.StrInhTmm
PMLJ1.Mod
No. Information
PMLJ1.Mod.stVal 5 5 2 1
PMLJ1.Health
No. Information
PMLJ1.Health.stVal 3 1
PMLJ1.Str
No. Information
PMLJ1.Str.general 0 1
PMLJ1.Op
No. Information
PMLJ1.Op.general 0 1
PMLJ1.LodJamAlm
No. Information
PMLJ1.LodJamAlm.stVal 0 1
PMLJ1.ChgSet
No. Information
PMLJ1.ChgSet.stVal 0 1
PTUF1.Mod
No. Information
PTUF1.Mod.stVal 5 5 2 2 2 1
PTUF1.Health
No. Information
PTUF1.Health.stVal 3 1
PTUF1.Str
No. Information
PTUF1.Str.general 0 0 0 1
PTUF1.Op
No. Information
PTUF1.Op.general 0 0 0 1
PTUF1.BlkV
No. Information
PTUF1.BlkV.stVal 0 0 0 1
PTUF2.Mod
No. Information
PTUF2.Mod.stVal 5 5 2 2 2 1
PTUF2.Health
No. Information
PTUF2.Health.stVal 3 1
PTUF2.Str
No. Information
PTUF2.Str.general 0 0 0 1
PTUF2.Op
No. Information
PTUF2.Op.general 0 0 0 1
PTUF2.BlkV
No. Information
PTUF2.BlkV.stVal 0 0 0 1
PTUF3.Mod
No. Information
PTUF3.Mod.stVal 5 5 2 2 2 1
PTUF3.Health
No. Information
PTUF3.Health.stVal 3 1
PTUF3.Str
No. Information
PTUF3.Str.general 0 0 0 1
PTUF3.Op
No. Information
PTUF3.Op.general 0 0 0 1
PTUF3.BlkV
No. Information
PTUF3.BlkV.stVal 0 0 0 1
PTUF4.Mod
No. Information
PTUF4.Mod.stVal 5 5 2 2 2 1
PTUF4.Health
No. Information
PTUF4.Health.stVal 3 1
PTUF4.Str
No. Information
PTUF4.Str.general 0 0 0 1
PTUF4.Op
No. Information
PTUF4.Op.general 0 0 0 1
PTUF4.BlkV
No. Information
PTUF4.BlkV.stVal 0 0 0 1
PTOF1.Mod
No. Information
PTOF1.Mod.stVal 5 5 5 2 2 2 1
PTOF1.Health
No. Information
PTOF1.Health.stVal 3 1
PTOF1.Str
No. Information
PTOF1.Str.general 0 0 1 0
PTOF1.Op
No. Information
PTOF1.Op.general 0 0 1 0
PTOF1.BlkV
No. Information
PTOF1.BlkV.stVal 0 0 1 0
PTOF2.Mod
No. Information
PTOF2.Mod.stVal 5 5 5 2 2 2 1
PTOF2.Health
No. Information
PTOF2.Health.stVal 3 1
PTOF2.Str
No. Information
PTOF2.Str.general 0 0 1 0
PTOF2.Op
No. Information
PTOF2.Op.general 0 0 1 0
PTOF2.BlkV
No. Information
PTOF2.BlkV.stVal 0 0 1 0
PTOF3.Mod
No. Information
PTOF1.Mod.stVal 5 5 5 2 2 2 1
PTOF3.Health
No. Information
PTOF3.Health.stVal 3 1
PTOF3.Str
No. Information
PTOF3.Str.general 0 0 1 0
PTOF3.Op
No. Information
PTOF3.Op.general 0 0 1 0
PTOF3.BlkV
No. Information
PTOF3.BlkV.stVal 0 0 1 0
PTOF4.Mod
No. Information
PTOF4.Mod.stVal 5 5 5 2 2 2 1
PTOF4.Health
No. Information
PTOF4.Health.stVal 3 1
PTOF4.Str
No. Information
PTOF4.Str.general 0 0 1 0
PTOF4.Op
No. Information
PTOF4.Op.general 0 0 1 0
PTOF4.BlkV
No. Information
PTOF4.BlkV.stVal 0 0 1 0
PTTR1.Mod
No. Information
PTTR1.Mod.stVal 5 2 1
PTTR1.Health
No. Information
PTTR1.Health.stVal 3 1
PTTR1.Str
No. Information
PTTR1.Str.general 0 1
PTTR1.Op
