Siprotec Multi-Functional Protectiv Relays 7SJ61... 7SJ64 Overcurrent Protection 7SJ80 Motor Protection 7SK80

Download as pdf or txt
Download as pdf or txt
You are on page 1of 178

Preface, Table of Contents

Applications 1
SIPROTEC Basics 2
Mapping 3
Multi-Functional Protectiv
Relays Literature, Index
7SJ61...7SJ64

Overcurrent Protection
7SJ80

Motor Protection
7SK80

IEC 61850
PIXIT

C53000-G1140-C211-4
Disclaimer of Liability Copyright
We have checked the text of this manual against the hardware and Copyright © Siemens AG 2010
software described. However, deviations from the description can- Dissemination or reproduction of this document, or evaluation and
not be completely ruled out, so that no liability can be accepted for communication of its contents, is not authorized except where ex-
any errors or omissions contained in the information given. pressly permitted. Violations are liable for damages. All rights re-
The information given in this document is reviewed regularly and served, particularly for the purposes of patent application or
any necessary corrections will be included in subsequent editions. trademark registration.
We appreciate any suggestions for improvement.
We reserve the right to make technical improvements without no- Registered Trademarks
tice. SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks
of Siemens AG. Other designations in this manual might be trade-
Document Release V04.20.00 marks whose use by third parties for their own purposes would in-
Edition 03.2010 fringe the rights of the owner.

Siemens Aktiengesellschaft Order No.: C53000-G1140-C211-4


Preface

Purpose of this manual


In this Manual, you will find the
‰ Specification of the applications of the IEC 61850 interface

‰ General information about the effects of configuration of your device to the different Logical
Nodes and DOIs
‰ Mapping of device relevant information to Logical Nodes as part of protocol IEC61850

Target audience
This manual is intended mainly for all persons who configure, parameterize and operate a
SIPROTEC Devices 7SJ61, 7SJ62, 7SJ63, 7SJ64, 7SJ80, 7SK80.

Scope of validity of this Manual


SIPROTEC 7SJ61, 7SJ62 and 7SJ64, Versions 4.7, 4.8
SIPROTEC 7SJ63, Version 4.66
SIPROTEC 7SJ80, Version 4.6
SIPROTEC 7SK80, Version 4.6

Standards
This document has been created according to the ISO 9001 quality standards.

Further Support
If you have questions about SIPROTEC IEC 61850 interface, please contact your Siemens sales
representative.

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 3


C53000-G1140-C211-4, Edition 03.2010
4 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT
C53000-G1140-C211-4, Edition 03.2010
Table of contents

1 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Association model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3 Server model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.4 Data set model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.5 Substitution model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.6 Setting group control model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.7 Reporting model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.7.1 Unbuffered Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.7.2 Buffered Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.8 Logging model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.9 Generic substation model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.10 Transmission of sample values model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.11 Control model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1.12 Time and time synchronisation model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.13 File transfer model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.14 General items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.15 TISSUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.2 Effects of Configuration on the Logical Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2.1 Function parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2.2 Function parameters SIPROTEC 7SJ61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.2.3 Function parameters SIPROTEC 7SJ62/63/64 . . . . . . . . . . . . . . . . . . . . . . . . . 38
2.2.4 Function parameters SIPROTEC 7SJ80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.2.5 Function parameters SIPROTEC 7SK80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.3 Allocation of Logical Nodes to Logical Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
2.4 Logical Node LLN0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.4.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.4.2 Logical Devices MEAS, DR and EXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2.4.3 Logical Device CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.5 DOI Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2.5.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2.5.2 Logical Devices MEAS, CTRL, DR and EXT. . . . . . . . . . . . . . . . . . . . . . . . . . . 59

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 5


C53000-G1140-C211-4, Edition 03.2010
Table of contents

3 Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

3.1 Device (LPHD1, CALH1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62


3.1.1 Error with a summary alarm and Alarm summary event . . . . . . . . . . . . . . . . . . . 63
3.2 Oscillographic Fault Records (RDRE1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2) . . . . . . . . . . . . . . . . . . 68
3.3.1 Overcurrent Protection 50, 51 PH (PTOC6, PTOC7, PTOC1, PTOC18) . . . . . . 68
3.3.2 Overcurrent Protection 50N, 51N (PTOC8, PTOC9, PTOC2) . . . . . . . . . . . . . . 74
3.3.3 Overcurrent Protection 50N, 51N (PTRC2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3) . . . . . . . . . . . . . . . . . 81
3.4.1 Directional Overcurrent Protection 67 (PTOC10, PTOC11, PTOC3) . . . . . . . . . 81
3.4.2 Directional Overcurrent Protection 67N (PTOC12, PTOC13, PTOC4) . . . . . . . . 85
3.4.3 Directional Overcurrent Protection 67N (PTRC3) . . . . . . . . . . . . . . . . . . . . . . . . 89
3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17) . . . . . . . . . . . . . . . . . . . 93
3.6 Voltage Protection 27, 59 (PTUVx, PTOVx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
3.6.1 Undervoltage Protection 27 (PTUV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
3.6.2 Undervoltage Protection 27 (PTUV2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
3.6.3 Overvoltage Protection 59 (PTOV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
3.6.4 Overvoltage Protection 59 (PTOV2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5). . . . . . . . . . . . . . . 104
3.8 Motor Protection (PMSS1, PMRI1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
3.8.1 Motor Starting Protection 48 (PMSS1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
3.8.2 Motor Restart Inhibit 66 (PMRI1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
3.9 Load Jam Protection (PMLJ1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
3.10 Frequency protection 81 O/U (PTUFx, PTOFx). . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
3.10.1 Frequency protection 81-1 U (PTUF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
3.10.2 Frequency protection 81-2 U (PTUF2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
3.10.3 Frequency protection 81-3 U (PTUF3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
3.10.4 Frequency protection 81-4 U (PTUF4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
3.10.5 Frequency protection 81-1 O (PTOF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
3.10.6 Frequency protection 81-2 O (PTOF2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
3.10.7 Frequency protection 81-3 O (PTOF3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
3.10.8 Frequency protection 81-4 O (PTOF4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
3.11 Thermal overload protection (PTTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) . . . . . . . . . . . . . . . . . 131
3.12.1 Ground Fault Protection 64 (PHIZ1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
3.12.2 Ground Fault Protection 50N(s) (PSDE1, PSDE2) . . . . . . . . . . . . . . . . . . . . . . . 135
3.12.3 51 N(s) (PSDE3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
3.13 Automatic Reclosing System 79 (RREC1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
3.14 Fault Locator (RFLO1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
3.15 Circuit breaker failure protection 50BF(RBRF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
3.16 Synchronism and Voltage Check 25 (RSYNx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
3.17 Three-pole tripping 52 Breaker (XCBR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
3.18 Tripping Logic of the Entire Device (PTRC1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162

6 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Table of contents

3.19 Measurement (MMXU1, MSQI1, MMTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164


3.19.1 Measures (MMXU1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
3.19.2 Measured values, symmetrical components (MSQI1) . . . . . . . . . . . . . . . . . . . . 169
3.19.3 Power Metering (MMTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

Literature

Index

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 7


C53000-G1140-C211-4, Edition 03.2010
Table of contents

8 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications 1

Contents
This chapter specifies the protocol implementation extra information for testing (PIXIT) of the
IEC 61850 interface in SIPROTEC 7SJ6, 7SJ80, 7SK80.

1.1 General 10

1.2 Association model 11

1.3 Server model 12

1.4 Data set model 13

1.5 Substitution model 14

1.6 Setting group control model 15

1.7 Reporting model 16

1.8 Logging model 19

1.9 Generic substation model 20

1.10 Transmission of sample values model 22

1.11 Control model 23

1.12 Time and time synchronisation model 25

1.13 File transfer model 26

1.14 General items 27

1.15 TISSUES 28

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 9


C53000-G1140-C211-4, Edition 03.2010
Applications
1.1 General

1.1 General

This chapter specifies the protocol implementation extra information for testing (PIXIT) of the
IEC 61850 interface in SIPROTEC 7SJ6, 7SJ80, 7SK80.
It is based on the service subset definition given in the protocol implementation conformance
statement (PICS), which is specified within the user manual SIPROTEC 4 Ethernet Module
EN 100 IEC 61850 Electrical Interface 100 MBit, Manual /1/“.
The following applicable ACSI service models are specified:
‰ Association model

‰ Server model

‰ Data set model

‰ Substitution model

‰ Setting group control model

‰ Reporting model

‰ Logging model

‰ Generic substitution model

‰ Transmission of sample values model

‰ Control model
‰ Time and time synchronisation model

‰ File transfer model

‰ General items

Together with the PICS and the MICS the PIXIT forms the basis for a conformance test
according to IEC 61850-10.

The mapping between the IEC 61850 server data model and the SIPROTEC specific data is
specified in Chapter 3.

10 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.2 Association model

1.2 Association model

Description Value / Clarification

Maximum number of clients that can set-up 5 with IEC 61850 Protocol Update
an association simultaneously Version EN100 V04.02 and lower

6 with IEC 61850 Protocol Update


Version EN100 V04.03 and higher

Lost connection detection time range 10 seconds


(default range of TCP_KEEPALIVE is 1 –
20 seconds)

Is authentication supported N

What called association parameters are Transport selector Y


necessary for successful association ? Session selector Y
Presentation selector Y
AP Title ANY
AE Qualifier ANY

Where
Y means: as defined within the ICD-File
ANY means: any value accepted

What is the maximum and minimum MMS Max MMS PDU size 32768
PDU size ? Min MMS PDU size

What is the typical startup time after a 15 SECONDS


power supply interrupt ?

<additional items>

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 11


C53000-G1140-C211-4, Edition 03.2010
Applications
1.3 Server model

1.3 Server model

Description Value / Clarification

Which analogue value (MX) quality bits are Validity:


supported (can be set by server) ? Y Good,
Y Invalid,
N Reserved,
Y Questionable
Y Overflow
Y OutofRange
N BadReference
N Oscillatory
Y Failure
Y OldData
N Inconsistent
Y Inaccurate

Source:
Y Process
N Substituted
Y Test
Y OperatorBlocked

Which status value (ST) quality bits are Validity:


supported (can be set by server) ? Y Good,
Y Invalid,
N Reserved,
Y Questionable
N BadReference
Y Oscillatory
Y Failure
Y OldData
N Inconsistent
N Inaccurate

Source:
Y Process
Y Substituted
Y Test
Y OperatorBlocked

What is the maximum number of data Not restricted; depends on the max. MMS PDU size given
values in one GetDataValues request ? above.

What is the maximum number of data Not restricted; depends on the max. MMS PDU size given
values in one SetDataValues request ? above. No Data Attribute within our object directory is
writable with the service SetDataValues.

<additional items>

12 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.4 Data set model

1.4 Data set model

Description Value / Clarification

Maximum number of data elements in one Not limited by an internal configuration parameter. It
data set depends on the available memory.

How many persistent data sets can be 64 data sets for each LD. It depends on the available
created by one or more clients ? memory.

How many non-persistent data sets can be 10 data sets. It depends on the available memory.
created by one or more clients ?

additional items:

Maximum number of data sets Could not be defined, it depends on the available memory
space. In principle, this information it not necessary from
type conformance testing standpoint.

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 13


C53000-G1140-C211-4, Edition 03.2010
Applications
1.5 Substitution model

1.5 Substitution model

This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850
Electrical Interface 100 MBit, Manual /1/).

14 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.6 Setting group control model

1.6 Setting group control model

Description Value / Clarification

What is the number of supported setting Setting groups available for LLN0 only in LD PROT. The
groups for each logical device ? number of supported setting groups is 1 or 4, it depends
on the given configuration. Specified in the ICD-File.

What is the effect of when and how the Just SelectActiveSG service will supported according to
non-volatile storage is updated ? PICS.
(compare IEC 61850-8-1 $16.2.4)

<additional items>

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 15


C53000-G1140-C211-4, Edition 03.2010
Applications
1.7 Reporting model

1.7 Reporting model

1.7.1 Unbuffered Report

Description Value / Clarification

The supported trigger conditions are Y Integrity


Y Data change
Y Quality change
Y Data update
Y General Interrogation

The supported optional fields are Y Sequence-number


Y Report-time-stamp
Y Reason-for-inclusion
Y Data-set-name
Y Data-reference
N Buffer-overflow
N EntryID
Y Conf-rev
Y Segmentation

Can the server send segmented reports ? Y

Mechanism on second internal data Send report immediately


change notification of the same analogue
data value within buffer period
(Compare IEC 61850-7-2 $14.2.2.9)

Multi client URCB approach All clients can access all URCB’s
(Compare IEC 61850-7-2 $14.2.1)

additional items:

Interrupt of general interrogation Running GI could not be interrupted. If a new GI request


occurs during a running GI, the current GI will be finished
first before the second GI request will be processed.

Integrity period Configurable >=1 second;

Dynamic URCB reservation after an abort Reservation of the URCB is lost. After a re-establishment
of the client/server association of the association the URCB reservation has to be done
by the client before. This behavior is implemented to
avoid unnecessary memory residuals if temporarily client
associations (e.g. for maintenance) are established.

Configured URCB reservation after an Reservation of the URCB is not lost.


abort of the client/server association

16 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.7 Reporting model

1.7.2 Buffered Report

Description Value / Clarification

The supported trigger conditions are Y Integrity


Y Data change
Y Quality change
Y Data update
Y General Interrogation

The supported optional fields are Y Sequence-number


Y Report-time-stamp
Y Reason-for-inclusion
Y Data-set-name
Y Data-reference
Y Buffer-overflow
Y EntryID
Y Conf-rev
Y Segmentation

Can the server send segmented reports ? Y

Mechanism on second internal data Buffer the Entry


change notification of the same analogue Send report if the report is enabled
data value within buffer period
(Compare IEC 61850-7-2 $14.2.2.9)

Multi client BRCB approach All clients can access all BRCB’s
(Compare IEC 61850-7-2 $14.2.1)

What is the format of EntryID ? First 2 Byte : Integer


Last 6 Bytes: BTime6 time stamp

What is the buffer size for each BRCB or About 1 MB are available for the buffering.
how many reports can be buffered ? Each BRCB has an extension attribute Memory that
display the percentage of those 1 MB that have been
reserved/forseen for its own entries.
Default amount 1 MB/(2*Number of logical devices)

additional items:

Interrupt of general interrogation Running GI could not be interrupted. If a new GI request


occurs during a running GI, the current GI will be finished
first before the second GI request will be processed.

Integrity period Configurable >=1 second;

Dynamic BRCB reservation after an abort Reservation of the BRCB has been fixed with TISSUE
of the client/server association 453.
The value of the attribute ResvTms delivers the time
interval during which the reservation is still active after the
connection has been lost. In case a BRCB is still
reserved, and a client connects with the same IP address
as the one used during the reservation, then the BRCB
attribute can be written by this client without prior setting
the ResvTms attribute as long as the reservation timer
has not expired.

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 17


C53000-G1140-C211-4, Edition 03.2010
Applications
1.7 Reporting model

Configured BRCB reservation after an Reservation of the BRCB is not lost for BRCBs that have
abort of the client/server association been pre-associated to a specific client (pre-association
defined with means of the CLientLN element with the
BRCB instantiation in the SCD file).
Reservation of a BRCB is lost for BRCBs, that have not
been pre-associated to a specific client, after the
expiration of the reservation timer set with the ResvTms
attribute. In case ResvTms is not set (backward
compatibility), ResvTms will get a default value for all
preconfigured BRCBs that are not pre-associated to a
specific client.

Optional use of a flow control for As specified in the IEC61850-7-2, transmission of entries
transmitting history of a BRCB may required some times, depending of the amount of
entries that have to be transmitted.
Therefore, the SIPROTEC has an optional flow control
feature to accelerate the transmission of the entries: each
BRCB has an extended attribute MaxOutReports that can
be set from the associated-client to change the
transmmision strategy of the entries. The number ordered
will then be transmitted as long as they exist in the buffer;
the server then reset the attribute to 0 and wait for the
client to set it again in order to continue the history
transmission with MaxOutReports entries. The attribute
only influences the flow control of entries while dealing
with the history, and not after the history transmission has
completed.

18 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.8 Logging model

1.8 Logging model

This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850
Electrical Interface 100 MBit, Manual /1/).

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 19


C53000-G1140-C211-4, Edition 03.2010
Applications
1.9 Generic substation model

1.9 Generic substation model

Description Value / Clarification

What is the behavior when one subscribed The telegram will be discarded (i.e not forwarded to the
GOOSE message isn’t received or application) since it is corrupt or syntactically incorrect
syntactically incorrect ? and therefore not readable. The data objects will be
declared as invalid after a timeout detection since no
telegram have been received by the application.

What is the behavior when a subscribed Error message will be stored into the error buffer (could
GOOSE message is out-of-order ? be accessed by EN100 web-server).
All expected data objects will be declared as invalid.

What is the behavior when a subscribed The sequence number given in the GOOSE-message is
GOOSE message is duplicated ? out-of-order. Error message will be stored into the error
buffer (could be accessed by EN100 web-server).
All expected data objects will be declared as invalid.

additional items:

Maximum number of GOOSE messages <= 16 ; It depends on the available memory.


which could be sent

Maximum number of GOOSE messages <= 128 ; It depends on the available memory.
which could be received

Interpretation of GOOSE messages at 1. Received GOOSE data objects without assigned


subscriber side quality attribute are interpreted as invalid.
2. Received GOOSE data objects which quality attribute
are set to questionable are changed to invalid.

