Installation Manual: Veritas R8 Plus/Veritas Excel
Installation Manual: Veritas R8 Plus/Veritas Excel
Contents
1. Quick Reference and Factory Settings............... 4 The Miscellaneous Selections ... !! - !$ .... 21
Programming Guide .......................................................4 Miscellaneous Selections Zero ................. !! ..... 21
Reference Table .............................................................5 Miscellaneous Selections One ................. !% ..... 21
Miscellaneous Options ..................................................6
Miscellaneous Selections Two ................. !& ..... 22
2. System Overview................................................. 7 Miscellaneous Selections Three ................ !$ ..... 23
System Architecture.......................................................7 Number of Alarm Activations (Re-arms) . !' .... 23
Control Panels ..........................................................................7
Testing the Sounders, Strobe ............... !( .... 24
Veritas R8 Plus & Excel ........................................................7
Remote Keypads ......................................................................7
Walk Testing ......................... !) or %" .... 24
Veritas R8 Remote Keypad..................................................7 Re-Loading the Factory Settings ........... !* .... 24
Veritas Excel Remote Keypad..............................................7 Programming the SW+ Output .............. !# .... 25
3. Installation ........................................................... 8 Configuring Remote Keypads ............... !" .... 25
Installation Sequence ....................................................8 Programming Zone Types ........ %% - %# .... 26
Control Panel..................................................................8 24 Hour Zone Types............................................................... 27
Mounting the Control Panel......................................................8
Programming the Zone Type ......... %% - %# ..... 27
Wiring the Control Panel...........................................................8
Control Panel PCB Layout......................................................9 Changing Part Set Zone Types .. &! - &$ .... 27
Connecting AC Mains............................................................10 Programming Part Sets Zone Changes ...... &! ..... 28
Connecting Batteries ..............................................................10
Changing Zones to Entry/Exit .................. &% ..... 28
Installing Remote Keypads..........................................10
Changing Zones to Inhibited Entry ............ && ..... 28
Cable Distances......................................................................10
Keypad Addressing ................................................................10
Changing Zones to Guard ...................... &$ ..... 28
Configuring the Keypads........................................................10 Programming the Date and Time &( - &) .... 28
Zone Connections ........................................................11 Programming the Date .......................... &( ..... 28
Magnetic Contacts and Panic Buttons...................................11
Programming the Time ......................... &) ..... 29
Powered Detectors ................................................................12
End Of Line Technology.........................................................13 Programming the Service Timers &* - &" ... 29
Global System Tamper.................................................14 Programming Service Timer One .............. &* ..... 29
Speaker Connections...................................................14 Programming Service Timer Two .............. &# ..... 29
Internal Siren(s)............................................................14 Programming Service Timer Three ............ &" ..... 29
Wiring the External Sounder........................................15
Programming System Timers .... $% - $" .... 30
Popular SAB Wiring Diagrams ...............................................15
Wiring a Communicator ...............................................16 The Seven Event Basic Log ...... '! - '* .... 30
Wiring Example.......................................................................16
Clearing the Seven Event Basic Log ........... '! ..... 30
Connecting a Computer...............................................17
Displaying the Seven Event Basic Log '% - '*..... 30
PC-Com.........................................................................17
Commissioning (Initial Power Up) ..............................17 Programming the Suites ........... '# - (" .... 31
Servicing the System ...................................................18 Programming the Zone Disable Suite ......... '# ..... 31
Trouble Shooting..........................................................18 Programming the Zone Soak Test Suite ...... '" ..... 31
4. Programming the Control Panel ....................... 20 Programming the Full Set Suite ................ (! ..... 31
Introduction ..................................................................20 Programming the Part Set Suites .... (% - (' ..... 31
The Programming Menu ............... !! - "# ......20 Programming the Chime Suite ................. (( ..... 32
Programming With an LCD Keypad .......................................20 Programming the Cleaner Suite ................ () ..... 32