No. Information
PTTR1.Op.general 0 1
PTTR1.AlmThm
No. Information
PTTR1.AlmThm.general 0 1
PHIZ1.Mod
No. Information
PHIZ1.Mod.stVal 5 2 2 2 2 2 1
PHIZ1.Health
No. Information
PHIZ1.Health.stVal 3 1
PHIZ1.Str
No. Information
PHIZ1.Str.general 0 1
PHIZ1.Str.dirGeneral
No. Information
PHIZ1.Str.dirGeneral 0 0 1 2 3 0
PHIZ1.Str.phsA
No. Information
PHIZ1.Str.phsA 0 0 1 1 1 1
PHIZ1.Str.dirPhsA
No. Information
PHIZ1.Str.dirPhsA 0 0 1 2 0 0
PHIZ1.Str.phsB
No. Information
PHIZ1.Str.phsB 0 0 1 1 1 1
PHIZ1.Str.dirPhsB
No. Information
PHIZ1.Str.dirPhsB 0 0 1 2 0 0
PHIZ1.Str.phsC
No. Information
PHIZ1.Str.phsC 0 0 1 1 1 1
PHIZ1.Str.dirPhsC
No. Information
PHIZ1.Str.dirPhsC 0 0 1 2 0 0
PHIZ1.Op
No. Information
PHIZ1.Op.general 0 1
PSDE1.Mod
No. Information
PSDE1.Mod.stVal 5 2 2 1
PSDE1.Health
No. Information
PSDE1.Health.stVal 3 1
PSDE1.Str
No. Information
PSDE1.Str.general 0 1
PSDE1.Str.dirGeneral
No. Information
PSDE1.Str.dirGeneral 0 0 1 2 3 0
PSDE1.Op
No. Information
PSDE1.Op.general 0 1
PSDE2.Mod
No. Information
PSDE2.Mod.stVal 5 2 2 1
PSDE2.Health
No. Information
PSDE2.Health.stVal 3 1
PSDE2.Str
No. Information
PSDE2.Str.general 0 1
PSDE2.Str.dirGeneral
No. Information
PSDE2.Str.dirGeneral 0 0 1 2 3 0
PSDE2.Op
No. Information
PSDE2.Op.general 0 1
PSDE3.Mod
No. Information
M.of PU TD (P3131) = ∞ x 1 0 0 0
PSDE3.Mod.stVal 5 5 2 2 1
PSDE3.Health
No. Information
PSDE3.Health.stVal 3 3 1
PSDE3.Str
No. Information
PSDE3.Str.general 0 1
PSDE3.Str.dirGeneral
No. Information
PSDE3.Str.dirGeneral 0 0 1 2 3 0
PSDE3.Op
No. Information
PSDE3.Op.general 0 1
RREC1.Mod
No. Information
RREC1.Mod.stVal 5 2 1
RREC1.Health
No. Information
RREC1.Health.stVal 3 1
RREC1.Op
No. Information
RREC1.Op.general 0 1
RREC1.AutoRecSt
No. Information
RREC1.AutoRecSt.stVal 3 2 3 1
RFLO1.Mod
No. Information
RFLO1.Mod.stVal 1
RFLO1.Health
No. Information
RFLO1.Health.stVal 3 1
RFLO1.FltZ
RFLO1.FltZ.units.multiplier 0 1
RFLO1.FltDiskm
1119 Flt Locator: Distance to fault RFLO1.FltDiskm.mag.f Measured value Absolute value
or (dist =)
1122 RFLO1.FltDiskm.units.SIUnit 2 Meter
RFLO1.FltDiskm.units.multiplier 3 Kilo
RFLO1.FltDisPrc
1120 Flt Locator: Distance [%] to fault RFLO1.FltDisPrc.mag.f Measured value Absolute value
(d[%] =)
RFLO1.FltDisPrc.units.SIUnit 1 NONE
RFLO1.FltDisPrc.multiplier 0 1
RBRF1.Mod
No. Information
RBRF1.Mod.stVal 5 1 2
RBRF1.Health
No. Information
RBRF1.Health.stVal 3 1
RBRF1.Str
No. Information
RBRF1.Str.general 0 1 1 1
RBRF1.OpEx
No. Information
RBRF1.OpEx.general 0 1
RBRF1.OpIn
No. Information
RBRF1.OpIn.general 0 1
RSYN1.Mod
No. Information