GOOSE subscriber behavior in case of After a GOOSE multicast application association has
missing GOOSE messages been interrupted, the reception of the second consecutive
GOOSE telegram is required to validate the state of this
GOOSE association again.
However, the IED tolerates a missing telegram as long as
the next telegram (expected n, received n+1) is received
within the time allowed to live time out detection (the time
allowed to live timeout detection occurs after 2*TAL).

GOOSE subscriber behaviour in case of If a message is received twice or more, the IED already
multiple GOOSE messages reports an error after the second reception. Therefore,
network configuration error can be more easily tracked.

What is the behavior when a GOOSE Error message will be stored into the error buffer (could
header parameter is mismatching with the be accessed by EN100 web-server).
expected one? All expected data objects will be declared as invalid.
(datSet, goID, confRev, numDatSetEntries,
number of allData)

What is the behavior when a Error message will be stored into the error buffer (could
timeAllowedToLive is 0? be accessed by EN100 web-server) since the
timeAllowedToLive expired.
All expected data objects will be declared as invalid.

20 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.9 Generic substation model

What is the behavior when there is an out- The confRev attribute in the header guarantees that the
of-order entry in the allData? allData entries are in the correct order. Therefore, it’s
necessary to check the confRev attribute. There is no
chance to detect such an out-of-order.

What is the behavior when no telegram is To avoid an incorrect timeout detection, the subscriber
received within a TAL timeout? detects a timeout after a period of 2×TAL.
The information is then declared as questionable,
oldData.

What is the behavior when a GOOSE Since the goCBRef shall be unique stationwide, the
header parameter goCBRef is mismatching received telegram with the mismatched goCBRef will be
with the expected one? discarted: it has not been published. In that case only the
timeout detection will set the data to invalid.

What is the behavior when a GOOSE The APPID is a link layer parameter. It is used as a filter
header parameter APPID is mismatching on link layer. If the APPID is mismatching, the tellegram
with the expected one? will therefore be discarded on link layer without notifying
the application. Only the timeout detection will set the
data to invalid.

What is the behavior when a GOOSE The t parameter is not checked. Therefore it doesn't lead
header parameter t is not increasing? to any error detection.

What is the behavior when The telegram is discarded since it is corrupt (not well
numDatSetEntries and number of allData formed). After the timeout detection (no telegram
are inconsistent? forwarded to the application) the data objects are
declared invalid.

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 21


C53000-G1140-C211-4, Edition 03.2010
Applications
1.10 Transmission of sample values model

1.10 Transmission of sample values model

Compare the “Implementation Guidelines for Electrical Current and Voltage Transducers
according to IEC 60044-7/8 with Digital Output according to IEC 61850-9-2; Version 1.0; as
specified by ABB, Areva, Landis+Gyr, OMICRON and SIEMENS

This service will not be supported (see also SIPROTEC 4 Ethernet Module EN 100 IEC 61850
Electrical Interface 100 MBit, Manual /1/).

22 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.11 Control model

1.11 Control model

Description Value / Clarification

What control models are supported ? Y Status-only


Y Direct-with-normal-security
N Sbo-with-normal-security
Y Direct-with-enhanced-security
Y Sbo-with-enhanced-security

Is Time activated operate (operTm) N


supported

What is the behavior when the test attribute Will be acknowledged with negative response. The
is set in the SelectWithValue and/or AddCause attribute will be set to “not supported”
Operate request ?

What are the conditions for the time (T) Time attribute is not relevant.
attribute in the SelectWithValue and/or
Operate request ?

Is “operate-many” supported ? N

Is pulse configuration supported ? N

What check conditions are supported ? Y Synchrocheck


Y Interlock-check

What service error types are supported ? Y Instance-not-available


Y Instance-in-use
Y Access-violation
Y Access-not-allowed-in-current-state
Y Parameter-value-inappropriate
Y Parameter-value-inconsistent
Y Class-not-supported
Y Instance-locked-by-other-client
Y Control-must-be-selected
Y Type-conflict
Y Failed-due-to-communications
Y Constraint failed-due-to-server-constraint

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 23


C53000-G1140-C211-4, Edition 03.2010
Applications
1.11 Control model

What additional cause diagnosis are N Blocked-by-switching-hierarchy


supported ? Y Select-failed
Y Invalid-position
Y Position-reached
Y Parameter-change-in-execution
Y Step-limit
Y Blocked-by-Mode
Y Blocked-by-process
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
Y 1-of-n-control
Y Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip
Y Object-not-selected

additional items:

What additional cause diagnosis Y Plausibility_error


extensions are supported ? Y Parameter_setting_invalid
Y Hardware_error
Y System_overload
Y Internal_fault
Y Command_sequence_error

Changing the control services by N


configuration

Inconsistency between Select and (Oper or Oper or cancel will be acknowledged with negative
cancel) response if inconsistencies to the select request are
detected.
The following attributes will not be checked in this case:
T (Time)

Cancel request could be sent after an Y


operate request.

Format of the control time stamp attribute ? TimeStamp instead of EntryTime


acc. to the 7-2 Errata List.

Negative response for select request could If test mode is activated or


be performed only If the selection is always done.

24 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.12 Time and time synchronisation model

1.12 Time and time synchronisation model

Description Value / Clarification

What kind of quality bits are supported ? N LeapSecondsKnown


Y ClockFailure
Y ClockNotSynchronized

What kind of quality accuracy bits are Y Invalid


supported ? N Unspecified

What is the behavior when the time The quality attribute “ClockFailure” will be set to TRUE
synchronization signal/messages are lost ? after a configured time period.

What is the behaviour when the time A stratum with a value greater than 3 with the SNTP time
synchronisation messages indicate that the synchronization messages indicates that the time server
stratum is greater than 3? has a questionable synchronisation.
It might also indicate that no GPS connection are
available.
Therefore the time quality attribute
“ClockNotSynchronized” will be set to TRUE as long as
the stratum content is greater than 3.

additional items:

What is the behavior at start up time when The “ClockNotSynchronized” attribute is set to TRUE as
a time synchronization via SNTP is long as no time synchronization is established.
configured ?

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 25


C53000-G1140-C211-4, Edition 03.2010
Applications
1.13 File transfer model

1.13 File transfer model

Description Value / Clarification

What is structure of files and directories? Directory name / COMTRADE / *;


Directory name / LD / *;
Files according to the comtrade standard.

What is the resulting behavior if no file If no file specification is present in the directory request,
specification is present in the file directory all files are returned - not only the files in the root
request? directory.

Is the IETF FTP protocol also implemented ? N

Directory names are separated from the file “/”


name by

The maximum file name size including path 64


(default 64 chars)

Are directory/file name case sensitive Case sensitive

Maximum file size Not limited by implementation or configuration. Depends


on available memory.

additional items:

Maximum number of clients that can use the 1


FTP service simultaneously

Maximum number of files that can be 1


accessed simultaneously

26 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.14 General items

1.14 General items

Description Value / Clarification

IED behavior when the Logical Device Unlike the definition of the Data Objects “Mod/Beh” in IEC
is blocked : LLN0.Mod.stVal = blocked 61850-7-4, outputs to the process will be generated.
Details to this behavior are specified in SIPROTEC 4
Ethernet Module EN 100 IEC 61850 Electrical Interface
100 MBit, Manual /1/

additional items:

GOOSE Proxy object To be able to subscribe Data over GOOSE, Proxy


Objects are added into the object directory.
Typically, they are Data of GGIO logical nodes:
SPCSOxx, DPCSOxx, ISCSOxx.
The Data Attributes of those Data are ctlVal, q and t.
The control model associated to those Data is status-only.
They are not controllable from an IEC61850 client, and
their function is only to enable the GOOSE subscribing.

What is the type of the attribute actVal in The type is integer 32 (INT32).
the BCR (Binary Counter Reading) CDC?

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 27


C53000-G1140-C211-4, Edition 03.2010
Applications
1.15 TISSUES

1.15 TISSUES

Topic TISSUE Link Description Impact of


-No. Interoper.

Object Model 120 http://www.tissue.iec61850.com/ Type - Mod.stVal and -


tissue.mspx?issueid=120 Mod.ctlVal

146 http://www.tissue.iec61850.com/ CtxInt -


tissue.mspx?issueid=146

173 http://www.tissue.iec61850.com/ Ctl modelling -


tissue.mspx?issueid=173 harmonization

234 http://www.tissue.iec61850.com/ New type CtxInt x


tissue.mspx?issueid=234

Services 377 http://www.tissue.iec61850.com/ DeleteDataSet response- -


tissue.mspx?issueid=377

276 http://www.tissue.iec61850.com/ File Services Negative -


tissue.mspx?issueid=276 Responses

183 http://www.tissue.iec61850.com/ GetNameList error x


tissue.mspx?issueid=183 handling

165 http://www.tissue.iec61850.com/ Improper Error Response x


tissue.mspx?issueid=165 for GetDataSetValues

116 http://www.tissue.iec61850.com/ GetNameList with empty x


tissue.mspx?issueid=116 response?

Reporting 474 http://www.tissue.iec61850.com/ GI for URCB -


tissue.mspx?issueid=474

453 http://www.tissue.iec61850.com/ Reporting & Logging x


tissue.mspx?issueid=453 model revision

438 http://www.tissue.iec61850.com/ EntryTime base should -


tissue.mspx?issueid=438 be GMT

349 http://www.tissue.iec61850.com/ BRCB TimeOfEntry has x


tissue.mspx?issueid=349 two definitions

348 http://www.tissue.iec61850.com/ URCB class and report x


tissue.mspx?issueid=348

28 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Applications

1.15 TISSUES

Reporting 344 http://www.tissue.iec61850.com/ TimeOfEntry misspelled -


tissue.mspx?issueid=344

335 http://www.tissue.iec61850.com/ Clearing of Bufovfl x


tissue.mspx?issueid=335

332 http://www.tissue.iec61850.com/ Ambiguity in use of x


tissue.mspx?issueid=332 trigger options

329 http://www.tissue.iec61850.com/ Reporting and BufOvl x


tissue.mspx?issueid=329

322 http://www.tissue.iec61850.com/ Write Configuration


tissue.mspx?issueid=322 attribute of BRCBs

301 http://www.tissue.iec61850.com/ SqNum in Buffered -


tissue.mspx?issueid=301 Reports

300 http://www.tissue.iec61850.com/ Attribute Resv in BRCB x


tissue.mspx?issueid=300

298 http://www.tissue.iec61850.com/ Type of SqNum x


tissue.mspx?issueid=298

297 http://www.tissue.iec61850.com/ Sequence number x


tissue.mspx?issueid=297

278 http://www.tissue.iec61850.com/ EntryId not valid for a x


tissue.mspx?issueid=278 server

275 http://www.tissue.iec61850.com/ Confusing statement on x


tissue.mspx?issueid=275 GI usage

191 http://www.tissue.iec61850.com/ BRCB: Integrity and x


tissue.mspx?issueid=191 buffering reports

190 http://www.tissue.iec61850.com/ BRCB: EntryId and x


tissue.mspx?issueid=190 TimeOfEntry

177 http://www.tissue.iec61850.com/ Ignoring OptFlds bits for -


tissue.mspx?issueid=177 URCB

52 http://www.tissue.iec61850.com/ Ambiguity GOOSE x


tissue.mspx?issueid=52 SqNum

49 http://www.tissue.iec61850.com/ BRCB TimeOfEntry? x


tissue.mspx?issueid=49

Control Model 46 http://www.tissue.iec61850.com/ Synchro check cancel x


tissue.mspx?issueid=46

44 http://www.tissue.iec61850.com/ AddCause - Object not x


tissue.mspx?issueid=44 sel

30 http://www.tissue.iec61850.com/ control parameter T x


tissue.mspx?issueid=30

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 29


C53000-G1140-C211-4, Edition 03.2010
Applications
1.15 TISSUES

30 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics 2

Contents
This chapter contains general information about the effects of device configuration on Logical
Nodes and DOIs.

2.1 General 32

2.2 Effects of Configuration on the Logical Nodes 34

2.3 Allocation of Logical Nodes to Logical Devices 49

2.4 Logical Node LLN0 53

2.5 DOI Behavior 58

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 31


C53000-G1140-C211-4, Edition 03.2010
Basics
2.1 General

2.1 General

The protocol IEC 61850 was developed to define a standard that can be internationally
employed for the transmission of power automation system data.
This cross national standard enables an interoperability between automation systems and
devices made by different manufacturers.
The devices and high voltage bay control units of the SIPROTEC 4 series can be equipped with
an Ethernet module EN100 via which the protocol IEC 61850 is interpreted.
The configuration of the protocol and the integration of the device with redundant IEC 61850
interfaces in your network are performed via the configuration system DIGSI.
For details please refer to the manuals:
‰ SIPROTEC 4 Ethernet Module EN 100 IEC 61850 Electrical Interface 100 MBit, Manual /1/
and
‰ SIPROTEC 4 System Description /2/.

Note
The following definitions are taken mainly from standard IEC 61850, Technical Specification
IEC TS 61850-2.

Logical Devices
LD Logical Devices represent a functional structuring of the LN Logical Nodes of a SIPROTEC
device.
The following Logical Devices are present:
‰ Logical Device Protection PROT

‰ Logical Device Measurement MEAS

‰ Logical Device Disturbance Recorder DR

‰ Logical Device Control CTRL


‰ Logical Device Extended EXT

Each LD contains LN LLN0 and LN LPHD1.


The allocation of the Logical Nodes to the Logical Devices is listed in Chapter 2.3.

32 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.1 General

Logical Node LN
Smallest part of a function that exchanges data. A logical node is an object defined by its data
and methods.

Data object instance DOI


A Data object is part of a logical node object representing specific information for example status
of measurement. From an object-oriented point of view, a data object is an instance of a data
class. Specific data classes carry the semantic within a logical node.

Data attribute instance DAI


A Data attribute defines the name (semantic), format, range of possible values, and
representation of values while being communicated.

Annunciation types via GOOSE


Generic Object Oriented Substation Event
A GOOSE report enables high speed trip signals to be issued with a high probability of delivery.
The following types of information can be configured via GOOSE.
‰ External single point indication O/O

‰ External single point indication I/O

‰ External double point indication


‰ External double point indication, fast

‰ External operational measured values

‰ External metered values

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 33


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

2.2 Effects of Configuration on the Logical Nodes

2.2.1 Function parameters

Depending on the configuration of the function parameters the functions of the SIPROTEC are
enabled or disabled. If a function is disabled, the corresponding Logical Node is not available.

The following Logical Nodes are always available:

Logical Device Protection: LLN0, LPHD1, XCBR1,


PTRC1
Logical Device Measurement: LLN0, LPHD1, MMXU1,
MMTR1, MSQI1
Logical Device Control: LLN0, LPHD1, CALH1

34 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

2.2.2 Function parameters SIPROTEC 7SJ61

The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.

Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes

No. Function Setting Logical Nodes

103 Setting Group Change Option No effect

104 Oscillographic Fault Records Disabled -

Enabled RDRE1

112 50/51 (Charac. Phase) Disabled -


Overcurrent Protection
Definite Time PTOC6, PTOC7,
PTOC18, PTRC2

TOC IEC PTOC6, PTOC7, PTOC1


PTOC18, PTRC2

TOC ANSI PTOC6, PTOC7,


PTOC1, PTOC18,
PTRC2

User Defined PU PTOC6, PTOC7, PTOC1


PTOC18, PTRC2

Userdef. Reset PTOC6, PTOC7, PTOC1,


PTOC18, PTRC2

113 50N/51N (Charac. Ground) Disabled -


Overcurrent Protection
Definite Time PTOC8, PTOC9, PTRC2

TOC IEC PTOC8, PTOC9, PTOC2,


PTRC2

TOC ANSI PTOC8, PTOC9, PTOC2,


PTRC2

User Defined PU PTOC8, PTOC9, PTOC2,


PTRC2

Userdef. Reset PTOC8, PTOC9, PTOC2,


PTRC2

117 Cold Load Pickup No effect

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 35


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

122 2nd Harmonic Inrush Restraint No effect

127 50 1Ph Disabled -


Single Phase Overcurrent Protection
Enabled PTOC16, PTOC17

131 (sens.) Ground fault Disabled -

Enabled PHIZ1, PSDE1, PSDE2

133 Intermittent earth fault protection No effect

140 46 Negative Sequence Protection Disabled -

TOC ANSI / TOC IEC PTOC14, PTOC15,


PTOC5

Definite Time PTOC14, PTOC15

141 48 Startup Supervision of Motors Disabled -

Enabled PMSS1

142 49 Thermal Overload Protection Disabled -

No ambient temp PTTR1

With amb. temp. PTTR1

143 66 Startup Counter for Motors Disabled -

Enabled PMRI1

144 Load Jam Protection Disabled -

Enabled PMLJ1

170 50BF Breaker Failure Protection Disabled -

Enabled RBRF1

enabled w/ 3I0> RBRF1

171 79 Auto-Reclose Function Disabled -

Enabled RREC1

172 52 Breaker Wear Monitoring No effect

36 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

Table 2-1 SIPROTEC 7SJ61 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

182 74TC Trip Circuit Supervision Disabled -

2 Binary Inputs DOI CirSpv, LN XCBR


LD PROT

1 Binary Input DOI CirSpv, LN XCBR


LD PROT

190 External Temperature Input No effect

191 Ext. Temperature Input Connection Type No effect

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 37


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

2.2.3 Function parameters SIPROTEC 7SJ62/63/64

The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.

Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes

No. Function Setting Logical Nodes

103 Setting Group Change Option No effect

104 Oscillographic Fault Records Disabled -

Enabled RDRE1

112 50/51 (Charac. Phase) Disabled -


Overcurrent Protection
Definite Time PTOC6, PTOC7,
PTOC18, PTRC2

TOC IEC PTOC6, PTOC7, PTOC1


PTOC18, PTRC2

TOC ANSI PTOC6, PTOC7,


PTOC1, PTOC18,
PTRC2

User Defined PU PTOC6, PTOC7, PTOC1


PTOC18, PTRC2

Userdef. Reset PTOC6, PTOC7, PTOC1,


PTOC18, PTRC2

113 50N/51N (Charac. Ground) Disabled -


Overcurrent Protection
Definite Time PTOC8, PTOC9, PTRC2

TOC IEC PTOC8, PTOC9, PTOC2,


PTRC2

TOC ANSI PTOC8, PTOC9, PTOC2,


PTRC2

User Defined PU PTOC8, PTOC9, PTOC2,


PTRC2

Userdef. Reset PTOC8, PTOC9, PTOC2,


PTRC2

38 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

115 67, 67-TOC Disabled -


Directional Overcurrent Protection
Definite Time PTOC10, PTOC11,
PTRC3

TOC IEC PTOC10, PTOC11,


PTOC3, PTRC3

TOC ANSI PTOC10, PTOC11,


PTOC3, PTRC3

User Defined PU PTOC10, PTOC11,


PTOC3, PTRC3

Userdef. Reset PTOC10, PTOC11,


PTOC3, PTRC3

116 67N, 67N-TOC Disabled -


Directional Overcurrent Protection
Definite Time PTOC12, PTOC13,
PTRC3

TOC IEC PTOC12, PTOC13,


PTOC4, PTRC3

TOC ANSI PTOC12, PTOC13,


PTOC4, PTRC3

User Defined PU PTOC12, PTOC13,


PTOC4, PTRC3

Userdef. Reset PTOC12, PTOC13,


PTOC4, PTRC3

117 Cold Load Pickup No effect

122 2nd Harmonic Inrush Restraint No effect

127 50 1Ph Disabled -


Single Phase Overcurrent Protection
Enabled PTOC16, PTOC17

130 (sens.) Ground fault dir. characteristic cos ϕ / sin ϕ see Parameter 131

V0/I0 ϕ mea. see Parameter 131

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 39


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

131 (sensitive) Ground fault Disabled -


and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
cos ϕ / sin ϕ
TOC IEC PHIZ1, PSDE2, PSDE3

TOC IANSI PHIZ1, PSDE2, PSDE3

User Defined PU PHIZ1, PSDE2, PSDE3

Log. inverse 1 PHIZ1, PSDE2, PSDE3

Log. inverse 2 PHIZ1, PSDE2, PSDE3

131 (sensitive) Ground fault Disabled -


and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
V0/I0 ϕ mea.
User Defined PU PHIZ1, PSDE1, PSDE2

133 Intermittent earth fault protection No effect

140 46 Negative Sequence Protection Disabled -

TOC ANSI PTOC14, PTOC15,


PTOC5

TOC IEC PTOC14, PTOC15,


PTOC5

Definite Time PTOC14, PTOC15

141 48 Startup Supervision of Motors Disabled -

Enabled PMSS1

142 49 Thermal Overload Protection Disabled -

No ambient temp PTTR1

With amb. temp. PTTR1

143 66 Startup Counter for Motors Disabled -

Enabled PMRI1

144 Load Jam Protection Disabled -

Enabled PMLJ1

40 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

150 27, 59 Under/Overvoltage Protection Disabled -

Enabled PTUV1, PTUV2,


PTOV1, PTOV2

154 81 Over/Underfrequency Protection Disabled -

Enabled PTOF1 – PTOF4,


PTUF1 – PTUF4

161 25 Function group 1 Disabled -


Synchronism and Voltage Check
ASYN/SYNCHRON RSYN1

SYNCHROCHECK RSYN1

162 25 Function group 2 Disabled -


Synchronism and Voltage Check
ASYN/SYNCHRON RSYN2

SYNCHROCHECK RSYN2

163 25 Function group 3 Disabled -


Synchronism and Voltage Check
ASYN/SYNCHRON RSYN3

SYNCHROCHECK RSYN3

164 25 Function group 4 Disabled -


Synchronism and Voltage Check
ASYN/SYNCHRON RSYN4

SYNCHROCHECK RSYN4

170 50BF Breaker Failure Protection Disabled -

Enabled RBRF1

enabled w/ 3I0> RBRF1

171 79 Auto-Reclose Function Disabled -

Enabled RREC1

172 52 Breaker Wear Monitoring No effect

180 Fault Locator Disabled -

Enabled RFLO1

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 41


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

Table 2-2 SIPROTEC 7SJ62/63/64 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

181 Line sections for fault locator No effect

182 74TC Trip Circuit Supervision Disabled -

2 Binary Inputs DOI CirSpv, LN XCBR


LD PROT

1 Binary Input DOI CirSpv, LN XCBR


LD PROT

190 External Temperature Input No effect

191 Ext. Temperature Input Connection Type No effect

42 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

2.2.4 Function parameters SIPROTEC 7SJ80

The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.

Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes

No. Function Setting Logical Nodes

103 Setting Group Change Option No effect

104 Oscillographic Fault Records Disabled -

Enabled RDRE1

112 50/51 (Charac. Phase) Disabled -


Overcurrent Protection
Definite Time PTOC6, PTOC7,
PTOC18, PTRC2

TOC IEC PTOC6, PTOC7, PTOC1


PTOC18, PTRC2

TOC ANSI PTOC6, PTOC7,


PTOC1, PTOC18,
PTRC2

113 50N/51N (Charac. Ground) Disabled -


Overcurrent Protection
Definite Time PTOC8, PTOC9, PTRC2

TOC IEC PTOC8, PTOC9, PTOC2,


PTRC2

TOC ANSI PTOC8, PTOC9, PTOC2,


PTRC2

115 67, 67-TOC Disabled -


Directional Overcurrent Protection
Definite Time PTOC10, PTOC11,
PTRC3

TOC IEC PTOC10, PTOC11,


PTOC3, PTRC3

TOC ANSI PTOC10, PTOC11,


PTOC3, PTRC3

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 43


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

116 67N, 67N-TOC Disabled -


Directional Overcurrent Protection
Definite Time PTOC12, PTOC13,
PTRC3

TOC IEC PTOC12, PTOC13,


PTOC4, PTRC3

TOC ANSI PTOC12, PTOC13,


PTOC4, PTRC3

117 Cold Load Pickup No effect

122 2nd Harmonic Inrush Restraint No effect

127 50 1Ph Disabled -


Single Phase Overcurrent Protection
Enabled PTOC16, PTOC17

130 (sens.) Ground fault dir. characteristic cos ϕ / sin ϕ see Parameter 131

V0/I0 ϕ mea. see Parameter 131

131 (sensitive) Ground fault Disabled -


and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
cos ϕ / sin ϕ
User Defined PU PHIZ1, PSDE2, PSDE3

131 (sensitive) Ground fault Disabled -


and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
V0/I0 ϕ mea.
User Defined PU PHIZ1, PSDE1, PSDE2

140 46 Negative Sequence Protection Disabled -

TOC ANSI PTOC14, PTOC15,


PTOC5

TOC IEC PTOC14, PTOC15,


PTOC5

Definite Time PTOC14, PTOC15

142 49 Thermal Overload Protection Disabled -

No ambient temp PTTR1

44 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

Table 2-3 SIPROTEC 7SJ80 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

150 27, 59 Under/Overvoltage Protection Disabled -

Enabled PTUV1, PTUV2,


PTOV1, PTOV2

154 81 Over/Underfrequency Protection Disabled -

Enabled PTOF1 – PTOF4,


PTUF1 – PTUF4

161 25 Function group 1 Disabled -


Synchronism and Voltage Check
SYNCHROCHECK RSYN1

170 50BF Breaker Failure Protection Disabled -

Enabled RBRF1

enabled w/ 3I0> RBRF1

171 79 Auto-Reclose Function Disabled -

Enabled RREC1

172 52 Breaker Wear Monitoring No effect

180 Fault Locator Disabled -

Enabled RFLO1

181 Line sections for fault locator 1 Section No effect


2 Sections
3 Sections

182 74TC Trip Circuit Supervision Disabled -

2 Binary Inputs DOI CirSpv, LN XCBR


LD PROT

1 Binary Input DOI CirSpv, LN XCBR


LD PROT

192 Capacitive voltage measurement No effect

617 Port B usage No effect

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 45


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

2.2.5 Function parameters SIPROTEC 7SK80

The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.

Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes

No. Function Setting Logical Nodes

103 Setting Group Change Option No effect

104 Oscillographic Fault Records Disabled -

Enabled RDRE1

112 50/51 (Charac. Phase) Disabled -


Overcurrent Protection
Definite Time PTOC6, PTOC7,
PTOC18, PTRC2

TOC IEC PTOC6, PTOC7, PTOC1


PTOC18, PTRC2

TOC ANSI PTOC6, PTOC7,


PTOC1, PTOC18,
PTRC2

113 50N/51N (Charac. Ground) Disabled -


Overcurrent Protection
Definite Time PTOC8, PTOC9, PTRC2

TOC IEC PTOC8, PTOC9, PTOC2,


PTRC2

TOC ANSI PTOC8, PTOC9, PTOC2,


PTRC2

116 67N, 67N-TOC Disabled -


Directional Overcurrent Protection
Definite Time PTOC12, PTOC13,
PTRC3

TOC IEC PTOC12, PTOC13,


PTOC4, PTRC3

TOC ANSI PTOC12, PTOC13,


PTOC4, PTRC3

117 Cold Load Pickup No effect

46 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.2 Effects of Configuration on the Logical Nodes

Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

122 2nd Harmonic Inrush Restraint No effect

130 (sens.) Ground fault dir. characteristic cos ϕ / sin ϕ see Parameter 131

V0/I0 ϕ mea. see Parameter 131

131 (sensitive) Ground fault Disabled -


and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
cos ϕ / sin ϕ
User Defined PU PHIZ1, PSDE2, PSDE3

131 (sensitive) Ground fault Disabled -


and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
V0/I0 ϕ mea.
User Defined PU PHIZ1, PSDE1, PSDE2

140 46 Negative Sequence Protection Disabled -

TOC ANSI PTOC14, PTOC15,


PTOC5

TOC IEC PTOC14, PTOC15,


PTOC5

Definite Time PTOC14, PTOC15

141 48 Startup Supervision of Motors Disabled -

Enabled PMSS1

142 49 Thermal Overload Protection Disabled -

No ambient temp PTTR1

With amb. temp. PTTR1

143 66 Startup Counter for Motors Disabled -

Enabled PMRI1

144 Load Jam Protection Disabled -

Enabled PMLJ1

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 47


C53000-G1140-C211-4, Edition 03.2010
Basics
2.2 Effects of Configuration on the Logical Nodes

Table 2-4 SIPROTEC 7SK80 - Effects of Function parameters to the Logical Nodes (Forts.)

No. Function Setting Logical Nodes

150 27, 59 Under/Overvoltage Protection Disabled -

Enabled PTUV1, PTUV2,


PTOV1, PTOV2

154 81 Over/Underfrequency Protection Disabled -

Enabled PTOF1 – PTOF4,


PTUF1 – PTUF4

170 50BF Breaker Failure Protection Disabled -

Enabled RBRF1

enabled w/ 3I0> RBRF1

172 52 Breaker Wear Monitoring No effect

182 74TC Trip Circuit Supervision Disabled -

2 Binary Inputs DOI CirSpv, LN XCBR


LD PROT

1 Binary Input DOI CirSpv, LN XCBR


LD PROT

190 External Temperature Input No effect

191 Ext. Temperature Input Connection Type No effect

192 Capacitive voltage measurement No effect

617 Port B usage No effect

48 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.3 Allocation of Logical Nodes to Logical Devices

2.3 Allocation of Logical Nodes to Logical Devices

All Logical Nodes (LN) are allocated to Logical Devices (LD). The following tables show this
allocation and the DOIs available for each LN.

LD PROT
The Logical Device PROT (Protection) contains the following LNs:

Table 2-5 LD PROT - Logical Nodes

LN Function DOI

LLN0 General Mod, Beh, Health, NamPlt, OpTmh

PTRC1 General device pickup Mod, Beh, Health, NamPlt, Str,Tr,FinTr


General OFF

XCBR1 52 Breaker Mod, Beh, Health, NamPlt, Loc, OpCnt, Pos


Three-pole tripping BlkOpn, BlkCls, CBOpCap
SumSwARs1, SumSwARs2, SumSwARs3

PTOC6 50/51 (Charac. Phase) Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC7
PTOC1
PTOC18
PTRC2

PTOC8 50N/51N (Charac. Ground) Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC9
PTOC2
PRTC2

PTOC10 67, 67-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC11
PTOC3
PTRC3

PTOC12 67N, 67N-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC13
PTOC4
PRTC2

PTOC16 50 1Ph Mod, Beh, Health, NamPlt, Str, Op


PTOC17

PTUV1 27 Undervoltage Protection Mod, Beh, Health, NamPlt, Str, Op


PTUV2

PTOV1 59 Overvoltage Protection Mod, Beh, Health, NamPlt, Str, Op


PTOV2

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 49


C53000-G1140-C211-4, Edition 03.2010
Basics
2.3 Allocation of Logical Nodes to Logical Devices

Table 2-5 LD PROT - Logical Nodes (Forts.)

LN Function DOI

PTOC14 46 Negative Sequence Protection Mod, Beh, Health, NamPlt, Str, Op


PTOC15
PTOC5

PMSS1 48 Startup Supervision of Motors Mod, Beh, Health, NamPlt, Str, Op

PMRI1 66 Startup Counter for Motors Mod, Beh, Health, NamPlt, Op, StrInhTmm

PMLJ1 Load Jam Protection Mod, Beh, Health, NamPlt, Str, Op, LDJamAlm,
ChgSet

PTUF1 81 Underfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV
PTUF2
PTUF3
PTUF4

PTOF1 81 Overfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV
PTOF2
PTOF3
PTOF4

PTTR1 49 Thermal Overload Protection Mod, Beh, Health, NamPlt, Str, Op, AlmThm

PSDE1 (sensitive) Ground fault Mod, Beh, Health, NamPlt, Str, Op


PSDE2
PSDE3

PHIZ1 (sensitive) Ground fault Mod, Beh, Health, NamPlt, Str, Op

RREC1 79 Auto-Reclose Function Mod, Beh, Health, NamPlt, Op, AutoRecSt

RFLO1 Fault Locator Mod, Beh, Health, NamPlt, FltZ, FltDiskm, FltDisPrc

RBRF1 50BF Breaker Failure Protection Mod, Beh, Health, NamPlt, Str, OpEx, OpIn

LPHD1 Device PhyNam, PhyHealth, Proxy

50 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.3 Allocation of Logical Nodes to Logical Devices

LD MEAS
The Logical Device MEAS (Measurement) contains the following LNs:

Table 2-6 LD MEAS - Logical Nodes

LN Function DOIs

LLN0 General Mod, Beh, Health, NamPlt

MMXU1 Operational measured values Mod, Beh, Health, NamPlt,


TotW, TotVAr, TotVA, TotPF, Hz, PPV, PhV, A

MMTR1 Power Metering Mod, Beh, Health, NamPlt,


SupWh, SupVArh, DmdWh, DmdVArh

MSQI1 Measured values, symmetrical Mod, Beh, Health, NamPlt, SeqA, SeqV
components

LPHD1 Device PhyNam, PhyHealth, Proxy

LD DR
The Logical Device DR (Disturbance Recorder) contains the following LNs:

Table 2-7 LD DR - Logical Nodes

LN Function DOIs

LLN0 General Mod, Beh, Health, NamPlt

RDRE1 Oscillographic Fault Records Mod, Beh, Health, NamPlt, RcdMade, RcdStr
FltNum, GriFltNum

LPHD1 Device PhyNam, PhyHealth, Proxy

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 51


C53000-G1140-C211-4, Edition 03.2010
Basics
2.3 Allocation of Logical Nodes to Logical Devices

LD CTRL
The Logical Device CTRL (Control) contains the following LNs:

Table 2-8 LD CTRL - Logical Nodes

LN Function DOIs

LLN0 General Mod, Beh, Health, NamPlt, LEDRs, Loc

RSYN1 25 Function group 1 Mod, Beh, Health, NamPlt,


RSYN2 25 Function group 2 Rel, VInd, AngInd, HzInd, SynPrg,
RSYN3 25 Function group 3 DifVClc, DifHzClc, DifAngClc
RSYN4 25 Function group 4

CALH1 Error with a summary alarm and Mod, Beh, Health, NamPlt, GrAlm, GrWrn,
Alarm summary event ErrBoard1, ErrBoard2, ErrBoard3, ErrBoard4,
ErrBoard5, ErrBoard6, ErrBoard7

LPHD1 Device PhyNam, PhyHealth, Proxy, CtlNum, DevStr

LD EXT
The Logical Device EXT (Extended) contains the following LNs:

Table 2-9 LD EXT - Logical Nodes

LN Function DOIs

LLN0 General Mod, Beh, Health, NamPlt, LEDRs, Loc

LPHD1 Device PhyNam, PhyHealth, Proxy, CtlNum

The Logical Nodes of the switching (and userdefined) objects will be created by DIGSI during
the parameterization of your SIPROTEC device.
MICS, Model Implementation Conformance Statement, shows the assignment of the DOIs;
you can use DIGSI to print the MICS.