Available LCD Menus .............................................................20 Programming the Double Knock Suite ........ (* ..... 32
Programming the Manual Omit Suite .......... (# ..... 32
Programming the Zone Invert Suite ............ (" ..... 32
2 INS045
Veritas R8 Plus & Excel Installation Manual Contents
Assigning Access Codes ........... )! - *" .... 33 1. Quick Reference and Factory Settings
User Number...........................................................................33
Access Code...........................................................................33
2. System Overview
Access Level ...........................................................................33
Access Types.........................................................................34
Changing Your Own Access Code ............. )! ......34 3. Installation
Assigning New Access Codes ........ )% - *# ......34
Installing Remote Keypads
Programming Access Codes .................. )% - )# ......34
Programming Access Levels .................. *% - *# ......34
Displaying User Information ......... )" & *" ......35 Zone Connections
Displaying Your User Number .............................. )" ......35
Displaying Your Access Level .............................. *" ......35
External Sounder Connections
5. Specifications
6. Installation Records
INS045 3
Quick Reference and Factory Settings Veritas R8 Plus & Excel Installation Manual
4 INS045
Veritas R8 Plus & Excel Installation Manual Quick Reference and Factory Settings
Reference Table
INS045 5
Quick Reference and Factory Settings Veritas R8 Plus & Excel Installation Manual
Miscellaneous Options
6 INS045
Veritas R8 Plus & Excel Installation Manual System Overview
2. System Overview
System Architecture
8 Zone Inputs
6 Keypads (mixed)
Veritas R8 Plus
Zo nes
1 2 3 4 5 6 7 8 Un set
Tamp er
!"#$%&'()*+",
Veritas Excel
-.(/&#(012--3-- Unse t
FULL
1 2 3 OMIT
8 x 100mA
Outputs Veritas Excel 4 5 6
PART
PROG
1
4 ghi
2 abc
5 jkl
3 def
6 mno
Omit
Chime
Reset
7 8 9 0 RESET
7 pqrs 8 tuv 9 wxyz Part
PC-Com
INS045 7
Installation Veritas R8 Plus & Excel Installation Manual
3. Installation
Installation Sequence Control Panel
Before attempting to install the alarm system, read this
Mounting the Control Panel
section. Once you have an overall understanding of the
installation sequence, carefully work through each step. Mount the control panel on a flat, plumb wall using at least
three appropriate screws. The rear casing has been
1. Design the Layout designed with a central key-hole slot so that mounting is
Make a rough sketch of the premises to get an idea of possible without removing the Printed Circuit Board (PCB).
where the alarm detection devices, keypads etc. are to be The angled slot in the lower corner has been provided to
located. allow the panel to be levelled easily. If the PCB has to be
removed, carefully pull back the two front PCB securing
2. Mounting the Panel
clips, lift the front of the PCB and slide it downward. To
The control panel should be mounted in a dry area close to replace the PCB simply reverse the above procedure.
an unswitched AC power source.
8 INS045
Veritas R8 Plus & Excel Installation Manual Installation
Box
Tamper
JP1 SW1
Power
LED1
F5 Power Supply
F1 Bell
F2 & Strobe
Battery
Com 1
S D C B A PL1
- + + - + -
Batt Strb 0V Tamp Bell +12V SW+ Tamp
A.C. LS Aux
INS045 9
Installation Veritas R8 Plus & Excel Installation Manual
Keypad Addressing
Connecting Batteries
Each keypad MUST be given a different address using the
Up to one 12V 7Ah battery can be fitted inside the control DIP switch on the PCB as follows:
panel to provide continued operation in the event of an AC
mains failure. Address DIP 1 DIP 2 DIP 3 DIP 4
2
N/A
N/A
Off
Off
Off
Off
Off
On
1 2 3 4
1 2 3 4
Connect the red battery lead to the positive terminal of the 3 N/A Off On Off 1 2 3 4
+ + 6 N/A On Off On
12V _ Battery 1 2 3 4
2.1Ah - 7Ah
Battery - +, NEVER set two RKPs to the same address.
Keypads are factory set to Address 1.
Installing Remote Keypads If the keypad is powered but offline (i.e. T and R not
connected) it will display its address.
A maximum of 6 remote keypads can be connected to the
keypad network. The Veritas R8 Plus and the Veritas Excel If an invalid address is selected, the keypad will
supports both LED and LCD keypads. sound an error tone.
The networks are made up of four terminals incorporating
power and data. To ensure correct operation, all four terminals Configuring the Keypads
on the device must be connected to the corresponding
When the system is powered up it automatically checks and
terminals on the control panel, or previous keypad. The table
configures all connected keypads. It is strongly
below shows each terminal and its description:
recommended that the system is completely powered down
(mains and battery) before wiring a keypad. If a keypad is
Terminal Description
added without removing power then it must be configured
+ +12V Supply (see page 25).
- 0V Supply
T
R
Transmit Data
Receive Data
+, If an RKP is configured but off-line, the system will
have a tamper fault.
10 INS045
Veritas R8 Plus & Excel Installation Manual Installation
Zone Connections
Detection devices such as PIR’s, Door Contacts, PA Buttons etc. are all connected to the 8 zone terminals on the Veritas R8
Plus and Veritas Excel control panel.
+, If a zone is not being used it should be either linked out or disabled (see page 31).
Figure 1a - Wiring a Single Magnetic Contact to a Zone (see also Figure 4).
Figure 1b - Wiring Multiple Magnetic Contacts to a Zone (see also Figure 4).