RSYN1.Mod.stVal 1 2 5
RSYN1.Health
No. Information
RSYN1.Health.stVal 3 3 2 1
RSYN1.Rel
No. Information
RSYN1.Rel.stVal 0 1
RSYN1.VInd
No. Information
RSYN1.VInd.stVal 1 0
RSYN1.AngInd
No. Information
RSYN1.AngInd.stVal 1 0
RSYN1.HzInd
No. Information
RSYN1.HzInd.stVal 1 0
RSYN1.SynPrg
No. Information
RSYN1.SynPrg.stVal 0 1
RSYN1.DifVCIc
RSYN1.DifVClc.units.SIUnit 29 V (Volt)
RSYN1.DifVClc.units.multiplier 3 Kilo
RSYN1.DifHzCIc
RSYN1. DifHzClc.units.SIUnit 33 Hz
RSYN1. DifHzClc.units.multiplier 0 1
RSYN1.DifAngCIc
RSYN1. DifAngClc.units.multiplier 0 1
RSYN2.Mod
No. Information
RSYN2.Mod.stVal 1 2 5
RSYN2.Health
No. Information
RSYN2.Health.stVal 3 3 2 1
RSYN2.Rel
No. Information
RSYN2.Rel.stVal 0 1
RSYN2.VInd
No. Information
RSYN2.VInd.stVal 1 0
RSYN2.AngInd
No. Information
RSYN2.AngInd.stVal 1 0
RSYN2.HzInd
No. Information
RSYN2.HzInd.stVal 1 0
RSYN2.SynPrg
No. Information
RSYN2.SynPrg.stVal 0 1
RSYN2.DifVCIc
RSYN2.DifVClc.units.SIUnit 29 V (Volt)
RSYN2.DifVClc.units.multiplier 3 Kilo
RSYN2.DifHzCIc
RSYN2. DifHzClc.units.SIUnit 33 Hz
RSYN2. DifHzClc.units.multiplier 0 1
RSYN2.DifAngCIc
RSYN2. DifAngClc.units.multiplier 0 1
RSYN3.Mod
No. Information
RSYN3.Mod.stVal 1 2 5
RSYN3.Health
No. Information
RSYN3.Health.stVal 3 3 2 1
RSYN3.Rel
No. Information
RSYN3.Rel.stVal 0 1
RSYN3.VInd
No. Information
RSYN3.VInd.stVal 1 0
RSYN3.AngInd
No. Information
RSYN3.AngInd.stVal 1 0
RSYN3.HzInd
No. Information
RSYN3.HzInd.stVal 1 0
RSYN3.SynPrg
No. Information
RSYN3.SynPrg.stVal 0 1
RSYN3.DifVCIc
RSYN3.DifVClc.units.SIUnit 29 V (Volt)
RSYN3.DifVClc.units.multiplier 3 Kilo
RSYN3.DifHzCIc
RSYN3. DifHzClc.units.SIUnit 33 Hz
RSYN3. DifHzClc.units.multiplier 0 1
RSYN3.DifAngCIc
RSYN3. DifAngClc.units.multiplier 0 1
RSYN4.Mod
No. Information
RSYN4.Mod.stVal 1 2 5
RSYN4.Health
No. Information
RSYN4.Health.stVal 3 3 2 1
RSYN4.Rel
No. Information
RSYN4.Rel.stVal 0 1
RSYN4.VInd
No. Information
RSYN4.VInd.stVal 1 0
RSYN4.AngInd
No. Information
RSYN4.AngInd.stVal 1 0
RSYN4.HzInd
No. Information
RSYN4.HzInd.stVal 1 0
RSYN4.SynPrg
No. Information
RSYN4.SynPrg.stVal 0 1
RSYN4.DifVCIc
RSYN4.DifVClc.units.SIUnit 29 V (Volt)
RSYN4.DifVClc.units.multiplier 3 Kilo
RSYN4.DifHzCIc
RSYN4. DifHzClc.units.SIUnit 33 Hz
RSYN4. DifHzClc.units.multiplier 0 1
RSYN4.DifAngCIc
RSYN4. DifAngClc.units.multiplier 0 1
XCBR1.Mod
No. Information
XCBR1.Mod.stVal 1 5
XCBR1.Health
No. Information
XCBR1.Health.stVal 3 1
XCBR1.Loc
No. Information
XCBR1.Loc.stVal 1 0
XCBR1.OpCnt
XCBR1.Pos
No. Information
XCBR1.BlkOpn
No. Information
XCBR1.BlkOpn.stVal 0 1
XCBR1.BlkCls