52 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.4 Logical Node LLN0

2.4 Logical Node LLN0

2.4.1 Logical Device PROT

LLN0.Mod

No. Information

52 At Least 1 Protection Funct. is Active (ProtActive) 0 1 1 1 1

Test mode (Test mode) x 0 0 1 1

Stop data transmission (DataStop) x 0 1 0 1

LLN0.Mod.stVal 5 1 2 3 4

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

LLN0.Beh

No. Information

52 At Least 1 Protection Funct. is Active (ProtActive) 0 1 1 1 1

Test mode (Test mode) x 0 0 1 1

Stop data transmission (DataStop) x 0 1 0 1

LLN0.Beh.stVal 5 1 2 3 4

device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

LLN0.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

LLN0.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 53


C53000-G1140-C211-4, Edition 03.2010
Basics
2.4 Logical Node LLN0

LLN0.OpTmh

No. Information Value

1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)

54 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.4 Logical Node LLN0

2.4.2 Logical Devices MEAS, DR and EXT

LLN0.Mod

No. Information

51 Device is Operational and Protecting (Device OK) x x x x

Test mode (Test mode) 1 1 0 0

Stop data transmission (DataStop) 1 0 1 0

LLN0.Mod.stVal 4 3 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

LLN0.Beh

No. Information

51 Device is Operational and Protecting (Device OK) 0 1 1 1 1

Test mode (Test mode) x 0 0 1 1

Stop data transmission (DataStop) x 0 1 0 1

LLN0.Beh.stVal 5 1 2 3 4

device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

LLN0.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

LLN0.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 55


C53000-G1140-C211-4, Edition 03.2010
Basics
2.4 Logical Node LLN0

LLN0.OpTmh

No. Information Value

1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)

2.4.3 Logical Device CTRL

LLN0.Mod

No. Information

55 Reset Device (Reset Device) 1 1 1 1 1

51 Device is Operational and Protecting (Device OK) 1 1 1 1 0

Test mode (Test mode) 1 1 0 0 0

Stop data transmission (DataStop) 1 0 1 0 0

LLN0.Mod.stVal 4 3 2 1 5

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

LLN0.Beh

No. Information

55 Reset Device (Reset Device) 1 1 1 1 1

51 Device is Operational and Protecting (Device OK) 1 1 1 1 0

Test mode (Test mode) 1 1 0 0 0

Stop data transmission (DataStop) 1 0 1 0 0

LLN0.Beh.stVal 4 3 2 1 5

device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

56 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.4 Logical Node LLN0

LLN0.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

LLN0.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

LLN0.OpTmh

No. Information Value

1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 57


C53000-G1140-C211-4, Edition 03.2010
Basics
2.5 DOI Behavior

2.5 DOI Behavior

2.5.1 Logical Device PROT

For the Logical Nodes of the PROT Logical Device, LNx.Beh.stVal is formed from
LNx.Mod.stVal of the Logical Node and the status of the following device messages:
‰ Test mode (Test mode),

‰ Stop data transmission and

‰ At Least 1 Protection Funct. is Active.

No. Information

Test mode (Test mode) x 0 1 0 1 0 1 x

Stop data transmission (DataStop) x 0 0 1 1 x x x

52 At Least 1 Protection Funct. is Active (ProtActive) x 1 1 1 1 1 1 0

LNx .Mod.stVal 5 1 1 1 1 2 2 x

LNx.Beh.stVal 5 1 3 2 4 2 4 5

device annunciation / setting: 1 - ON / TRUE IEC Status stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

58 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Basics

2.5 DOI Behavior

2.5.2 Logical Devices MEAS, CTRL, DR and EXT

For the Logical Nodes of the MEAS, CTRL, DR and EXT Logical Devices, LNx.Beh.stVal is
formed from LNx.Mod.stVal of the Logical Node and the status of the following device
messages:
‰ Test mode (Test mode),

‰ Stop data transmission.

No. Information

Test mode (Test mode) x 0 1 0 1 0 1

Stop data transmission (DataStop) x 0 0 1 1 x x

LNx .Mod.stVal 5 1 1 1 1 2 2

LNx.Beh.stVal 5 1 3 2 4 2 4

device annunciation / setting: 1 - ON / TRUE IEC Status stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 59


C53000-G1140-C211-4, Edition 03.2010
Basics
2.5 DOI Behavior

60 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping 3

Contents
This chapter shows the mapping of the information relevant to the device on the Logical Node of
protocol IEC61850. It is structured according to function. In Chapter 2 you can find what
consequences non-configured functions have on the Logical Nodes as well as general
information about IEC 61850 mapping of information.

3.1 Device (LPHD1, CALH1) 62

3.2 Oscillographic Fault Records (RDRE1) 66

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2) 68

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3) 81

3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17) 93

3.6 Voltage Protection 27, 59 (PTUVx, PTOVx) 96

3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5) 104

3.8 Motor Protection (PMSS1, PMRI1) 108

3.9 Load Jam Protection (PMLJ1) 111

3.10 Frequency protection 81 O/U (PTUFx, PTOFx) 113

3.11 Thermal overload protection (PTTR1) 129

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) 131

3.13 Automatic Reclosing System 79 (RREC1) 140

3.14 Fault Locator (RFLO1) 142

3.15 Circuit breaker failure protection 50BF(RBRF1) 144

3.16 Synchronism and Voltage Check 25 (RSYNx) 146

3.17 Three-pole tripping 52 Breaker (XCBR1) 158

3.18 Tripping Logic of the Entire Device (PTRC1) 162

3.19 Measurement (MMXU1, MSQI1, MMTR1) 164

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 61


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.1 Device (LPHD1, CALH1)

3.1 Device (LPHD1, CALH1)

LPHD1.DevStr

No. Information

56 Initial Start of Device (Initial Start) 0 0 1 1

67 Resume (Resume) 0 1 0 1

LPHD1.DevStr.stVal T 2 1 T

device annunciation: 1 - ON IEC Status DevStr.stVal: 1 - Initial Start


0 - OFF 2 - Resume
T - toggel between 1 and 2

LPHD1.Proxy

No. Information

55 Reset Device (Reset Device) 0 1

LPHD1.Proxy.stVal 1 0

device annunciation: 1 - ON IEC Status Proxy.stVal: 0 - DEVICE is not a PROXY


0 - OFF 1 - DEVICE is a PROXY

LPHD1.PhyHealth

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

LPHD1.PhyHealth.stVal 3 1

device annunciation: 1 - ON IEC Status PhyHealth.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

62 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.1 Device (LPHD1, CALH1)

3.1.1 Error with a summary alarm and Alarm summary event

CALH1.Mod

No. Information

51 Device is Operational and Protecting (Device OK) 1 0

CALH1.Mod.stVal 1 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF

CALH1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

CALH1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

CALH1.GrAlm

No. Information

140 Error with a summary alarm (Error Sum Alarm) 1 0

CALH1.GrAlm.stVal 1 0

device annunciation: 1 - ON IEC Status GrAlm.stVal: 0 - FALSE


0 - OFF 1 - TRUE

CALH1.GrWrn

No. Information

160 Alarm Summary Event (Alarm Sum Event) 1 0

CALH1.GrWrn.stVal 1 0

device annunciation: 1 - ON IEC Status GrWrn.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 63


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.1 Device (LPHD1, CALH1)

The LN CALH1.ErrBoard1 to CALH1.ErrBoard7 are available with Firmware


7SJ61 V4.71 and higher, 7SJ62 V4.71 and higher, 7SJ64 V4.71 and higher,
7SJ80 V4.61 and higher, 7SK80 V4.61 and higher

CALH1.ErrBoard1

No. Information

183 Error Board 1 (Error Board 1) 1 0

CALH1.ErrBoard1.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard1.stVal: 0 - FALSE


0 - OFF 1 - TRUE

CALH1.ErrBoard2

No. Information

184 Error Board 2 (Error Board 2) 1 0

CALH1.ErrBoard2.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard2.stVal: 0 - FALSE


0 - OFF 1 - TRUE

CALH1.ErrBoard3

No. Information

185 Error Board 3 (Error Board 3) 1 0

CALH1.ErrBoard3.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard3.stVal: 0 - FALSE


0 - OFF 1 - TRUE

CALH1.ErrBoard4

No. Information

186 Error Board 4 (Error Board 4) 1 0

CALH1.ErrBoard4.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard4.stVal: 0 - FALSE


0 - OFF 1 - TRUE

64 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.1 Device (LPHD1, CALH1)

CALH1.ErrBoard5

No. Information

187 Error Board 5 (Error Board 5) 1 0

CALH1.ErrBoard5.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard5.stVal: 0 - FALSE


0 - OFF 1 - TRUE

CALH1.ErrBoard6

No. Information

188 Error Board 6 (Error Board 6) 1 0

CALH1.ErrBoard6.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard6.stVal: 0 - FALSE


0 - OFF 1 - TRUE

CALH1.ErrBoard7

No. Information

189 Error Board 7 (Error Board 7) 1 0

CALH1.ErrBoard7.stVal 1 0

device annunciation: 1 - ON IEC Status ErrBoard7.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 65


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.2 Oscillographic Fault Records (RDRE1)

3.2 Oscillographic Fault Records (RDRE1)

RDRE1.Mod

No. Information

55 Reset Device (Reset Device) x

RDRE1.Mod.stVal 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

RDRE1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

RDRE1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

RDRE1.RcdMade

No. Information

30053 Fault recording is running (Fault rec. run.) 0 1

RDRE1.RcdMade.stVal 1 0

device annunciation: 1 - ON IEC Status RcdMade.stVal: 0 - FALSE


0 - OFF 1 - TRUE
(Recording complete)

66 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.2 Oscillographic Fault Records (RDRE1)

RDRE1.FltNum

No. Information Value

302 Fault Event (Fault Event) RDRE1.FltNum.stVal Present fault number

RDRE1.GriFltNum

No. Information Value

301 Power System fault (Pow.Sys.Flt.) RDRE1.GriFltNum.stVal Network fault number

RDRE1.RcdStr

No. Information

30053 Fault recording is running (Fault rec. run.) 0 1

RDRE1.RcdStr.stVal 0 1

device annunciation: 1 - ON IEC Status RcdStr.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 67


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

3.3.1 Overcurrent Protection 50, 51 PH (PTOC6, PTOC7, PTOC1, PTOC18)

PTOC6.Mod

No. Information

1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

50-1 PICKUP (P1204) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC6.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC6.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC6.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC6.Str

No. Information

1810 50-1 picked up (50-1 picked up) 0 1

PTOC6.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

68 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC6.Op

No. Information

1815 50-1 TRIP (50-1 TRIP) 0 1

PTOC6.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC6.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC6.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC7.Mod

No. Information

1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

50-2 PICKUP (P1202) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC7.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC7.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC7.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 69


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC7.Str

No. Information

1800 50-2 picked up (50-2 picked up) 0 1

PTOC7.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC7.Op

No. Information

1805 50-2 TRIP (50-2 TRIP) 0 1

PTOC7.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC7.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC7.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC1.Mod

No. Information

1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

51 PICKUP (P1207) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC1.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

70 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC1.Str

No. Information

1820 51 picked up (51 picked up) 0 1

PTOC1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC1.Op

No. Information

1825 51 TRIP (51 TRIP) 0 1

PTOC1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC1.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC1.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 71


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC18.Mod

No. Information

1753 50/51 O/C is ACTIVE (50/51 PH ACT) x x x x x

1752 50/51 O/C is BLOCKED (50/51 PH BLK) x x x 1 0

1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0 0 0

50-3 PICKUP(P1217) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC18.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC18.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC18.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC18.Str

No. Information

1767 50-3 picked up (50-3 picked up) 0 1

PTOC18.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

72 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC18.Op

No. Information

1769 50-3 TRIP (50-3 TRIP) 0 1

PTOC18.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC18.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC18.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 73


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

3.3.2 Overcurrent Protection 50N, 51N (PTOC8, PTOC9, PTOC2)

PTOC8.Mod

No. Information

7158 50N/51N is ACTIVE (50N/51N ACT) x x x x x

7157 50N/51N is BLOCKED (50N/51N BLK) x x x 1 0

7156 50N/51N is OFF (50N/51N OFF) 1 x 0 0 0

50N-1 PICKUP (P1304) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC8.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC8.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC8.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC8.Str

No. Information

1834 50N-1 picked up (50N-1 picked up) 0 1

PTOC8.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

74 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC8.Op

No. Information

1836 50N-1 TRIP (50N-1 TRIP) 0 1

PTOC8.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC8.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC8.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC9.Mod

No. Information

7158 50N/51N is ACTIVE (50N/51N ACT) x x x x x

7157 50N/51N is BLOCKED (50N/51N BLK) x x x 1 0

7156 50N/51N is OFF (50N/51N OFF) 1 x 0 0 0

50N-2 PICKUP (P1302) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC9.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC9.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC9.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 75


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC9.Str

No. Information

1831 50N-2 picked up (50N-2 picked up) 0 1

PTOC9.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC9.Op

No. Information

1833 50N-2 TRIP (50N-2 TRIP) 0 1

PTOC9.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC9.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC9.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC2.Mod

No. Information

7158 50N/51N is ACTIVE (50N/51N ACT) x x x x x

7157 50N/51N is BLOCKED (50N/51N BLK) x x x 1 0

7156 50N/51N is OFF (50N/51N OFF) 1 x 0 0 0

51N PICKUP (P1307) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC2.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

76 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTOC2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC2.Str

No. Information

1837 51N picked up (51N picked up) 0 1

PTOC2.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC2.Op

No. Information

1839 51N TRIP (51N TRIP) 0 1

PTOC2.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC2.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC2.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 77


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

3.3.3 Overcurrent Protection 50N, 51N (PTRC2)

PTRC2.Mod

No. Information

1753 50/51 O/C is ACTIVE (50/51 PH ACT) or x x x x


1758 50N/51N is ACTIVE (50N/51N ACT)

1752 50/51 O/C is BLOCKED (50/51 PH BLK) and x x 1 0


1757 50N/51N is BLOCKED (50N/51N BLK)

1751 50/51 O/C switched OFF (50/51 PH OFF) and 1 0 0 0


1756 50N/51N is OFF (50N/51N OFF)

Frequency range is exceeded x 1 x 0

PTRC2.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTRC2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTRC2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTRC2.Str

No. Information

1761 50(N)/51(N) O/C PICKUP (50(N)/51(N) PU) 0 1

PTRC2.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTRC2.Str.dirGeneral

No. Information

PTRC2.Str.dirGeneral 0

device annunciation: IEC Status Str.dirGeneral: 0 - UNKNOWN

78 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTRC2.Str.phsA

No. Information

1762 50/51 Phase A picked up (50/51 Ph A PU) 0 1

PTRC2.Str.phsA 0 1

device annunciation: 1 - ON IEC Status Str.phsA: 0 - FALSE


0 - OFF 1 - TRUE

PTRC2.Str.dirPhsA

No. Information

PTRC2.Str.dirPhsA 0

device annunciation: IEC Status Str.dirPhsA: 0 - UNKNOWN

PTRC2.Str.phsB

No. Information

1763 50/51 Phase B picked up (50/51 Ph B PU) 0 1

PTRC2.Str.phsB 0 1

device annunciation: 1 - ON IEC Status Str.phsB: 0 - FALSE


0 - OFF 1 - TRUE

PTRC2.Str.dirPhsB

No. Information

PTRC2.Str.dirPhsB 0

device annunciation: IEC Status Str.dirPhsB: 0 - UNKNOWN

PTRC2.Str.phsC

No. Information

1764 50/51 Phase C picked up (50/51 Ph C PU) 0 1

PTRC2.Str.phsC 0 1

device annunciation: 1 - ON IEC Status Str.phsC: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 79


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)