+, Mixing powered detectors and magnetic contacts on one zone is easiest if the wiring is taken from the control panel to
the powered detectors first.
INS045 11
Installation Veritas R8 Plus & Excel Installation Manual
Powered Detectors
Always consult the manufacturer's connection instructions. Powered detectors are connected to one of the eight terminal pairs
labelled Z1 to Z8 on the control panel and are powered from the two terminals labelled AUX on the control panel as follows:
+, Power is wired in parallel, whereas normally closed alarm loops are wired in series, (normally open alarm loops are wired
in parallel).
Mixing powered detectors and magnetic contacts on one zone is easiest if the wiring is taken from the control panel to
the powered detectors first.
BS 4737 requires that if two or more powered detectors are connected to one zone, they must each have an audible or
visual latching indication or both, except on an entry/exit route.
12 INS045
Veritas R8 Plus & Excel Installation Manual Installation
Those already familiar with End of Line (EOL) Technology Miscellaneous Option 3.2 (S/C = Tamper) Off
(sometimes referred to as Balanced Zones) may wish to Miscellaneous Option 3.3 (O/C = Tamper) Off
skip this section.
So called Normally Closed Loops have only two possible
states, that is either open (zone in fault) or closed (zone ALARM LID
clear). It is therefore necessary to have separate 24 hour
tamper loop(s) to protect the zones when the system is ZONE TAMPER
unset and they are not being monitored.
Figure 3a - Normally Closed Operation.
End of Line Resistance is a technique which, by adding
resistance at the last detector in the loop, provides each
loop with its own 24 hour tamper protection.
The panel can distinguish up to four possible states; low Miscellaneous Option 3.2 (S/C = Tamper) On
resistance (10kΩ) is interpreted as zone clear, high Miscellaneous Option 3.3 (O/C = Tamper) Off
resistance (33kΩ) is interpreted as zone in fault. Short
circuit may optionally be interpreted as tampering or zone 10K
clear. Open circuit may optionally be interpreted as ALARM LID
tampering or zone in fault.
ZONE
Resistors are coded with coloured bands to identify the
different values, as follows: Figure 3b - "American" Operation.
Resistor Colour Code
10kΩ Brown, Black, Orange, Brown
22kΩ Red, Red, Orange, Brown Miscellaneous Option 3.2 (S/C = Tamper) Off
33kΩ Orange, Orange, Orange, Brown Miscellaneous Option 3.3 (O/C = Tamper) On
to fit the EOL resistor(s) in the panel than in the Figure 3d - High Security Operation (one detector
detector. per zone).
INS045 13
Installation Veritas R8 Plus & Excel Installation Manual
+, The control panel is supplied with a link fitted across the Global System Tamper to simulate a closed circuit. This link
would usually be removed during installation. However the Global System Tamper will typically only be used with
normally closed operation, with EOL operation the tamper link would usually be left in place.
Speaker Connections
This output can be used for driving up to one 16Ω or two 8Ω loudspeakers as shown below:
+, The total load including the built-in speaker must not be less than 16Ω (e.g. 1 x 16Ω speaker, 2 x 8Ω speakers in series, etc.).
The polarity of extension speakers is usually unimportant, however, the polarity of the L/S terminals is indicated by a + and -.
Internal Siren(s)
If required these are connected to two of the external sounder connections, in addition to the external sounder, as follows:
Terminal Connect To
A Siren Positive Supply (+12V)
B Siren Negative Activate/Negative Supply (0V)
14 INS045
Veritas R8 Plus & Excel Installation Manual Installation
Always consult the manufacturer's connection instructions. The following diagrams illustrate how to connect the control
The external sounder and strobe are connected to the five panel to the most popular makes of SAB:
terminals labelled SAB on the control panel as follows:
Figure 6 - Common SAB Connections
Terminal Description
A Permanent Positive Supply (+12V)
B Switched Negative to Activate Sounder
C Negative Tamper Return
D Permanent Negative Supply (0V)
S Switched Negative to Activate Strobe
INS045 15
Installation Veritas R8 Plus & Excel Installation Manual
Wiring a Communicator
The control panel has eight outputs, which can be used for
connecting to a stand-alone communicator. The table below
shows the characteristics for each output:
Wiring Example
The diagram below shows a typical wiring example:
Channel Inputs
Programmed
Stand Alone
as Positive Communicator
Figure 6f - Activeguard AU101. Removed
Control
Figure 6g - CQR Integra HS. Communicator
Panel
Interface
16 INS045
Veritas R8 Plus & Excel Installation Manual Installation
Connecting a Computer • Enter the factory set User code '$&%. The error
tone will stop.
