Resumo Da Norma ANSI/TIA/EIA 568-B: (Retirado Do Catálogo Fcs - Furukawa Cabling System)

The document summarizes standards for telecommunications cabling in commercial buildings, including ANSI/TIA/EIA 568-B from 2001 which replaced the 568-A standard. It also lists other relevant standards and specifications from standards bodies like TIA, EIA, IEEE, IEC, ANSI, and ATM Forum. The 568-B standard includes requirements for balanced twisted pair cabling, fiber optic cabling, and defines the minimum cabling infrastructure for telecommunications rooms and work areas.

Uploaded by

Hector Leines
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views5 pages

Resumo Da Norma ANSI/TIA/EIA 568-B: (Retirado Do Catálogo Fcs - Furukawa Cabling System)

The document summarizes standards for telecommunications cabling in commercial buildings, including ANSI/TIA/EIA 568-B from 2001 which replaced the 568-A standard. It also lists other relevant standards and specifications from standards bodies like TIA, EIA, IEEE, IEC, ANSI, and ATM Forum. The 568-B standard includes requirements for balanced twisted pair cabling, fiber optic cabling, and defines the minimum cabling infrastructure for telecommunications rooms and work areas.

Uploaded by

Hector Leines
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

ISO/IEC 11801 Generic Cabling for Customer Premises - 1995;

TIA/EIA 568-A Comercial Building Telecommunications Cabling Standard - 1995

TIA/EIA 568-A-1 Addendum n.1 to TIA/EIA 568-A 1997 Propagation Delay and Delay Skew
Specifications for 100 ohms 4 pair cable;

TIA/EIA 569 Commercial Building Standard for Telecommunication Pathways and Spaces 1998;

TIA/EIA 606 Administration Standard for the Telecommunications Infrastructure of ommercial


Buildings 1993;

TIA/EIA TSB 67 Transmission Performance Specification for Field Testing of Unshielded Twisted-
Pair Cabling Systems 1995;

TIA/EIA TSB 72 Centralized Optical Fiber Cabling Guidelines 1995;

TIA/EIA TSB 75 Additional Horizontal Cabling Practices for Open Offices 1996;

EIA 310-D Cabinets, Racks, Panels and Associated Equipaments;

TIA/EIA 587 Fiber Optic Graphic Symbols;

IEC 617-10 Graphical Symbols for Diagrams - part 10 Telecommunications Transmission;

ANSI/IEEE 802.3 Local Area Networks-Part 3 CSMA/CD Access Method and Physical Layer
Specifications 1996;

IEEE 802.1-Q Draft Standards for LAN/MAN VLANS 1997;

IEEE 802.3 z DRAFT CSMA/CD Method and Physical Specification for 1000 Mbps Operation - 1997;

ANSI/IEEE 802.3u MAC Parameters, Physical Layer, MAUs and Repeater for 100 Mbps Operation,
Type 100BASE-T 1995;

ANSI/IEEE 802.12 Demand Priority Access Method, Physical Layer and Repeater for 100 Mbps
Operation, Type 100MB/s 1995;

ATM FORUM User Network Specification (UNI) version 3.1-1994;

ATM FORUM 622.08 Mbps Physical Layer Specification AF-phy-0046.000 -1996;

BICSI Telecommunications Distribution Methods Manual Vol I e II - 1995;

ABNT Norma NB-54.

Para fazer comentários ou sugestões a respeito desta norma envie um e-mail para

Resumo da norma ANSI/TIA/EIA 568-B

(RETIRADO DO CATÁLOGO FCS - FURUKAWA CABLING SYSTEM)


O documento ANSI/TIA/EIA 568-B substituiu, em 2001, o ANSI/TIA/EIA 568-A, como o
"Padrão de Cabeamento de Telecomunicações em Edifícios Comerciais". Os adendos 1 até
5 do documento 568-A e todos os TSBs ( Technical Systems Bulletins 62, 67, 72,75 e 95 ),
foram incorporados no padrão 568-B.

O novo documento é dividido em três seções:

- B.1 - "Comercial Building Telecommunications Cabling Standard"


- B.2 - "Balanced Twisted Pair Cabling Components"
- B.3 - "Optical Fiber Cabling Components Standard"

ANSI/TIA/EIA 568-B – B.1

Este padrão incorpora e remodela o conteúdo técnico dos seguintes documentos:

- TIA/EIA TSB 67 – Transmission Performance Specifications for Field Testing of


Unshielded Twisted Pair Cabling Systems
- TIA/EIA TSB 72 – Centralized Optical Fiber Cabling
- TIA/EIA TSB 75 – Additional Horizontal Cabling Practices for Open Offices
- TIA/EIA TSB 95 – Additional Transmission Performance Guidelines for 4-Pair 100
Ohms Category 5 Cabling
- ANSI/TIA/EIA 568-A-1 – Propagation Delay and Delay Skew Specifications for 100
Ohms 4 Pair Cable
- ANSI/TIA/EIA-568-A-2 – Corrections and Additions to TIA/EIA-568-A
- ANSI/TIA/EIA-568-A-3 - Performance Specifications for Hybrid Cables
- ANSI/TIA/EIA-568-A-4 – Production Modular Cord NEXT Loss Test Method and
Requirements for Unshielded Twisted Pair Cabling
- ANSI/TIA/EIA-568-A-5 – Transmission PerformanceSpecifications for 4 Pair 100 Ohms
Category 5e Cabling
- TIA/EIA/IS-729 – Technical Specifications for 100 Ohms Screened Twisted Pair Cabling