PTRC2.Str.dirPhsC

No. Information

PTRC2.Str.dirPhsC 0

device annunciation: IEC Status Str.dirPhsC: 0 - UNKNOWN

PTRC2.Str.neut

No. Information

1765 50N/51N picked up (50N/51NPickedup) 0 1

PTRC2.Str.neut 0 1

device annunciation: 1 - ON IEC Status Str.neut: 0 - FALSE


0 - OFF 1 - TRUE

PTRC2.Str.dirNeut

No. Information

PTRC2.Str.dirNeut 0

device annunciation: IEC Status Str.dirPhsC: 0 - UNKNOWN

PTRC2.Op

No. Information

1791 50(N)/51(N) TRIP (50(N)/51(N)TRIP) 0 1

PTRC2.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

80 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

3.4.1 Directional Overcurrent Protection 67 (PTOC10, PTOC11, PTOC3)

PTOC10.Mod

No. Information

2653 67/67-TOC is ACTIVE (67 ACTIVE) x x x x x

2652 67/67-TOC is BLOCKED (67 BLOCKED) x x x 1 0

2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 x 0 0 0

67-1 PICKUP (P1504) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC10.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC10.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC10.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC10.Str

No. Information

2660 67-1 picked up (67-1 picked up) 0 1

PTOC10.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 81


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTOC10.Op

No. Information

2665 67-1 TRIP (67-1 TRIP) 0 1

PTOC10.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC10.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC10.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC11.Mod

No. Information

2653 67/67-TOC is ACTIVE (67 ACTIVE) x x x x x

2652 67/67-TOC is BLOCKED (67 BLOCKED) x x x 1 0

2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 x 0 0 0

67-2 PICKUP (P1502) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC11.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC11.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC11.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

82 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTOC11.Str

No. Information

2642 67-2 picked up (67-2 picked up) 0 1

PTOC11.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC11.Op

No. Information

2649 67-2 TRIP (67-2 TRIP) 0 1

PTOC11.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC11.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC11.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC3.Mod

No. Information

2653 67/67-TOC is ACTIVE (67 ACTIVE) x x x x x

2652 67/67-TOC is BLOCKED (67 BLOCKED) x x x 1 0

2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 x 0 0 0

67-TOC PICKUP (P1507) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC3.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 83


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTOC3.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC3.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC3.Str

No. Information

2670 67-TOC picked up (67-TOC picked up) 0 1

PTOC3.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC3.Op

No. Information

2675 67-TOC TRIP (67-TOC TRIP) 0 1

PTOC3.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC3.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC3.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

84 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

3.4.2 Directional Overcurrent Protection 67N (PTOC12, PTOC13, PTOC4)

PTOC12.Mod

No. Information

2658 67N/67N-TOC is ACTIVE (67N ACTIVE) x x x x x

2657 67N/67N-TOC is BLOCKED (67N BLOCKED) x x x 1 0

2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0 0 0

67N-1 PICKUP (P1604) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC12.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC12.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC12.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC12.Str

No. Information

2681 67N-1 picked up (67N-1 picked up) 0 1

PTOC12.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 85


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTOC12.Op

No. Information

2683 67N-1 TRIP (67N-1 TRIP) 0 1

PTOC12.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC12.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC12.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC13.Mod

No. Information

2658 67N/67N-TOC is ACTIVE (67N ACTIVE) x x x x x

2657 67N/67N-TOC is BLOCKED (67N BLOCKED) x x x 1 0

2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0 0 0

67N-2 PICKUP (P1602) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC13.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC13.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC13.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

86 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTOC13.Str

No. Information

2646 67N-2 picked up (67N-2 picked up) 0 1

PTOC13.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC13.Op

No. Information

2679 67N-2 TRIP (67N-2 TRIP) 0 1

PTOC13.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC13.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC13.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

PTOC4.Mod

No. Information

2658 67N/67N-TOC is ACTIVE (67N ACTIVE) x x x x x

2657 67N/67N-TOC is BLOCKED (67N BLOCKED) x x x 1 0

2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0 0 0

M.of PU TD (P1630) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC4.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 87


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTOC4.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC4.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC4.Str

No. Information

2684 67N-TOC picked up (67N-TOCPickedup) 0 1

PTOC4.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC4.Op

No. Information

2686 67N-TOC TRIP (67N-TOC TRIP) 0 1

PTOC4.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC4.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PTOC4.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

88 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

3.4.3 Directional Overcurrent Protection 67N (PTRC3)

PTRC3.Mod

No. Information

67/67-TOC is ACTIVE (67 ACTIVE) (I 2653) or x x x x


67N/67N-TOC is ACTIVE (67N ACTIVE) (I 2658)

67/67-TOC is BLOCKED (67 BLOCKED) (I 2652) and x x 1 0


67N/67N-TOC is BLOCKED (67N BLOCKED) (I 2657)

67/67-TOC switched OFF (67/67-TOC OFF) (I 2651) and 1 0 0 0


67N/67N-TOC switched OFF (67N OFF) (I 2656)

Frequency range is exceeded x 1 x 0

PTRC3.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTRC3.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTRC3.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTRC3.Str

No. Information

2691 67/67N picked up (67/67N pickedup) 0 1

PTRC3.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 89


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTRC3.Str.dirGeneral

No. Information

2691 67/67N picked up (67/67N picked up) 0 1 1 1 1

Phase A forward (Phase A forward) (I 2628) or x 0 1 0 1


Phase B forward (Phase B forward) (I 2629) or
Phase C forward (Phase C forward) (I 2630) or
Ground forward (Ground forward) (I 2635)

Phase A reverse (Phase A reverse) (I 2632) or x 0 0 1 1


Phase B reverse (Phase B reverse) (I 2633) or
Phase C reverse (Phase C reverse) (I 2634) or
Ground reverse (Ground reverse) (I 2636)

PTRC3.Str.dirGeneral 0 0 1 2 3

device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN


0 - OFF 1 - FORWARD
2 - BACKWARD
3 - BOTH

PTRC3.Str.phsA

No. Information

2692 67/67-TOC Phase A picked up (67 A picked up) 0 1

PTRC3.Str.phsA 0 1

device annunciation: 1 - ON IEC Status Str.phsA: 0 - FALSE


0 - OFF 1 - TRUE

PTRC3.Str.dirPhsA

No. Information

2692 67/67-TOC Phase A picked up (67 A picked up) 0 1 1 1 1

2628 Phase A forward (Phase A forward) x 0 1 0 1

2632 Phase A reverse (Phase A reverse) x 0 0 1 1

PTRC3.Str.dirPhsA 0 0 1 2 3

device annunciation: 1 - ON IEC Status Str.dirPhsA: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

90 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTRC3.Str.phsB

No. Information

2693 67/67-TOC Phase B picked up (67 B picked up) 0 1

PTRC3.Str.phsB 0 1

device annunciation: 1 - ON IEC Status Str.phsB: 0 - FALSE


0 - OFF 1 - TRUE

PTRC3.Str.dirPhsB

No. Information

2693 67/67-TOC Phase B picked up (67 B picked up) 0 1 1 1 1

2629 Phase B forward (Phase B forward) x 0 1 0 1

2633 Phase B reverse (Phase B reverse) x 0 0 1 1

PTRC3.Str.dirPhsB 0 0 1 2 3

device annunciation: 1 - ON IEC Status Str.dirPhsB: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

PTRC3.Str.phsC

No. Information

2694 67/67-TOC Phase C picked up (67 C picked up) 0 1

PTRC3.Str.phsC 0 1

device annunciation: 1 - ON IEC Status Str.phsC: 0 - FALSE


0 - OFF 1 - TRUE

PTRC3.Str.dirPhsC

No. Information

2694 67/67-TOC Phase C picked up (67 C picked up) 0 1 1 1 1

2630 Phase C forward (Phase C forward) x 0 1 0 1

2634 Phase C reverse (Phase C reverse) x 0 0 1 1

PTRC3.Str.dirPhsC 0 0 1 2 3

device annunciation: 1 - ON IEC Status Str.dirPhsC: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 91


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)

PTRC3.Str.neut

No. Information

2695 67N/67N-TOC picked up (67N picked up) 0 1

PTRC3.Str.neut 0 1

device annunciation: 1 - ON IEC Status Str.neut: 0 - FALSE


0 - OFF 1 - TRUE

PTRC3.Str.dirNeut

No. Information

2695 67N/67N-TOC picked up (67N picked up) 0 1 1 1 1

2635 Ground forward (Ground forward) x 0 1 0 1

2636 Ground reverse (Ground reverse) x 0 0 1 1

PTRC3.Str.dirNeut 0 0 1 2 3

device annunciation: 1 - ON IEC Status Str.dirPhsC: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

PTRC3.Op

No. Information

2696 67/67N TRIP (67/67N TRIP) 0 1

PTRC3.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

92 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)

3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)

PTOC16.Mod

No. Information

5963 50 1Ph is ACTIVE (50 1Ph ACTIVE) x x x x x

5962 50 1Ph is BLOCKED (50 1Ph BLOCKED) x x x 1 0

5961 50 1Ph is OFF (50 1Ph OFF) 1 x 0 0 0

50 1Ph-1 PICKUP (P2705) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC16.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC16.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC16.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC16.Str

No. Information

5974 50 1Ph-1 picked up (50 1Ph-1 PU) 0 1

PTOC16.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 93


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)

PTOC16.Op

No. Information

5975 50 1Ph-1 TRIP (50 1Ph-1 TRIP) 0 1

PTOC16.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC17.Mod

No. Information

5963 50 1Ph is ACTIVE (50 1Ph ACTIVE) x x x x x

5962 50 1Ph is BLOCKED (50 1Ph BLOCKED) x x x 1 0

5961 50 1Ph is OFF (50 1Ph OFF) 1 x 0 0 0

50 1Ph-2 PICKUP (P2703) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PTOC17.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC17.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC17.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

94 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)

PTOC17.Str

No. Information

5977 50 1Ph-2 picked up (50 1Ph-2 PU) 0 1

PTOC17.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC17.Op

No. Information

5979 50 1Ph-2 TRIP (50 1Ph-2 TRIP) 0 1

PTOC17.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 95


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

3.6.1 Undervoltage Protection 27 (PTUV1)

PTUV1.Mod

No. Information

6532 27 Undervoltage protection is ACTIVE (27 ACTIVE) x x x x

6531 27 Undervoltage protection is BLOCKED (27 BLOCKED) x x 1 0

170 VT Fuse Failure (alarm instantaneous) (VT FuseFail) x 1 x 0

6530 27 Undervoltage protection switched OFF (27 OFF) 1 0 0 0

PTUV1.Mod.stVal 5 2 2 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTUV1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTUV1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

96 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

PTUV1.Str

No. Information

6533 27-1 Undervoltage picked up (27-1 picked up) 0 x 1

6534 27-1 Undervoltage PICKUP w/curr. superv (27-1 PU CS) 0 1 x

PTUV1.Str.general 0 1 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE
x - irrelevant

PTUV1.Op

No. Information

6539 27-1 Undervoltage TRIP (27-1 TRIP) 0 1

PTUV1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 97


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

3.6.2 Undervoltage Protection 27 (PTUV2)

PTUV2.Mod

No. Information

6532 27 Undervoltage protection is ACTIVE (27 ACTIVE) x x x x

6531 27 Undervoltage protection is BLOCKED (27 BLOCKED) x x 1 0

170 VT Fuse Failure (alarm instantaneous) (VT FuseFail) x 1 x 0

6530 27 Undervoltage protection switched OFF (27 OFF) 1 0 0 0

PTUV2.Mod.stVal 5 2 2 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTUV2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTUV2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

98 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

PTUV2.Str

No. Information

6537 27-2 Undervoltage picked up (27-2 picked up) 0 x 1

6538 27-2 Undervoltage PICKUP w/curr. superv (27-2 PU CS) 0 1 x

PTUV2.Str.general 0 1 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE
X - irrelevant

PTUV2.Op

No. Information

6540 27-2 Undervoltage TRIP (27-2 TRIP) 0 1

PTUV2.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 99


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

3.6.3 Overvoltage Protection 59 (PTOV1)

PTOV1.Mod

No. Information

6567 59-Overvoltage protection is ACTIVE (59 ACTIVE) x x x x

6566 59-Overvoltage protection is BLOCKED (59 BLOCKED) x x 1 0

6565 59-Overvoltage protection switched OFF (59 OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PTOV1.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOV1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOV1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOV1.Str

No. Information

6568 59 picked up (59-1 picked up) 0 1

PTOV1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

100 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

PTOV1.Op

No. Information

6570 59 TRIP (59-1 TRIP) 0 1

PTOV1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 101


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

3.6.4 Overvoltage Protection 59 (PTOV2)

PTOV2.Mod

No. Information

6567 59-Overvoltage protection is ACTIVE (59 ACTIVE) x x x x

6566 59-Overvoltage protection is BLOCKED (59 BLOCKED) x x 1 0

6565 59-Overvoltage protection switched OFF (59 OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PTOV2.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOV2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOV2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOV2.Str

No. Information

6571 59-2 Overvoltage V>> picked up (59-2 picked up) 0 1

PTOV2.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

102 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.6 Voltage Protection 27, 59 (PTUVx, PTOVx)

PTOV2.Op

No. Information

6573 59-2 Overvoltage V>> TRIP (59-2 TRIP) 0 1

PTOV2.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 103


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)

3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)

PTOC14.Mod

No. Information

5153 46 is ACTIVE (46 ACTIVE) x x x x

5152 46 is BLOCKED (46 BLOCKED) x x 1 0

5151 46 switched OFF (46 OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PTOC14.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC14.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC14.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC14.Str

No. Information

5165 46-1 picked up (46-1 picked up) 0 1

PTOC14.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

104 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)

PTOC14.Op

No. Information

46-1 TRIP (46-1 TRIP) 0 1

PTOC14.Op.general 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOC15.Mod

No. Information

5153 46 is ACTIVE (46 ACTIVE) x x x x

5152 46 is BLOCKED (46 BLOCKED) x x 1 0

5151 46 switched OFF (46 OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PTOC15.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC15.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC15.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTOC15.Str

No. Information

5159 46-2 picked up (46-2 picked up) 0 1

PTOC15.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 105


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)

PTOC15.Op

No. Information

46-2 TRIP (46-2 TRIP) 0 1

PTOC15.Op.general 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOC5.Mod

No. Information

5153 46 is ACTIVE (46 ACTIVE) x x x x

5152 46 is BLOCKED (46 BLOCKED) x x 1 0

5151 46 switched OFF (46 OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PTOC5.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOC5.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOC5.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

106 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)

PTOC5.Str

No. Information

5166 46-TOC picked up (46-TOC pickedup) 0 1

PTOC5.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PTOC5.Op

No. Information

46-TOC TRIP (46-TOC TRIP) 0 1

PTOC5.Op.general 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 107


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.8 Motor Protection (PMSS1, PMRI1)

3.8 Motor Protection (PMSS1, PMRI1)

3.8.1 Motor Starting Protection 48 (PMSS1)

PMSS1.Mod

No. Information

6813 Startup supervision is ACTIVE (START-SUP ACT) x x x x

6812 Startup supervision is BLOCKED (START-SUP BLK) x x 1 0

6811 Startup supervision OFF (START-SUP OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PMSS1.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PMSS1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PMSS1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

108 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.8 Motor Protection (PMSS1, PMRI1)

PMSS1.Str

No. Information

6823 Startup supervision Pickup (START-SUP pu) 0 1

PMSS1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PMSS1.Op

No. Information

6821 Startup supervision TRIP (START-SUP TRIP) 0 1

PMSS1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 109


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.8 Motor Protection (PMSS1, PMRI1)

3.8.2 Motor Restart Inhibit 66 (PMRI1)

PMRI1.Mod

No. Information

4826 66 Motor start protection ACTIVE (66 ACTIVE) x x x

4825 66 Motor start protection BLOCKED (66 BLOCKED) x 1 0

4824 66 Motor start protection OFF (66 OFF)) 1 0 0

PMRI1.Mod.stVal 5 2 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PMRI1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PMRI1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PMRI1.Op

No. Information

4827 66 Motor start protection TRIP (66 TRIP) 0 1

PMRI1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PMRI1.StrInhTmm

No. Information Value

809 Time untill release of reclose-blocking (T reclose=) PMRI1.StrInhTmm.stVal Absolute value

110 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.9 Load Jam Protection (PMLJ1)

3.9 Load Jam Protection (PMLJ1)

Function available with Firmware


7SJ61 V4.71 and higher, 7SJ62 V4.71 and higher, 7SJ64 V4.71 and higher,
7SJ80 V4.60 and higher, 7SK80 V4.60 and higher

PMLJ1.Mod

No. Information

10023 Load Jam Protection is ACTIVE (JAM PROT.ACTIVE) x x x 1

10021 Load Jam Protection is BLOCKED (JAM PROT.BLOCK.) x x 1 0

10022 Load Jam Protection is OFF (JAM PROT.OFF) 1 0 0 0

Frequency range is exceeded x 1 0 0

PMLJ1.Mod.stVal 5 5 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PMLJ1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PMLJ1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 111


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.9 Load Jam Protection (PMLJ1)

PMLJ1.Str

No. Information

10025 Load Jam Protection picked up (Load Jam pickup) 0 1

PMLJ1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PMLJ1.Op

No. Information

10026 Load Jam Protection TRIP (Load Jam TRIP) 0 1

PMLJ1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PMLJ1.LodJamAlm

No. Information

10024 Load Jam Protection alarm (Load Jam alarm) 0 1

PMLJ1.LodJamAlm.stVal 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PMLJ1.ChgSet

No. Information

1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1

PMLJ1.ChgSet.stVal 0 1

device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE


0 - OFF 1 - TRUE

112 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.1 Frequency protection 81-1 U (PTUF1)