The Veritas R8 Plus and Veritas Excel both support local • Enter the factory set Engineer code %&$' and
uploading and downloading between the control panel and a press , to access the Programming Menu and
PC running Veritas UDL software. Uploading and disable 24 Hour zones (Fire, PA and Tamper) via the
Downloading can be used to program and interrogate the Engineer code. All the zone lights will illuminate.
control panel.
• Perform a Walk Test as described in on page 24.
+, In order to upload and download to the control panel
locally, a PC-Com lead is required.
Remember that some powered detectors (e.g. PIRs and
Combined Technology Detectors) take several minutes
to warm up and become operational.
• Test the internal sounder, external sounder and strobe
Box
Tamp er
JP1
SW1
as described on page 24. To adjust the low-level
volume use the control 'pot' on the PCB (see page 9),
Pow er
LED1
F5 Pow e r Supply
F1 Bell
F2 & St robe
Com1
S D C B A PL1
A.C .
-
Ba tt
+
Str b 0V Ta mp Be ll +12 V
+
LS
- +
Aux
-
SW+ Ta mp
INS045 17
Installation Veritas R8 Plus & Excel Installation Manual
• Remove the screw covers by inserting a screwdriver • If the remote keypad was connected after the control
into the screw cover slot and turning anti-clockwise panel was powered up, disconnect all power
whilst applying pressure outwards. momentarily and reconnect. This automatically
configures all remote keypads on the system, (also see
• Unscrew the lid screws and remove the lid. page 25).
• On completion replace the lid and secure with the lid • Check you are using the correct codes. Factory-set
screws - do not over-tighten.
Engineer code is %&$'. Factory-set User code is
• Replace the screw covers. '$&%.
• Press . to leave the Programming Menu. All the • If using one or more RKPs on battery only, try using
zone lights will turn off. mains as the battery may be flat.
• Switch on the mains supply to the control panel. The • Check that the codes have not been changed. If the
Power light will stop flashing and stay on continuously. codes have been lost (see page 24).
• Check that the membrane keypad tail is all the way
Trouble Shooting home in its connector on the PCB.
18 INS045
Veritas R8 Plus & Excel Installation Manual Installation
Unit Will Not Set and Bleeps 9 Times Unit Goes Into False Alarm
The system has a tamper fault and the Tamper light will be • Check that the terminal screws are fully down on all
on. Using the extended display during Walk Test (see page terminals but do not over tighten.
24) identify the cause of the tamper fault: • If you have a meter use it to check the loop resistance
• If the extended display identifies the fault as an EOL (wires that run under carpets are easily damaged).
tamper then identify the zone(s) from the normal display
and check the zone wiring. Unit Makes No Sound
• If the extended display identifies the fault as bell box • Check that the variable resistor (pot) on the PCB which
tamper, then the cause may either be Bell Tamper or controls the volume of low level tones is NOT turned
Global System Tamper. Temporarily replace the system fully clockwise. The volume increases as the pot is
tamper link (TAMP): turned anti-clockwise.
• If the tamper fault persists then it is due to the Bell • Check the auxiliary fuse F3 and replace if blown.
Tamper - check the bell wiring, the bell lid and/or • Check the speaker connections to the L/S terminals on
screw tamper, and the bell wall tamper (if fitted). the PCB.
• If the tamper fault clears then it is due to the system
tamper. Remove the system tamper link and the System Operates but Keypad Makes No Sound
tamper fault will reappear - check the system
tamper wiring and the lid tamper on all detectors. • If an older version remote keypad has been fitted the
system must be programmed for old style sounds as
follows: Enter the Engineer code ----, press
Remove ALL Temporary Links.
,, enter !!, press #, press ,, press
• If the extended display identifies the fault as lid tamper, ..
it may refer either to the control panel or the remote
keypad(s). Try stretching the springs and ensure all External Sounder/Strobe Does Not Work
connections are secure.
• Check wiring connections by referring to the diagrams
• To set the system with a tamper fault use the following on page 15.
procedure:
• Check the bell/strobe fuse F2 and replace if blown.
• Enter the User code ----. Press 0 or
• To check the external sounder make a temporary
1. The system will sound a repeating series of connection between SAB B and D.
9 bleeps. Press /. The display will illuminate the
zones that are about to be armed. Press ". The • To check the strobe make a temporary connection
between SAB S and D.
Tamper light will turn off. Press ,. The exit tone
and exit timer will start.
The Panic Button Does Not Work
• To prevent repeated false alarms due to an intermittent
tamper fault when the system is unset, omit Tamper as • Check that the Zone Type of the zone to which the panic
described above, then abort the setting procedure by button is connected is programmed as PA (see page 27).
re-entering the User code. • Check that the zone to which the panic button is
• To prevent Tamper from being omitted (see page 22). connected is not omitted in part set (see page 31).