CABEAMENTO BACKBONE

Os meios de transmissão reconhecidos são:

- Cabo par trançado sem blindagem, 4 pares 100 Ohms UTP


- Cabo óptico Multimodo 50/125 um ou 62,5/125 um
- Cabo óptico Monomodo

CABEAMENTO HORIZONTAL

Os meios de transmissão reconhecidos são:

- Cabo par trançado sem blindagem, 4 pares 100 Ohms UTP ou SC/TP (Screened Twisted
Pair)
- Cabo óptico Multimodo de 2 fibras 50/125 um ou 62,5/125 um
- Cabo par trançado blindado 2 pares 150 Ohms (STP-A), que não é recomendado para
novas instalações

ÁREA DE TRABALHO

No mínimo duas tomadas / conectores de telecomunicações são necessárias por área de


trabalho:

Primeira Tomada (obrigatório):

- Cabo par trançado sem blindagem (UTP) 4 pares 100 Ohms ou SC/TP e conector
Categoria 5e associado

Segunda Tomada:

- Cabo par trançado sem blindagem(UTP) 4 pares 100 Ohms ou SC/TP e conector
Categoria 5e associado.

- Cabo de 2 fibras ópticas 62,5/125 um e/ou 50/125 um e conectores ópticos (recomendado


o SC ou os SFF – Small Form Factor).

- Cabo STP-A 150 Ohms e conector (não recomendado paranovas instalações).

- É permitido um ponto de transição ou consolidação.

- Componentes como bridges, taps e splices não são permitidos para soluções em UTP.

- Tomadas adicionais são permitidas, desde que igualem ou excedam o mínimo de


performanceexigido.

- Cordões de equipamentos devem ter a mesma performance dos patch cords.

ANSI/TIA/EIA 568-B – B.2

BALANCED TWISTED PAIR CABLING COMPONENTS

Inclui os requisitos de melhoria de performance para cabos UTP e correspondente conexão


de hardware e conectores fêmea categorias 3. 5e e 6.

Os testes devem ser efetuados no cabo horizontal, na conexão de hardware e nos cordões de
manobra, na faixa de freqüência de 1 a 250 MHz.

As características a serem testadas são as seguintes :

- PERDA DE INSERÇÃO
- PERDA DE RETORNO
- NEXT
- PARADIAFONIA CATEGORIA 6 (apenas para os cordões de manobra)

Os requisitos das Categorias 3 e 5e são aprovados pela ANSI/TIA/EIA 568-A e os


requisitos da Categoria 6 são valores propostos em drafts contidos em adendos.

PARÂMETROS DE DESEMPENHO DE TRANSMISSÃO

(*) Somente se o canal/enlace seguir os critérios de uma performance de transmissão


especificada pelo TSB-95

PARÂMETROS DE DESEMPENHO DE TRANSMISSÃO PARA CATEGORIAS

NÃO-PADRONIZADAS

ANSI/TIA/EIA 568-B – B.3

OPTICAL FIBER CABLING COMPONENTS STANDARD

Este padrão inclui requisitos de transmissão de cabos e componentes de fibras ópticas:

- Performance de Conectores Ópticos Multimodo e Monomodo:

A perda de inserção máxima para todos os tipos de conector é 0,75 dB. A perda de retorno
máxima é – 20 dB para cabos multimodo e – 26 dB para cabos monomodo.

- Raio de Curvatura Mínimo e Força de Tensionamento

Os cabos de 2 e 4 fibras utilizados para cabeamento horizontal devem suportar raio de


curvatura de 25 mm (1”) sob nenhuma condição de carga.

Os cabos de 2 e 4 fibras para serem lançados através do caminho horizontal durante a


instalação devem suportar raio de curvatura de 50 mm (2”) sob tração de 222 N (50 lbf).

Todas as outras fibras internas devem suportar um raio de curvatura de 10 vezes o diâmetro
externo do cabo sob nenhuma condiçãode carga e 15 vezeso diâmetro externo sob uma
tensão de carga no cabo até o limite avaliado.

Cabos para instalação externa devem suportar raio de curvatura de 10 vezes o diâmetro do
cabo sob nenhuma condição de carga e 20 vezes o diâmetro externo quando setrata de
tensãode carga no cabo até o limite avaliado.

Cabos para instalação externa devem atender um mínimo de 2670 N de força de tensão.

- Conectores 568SC:
A posição das 2 fibras no conector e adaptador 568 SC devem ser referenciadas como
posição A e posição B.

O conector e adaptador Multimodo deve ser bege

O conector e adaptador Monomodo deve ser azul

- Conectores SFF (Small Form Factor)

Pode ser usado em cross connect horizontal intermediário e principal, pontos de


consolidação e áreas de trabalho.

PARÂMETROS DE DESEMPENHO DE TRANSMISSÃO EM CABOS ÓPTICOS