PTUF1.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x 1 0

5206 >BLOCK 81-1 (>BLOCK 81-1) x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x 1 x x 0

5211 81 OFF (81 OFF) x 1 0 0 0 0

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 1 1 1 1

PTUF1.Mod.stVal 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTUF1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTUF1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 113


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTUF1.Str

No. Information

5232 81-1 picked up (81-1 picked up) 0 0 1 1

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1

PTUF1.Str.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF1.Op

No. Information

5236 81-1 TRIP (81-1 TRIP) 0 0 1 1

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1

PTUF1.Op.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF1.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1

PTUF1.BlkV.stVal 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

114 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.2 Frequency protection 81-2 U (PTUF2)

PTUF2.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x 1 0

5207 >BLOCK 81-2 (>BLOCK 81-2) x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x 1 x x 0

5211 81 OFF (81 OFF) x 1 0 0 0 0

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 1 1 1 1

PTUF2.Mod.stVal 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTUF2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTUF2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 115


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTUF2.Str

No. Information

5233 81-2 picked up (81-2 picked up) 0 0 1 1

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1

PTUF2.Str.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF2.Op

No. Information

5237 81-2 TRIP (81-2 TRIP) 0 0 1 1

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1

PTUF2.Op.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF2.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1

PTUF2.BlkV.stVal 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

116 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.3 Frequency protection 81-3 U (PTUF3)

PTUF3.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x 1 0

5208 >BLOCK 81-3 (>BLOCK 81-3) x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x 1 x x 0

5211 81 OFF (81 OFF) x 1 0 0 0 0

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 1 1 1 1

PTUF3.Mod.stVal 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTUF3.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTUF3.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 117


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTUF3.Str

No. Information

5234 81-3 picked up (81-3 picked up) 0 0 1 1

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1

PTUF3.Str.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF3.Op

No. Information

5238 81-3 TRIP (81-3 TRIP) 0 0 1 1

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1

PTUF3.Op.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF3.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1

PTUF3.BlkV.stVal 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

118 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.4 Frequency protection 81-4 U (PTUF4)

PTUF4.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x 1 0

5209 >BLOCK 81-4 (>BLOCK 81-4) x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x 1 x x 0

5211 81 OFF (81 OFF) x 1 0 0 0 0

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 1 1 1 1

PTUF4.Mod.stVal 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTUF4.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTUF4.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 119


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTUF4.Str

No. Information

5235 81-4 picked up (81-4 picked up) 0 0 1 1

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1

PTUF4.Str.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF4.Op

No. Information

5239 81-4 TRIP (81-4 TRIP) 0 0 1 1

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1

PTUF4.Op.general 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTUF4.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1

PTUF4.BlkV.stVal 0 0 0 1

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

120 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.5 Frequency protection 81-1 O (PTOF1)

PTOF1.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x x 1 0

5206 >BLOCK 81-1 (>BLOCK 81-1) x x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x x 1 x x 0

5211 81 OFF (81 OFF) x x 1 0 0 0 0

81-1 PICKUP (P5403/5404) ≤ Rated Frequency (P214) x 1 x 0 0 0 0

PTOF1.Mod.stVal 5 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOF1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOF1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 121


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTOF1.Str

No. Information

5232 81-1 picked up (81-1 picked up) 0 0 1 1

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1

PTOF1.Str.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF1.Op

No. Information

5236 81-1 TRIP (81-1 TRIP) 0 0 1 1

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1

PTOF1.Op.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF1.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1

PTOF1.BlkV.stVal 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

122 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.6 Frequency protection 81-2 O (PTOF2)

PTOF2.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x x 1 0

5207 >BLOCK 81-2 (>BLOCK 81-2) x x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x x 1 x x 0

5211 81 OFF (81 OFF) x x 1 0 0 0 0

81-2 PICKUP (P5406/5407) ≤ Rated Frequency (P214) x 1 x 0 0 0 0

PTOF2.Mod.stVal 5 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOF2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOF2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 123


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTOF2.Str

No. Information

5233 81-2 picked up (81-2 picked up) 0 0 1 1

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1

PTOF2.Str.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF2.Op

No. Information

5237 81-2 TRIP (81-2 TRIP) 0 0 1 1

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1

PTOF2.Op.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF2.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1

PTOF2.BlkV.stVal 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

124 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.7 Frequency protection 81-3 O (PTOF3)

PTOF3.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x x 1 0

5208 >BLOCK 81-3 (>BLOCK 81-3) x x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x x 1 x x 0

5211 81 OFF (81 OFF) x x 1 0 0 0 0

81-3 PICKUP (P5409/5410) ≤ Rated Frequency (P214) x 1 x 0 0 0 0

PTOF1.Mod.stVal 5 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOF3.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOF3.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 125


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTOF3.Str

No. Information

5234 81-3 picked up (81-3 picked up) 0 0 1 1

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1

PTOF3.Str.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF3.Op

No. Information

5238 81-3 TRIP (81-3 TRIP) 0 0 1 1

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1

PTOF3.Op.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF3.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1

PTOF3.BlkV.stVal 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

126 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

3.10.8 Frequency protection 81-4 O (PTOF4)

PTOF4.Mod

No. Information

5213 81 ACTIVE (81 ACTIVE) x x x x x x x

5212 81 BLOCKED (81 BLOCKED) x x x x x 1 0

5209 >BLOCK 81-4 (>BLOCK 81-4) x x x x 1 x 0

5214 81 Under Voltage Block (81 Under V Blk) x x x 1 x x 0

5211 81 OFF (81 OFF) x x 1 0 0 0 0

81-4 PICKUP (P5412/5413) ≤ Rated Frequency (P214) x 1 x 0 0 0 0

PTOF4.Mod.stVal 5 5 5 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTOF4.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTOF4.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 127


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.10 Frequency protection 81 O/U (PTUFx, PTOFx)

PTOF4.Str

No. Information

5235 81-4 picked up (81-4 picked up) 0 0 1 1

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1

PTOF4.Str.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF4.Op

No. Information

5239 81-4 TRIP (81-4 TRIP) 0 0 1 1

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1

PTOF4.Op.general 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

PTOF4.BlkV

No. Information

5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1

81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1

PTOF4.BlkV.stVal 0 0 1 0

device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE


0 - OFF / FALSE 1 - TRUE

128 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.11 Thermal overload protection (PTTR1)

3.11 Thermal overload protection (PTTR1)

PTTR1.Mod

No. Information

1513 49 Overload Protection is ACTIVE (49 O/L ACTIVE) x x x

1512 49 Overload Protection is BLOCKED (49 O/L BLOCK) x 1 0

1511 49 Overload Protection is OFF (49 O / L OFF) 1 0 0

PTTR1.Mod.stVal 5 2 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTTR1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTTR1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTTR1.Str

No. Information

1517 49 Winding Overload (49 Winding O/L) 0 1

PTTR1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 129


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.11 Thermal overload protection (PTTR1)

PTTR1.Op

No. Information

1521 49 Thermal Overload TRIP (49 Th O/L TRIP) 0 1

PTTR1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PTTR1.AlmThm

No. Information

1516 49 Overload Alarm! Near Thermal Trip (49 O/L Θ Alarm) 0 1

PTTR1.AlmThm.general 0 1

device annunciation: 1 - ON IEC Status AlmThm.general: 0 - FALSE


0 - OFF 1 - TRUE

130 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

3.12.1 Ground Fault Protection 64 (PHIZ1)

PHIZ1.Mod

No. Information

1212 50Ns/67Ns is ACTIVE (50Ns/67Ns ACT) x x x x x x x

1230 Sensitive ground fault detection BLOCKED (Sens. Gnd block) x 1 x x x x 0

170 VT Fuse Failure (alarm instantaneous) (VT FuseFail) x x 1 x x x 0

6509 >Failure: Feeder VT (>FAIL:FEEDER VT) x x x 1 x x 0

6510 >Failure: Busbar VT (>FAIL: BUS VT) x x x x 1 x 0

1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 0 0 0 0 0 0

Frequency range is exceeded x x x x x 1 0

PHIZ1.Mod.stVal 5 2 2 2 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PHIZ1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PHIZ1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PHIZ1.Str

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 1

PHIZ1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 131


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

PHIZ1.Str.dirGeneral

No. Information

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1

PHIZ1.Str.dirGeneral 0 0 1 2 3 0

device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH

PHIZ1.Str.phsA

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1

1272 Sensitive Ground fault picked up in Ph A (Sens. Gnd Ph A) x 0 1 1 1 1

PHIZ1.Str.phsA 0 0 1 1 1 1

device annunciation: 1 - ON IEC Status Str.phsA: 0 -FALSE


0 - OFF 1 - TRUE

PHIZ1.Str.dirPhsA

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1

1272 Sensitive Ground fault picked up in Ph A (Sens. Gnd Ph A) x 0 1 1 1 1

PHIZ1.Str.dirPhsA 0 0 1 2 0 0

device annunciation: 1 - ON IEC Status Str.dirPhsA: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

132 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

PHIZ1.Str.phsB

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1

1273 Sensitive Ground fault picked up in Ph B (Sens. Gnd Ph B) x 0 1 1 1 1

PHIZ1.Str.phsB 0 0 1 1 1 1

device annunciation: 1 - ON IEC Status Str.phsB: 0 -FALSE


0 - OFF 1 - TRUE

PHIZ1.Str.dirPhsB

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1

1273 Sensitive Ground fault picked up in Ph B (Sens. Gnd Ph B) x 0 1 1 1 1

PHIZ1.Str.dirPhsB 0 0 1 2 0 0

device annunciation: 1 - ON IEC Status Str.dirPhsB: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 133


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

PHIZ1.Str.phsC

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1

1274 Sensitive Ground fault picked up in Ph C (Sens. Gnd Ph C) x 0 1 1 1 1

PHIZ1.Str.phsC 0 0 1 1 1 1

device annunciation: 1 - ON IEC Status Str.phsC: 0 -FALSE


0 - OFF 1 - TRUE

PHIZ1.Str.dirPhsC

No. Information

1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1

1274 Sensitive Ground fault picked up in Ph C (Sens. Gnd Ph C) x 0 1 1 1 1

PHIZ1.Str.dirPhsC 0 0 1 2 0 0

device annunciation: 1 - ON IEC Status Str.dirPhsC: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD

PHIZ1.Op

No. Information

1217 64 displacement voltage element TRIP (64 TRIP) 0 1

PHIZ1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

134 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

3.12.2 Ground Fault Protection 50N(s) (PSDE1, PSDE2)

PSDE1.Mod

No. Information

1212 50Ns/67Ns is ACTIVE (50Ns/67Ns ACT) x x x x

1230 Sensitive ground fault detection BLOCKED (Sens. Gnd block) x x 1 0

1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PSDE1.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PSDE1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PSDE1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PSDE1.Str

No. Information

1224 50Ns-1 Pickup (50Ns-1 Pickup) 0 1

PSDE1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 135


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

PSDE1.Str.dirGeneral

No. Information

1224 50Ns-1 Pickup (50Ns-1 Pickup) 0 1 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1

PSDE1.Str.dirGeneral 0 0 1 2 3 0

device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH

PSDE1.Op

No. Information

1226 50Ns-1 TRIP (50Ns-1 TRIP) 0 1

PSDE1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

PSDE2.Mod

No. Information

1212 50Ns/67Ns is ACTIVE (50Ns/67Ns ACT) x x x x

1230 Sensitive ground fault detection BLOCKED (Sens. Gnd block) x x 1 0

1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 0 0 0

Frequency range is exceeded x 1 x 0

PSDE2.Mod.stVal 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

136 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

PSDE2.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PSDE2.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PSDE2.Str

No. Information

1221 50Ns-2 Pickup (50Ns-2 Pickup) 0 1

PSDE2.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

PSDE2.Str.dirGeneral

No. Information

1221 50Ns-2 Pickup (50Ns-2 Pickup) 0 1 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1

PSDE2.Str.dirGeneral 0 0 1 2 3 0

device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH

PSDE2.Op

No. Information

1223 50Ns-2 TRIP (50Ns-2 TRIP) 0 1

PSDE2.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 137


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

3.12.3 51 N(s) (PSDE3)

PSDE3.Mod

No. Information

1212 50Ns/67Ns is ACTIVE (50Ns/67Ns ACT) x x x x x

1230 Sensitive ground fault detection BLOCKED (Sens. Gnd block) x x x 1 0

1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 x 0 0 0

M.of PU TD (P3131) = ∞ x 1 0 0 0

Frequency range is exceeded x x 1 x 0

PSDE3.Mod.stVal 5 5 2 2 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

PSDE3.Health

No. Information

51 Device is Operational and Protecting (Device OK) x 0 1

16029 sens.grd.flt. 51Ns BLOCKED Setting Error (51Ns BLK PaErr) 1 x 0

PSDE3.Health.stVal 3 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM

PSDE3.Str

No. Information

1227 51Ns picked up (51Ns Pickup) 0 1

PSDE3.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

138 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.12 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)

PSDE3.Str.dirGeneral

No. Information

1227 51Ns picked up (51Ns Pickup) 0 1 1 1 1 1

1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x

1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x

1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1

PSDE3.Str.dirGeneral 0 0 1 2 3 0

device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN


0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH

PSDE3.Op

No. Information

1229 51Ns TRIP (51Ns TRIP) 0 1

PSDE3.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 139


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.13 Automatic Reclosing System 79 (RREC1)

3.13 Automatic Reclosing System 79 (RREC1)

RREC1.Mod

No. Information

2782 79 Auto recloser is switched ON (79 ON) x x x

2785 79 - Auto-reclose is dynamically BLOCKED (79 DynBlock) x 1 0

2781 79 Auto recloser is switched OFF (79 OFF) 1 0 0

RREC1.Mod.stVal 5 2 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

RREC1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

RREC1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

140 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.13 Automatic Reclosing System 79 (RREC1)

RREC1.Op

No. Information

2851 79 - Close command (79 Close) 0 1

RREC1.Op.general 0 1

device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE


0 - OFF 1 - TRUE

RREC1.AutoRecSt

No. Information

2801 79 - in progress (79 in progress) 1 1 0 0

2862 79 - cycle successful (79 Successful) 1 0 1 0

RREC1.AutoRecSt.stVal 3 2 3 1

device annunciation: 1 - ON IEC Status AutoRecST.stVal: 1 - ready


0 - OFF 2 - in progress
3 - successful

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 141


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.14 Fault Locator (RFLO1)

3.14 Fault Locator (RFLO1)

RFLO1.Mod

No. Information

Fault Locator (P180) = Enabled 1

RFLO1.Mod.stVal 1

device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON


0 - OFF / FALSE 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF

RFLO1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

RFLO1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

142 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.14 Fault Locator (RFLO1)

RFLO1.FltZ

No. Information Value

Absolute value of the fault RFLO1.FltZ.cVal.mag.f Measured value Absolute value


impedance
RFLO1.FltZ.units.SIUnit 30 Ω (Ohm)

RFLO1.FltZ.units.multiplier 0 1

Angle of the fault impedance RFLO1.FltZ.cVal.ang.f Measured value Angle in °

RFLO1.FltDiskm

No. Information Value

1119 Flt Locator: Distance to fault RFLO1.FltDiskm.mag.f Measured value Absolute value
or (dist =)
1122 RFLO1.FltDiskm.units.SIUnit 2 Meter

RFLO1.FltDiskm.units.multiplier 3 Kilo

RFLO1.FltDisPrc

No. Information Value

1120 Flt Locator: Distance [%] to fault RFLO1.FltDisPrc.mag.f Measured value Absolute value
(d[%] =)
RFLO1.FltDisPrc.units.SIUnit 1 NONE

RFLO1.FltDisPrc.multiplier 0 1

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 143


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.15 Circuit breaker failure protection 50BF(RBRF1)

3.15 Circuit breaker failure protection 50BF(RBRF1)

RBRF1.Mod

No. Information

1452 Breaker failure is BLOCKED (BkrFail BLOCK) x 0 1

1451 Breaker failure is switched OFF (BkrFail OFF) 1 0 0

RBRF1.Mod.stVal 5 1 2

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF

RBRF1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

RBRF1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

RBRF1.Str

No. Information

1456 50BF (internal) PICKUP (50BF int Pickup) 0 0 1 1

1457 50BF (external) PICKUP (50BF ext Pickup) 0 1 0 1

RBRF1.Str.general 0 1 1 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

144 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.15 Circuit breaker failure protection 50BF(RBRF1)

RBRF1.OpEx

No. Information

1481 50BF (external) TRIP (50BF ext TRIP) 0 1

RBRF1.OpEx.general 0 1

device annunciation: 1 - ON IEC Status OpEx.general: 0 - FALSE


0 - OFF 1 - TRUE

RBRF1.OpIn

No. Information

1480 50BF (internal) TRIP (50BF int TRIP) 0 1

RBRF1.OpIn.general 0 1

device annunciation: 1 - ON IEC Status OpIn.general: 0 - FALSE


0 - OFF 1 - TRUE
x - irrelevant

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 145


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.16 Synchronism and Voltage Check 25 (RSYNx)