• Check that the Zone Type of the zone to which the panic
Unit Will Not Set and Bleeps 1 - 8 Times button is connected is not changed in part set (see page
The system has one or more zone faults and the 27).
corresponding zone light(s) will be on. • Older version remote keypads do NOT support Keypad
PA (pressing $ and " together), see System
• Ensure that the zone is closed (doors shut, no
Operates but Makes No Sound, above.
movement in PIR detection area).
• Check the zone wiring and ensure all connections are Service Timers Cannot Be Programmed
secure.
Programming the service timers (&*, &#, &") is
• Check that detectors are powered correctly (i.e. correct prevented unless the current date (&() has been
polarity). programmed since the last power-up (see page 28).
INS045 19
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
Programming is usually unnecessary as the factory There are two ways to select options whilst in the
settings have been carefully selected to suit most Programming mode:
installations without alteration. However all functions are 1. Select an option directly by entering a 2-digit Option
fully programmable for Complete Control. code --.
The Programming Menu !! - "# +, All of the programming examples shown in this
section use this method of programming.
The Programming Menu can only be accessed when the
control panel is unset. 2. Using the ' key to scroll up and down through the
The display will normally look like this: menu options and then pressing ( or ) to
access the menu options.
+,
Zones
1 2 3 4 5 6 7 8 Unset (!"#$%&'(()*+",
Tamper -.(/&#((012--3-0 Wherever a ' symbol appears on the
display, the ' key can be used to search
Enter your 4-digit Engineer code (factory set to through the various menu options. The ( or
%&$'). The display will look like this: ) key can then be used to select the
Zones
displayed option.
1 2 3 4 5 6 7 8 Unset 456"(7++"8%"6
Tamper )9%"#(:8%$59(((;
20 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
1 Cancel Strobe with Bell Off Press the appropriate numbered button(s) to select or
2 Keypad PA, $ and " On de-select the corresponding option(s) as shown on the
3 Single Button Setting On display.
4
5
Silent Part Set Confirmation Tone
EN50131-1 Requirements
Off
Off
+, To display an explanation of the Misc. options
associated with a particular number, press and hold
6 Time Limit Engineer Access Off the corresponding key - (LCD Keypad only).
7 Reset Button Cancels Setting On
Press ,. The system will chime to confirm that the
8 Auto Omit AC Off new options have been accepted. The system will then
Option 1 - Cancel Bell With Strobe automatically revert to the Programming Menu.
When ‘ON’ the strobe will stop when the bell timer expires.
Option Miscellaneous Selections One Default
Option 2 - Keypad PA, $ and " 1 Internals Only on Unset Tamper Alarm On
When ‘ON’ Pressing 3 and 9 together will generate a 2 Internals Only on Part Set Zone Alarm On
keypad PA alarm.
3 Internals Only on Part Set Tamper Alarm On
Option 3 - Single Button Setting 4 Silent Part Set (no exit tone on part set) Off
When ‘ON’ The system can be set using the 0 or 5 High Level Chime (chime at full volume) Off
1 keys without the need to first enter a User code. 6 Invert Bell Output Off
Option 4 - Silent Part Set Confirmation Tone 7 Final Door Set Off
When ‘ON’ a confirmation tone is generated to indicate that 8 Unlock Engineer On
the alarm has set, Will only function if Silent Part Set (see
page 21) is also selected. Option 1 - Internals Only on Unset Tamper Alarm
When ‘ON’ a tamper alarm when unset will only activate the
Option 5 - EN 50131-1 Requirements
internal sounders.
When ‘ON’ the following features are enabled (see page 39).
1. Reset (after an alarm) requires the use of a User code. Option 2 - Internals Only on Part Set Zone Alarm
When ‘ON’ an alarm when part set will only activate the
2. An entry alarm (defined as an entry timeout or, a
internal sounders.
Guard zone activation during the entry period) invokes
a 30 second delay during which the communicator Option 3 - Internals Only on Part Set Tamper Alarm
output and external sounder are suppressed (i.e. the When ‘ON’ a tamper alarm when part set will only activate
alarm response is limited to the internal sounder(s) the internal sounders.
and external strobe for the first 30 seconds).
Option 4 - Silent Part Set
3. On unsetting the system the unset light will extinguish When ‘ON’ no exit tones will be heard when the alarm is
after 30 seconds. being part set.
INS045 21
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
From the Programming Menu, enter !&. The display will Option 3 - Disable User Ability to Omit Tampers
show the options currently selected. When ‘ON’ users cannot omit tampers.
Zones
Option 4 - Code PIN Tamper
Unset /$'+3(:8%'(1(((;
1 2 3 4 5 6 7 8
Tamper :8%'3(M(333333O3 When ‘ON’ a tamper alarm is generated after 16 invalid key
presses when unset.