No. Information
XCBR1.BlkCls.stVal 0 1
XCBR1.CBOpCap
No. Information
XCBR1.CBOpCap.stVal 1
XCBR1.CirSpv
No. Information
XCBR1.CirSpv.stVal 0 1
XCBR1.SumSwARs1
XCBR1.SumSwARs1.units.SIUnit 5 A (Ampere)
XCBR1.SumSwARs1.units.multiplier 3 Kilo
XCBR1.SumSwARs2
XCBR1.SumSwARs2.units.SIUnit 5 A (Ampere)
XCBR1.SumSwARs2.units.multiplier 3 Kilo
XCBR1.SumSwARs3
XCBR1.SumSwARs3.units.SIUnit 5 A (Ampere)
XCBR1.SumSwARs3.units.multiplier 3 Kilo
PTRC1.Mod
No. Information
PTRC1.Mod.stVal 1 5
PTRC1.Health
No. Information
PTRC1.Health.stVal 3 1
PTRC1.Str
No. Information
PTRC1.Str.general 0 1
PTRC1.Tr
No. Information
PTRC1.Tr.general 0 1
PTRC1.FinTr
No. Information
PTRC1.FinTr.stVal 0 1
MMXU1.Mod
No. Information
MMXU1.Mod.stVal 1
MMXU1.Health
No. Information
MMXU1.Health.stVal 3 1
MMXU1.TotW
MMXU1.TotW.units.SIUnit 62 W (Watt)
MMXU1.TotW.units.multiplier 6 Mega
MMXU1.TotVAr
MMXU1.TotVAr.units.SIUnit 63 VAr
MMXU1.TotVAr.units.multiplier 6 Mega
MMXU1.TotVA
MMXU1.TotVA.units.SIUnit 61 VA
MMXU1.TotVA.units.multiplier 6 Mega
MMXU1.TotPF
MMXU1.TotPF.units.SIUnit 1 NONE
MMXU1.TotPF.units.multiplier 0 1
MMXU1.Hz
MMXU1.Hz.units.SIUnit 33 Hz
MMXU1.Hz.units.multiplier 0 1
MMXU1.A
MMXU1.A.phsA.units.SIUnit 5 A (Ampere)
MMXU1.A.phsA.units.multiplier 0 1
MMXU1.A.phsB.units.SIUnit 5 A (Ampere)
MMXU1.A.phsB.units.multiplier 0 1
MMXU1.A.phsC.units.SIUnit 5 A (Ampere)
MMXU1.A.phsC.units.multiplier 0 1
MMXU1.A.phsC.units.SIUnit 5 A (Ampere)
MMXU1.A.phsC.units.multiplier 0 1
MMXU1.PPV
MMXU1.PPV.phsAB.units.SIUnit 29 V (Volt)
MMXU1.PPV.phsAB.units.multiplier 3 Kilo
MMXU1.PPV.phsBC.units.SIUnit 29 V (Volt)
MMXU1.PPV.phsBC.units.multiplier 3 Kilo
MMXU1.PPV.phsCA.units.SIUnit 29 V (Volt)
MMXU1.PPV.phsCA.units.multiplier 3 Kilo
MMXU1.PhV
MMXU1.PhV.phsA.units.SIUnit 29 V (Volt)
MMXU1.PhV.phsA.units.multiplier 3 Kilo
MMXU1.PhV.phsB.units.SIUnit 29 V (Volt)
MMXU1.PhV.phsB.units.multiplier 3 Kilo
MMXU1.PhV.phsC.units.SIUnit 29 V (Volt)
MMXU1.PhV.phsC.units.multiplier 3 Kilo
MMXU1.PhV.neut.units.SIUnit 29 V (Volt)
MMXU1.PhV.neut.units.multiplier 3 Kilo
MSQI1.Mod
No. Information
MSQI1.Mod.stVal 1
MSQI1.Health
No. Information
MSQI1.Health.stVal 3 1
MSQI1.SeqA
MSQI1.SeqA.c1.units.SIUnit 5 A (Ampere)
MSQI1.SeqA.c1.units.multiplier 0 1
MSQI1.SeqA.c2.units.SIUnit 5 A (Ampere)
MSQI1.SeqA.c2.units.multiplier 0 1
831 3Io (zero sequence) (3Io =) MSQI1.SeqA.c3.cVal.mag.f Measured value Absolute value
MSQI1.SeqA.c3.units.SIUnit 5 A (Ampere)
MSQI1.SeqA.c3.units.multiplier 0 1
MSQI1.SeqV
MSQI1.SeqV.c1.units.SIUnit 29 V (Volt)
MSQI1.SeqV.c1.units.multiplier 3 Kilo
