Sweep Frequency Response Analyzer: Sfra Tool For Detecting "Hidden" Transformer Faults
Sweep Frequency Response Analyzer: Sfra Tool For Detecting "Hidden" Transformer Faults
M5500
Sweep Frequency Response Analyzer
SFRA TOOL FOR The M5500 Sweep Frequency Response Analyzer (SFRA) is the newest generation of SFRA
diagnostic instrument from Doble. With incredibly fast sweep speed and expanded dynamic
DETECTING “HIDDEN” range, you can use the Doble M5500 test set to investigate the mechanical integrity of
TRANSFORMER FAULTS transformers, reactors and other equipment with windings. Coupled with the ease-of-use
and powerful features of the new SFRA v6 Software, conducting SFRA testing and analysis
of your apparatus has never been easier or more productive.
If you can measure the frequency response of a transformer, then you can identify physical
movement and other issues with the winding, core, and connections.
The M5500 sends an excitation signal into the transformer and measures the returning
signals. Comparing this response to baseline readings and test results from similar
units allows you to identify deviations and confirm internal mechanical problems.
The M5500 reduces the uncertainty about apparatus condition by providing solid
evidence of mechanical integrity or winding movement. Use it to help determine how a
transformer is deteriorating, if it can go back into service after a fault, or if it has been
damaged during transit.
Specify Doble SFRA baseline testing as part of the factory test for your new transformer
and call for retest at every major transportation mode change or crane lift. Use it after
system faults and during routine testing as part of your diagnostic toolkit.
FEATURES BENEFITS
• Lightweight and rugged portable test instrument • Ensure transformer performance, reduce maintenance costs and
• Typical sweep speeds between 15 and 30 seconds for reduced increase the service life of transformers
overall testing time • Identify problems such as core movement, winding deformation and
• Default frequency range of 20 Hz to 2 MHz, expanded displacement, faulty core grounds, partial winding collapse, hoop
range from 10 Hz to 25 MHz buckling, broken or loose clamping structures, shorted turns and open
windings
• Dynamic Range > 150 dB
• Use as part of your regular maintenance program or any time you
• Wired or wireless connection to the controlling PC
suspect a problem
• Includes new SFRA v6 Software for control and analysis
• Measurements are highly repeatable so even subtle changes can be
• “CE” mark indicating conformity to European Union directives
used for diagnostic purposes
regarding electromagnetic compliance, safety, and hazardous
substances
M5500 TECHNICAL SPECIFICATIONS
EXCITATION SOURCE M5500 RANGE
The M5500 provides a frequency response measurement
Channels 1
from 10 Hz to 25 MHz. Doble recommends the default
Frequency Range 10 Hz – 25 MHz user defined ,within
instrument frequency range setting of 20 Hz - 2 MHz for transformers as there is
Output Voltage 20 V pk-pk (10 V pk-pk at 50 Ohms) limited diagnostic value in measurements outside of this
Output Protection Short circuit protected range. The diagnostic frequency range of 20 Hz to 2 MHz
Source Impedance 50 Ohms covers the most important diagnostic areas:
MEASUREMENT CHANNELS • Core and Magnetic Properties
Channels 2 • Winding Movement and Deformation
Sampling Simultaneous
• Interconnections – Leads and Tap Changers
Frequency Range 10 Hz – 25 MHz
Max. Sampling rate 100 MS/s
Input Impedance 50 Ohms
M5500 RESOLUTION
The M5500 measures the frequency response at intervals
Recommended Calibration 1 year
controlled by the user. The default Tuned Frequency list
Interval
ensures frequency distribution consistent with other
ACCURACY
Doble SFRA instruments and compliance with IEC 60076-
Magnitude (guaranteed ± 0.1 dB (down to -60 dB)
18. The instrument can also be set to use logarithmic or
20 Hz - 2 MHz) ± 0.5 dB (-60 to -100 dB)
linear scaling. A constant excitation level is maintained
DATA COLLECTION for each frequency measurement. The M5500 has the
Test Method Sweep Frequency ability to auto-scale each frequency measurement and
PC Comm USB/Wireless optionally apply adaptive filtering - providing an overall
Frequency Range 20 Hz - 2 MHz (default), user defined within dynamic range of >150 dB in the default frequency range.
instrument frequency range
Number of Points 1045 points (default)
5000 points max COMPLIANCE
Dynamic Range (20 Hz - 2 MHz) >150 dB Electromagnetic EN 61326-1:2013
IF Bandwidth <10% of measurement frequency, adaptive Compatibility EN 55011 Class A
(EMC) Group 1
Point Spacing Variable, Linear or Logarithmic EN 61000-4-
DATA DISPLAY/EXPORT/ANALYSIS 2,3,4,5,6,8,11
Tabulation Frequency/Magnitude/Phase Environmental 1 IEC 60068-2-
Export Formats CSV/IEC/CIGRE 1,2,6,27,30,31
Plotting Frequency vs. Magnitude/Phase/Impedance Safety IEC 61010-1
/ Ratio EN 61010-1
Analysis Difference, Cross-Correlation, Leakage UL 61010-1
Channel CAN/CSA C22.2 No.
PHYSICAL SPECIFICATIONS 61010-1-12
Dimensions 12.25 x 9.5 x 3.7 in RoHS Directive 2011/65/
31 x 24 x 9.4 cm EU with amendment
Weight 7 lbs (3.2 kg) 2015/863/EU
Power Supply 24 VDC (40 W Universal AC in power supply)
Temperature -25° to + 55°C operating ORDERING INFORMATION
-40° to + 85°C storage
PART # PRODUCT
Relative Humidity 0% to 95% non condensing
TEST LEADS CONSTRUCTION M5500 Doble M5500 Sweep Frequency Response
Analyzer
Integrated three lead system in single cable set
Standard (362 kV and below): 60 ft/ 18 m Includes test set, power supply, AC power cord,
Optional (> 362 kV): 100 ft/ 30 m USB cable, and reference box in a rugged carry
IEC Method 1 kits also available case. Also includes soft carry bag with 60 ft.
standard SFRA test lead, shorting leads, extra
clips, and safety ground cable. License for two
users of SFRA Software v6 Professional
provided with each instrument.