Press the appropriate numbered button(s) to select or
de-select the corresponding option(s) as shown on the Option 5 - Random Number Remote Reset
display. When ‘ON’ Random Number Remote Reset is enabled.
22 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
Press the appropriate numbered button(s) to select or • Changing the state of the zone i.e. closed to open or
de-select the corresponding option(s) as shown on the open to closed will cause the system to set and
display. changing the state of the zone again i.e. closed to
open or open to closed will cause the system to unset.
+, To display an explanation of the Misc. options
associated with a particular number, press and hold • If there has been an alarm activation, the next open
the corresponding key - (LCD Keypad only). close of the Keyswitch will cause the system to enter
Recall and the next open close will Reset the panel
Press ,. The system will chime to confirm that the and return it to Unset.
new options have been accepted. The system will then
Option 7 - Automatically Omit Zone On Alarm
automatically revert to the Programming Menu.
When ‘ON’ the system will prevent multiple alarms from the
Option Miscellaneous Selections Three Default same zone. It should NOT be used if selecting non-latching
communicator outputs (see page 35).
1 Mains Frequency (off = 50Hz, on = 60Hz) Off
2 EOL Tamper Alarm on Zone Short Off
Option 8 - Automatically Omit Keyswitch Zone
When ‘ON’ a key switch cannot be used to unset the
3 EOL Tamper Alarm on Zone Open Off
system if it is tampered with.
4 Enable DD 243:2002 Options Off
5 Enable Confirmation After Entry Time Out Off
Number of Alarm Activations (Re-arms)+ !'
6 Momentary KEYSW Off
7 Automatically Omit Zone on Alarm Off From the Programming Menu, enter !'. The display will
8 Automatically Omit Keyswitch Zone when Off look like this.
EOL Tampered Zones
1 2 3 4 5 6 7 8 Unset 7,A(7+%$Q&%$59';
Tamper M-N
Option 1 - Mains Frequency
When ‘OFF’ the Mains frequency is set to 50Hz (UK). Enter the desired number of Alarm Activations as a two
digit number (e.g. for three Activations, enter !$). The
+, If the wrong Mains Frequency is selected the panel
will indicate a power fault.
display will indicate as each digit is entered. Press ,.
The control panel will chime to confirm that the new number
Option 2 - EOL Tamper Alarm on Zone Short of Activations has been accepted. The system will then
For details see page 13. automatically revert to the Programming Menu.
Option 3 - EOL Tamper Alarm on Zone Open
For details see page 13.
+, The total number of Activations should not be less
than 01.
INS045 23
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
Testing the Sounders, Strobe !( +, If the Tamper indicator is on and the panel bleeps 9
times an extended display reveals more information
From the Programming Menu, enter !(. The display will
about the source of the tamper fault(s). To toggle
look like this.
between the normal display and the extended
Zones
1 2 3 4 5 6 7 8 Unset C"'%(G5J96"#'((; display press /. The extended display is
Tamper 7+%$Q&%"M(333333
distinguished from the normal display by the Unset
The system outputs may be tested as follows: light being off. In the extended display the zones are
interpreted as follows:
Key Function
Zone Description
)+ Invoke bell box hold-off mode
(+ Toggle the SW+ output 1 Bell Tamper (including Global System Tamper)
'+ Toggle the internal sounder high level (alarm tone) 2 Not Applicable
$+ Toggle the internal sounder low level (entry/exit tone) 3 Lid Tamper (including RKP Lid Tamper)
&+ Toggle the strobe output 4 Line Monitor
%+ Toggle the external sounder (bell) output 5 RKP Off-Line
!+ Turn off all of the above 6 Not Applicable
7 Not Applicable
Conduct a Walk Test by triggering each of the system's The system will bleep each time the panel lid tamper
detection devices in turn and check that the control panel spring is pressed and released during the first 10
registers the corresponding zone as open. seconds after power up.
24 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
Option
1
SW+ Function
Set Positive (latching detectors)
+, NEVER set two RKPs to the same address.
Keypads are factory set to Address 1.
2 Alarm Positive with Latching Sensor Reset
(FTA detectors) If the keypad is powered but offline (i.e. T and R
3 Latching Shock Sensor Auto-Reset not connected) it will display its address.
(old style latching shock sensors)
4 Tamper If an invalid address is selected, the keypad will
5 Mains Fail sound an error tone.
6 Set Positive with Latching Sensor Reset
(latching detectors) From the Programming Menu, enter !". The display will
7 Walk Test show the zone numbers corresponding to remote keypads
8 Entry/Exit (RKPs) that are currently configured and on-line, while
flashing the zone numbers corresponding to RKPs that are
If connecting multiple detectors to one zone then: currently configured but off-line.