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN1.Mod

No. Information

170.0051 25-group 1 is BLOCKED (25-1 BLOCK) 0 1 x

170.2101 Sync-group 1 is switched OFF (25-1 OFF) 0 0 1

RSYN1.Mod.stVal 1 2 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

RSYN1.Health

No. Information

170.0050 25 Synchronization Error (25 Sync. Error) x x 1 0

51 Device is Operational and Protecting (Device OK) x x 1 1

170.2096 25 Multiple selection of func-groups (25 FG-Error) 1 x 0 0

170.2097 25 Setting error (25 Set-Error) x 1 0 0

RSYN1.Health.stVal 3 3 2 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM

RSYN1.Rel

No. Information

170.0049 25 Sync. Release of CLOSE Command (25 CloseRelease) 0 1

RSYN1.Rel.stVal 0 1

device annunciation: 1 - ON IEC Status Rel.stVal: 0 - FALSE


0 - OFF 1 - TRUE

146 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN1.VInd

No. Information

170.2030 25 Voltage difference (Vdiff) okay (25 Vdiff ok) 0 1

RSYN1.VInd.stVal 1 0

device annunciation: 1 - ON IEC Status VInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN1.AngInd

No. Information

170.2032 25 Angle difference (alphadiff) okay (25 αdiff ok) 0 1

RSYN1.AngInd.stVal 1 0

device annunciation: 1 - ON IEC Status AngInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN1.HzInd

No. Information

170.2031 25 Frequency difference (fdiff) okay (25 fdiff ok) 0 1

RSYN1.HzInd.stVal 1 0

device annunciation: 1 - ON IEC Status HzInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN1.SynPrg

No. Information

170.2022 25-group 1: measurement in progress (25-1 meas.) 0 1

RSYN1.SynPrg.stVal 0 1

device annunciation: 1 - ON IEC Status SynPrg.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 147


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN1.DifVCIc

No. Information Value

170.2054 dV = (dV =) RSYN1.DifVClc.mag.f Measured value Absolute value

RSYN1.DifVClc.units.SIUnit 29 V (Volt)

RSYN1.DifVClc.units.multiplier 3 Kilo

RSYN1.DifHzCIc

No. Information Value

170.2055 df = (df =) RSYN1. DifHzClc.mag.f Measured value Absolute value

RSYN1. DifHzClc.units.SIUnit 33 Hz

RSYN1. DifHzClc.units.multiplier 0 1

RSYN1.DifAngCIc

No. Information Value

170.2056 dalpha = (dα =) RSYN1. DifAngClc.mag.f Measured value Absolute value

RSYN1. DifAngClc.units.SIUnit 9 ° (Degree)

RSYN1. DifAngClc.units.multiplier 0 1

148 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN2.Mod

No. Information

170.0051 25-group 2 is BLOCKED (25-2 BLOCK) 0 1 x

170.2101 Sync-group 2 is switched OFF (25-2 OFF) 0 0 1

RSYN2.Mod.stVal 1 2 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

RSYN2.Health

No. Information

170.0050 25 Synchronization Error (25 Sync. Error) x x 1 0

51 Device is Operational and Protecting (Device OK) x x 1 1

170.2096 25 Multiple selection of func-groups (25 FG-Error) 1 x 0 0

170.2097 25 Setting error (25 Set-Error) x 1 0 0

RSYN2.Health.stVal 3 3 2 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM

RSYN2.Rel

No. Information

170.0049 25 Sync. Release of CLOSE Command (25 CloseRelease) 0 1

RSYN2.Rel.stVal 0 1

device annunciation: 1 - ON IEC Status Rel.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN2.VInd

No. Information

170.2030 25 Voltage difference (Vdiff) okay (25 Vdiff ok) 0 1

RSYN2.VInd.stVal 1 0

device annunciation: 1 - ON IEC Status VInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 149


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN2.AngInd

No. Information

170.2032 25 Angle difference (alphadiff) okay (25 αdiff ok) 0 1

RSYN2.AngInd.stVal 1 0

device annunciation: 1 - ON IEC Status AngInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN2.HzInd

No. Information

170.2031 25 Frequency difference (fdiff) okay (25 fdiff ok) 0 1

RSYN2.HzInd.stVal 1 0

device annunciation: 1 - ON IEC Status HzInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN2.SynPrg

No. Information

170.2022 25-group 2: measurement in progress (25-2 meas.) 0 1

RSYN2.SynPrg.stVal 0 1

device annunciation: 1 - ON IEC Status SynPrg.stVal: 0 - FALSE


0 - OFF 1 - TRUE

150 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN2.DifVCIc

No. Information Value

170.2054 dV = (dV =) RSYN2.DifVClc.mag.f Measured value Absolute value

RSYN2.DifVClc.units.SIUnit 29 V (Volt)

RSYN2.DifVClc.units.multiplier 3 Kilo

RSYN2.DifHzCIc

No. Information Value

170.2055 df = (df =) RSYN2. DifHzClc.mag.f Measured value Absolute value

RSYN2. DifHzClc.units.SIUnit 33 Hz

RSYN2. DifHzClc.units.multiplier 0 1

RSYN2.DifAngCIc

No. Information Value

170.2056 dalpha = (dα =) RSYN2. DifAngClc.mag.f Measured value Absolute value

RSYN2. DifAngClc.units.SIUnit 9 ° (Degree)

RSYN2. DifAngClc.units.multiplier 0 1

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 151


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN3.Mod

No. Information

170.0051 25-group 3 is BLOCKED (25-3 BLOCK) 0 1 x

170.2101 Sync-group 3 is switched OFF (25-3 OFF) 0 0 1

RSYN3.Mod.stVal 1 2 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

RSYN3.Health

No. Information

170.0050 25 Synchronization Error (25 Sync. Error) x x 1 0

51 Device is Operational and Protecting (Device OK) x x 1 1

170.2096 25 Multiple selection of func-groups (25 FG-Error) 1 x 0 0

170.2097 25 Setting error (25 Set-Error) x 1 0 0

RSYN3.Health.stVal 3 3 2 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM

RSYN3.Rel

No. Information

170.0049 25 Sync. Release of CLOSE Command (25 CloseRelease) 0 1

RSYN3.Rel.stVal 0 1

device annunciation: 1 - ON IEC Status Rel.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN3.VInd

No. Information

170.2030 25 Voltage difference (Vdiff) okay (25 Vdiff ok) 0 1

RSYN3.VInd.stVal 1 0

device annunciation: 1 - ON IEC Status VInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

152 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN3.AngInd

No. Information

170.2032 25 Angle difference (alphadiff) okay (25 αdiff ok) 0 1

RSYN3.AngInd.stVal 1 0

device annunciation: 1 - ON IEC Status AngInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN3.HzInd

No. Information

170.2031 25 Frequency difference (fdiff) okay (25 fdiff ok) 0 1

RSYN3.HzInd.stVal 1 0

device annunciation: 1 - ON IEC Status HzInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN3.SynPrg

No. Information

170.2022 25-group 3: measurement in progress (25-3 meas.) 0 1

RSYN3.SynPrg.stVal 0 1

device annunciation: 1 - ON IEC Status SynPrg.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 153


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN3.DifVCIc

No. Information Value

170.2054 dV = (dV =) RSYN3.DifVClc.mag.f Measured value Absolute value

RSYN3.DifVClc.units.SIUnit 29 V (Volt)

RSYN3.DifVClc.units.multiplier 3 Kilo

RSYN3.DifHzCIc

No. Information Value

170.2055 df = (df =) RSYN3. DifHzClc.mag.f Measured value Absolute value

RSYN3. DifHzClc.units.SIUnit 33 Hz

RSYN3. DifHzClc.units.multiplier 0 1

RSYN3.DifAngCIc

No. Information Value

170.2056 dalpha = (dα =) RSYN3. DifAngClc.mag.f Measured value Absolute value

RSYN3. DifAngClc.units.SIUnit 9 ° (Degree)

RSYN3. DifAngClc.units.multiplier 0 1

154 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN4.Mod

No. Information

170.0051 25-group 4 is BLOCKED (25-4 BLOCK) 0 1 x

170.2101 Sync-group 4 is switched OFF (25-4 OFF) 0 0 1

RSYN4.Mod.stVal 1 2 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

RSYN4.Health

No. Information

170.0050 25 Synchronization Error (25 Sync. Error) x x 1 0

51 Device is Operational and Protecting (Device OK) x x 1 1

170.2096 25 Multiple selection of func-groups (25 FG-Error) 1 x 0 0

170.2097 25 Setting error (25 Set-Error) x 1 0 0

RSYN4.Health.stVal 3 3 2 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM

RSYN4.Rel

No. Information

170.0049 25 Sync. Release of CLOSE Command (25 CloseRelease) 0 1

RSYN4.Rel.stVal 0 1

device annunciation: 1 - ON IEC Status Rel.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN4.VInd

No. Information

170.2030 25 Voltage difference (Vdiff) okay (25 Vdiff ok) 0 1

RSYN4.VInd.stVal 1 0

device annunciation: 1 - ON IEC Status VInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 155


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN4.AngInd

No. Information

170.2032 25 Angle difference (alphadiff) okay (25 αdiff ok) 0 1

RSYN4.AngInd.stVal 1 0

device annunciation: 1 - ON IEC Status AngInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN4.HzInd

No. Information

170.2031 25 Frequency difference (fdiff) okay (25 fdiff ok) 0 1

RSYN4.HzInd.stVal 1 0

device annunciation: 1 - ON IEC Status HzInd.stVal: 0 - FALSE


0 - OFF 1 - TRUE

RSYN4.SynPrg

No. Information

170.2022 25-group 4: measurement in progress (25-4 meas.) 0 1

RSYN4.SynPrg.stVal 0 1

device annunciation: 1 - ON IEC Status SynPrg.stVal: 0 - FALSE


0 - OFF 1 - TRUE

156 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.16 Synchronism and Voltage Check 25 (RSYNx)

RSYN4.DifVCIc

No. Information Value

170.2054 dV = (dV =) RSYN4.DifVClc.mag.f Measured value Absolute value

RSYN4.DifVClc.units.SIUnit 29 V (Volt)

RSYN4.DifVClc.units.multiplier 3 Kilo

RSYN4.DifHzCIc

No. Information Value

170.2055 df = (df =) RSYN4. DifHzClc.mag.f Measured value Absolute value

RSYN4. DifHzClc.units.SIUnit 33 Hz

RSYN4. DifHzClc.units.multiplier 0 1

RSYN4.DifAngCIc

No. Information Value

170.2056 dalpha = (dα =) RSYN4. DifAngClc.mag.f Measured value Absolute value

RSYN4. DifAngClc.units.SIUnit 9 ° (Degree)

RSYN4. DifAngClc.units.multiplier 0 1

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 157


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.17 Three-pole tripping 52 Breaker (XCBR1)

3.17 Three-pole tripping 52 Breaker (XCBR1)

XCBR1.Mod

No. Information

52 At Least 1 Protection Funct. is Active (ProtActive) 1 0

XCBR1.Mod.stVal 1 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF

XCBR1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

XCBR1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM

XCBR1.Loc

No. Information

55 Reset Device (Reset Device) 1 0

XCBR1.Loc.stVal 1 0

device annunciation: 1 - ON IEC Status Loc.stVal: 0 - FALSE


0 - OFF 1 - TRUE

XCBR1.OpCnt

No. Information Value

Number of TRIPs= (#of TRIPs=) XCBR1.OpCnt.stVal Metered value Absolute value

158 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.17 Three-pole tripping 52 Breaker (XCBR1)

XCBR1.Pos

No. Information

4601 >52-a contact (OPEN, if bkr is open) (>52-a) 0 1 0 1

4602 >52-b contact (OPEN, if bkr is closed) (>52-b) 0 0 1 1

XCBR1.Pos.stVal - if spontan information 11 01 10 11

XCBR1.Pos.stVal - if command is running 00 01 10 00

device annunciation: 1 - ON IEC Status Pos.stVal: 00 - INTERMEDIATE STATE


0 - OFF 01 - OFF
10 - ON
11 - BAD STATE

XCBR1.BlkOpn

No. Information

55 Reset Device (Reset Device) 1 0

XCBR1.BlkOpn.stVal 0 1

device annunciation: 1 - ON IEC Status BlkOpn.stVal: 0 - FALSE


0 - OFF 1 - TRUE

XCBR1.BlkCls

No. Information

55 Reset Device (Reset Device) 1 0

XCBR1.BlkCls.stVal 0 1

device annunciation: 1 - ON IEC Status BlkCls.stVal: 0 - FALSE


0 - OFF 1 - TRUE

XCBR1.CBOpCap

No. Information

XCBR1.CBOpCap.stVal 1

device annunciation: IEC Status CBOpCap.stVal: 1 - NONE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 159


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.17 Three-pole tripping 52 Breaker (XCBR1)

XCBR1.CirSpv

No. Information

6865 74TC Failure Trip Circuit (74TC Trip cir.) 0 1

XCBR1.CirSpv.stVal 0 1

device annunciation: 1 - ON IEC Status CirSpv.stVal: 0 - FALSE


0 - OFF 1 - TRUE

160 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.17 Three-pole tripping 52 Breaker (XCBR1)

XCBR1.SumSwARs1

No. Information Value

1021 Accumulation of XCBR1.SumSwARs1.actVal Metered value Current value of


interrupted current Ph A acummulated interrupted
(Σ Ia =) current = actVal × pulsQty

XCBR1.SumSwARs1.units.SIUnit 5 A (Ampere)

XCBR1.SumSwARs1.units.multiplier 3 Kilo

XCBR1.SumSwARs1.pulsQty 1.000000e-002 A / Metered value

XCBR1.SumSwARs2

No. Information Value

1022 Accumulation of XCBR1.SumSwARs2.actVal Metered value Current value of


interrupted current Ph B acummulated interrupted
(Σ Ib =) current = actVal × pulsQty

XCBR1.SumSwARs2.units.SIUnit 5 A (Ampere)

XCBR1.SumSwARs2.units.multiplier 3 Kilo

XCBR1.SumSwARs2.pulsQty 1.000000e-002 A / Metered value

XCBR1.SumSwARs3

No. Information Value

1023 Accumulation of XCBR1.SumSwARs3.actVal Metered value Current value of


interrupted current Ph C acummulated interrupted
(Σ Ic =) current = actVal × pulsQty

XCBR1.SumSwARs3.units.SIUnit 5 A (Ampere)

XCBR1.SumSwARs3.units.multiplier 3 Kilo

XCBR1.SumSwARs3.pulsQty 1.000000e-002 A / Metered value

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 161


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.18 Tripping Logic of the Entire Device (PTRC1)

3.18 Tripping Logic of the Entire Device (PTRC1)

PTRC1.Mod

No. Information

52 At Least 1 Protection Funct. is Active (ProtActive) 1 0

PTRC1.Mod.stVal 1 5

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF

PTRC1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

PTRC1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

PTRC1.Str

No. Information

501 Relay PICKUP (Relay PICKUP) 0 1

PTRC1.Str.general 0 1

device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE


0 - OFF 1 - TRUE

162 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.18 Tripping Logic of the Entire Device (PTRC1)

PTRC1.Tr

No. Information

511 Relay GENERAL TRIP command (Relay TRIP) 0 1

PTRC1.Tr.general 0 1

device annunciation: 1 - ON IEC Status Tr.general: 0 - FALSE


0 - OFF 1 - TRUE

PTRC1.FinTr

No. Information

2863 79 - Lockout (79 Lockout) 0 1

PTRC1.FinTr.stVal 0 1

device annunciation: 1 - ON IEC Status FinTr.stVal: 0 - FALSE


0 - OFF 1 - TRUE

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 163


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.19 Measurement (MMXU1, MSQI1, MMTR1)

3.19 Measurement (MMXU1, MSQI1, MMTR1)

3.19.1 Measures (MMXU1)

MMXU1.Mod

No. Information

55 Reset Device (Reset Device) x

MMXU1.Mod.stVal 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

MMXU1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

MMXU1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

164 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.19 Measurement (MMXU1, MSQI1, MMTR1)

MMXU1.TotW

No. Information Value

641 P (active power) (P =) MMXU1.TotW.mag.f Measured value Absolute value

MMXU1.TotW.units.SIUnit 62 W (Watt)

MMXU1.TotW.units.multiplier 6 Mega

MMXU1.TotVAr

No. Information Value

642 Q (reactive power) (Q =) MMXU1.TotVAr.mag.f Measured value Absolute value

MMXU1.TotVAr.units.SIUnit 63 VAr

MMXU1.TotVAr.units.multiplier 6 Mega

MMXU1.TotVA

No. Information Value

645 S (apparent power) (S =) MMXU1.TotVA.mag.f Measured value Absolute value

MMXU1.TotVA.units.SIUnit 61 VA

MMXU1.TotVA.units.multiplier 6 Mega

MMXU1.TotPF

No. Information Value

901 Power Factor (PF =) MMXU1.TotPF.mag.f Measured value Absolute value

MMXU1.TotPF.units.SIUnit 1 NONE

MMXU1.TotPF.units.multiplier 0 1

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 165


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.19 Measurement (MMXU1, MSQI1, MMTR1)

