0% found this document useful (0 votes)
68 views1 page

Generator Windings Pitch

This document discusses generator windings and the pros and cons of 2/3-pitch versus 4/5-pitch windings. Harmonics from non-linear loads can cause issues for generators and electrical systems. While 2/3-pitch generators produce little third harmonic current, they produce higher fifth and seventh harmonics which can increase motor heating. 4/5-pitch generators produce less harmonics overall and result in lower phase-to-neutral fault currents. For a given installation, factors like load type and future loads must be considered to determine the best winding pitch.

Uploaded by

Ivan_Uwais
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views1 page

Generator Windings Pitch

This document discusses generator windings and the pros and cons of 2/3-pitch versus 4/5-pitch windings. Harmonics from non-linear loads can cause issues for generators and electrical systems. While 2/3-pitch generators produce little third harmonic current, they produce higher fifth and seventh harmonics which can increase motor heating. 4/5-pitch generators produce less harmonics overall and result in lower phase-to-neutral fault currents. For a given installation, factors like load type and future loads must be considered to determine the best winding pitch.

Uploaded by

Ivan_Uwais
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Consultant’s Corner:

Generator Windings
Pitch

Question: Should you specify 2/3 - or 4/5 - pitch generator windings?


Answer: It depends... As non-linear loads make up and increasing portion of total electrical load profile, more thought is being
given to dealing with the phenomenon of their harmonics and its effect on gen sets, loads, cabling buses, protective relays and
circuit breakers. The problem becomes even more complex if the gen set is paralleled with the utility when harmonics on the utili-
ty line may cause some hard-to-trace problems.

Harmonics defined
Harmonics are multiples of the sine waveform produced by the generator. For example, 60 Hz is the fundamental waveform,
then 180 Hz (60 Hz x 3) is third harmonics, 300 Hz is fifth harmonics, 420 Hz is seventh harmonics, etc. Only odd-numbered
harmonics are important in this discussion.

All harmonics affect current waveform. If the waveform change is great enough (most notably in the third harmonic), loads that
use the 60 Hz waveform to trigger switching are affected. It can also deceive the gen set voltage regulator so it continually
"searches" for the correct excitation level to meet the needed voltage. It also can create excessive heat in transformers, UPS
and computers as well as throw off instrument readings.

Although 2/3-pitch generators produce little third harmonics current, they do produce much higher fifth and seventh harmonics
when compared with 4/5- and 5/6-pitch generators. This increases heating in motors which can shorten life.

Best practices
The best way to deal with harmonics concern is at specification. Present and future load profiles offer some insight into non-lin-
ear loads. If it is harmonic-rich, specifications should compensate for it.

If inductive loads make up the majority of the load, 4/5- or 5/6-pitch generators can be used with correct sizing. These generators
also result in phase-to-neutral faults much lower than 2/3-pitch unit.

Pitch pointers
There has been much written and even more speculated about the pros and cons of 2/3-pitch generators vs. 4/5- (and 5/6-) pitch
machines. Because the effects of third harmonics on electrical systems is installation-specific, few hard and fast rules apply. But,
in general, the following points are consistent across all generator and electrical systems:

1. Third harmonics current is generated almost totally by connected load - computer systems, UPS, variable-speed and fluores-
cent lighting. Only a negligible amount is produced by the generator, no matter what its winding pitch.

2. Third harmonic currents in identical paralleled gen sets are no problem if gen sets are carrying equal load. However, it may be
a problem if two generators of different pitches are paralleled.

3. While 2/3-pitch generators have very little third harmonic current compared to other pitches, the fifth and seventh harmonics
are nearly maximum at 2/3 pitch. Further, if a phase-to-neutral fault (the cause of 65 percent of all faults) occurs on a 2/3-pitch
machine, there will be higher fault currents, with the potential of more system damage and the need for higher interrupting capa-
bility circuit breakers - adding cost to the installation.

Call us
Many questions must be answered about an installation before it can be decided whether a 2/3-pitch or 4/5-pitch generator is
best. We stand ready to recommend the best course of action.

You might also like