MSQI1.SeqV.c2.units.SIUnit 29 V (Volt)
MSQI1.SeqV.c2.units.multiplier 3 Kilo
MSQI1.SeqV.c3.units.SIUnit 29 V (Volt)
MSQI1.SeqV.c3.units.multiplier 3 Kilo
MMTR1.Mod
No. Information
MMTR1.Mod.stVal 1
MMTR1.Health
No. Information
MMTR1.Health.stVal 3 1
MMTR1.SupWh
MMTR1.SupWh.units.SIUnit 72 Wh
MMTR1.SupWh.units.multiplier 6 Mega
MMTR1.SupVArh
MMTR1.SupVArh.units.SIUnit 73 VArh
MMTR1.SupVArh.units.multiplier 6 Mega
MMTR1.DmdWh
MMTR1.DmdWh.units.SIUnit 72 Wh
MMTR1.DmdWh.units.multiplier 6 Mega
MMTR1.DmdVArh
MMTR1.DmdVArh.units.SIUnit 73 VArh
MMTR1.DmdVArh.units.multiplier 6 Mega
/1/ SIPROTEC 4 Ethernet Module EN 100 IEC 61850 Electrical Interface 100 MBit,
Manual
C54000-G1176-C167
/2/ SIPROTEC 4 System Description
E50417-H1176-C151
/3/ SIPROTEC DIGSI, StartUP
E50417-G1176-C152
/4/ DIGSI CFC, Manual
E50417-H1176-C098
/5/ SIPROTEC SIGRA 4, Manual
E50417-H1176-C1100-C070
/6/ SIPROTEC Multi-Functional Protective Relay with Bay Control 7SJ61, Manual
C53000-G1140-C210
/7/ SIPROTEC Multi-Functional Protective Relay with Local Control 7SJ62/64,
Manual
C53000-G1140-C207
/8/ SIPROTEC Overcurrent Protection 7SJ80, Manual
E50417-G1140-C343
/9/ SIPROTEC Motor Protection 7SK80, Manual
E50417-G1140-C344
C Health 164
CALH1 34, 52, 63 Hz 166
ErrBoard1 64 Mod 164
ErrBoard2 64 PhV 168
ErrBoard3 64 PPV 167
ErrBoard4 64 TotPF 165
ErrBoard5 65 TotVA 165
ErrBoard6 65 TotVAr 165
ErrBoard7 65 TotW 165
GrAlm 63 MSQI1 34, 51, 169
GrWrn 63 Health 169
Health 63 Mod 169
Mod 63 SeqA 170
SeqV 170
D
DOI 33 P
PHIZ1 36, 40, 44, 47, 50, 131
F Health 131
Function parameters 34 Mod 131
Functional Scope Op 134
7SJ61 35 Str.dirGeneral 132
7SJ62/63/64 38 Str.dirPhsA 132
7SJ80 43 Str.dirPhsB 133
7SK80 46 Str.dirPhsC 134
Str.general 131
L Str.phsA 132
LD Str.phsB 133
CTRL (Control) 34, 52 Str.phsC 134
DR (Disturbance Recorder) 51 PMLJ1 36, 40, 47, 50, 111
EXT (Extended) 52 ChgSet 112
Logical Device 32 Health 111
MEAS (Measurement) 34, 51 LodJamAlm 112
PROT (Protection) 34, 49 Mod 111
LLN0 32, 34, 49, 51, 52 Op 112
Beh 53, 55, 56 Str 112
Health 53, 55, 57 PMRI1 36, 40, 47, 50, 110
Mod 55, 56 Health 110
OpTmh 54, 56, 57 Mod 110
Logical Node 33, 35, 38, 43, 46, 49 Op 110
LPHD1 32, 34, 50, 51, 52, 62 StrInhTmm 110
DevStr 62 PMSS1 36, 40, 47, 50, 108
PhyHealth 62 Health 108
Proxy 62 Mod 108
Op 109
M Str 109
MMTR1 34, 51, 171 PSDE1 36, 40, 44, 47, 50, 135
DmdVArh 172 Health 135
DmdWh 172 Mod 135
Health 171 Op 136
Mod 171 Str.dirGeneral 136
SupVArh 172 Str.general 135
SupWh 171 PSDE2 36, 40, 44, 47, 50, 136
MMXU1 34, 51, 164 Health 137
A 166, 169 Mod 136
X
XCBR1 34, 49, 158
BlkCls 159