Zones
• Latching detectors will indicate which detector(s) 1 2 3 4 5 6 7 8 Unset
Tamper
<X?(459S$=(((((;
<X?'(M(033333
activated during an alarm.
• First to Alarm (FTA) detectors will indicate which To update the configuration, press ,. The control
detector caused an alarm and which detectors were panel will scan for RKP addresses 1 to 6. As each RKP is
then activated during the alarm. detected the control panel will configure it as present and
show the zone number corresponding to its address.
Option 3 would typically be used with older designs of
latching shock sensor which do not have a Latch input and To leave configuring, press .. If the configuration
must be powered down to clear the Latch indication. In this has not been updated the panel will sound an error tone.
case the detectors would be powered from the SW+ The system will automatically revert to the Programming
output. Menu.
+, If selecting one of the options which incorporate +, NEVER set two RKPs to the same address.
latching sensor reset (2, 3 or 6) the user can force a Setting the address of an RKP is described in the
latching sensor reset, to clear the Latch/FTA remote keypad instructions.
indication, by entering their code and pressing
If an RKP is configured but off-line the system will
.. have a tamper fault.
The SW+ output can only sink (not source) current.
ALWAYS power down the control panel when wiring
If powering detectors from the SW+ output, connect
a remote keypad (RKP).
the detector +Ve to AUX+ and the detector -Ve to
SW+. It may be necessary to invert the SW+ polarity If an older version remote keypad has been fitted the
(see page 22). system must be programmed for old style sounds as
follows: Enter the Engineer code ----,
press ,, enter !!, press #, press
,, press ..
INS045 25
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
26 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
24 Hour Zone Types For example to program Zone 7 as a Guard zone, enter
%*, press $, press ,.
24 Hour zones (Fire, PA and Tamper), Keyswitch zones
and Push to Set zones should be monitored constantly. Key Description
When a zone is omitted the system no longer monitors %+ Program Zone Type
opening and closing of that zone. The Full and Part Set *+ Zone = 7
Suites (see page 31) provide a method of automatically $+ Zone Type = Guard
omitting zones when the system is set. Once a zone is , Program
omitted it will not be re-included until the system is next
set. It is important to ensure that 24 Hour zones (Fire, PA
and Tamper), Keyswitch zones and Push to Set zones are
+, A zone is often referred to by its Zone Type, e.g. a
zone with the PA Zone Type would be referred to as
not omitted by any of the Full or Part Set Suites or the a PA zone.
Cleaner Suite.
The system can be programmed to automatically change Changing Part Set Zone Types &! - &$
the Zone Type of any zone into either Exit/Entry, Inhibited
Entry or Guard on selected part sets (see page 27). The The Zone Type of any zone can be made to change when the
change will persist until the system is unset. It is important system is part set. The Zone Type can be changed into either
to ensure that 24 Hour zones (Fire, PA and Tamper), Entry/Exit, Inhibited Entry or Guard. It is also possible to
Keyswitch zones and Push to Set zones are not changed program which part set(s) will cause the Zone Type to
on part set. change. The change will persist until the system is next unset.
INS045 27
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
Programming Part Sets Zone Changes &! Changing Zones to Guard &$
The Control Panel has four part sets. Zone Types will only This suite defines the zones which will be changed into
be changed on selected part sets. For example the Control Guard zones on the selected part sets. For example the
Panel is factory set with Part Sets 1 and 3 selected. Thus Control Panel is factory set with Zone 1 included. Thus the
Zone Types will only be changed on Part Set 1 and Part Set Zone Type of Zone 1 will be changed (from Entry/Exit) into
3, not on Part Set 2 or Part Set 4. Guard on Part Sets 1 and 3.
From the Programming Menu, enter &!. The part sets From the Programming Menu, enter
currently selected will indicate. &$. The zones that
are currently included will indicate.
Zones
1 2 3 4 5 6 7 8 Unset 4E&9="(59(?G"%(; Zones
Tamper ?&#%(G"%(M03N3 1 2 3 4 5 6 7 8 Unset 4E&9="(%5(UJ
Tamper B59"'(M(03333333
Press the appropriate numbered button(s) of the part
Press the appropriate numbered button(s) of the
set(s) to be selected or de-selected. Press ,. The
zone(s) to be included or excluded. Press ,. The
system will chime to confirm that the new selection has
system will chime to confirm that the new suite has been
been accepted. The system will then automatically revert to
accepted. The system will then automatically revert to the
the Programming Menu.
Programming Menu.