MMXU1.Hz

No. Information Value

644 Frequency (Freq=) MMXU1.Hz.mag.f Measured value Absolute value

MMXU1.Hz.units.SIUnit 33 Hz

MMXU1.Hz.units.multiplier 0 1

MMXU1.A

No. Information Value

601 Ia (Ia =) MMXU1.A.phsA.cVal.mag.f Measured value Absolute value

MMXU1.A.phsA.units.SIUnit 5 A (Ampere)

MMXU1.A.phsA.units.multiplier 0 1

No. Information Value

602 Ib (Ib =) MMXU1.A.phsB.cVal.mag.f Measured value Absolute value

MMXU1.A.phsB.units.SIUnit 5 A (Ampere)

MMXU1.A.phsB.units.multiplier 0 1

No. Information Value

603 Ic (Ic =) MMXU1.A.phsC.cVal.mag.f Measured value Absolute value

MMXU1.A.phsC.units.SIUnit 5 A (Ampere)

MMXU1.A.phsC.units.multiplier 0 1

No. Information Value

604 In (In =) MMXU1.A.phsC.cVal.mag.f Measured value Absolute value

MMXU1.A.phsC.units.SIUnit 5 A (Ampere)

MMXU1.A.phsC.units.multiplier 0 1

166 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.19 Measurement (MMXU1, MSQI1, MMTR1)

MMXU1.PPV

No. Information Value

624 Va-b (Va-b=) MMXU1.PPV.phsAB.cVal.mag.f Measured value Absolute value

MMXU1.PPV.phsAB.units.SIUnit 29 V (Volt)

MMXU1.PPV.phsAB.units.multiplier 3 Kilo

No. Information Value

625 Vb-c (Vb-c=) MMXU1.PPV.phsBC.cVal.mag.f Measured value Absolute value

MMXU1.PPV.phsBC.units.SIUnit 29 V (Volt)

MMXU1.PPV.phsBC.units.multiplier 3 Kilo

No. Information Value

626 Vc-a (Vc-a=) MMXU1.PPV.phsCA.cVal.mag.f Measured value Absolute value

MMXU1.PPV.phsCA.units.SIUnit 29 V (Volt)

MMXU1.PPV.phsCA.units.multiplier 3 Kilo

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 167


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.19 Measurement (MMXU1, MSQI1, MMTR1)

MMXU1.PhV

No. Information Value

621 Va (Va =) MMXU1.PhV.phsA.cVal.mag.f Measured value Absolute value

MMXU1.PhV.phsA.units.SIUnit 29 V (Volt)

MMXU1.PhV.phsA.units.multiplier 3 Kilo

No. Information Value

622 Vb (Vb =) MMXU1.PhV.phsB.cVal.mag.f Measured value Absolute value

MMXU1.PhV.phsB.units.SIUnit 29 V (Volt)

MMXU1.PhV.phsB.units.multiplier 3 Kilo

No. Information Value

623 Vc (Vc =) MMXU1.PhV.phsC.cVal.mag.f Measured value Absolute value

MMXU1.PhV.phsC.units.SIUnit 29 V (Volt)

MMXU1.PhV.phsC.units.multiplier 3 Kilo

No. Information Value

627 VN (VN =) MMXU1.PhV.neut.cVal.mag.f Measured value Absolute value

MMXU1.PhV.neut.units.SIUnit 29 V (Volt)

MMXU1.PhV.neut.units.multiplier 3 Kilo

168 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.19 Measurement (MMXU1, MSQI1, MMTR1)

3.19.2 Measured values, symmetrical components (MSQI1)

MSQI1.Mod

No. Information

55 Reset Device (Reset Device) x

MSQI1.Mod.stVal 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

MSQI1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

MSQI1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 169


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.19 Measurement (MMXU1, MSQI1, MMTR1)

MSQI1.SeqA

No. Information Value

605 I1 (positive sequence) (I1 =) MSQI1.SeqA.c1.cVal.mag.f Measured value Absolute value

MSQI1.SeqA.c1.units.SIUnit 5 A (Ampere)

MSQI1.SeqA.c1.units.multiplier 0 1

No. Information Value

606 I2 (negative sequence) (I2 =) MSQI1.SeqA.c2.cVal.mag.f Measured value Absolute value

MSQI1.SeqA.c2.units.SIUnit 5 A (Ampere)

MSQI1.SeqA.c2.units.multiplier 0 1

No. Information Value

831 3Io (zero sequence) (3Io =) MSQI1.SeqA.c3.cVal.mag.f Measured value Absolute value

MSQI1.SeqA.c3.units.SIUnit 5 A (Ampere)

MSQI1.SeqA.c3.units.multiplier 0 1

MSQI1.SeqV

No. Information Value

629 V1 (positive sequence) (V1 =) MSQI1.SeqV.c1.cVal.mag.f Measured value Absolute value

MSQI1.SeqV.c1.units.SIUnit 29 V (Volt)

MSQI1.SeqV.c1.units.multiplier 3 Kilo

No. Information Value

630 V2 (negative sequence) (V2 =) MSQI1.SeqV.c2.cVal.mag.f Measured value Absolute value

MSQI1.SeqV.c2.units.SIUnit 29 V (Volt)

MSQI1.SeqV.c2.units.multiplier 3 Kilo

No. Information Value

832 Vo (zero sequence) (Vo =) MSQI1.SeqV.c3.cVal.mag.f Measured value Absolute value

MSQI1.SeqV.c3.units.SIUnit 29 V (Volt)

MSQI1.SeqV.c3.units.multiplier 3 Kilo

170 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Mapping

3.19 Measurement (MMXU1, MSQI1, MMTR1)

3.19.3 Power Metering (MMTR1)

MMTR1.Mod

No. Information

55 Reset Device (Reset Device) x

MMTR1.Mod.stVal 1

device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON


0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF

MMTR1.Health

No. Information

51 Device is Operational and Protecting (Device OK) 0 1

MMTR1.Health.stVal 3 1

device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK


0 - OFF 2 - WARNING
3 - ALARM

MMTR1.SupWh

No. Information Value

924 Wp Forward (Wp+=) MMTR1.SupWh.actVal Metered value Current value of acummulated


interrupted current =
actVal × pulsQty

MMTR1.SupWh.units.SIUnit 72 Wh

MMTR1.SupWh.units.multiplier 6 Mega

MMTR1.SupWh.pulsQty 3.464200e-005 Wh / Metered value

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 171


C53000-G1140-C211-4, Edition 03.2010
Mapping
3.19 Measurement (MMXU1, MSQI1, MMTR1)

MMTR1.SupVArh

No. Information Value

925 Wq Forward (Wq+=) MMTR1.SupVArh.actVal Metered value Current value of acummulated


interrupted current =
actVal × pulsQty

MMTR1.SupVArh.units.SIUnit 73 VArh

MMTR1.SupVArh.units.multiplier 6 Mega

MMTR1.SupVArh.pulsQty 3.464200e-005 VArh / Metered value

MMTR1.DmdWh

No. Information Value

928 Wp Reverse (Wp-=) MMTR1.DmdWh.actVal Metered value Current value of acummulated


interrupted current =
actVal × pulsQty

MMTR1.DmdWh.units.SIUnit 72 Wh

MMTR1.DmdWh.units.multiplier 6 Mega

MMTR1.DmdWh.pulsQty 3.464200e-005 Wh / Metered value

MMTR1.DmdVArh

No. Information Value

929 Wq Reverse (Wq-=) MMTR1.DmdVArh.actVal Metered value Current value of acummulated


interrupted current =
actVal × pulsQty

MMTR1.DmdVArh.units.SIUnit 73 VArh

MMTR1.DmdVArh.units.multiplier 6 Mega

MMTR1.DmdVArh.pulsQty 3.464200e-005 VArh / Metered value

172 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Literature

/1/ SIPROTEC 4 Ethernet Module EN 100 IEC 61850 Electrical Interface 100 MBit,
Manual
C54000-G1176-C167
/2/ SIPROTEC 4 System Description
E50417-H1176-C151
/3/ SIPROTEC DIGSI, StartUP
E50417-G1176-C152
/4/ DIGSI CFC, Manual
E50417-H1176-C098
/5/ SIPROTEC SIGRA 4, Manual
E50417-H1176-C1100-C070
/6/ SIPROTEC Multi-Functional Protective Relay with Bay Control 7SJ61, Manual
C53000-G1140-C210
/7/ SIPROTEC Multi-Functional Protective Relay with Local Control 7SJ62/64,
Manual
C53000-G1140-C207
/8/ SIPROTEC Overcurrent Protection 7SJ80, Manual
E50417-G1140-C343
/9/ SIPROTEC Motor Protection 7SK80, Manual
E50417-G1140-C344

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 173


C53000-G1140-C211-3, Edition 05.2009
174 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT
C53000-G1140-C211-3, Edition 05.2009
Index

C Health 164
CALH1 34, 52, 63 Hz 166
ErrBoard1 64 Mod 164
ErrBoard2 64 PhV 168
ErrBoard3 64 PPV 167
ErrBoard4 64 TotPF 165
ErrBoard5 65 TotVA 165
ErrBoard6 65 TotVAr 165
ErrBoard7 65 TotW 165
GrAlm 63 MSQI1 34, 51, 169
GrWrn 63 Health 169
Health 63 Mod 169
Mod 63 SeqA 170
SeqV 170
D
DOI 33 P
PHIZ1 36, 40, 44, 47, 50, 131
F Health 131
Function parameters 34 Mod 131
Functional Scope Op 134
7SJ61 35 Str.dirGeneral 132
7SJ62/63/64 38 Str.dirPhsA 132
7SJ80 43 Str.dirPhsB 133
7SK80 46 Str.dirPhsC 134
Str.general 131
L Str.phsA 132
LD Str.phsB 133
CTRL (Control) 34, 52 Str.phsC 134
DR (Disturbance Recorder) 51 PMLJ1 36, 40, 47, 50, 111
EXT (Extended) 52 ChgSet 112
Logical Device 32 Health 111
MEAS (Measurement) 34, 51 LodJamAlm 112
PROT (Protection) 34, 49 Mod 111
LLN0 32, 34, 49, 51, 52 Op 112
Beh 53, 55, 56 Str 112
Health 53, 55, 57 PMRI1 36, 40, 47, 50, 110
Mod 55, 56 Health 110
OpTmh 54, 56, 57 Mod 110
Logical Node 33, 35, 38, 43, 46, 49 Op 110
LPHD1 32, 34, 50, 51, 52, 62 StrInhTmm 110
DevStr 62 PMSS1 36, 40, 47, 50, 108
PhyHealth 62 Health 108
Proxy 62 Mod 108
Op 109
M Str 109
MMTR1 34, 51, 171 PSDE1 36, 40, 44, 47, 50, 135
DmdVArh 172 Health 135
DmdWh 172 Mod 135
Health 171 Op 136
Mod 171 Str.dirGeneral 136
SupVArh 172 Str.general 135
SupWh 171 PSDE2 36, 40, 44, 47, 50, 136
MMXU1 34, 51, 164 Health 137
A 166, 169 Mod 136

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 175


C53000-G1140-C211-4, Edition 03.2010
Index

Op 137 PTOC18 35, 38, 43, 46, 49


Str.dirGeneral 137 Health 72
Str.general 137 Mod 72
PSDE3 40, 44, 47, 50, 138 Op 73
Health 138 Str 72
Mod 138 PTOC2 35, 38, 43, 46, 49, 76
Op 139 ChgSet 77
Str.dirGeneral 139 Health 77
Str.general 138 Mod 76
PTOC1 35, 38, 43, 46, 49, 70 Op 77
ChgSet 71 Str 77
Health 71 PTOC3 39, 43, 49, 83
Mod 70 ChgSet 84
Op 71 Health 84
Str 71 Mod 83
PTOC10 39, 43, 49, 81 Op 84
ChgSet 82 Str 84
Health 81 PTOC4 39, 44, 46, 49, 87
Mod 81 ChgSet 88
Op 82 Health 88
Str 81 Mod 87
PTOC11 39, 43, 49, 82 Op 88
ChgSet 83 Str 88
Health 82 PTOC5 36, 40, 44, 47, 50, 106
Mod 82 Health 106
Op 83 Mod 106
Str 83 Op 107
PTOC12 39, 44, 46, 49, 85 Str 107
ChgSet 86 PTOC6 35, 38, 43, 46, 49, 68
Health 85 ChgSet 69
Mod 85 Health 68
Op 86 Mod 68
Str 85 Op 69
PTOC13 39, 44, 46, 49, 86 Str 68
ChgSet 87 PTOC7 35, 38, 43, 46, 49, 69
Health 86 ChgSet 70
Mod 86 Health 69
Op 87 Mod 69
Str 87 Op 70
PTOC14 36, 40, 44, 47, 50, 104 Str 70
Health 104 PTOC8 35, 38, 43, 46, 49
Mod 104 ChgSet 75
Op 105 Health 74
Str 104 Mod 74
PTOC15 36, 40, 44, 47, 50, 105 Op 75
Health 105 Str 74
Mod 105 PTOC9 35, 38, 43, 46, 49, 75
Op 106 ChgSet 76
Str 105 Health 75
PTOC16 36, 39, 44, 49, 93 Mod 75
Health 93 Op 76
Mod 93 Str 76
Op 94 PTOF1 41, 45, 48, 50, 121
Str 93 BlkV 122
PTOC17 36, 39, 44, 49, 94 Health 121
Health 94 Mod 121, 123
Mod 94 Op 122
Op 95 Str 122
Str 95 PTOF2 123

176 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010
Index

BlkV 124 Str.phsB 91


Health 123 Str.phsC 91
Mod 123 PTTR1 36, 40, 44, 47, 50, 129
Op 124 AlmThm 130
Str 124 Health 129
PTOF3 125 Mod 129
BlkV 126 Str 129
Health 125 Tr 130
Mod 125 PTUF1 41, 45, 48, 50, 113
Op 126 BlkV 114
Str 126 Health 113
PTOF4 127 Mod 113
BlkV 128 Op 114
Health 127 Str 114
Mod 127 PTUF2 115
Op 128 BlkV 116
Str 128 Health 115
PTOV1 41, 45, 48, 49, 100 Mod 115
Health 100 Op 116
Mod 100 Str 116
Op 101 PTUF3 117
Str 100 BlkV 118
PTOV2 41, 45, 48, 102 Health 117
Health 102 Mod 117
Mod 102 Op 118
Op 103 Str 118
Str 102 PTUF4 119
PTRC1 34, 49, 162 BlkV 120
FinTr 163 Health 119
Health 162 Mod 119
Mod 162 Op 120
Str 162 Str 120
Tr 163 PTUV1 41, 45, 48, 49, 96
PTRC2 35, 38, 43, 46, 49, 78 Health 96
Health 78 Mod 96
Mod 74, 78 Op 97
Op 74, 80 Str 97
Str 78 PTUV2 41, 45, 48, 98
Str.dirGeneral 78 Health 98
Str.dirNeut 80 Mod 98
Str.dirPhsA 79 Op 99
Str.dirPhsB 79 Str 99
Str.dirPhsC 80 PVOC1
Str.neut 80, 92 Mod 74, 80
Str.phsA 79
Str.phsB 79, 80, 91, 92 R
Str.phsC 79, 80, 91, 92 RBRF1 36, 41, 45, 48, 50, 144
PTRC3 39, 43, 49, 89 Health 144
Health 89 Mod 144
Mod 89 OpEx 145
Op 92 OpIn 145
Str 89 Str 144
Str.dirGeneral 90 RDRE1 35, 38, 43, 46, 51, 66
Str.dirNeut 92 FltNum 67
Str.dirPhsA 90 GriFltNum 67
Str.dirPhsB 91 Health 66
Str.dirPhsC 91 Mod 66
Str.neut 92 RcdMade 66, 67
Str.phsA 90 RcdStr 67

SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT 177


C53000-G1140-C211-4, Edition 03.2010
Index

RFLO1 41, 45, 50, 142 BlkOpn 159


FltDiskm 143 CBOpCap 159
FltDisPrc 143 CirSpv 160
FltZ 143 Health 158
Health 142 Loc 158
Mod 142 Mod 158
RREC1 36, 41, 45, 50, 140 OpCnt 158
AutoRecSt 141 Pos 159
Health 140 SumSwARs1 161
Mod 140 SumSwARs2 161
Op 141 SumSwARs3 161
RSYN1 41, 45, 52, 146
AngInd 147
DifAngCIc 148
DifHzCIc 148
DifVCIc 148
Health 146
HzInd 147
Mod 146
Rel 146
SynPrg 147
VInd 147
RSYN2 41, 149
AngInd 150
DifAngCIc 151
DifHzCIc 151
DifVCIc 151
Health 149
HzInd 150
Mod 149
Rel 149
SynPrg 150
VInd 149
RSYN3 41, 152
AngInd 153
DifAngCIc 154
DifHzCIc 154
DifVCIc 154
Health 152
HzInd 153
Mod 152
Rel 152
SynPrg 153
VInd 152
RSYN4 41, 155
AngInd 156
DifAngCIc 157
DifHzCIc 157
DifVCIc 157
Health 155
HzInd 156
Mod 155
Rel 155
SynPrg 156
VInd 155

X
XCBR1 34, 49, 158
BlkCls 159

178 SIPROTEC, SIPROTEC 7SJ6/7SJ8/7SK8 , PIXIT


C53000-G1140-C211-4, Edition 03.2010