Generator Windings Pitch
Generator Windings Pitch
Generator Windings
Pitch
Harmonics defined
Harmonics are multiples of the sine waveform produced by the generator. For example, 60 Hz is the fundamental waveform,
then 180 Hz (60 Hz x 3) is third harmonics, 300 Hz is fifth harmonics, 420 Hz is seventh harmonics, etc. Only odd-numbered
harmonics are important in this discussion.
All harmonics affect current waveform. If the waveform change is great enough (most notably in the third harmonic), loads that
use the 60 Hz waveform to trigger switching are affected. It can also deceive the gen set voltage regulator so it continually
"searches" for the correct excitation level to meet the needed voltage. It also can create excessive heat in transformers, UPS
and computers as well as throw off instrument readings.
Although 2/3-pitch generators produce little third harmonics current, they do produce much higher fifth and seventh harmonics
when compared with 4/5- and 5/6-pitch generators. This increases heating in motors which can shorten life.
Best practices
The best way to deal with harmonics concern is at specification. Present and future load profiles offer some insight into non-lin-
ear loads. If it is harmonic-rich, specifications should compensate for it.
If inductive loads make up the majority of the load, 4/5- or 5/6-pitch generators can be used with correct sizing. These generators
also result in phase-to-neutral faults much lower than 2/3-pitch unit.
Pitch pointers
There has been much written and even more speculated about the pros and cons of 2/3-pitch generators vs. 4/5- (and 5/6-) pitch
machines. Because the effects of third harmonics on electrical systems is installation-specific, few hard and fast rules apply. But,
in general, the following points are consistent across all generator and electrical systems:
1. Third harmonics current is generated almost totally by connected load - computer systems, UPS, variable-speed and fluores-
cent lighting. Only a negligible amount is produced by the generator, no matter what its winding pitch.
2. Third harmonic currents in identical paralleled gen sets are no problem if gen sets are carrying equal load. However, it may be
a problem if two generators of different pitches are paralleled.
3. While 2/3-pitch generators have very little third harmonic current compared to other pitches, the fifth and seventh harmonics
are nearly maximum at 2/3 pitch. Further, if a phase-to-neutral fault (the cause of 65 percent of all faults) occurs on a 2/3-pitch
machine, there will be higher fault currents, with the potential of more system damage and the need for higher interrupting capa-
bility circuit breakers - adding cost to the installation.
Call us
Many questions must be answered about an installation before it can be decided whether a 2/3-pitch or 4/5-pitch generator is
best. We stand ready to recommend the best course of action.