Changing Zones to Entry/Exit &% Programming the Date and Time &( - &)
This suite defines the zones which will be changed into
Entry/Exit zones on the selected part sets. For example the
Control Panel is factory set with Zone 2 included. Thus the
+, It is ESSENTIAL to program the current date (&()
and time (&)) for correct operation of the service
Zone Type of Zone 2 will be changed (from Inhibited Entry) timer(s) and the 250 Event Extended Log.
into Entry/Exit on Part Sets 1 and 3.
Programming the service timers (&*, &#,
From the Programming Menu, enter &%. The zones that &") is prevented unless the current date (&()
are currently included will indicate. has first been programmed.
Zones
1 2 3 4 5 6 7 8 Unset 4E&9="(%5()Y)9%; If the panel is completely powered down it will attempt
Tamper B59"'(M(31333333 to store the current time and date in NVM and continue
from this point when it is powered up. However it may
Press the appropriate numbered button(s) of the
be also desirable to select the Engineer Reset on Power
zone(s) to be included or excluded. Press ,. The
Up option (see page 22).
system will chime to confirm that the new suite has been
accepted. The system will then automatically revert to the
Programming Menu. Programming the Date &(
From the Programming Menu, enter &(. The display will
Changing Zones to Inhibited Entry && look like this.
This suite defines the zones which will be changed into Zones
1 2 3 4 5 6 7 8 Unset 4J##"9%(>&%"(((;
Inhibited Entry zones on the selected part sets. For example Tamper M-0Y-0Y-0
the Control Panel is factory set with no zones included. Thus
no zones will be changed into Inhibited Entry. Enter the current date as a 6 digit number; Day, Day,
Month, Month, Year, Year (e.g. to program the 1st of June
1998 enter !%!)"#). The display will indicate as
From the Programming Menu, enter &&. The zones that each digit of the new date is entered. Press ,. The
are currently included will indicate.
system will chime to confirm the new date has been
Zones
1 2 3 4 5 6 7 8 Unset 4E&9="(%5(KY)9%; accepted. The system will then automatically revert to the
Tamper B59"'(M(33333333 Programming Menu and all the zone lights will illuminate.
Press the appropriate numbered button(s) of the
zone(s) to be included or excluded. Press ,. The
system will chime to confirm that the new suite has been
accepted. The system will then automatically revert to the
Programming Menu.
28 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
Enter the current time as a 6 digit number; Hour, Hour, Enter Service Timer One (Reminder) date as a 6 digit
Minute, Minute, Second, Second using 24 hour format number; Day, Day, Month, Month, Year, Year (e.g. to
(e.g. to program 7 minutes and 3 seconds past 2pm program the 1st of April 1999 enter !%!'""). The
(14:07:03) enter %'!*!$). The display will indicate display will indicate as each digit of the new date is
as each digit of the new time is entered. Press ,. entered. Press ,. The system will chime to confirm
The system will chime to confirm the new time has been the new date has been accepted. The system will then
accepted. The system will then automatically revert to the automatically revert to the Programming.
Programming Menu.
Programming Service Timer Two &#
Programming the Service Timers &* - &" From the Programming Menu, enter &#. The display will
+, &) It is essential to program the current date (&() and
time ( ) for correct operation of the service timers.
look like this.
Zones
Unset G"#Q$+"(CA#(1((;
1 2 3 4 5 6 7 8
Tamper M-0Y-0Y-0
Programming the service timers (&*, &#,
&") is prevented unless the current date (&() Enter Service Timer Two (Nuisance) date as a 6 digit
has first been programmed. number; Day, Day, Month, Month, Year, Year (e.g. to
program the 25th of December 2000 enter
The user can turn off chime globally or on individual
&(%&!! ). The display will indicate as each digit of
zones but where still selected it will remain at high
level until reprogrammed by an Engineer. the new date is entered. Press ,. The system will
chime to confirm the new date has been accepted. The
system will then automatically revert to the Programming
-,Disclaimer:
It is the responsibility of the Installer to obtain prior
Menu.
Any one, any two, or all three timers can be programmed for Enter Service Timer Three (Lockout) date as a 6 digit
the same or different dates. To disable a service timer simply number; Day, Day, Month, Month, Year, Year (e.g. to
program an invalid or expired date. Expired service timers are
program the 1st of January 2001 enter !%!%!%).
automatically cleared when an Engineer code is entered.
The display will indicate as each digit of the new date is
entered. Press ,. The system will chime to confirm
Service Timer One - Reminder the new date has been accepted. The system will then
Service Timer One is designed to be used as a reminder. automatically revert to the Programming Menu.
When it expires it turns on high level chime on all eight
zones the first time the panel is set/unset.
Service Timer Two - Nuisance
Service Timer Two is designed to be used as a nuisance.
When it expires it turns on high level chime on all eight
zones every time the panel is set/unset.
Service Timer Three - Lockout
Service Timer Three is designed to be used as a lockout.
When it expires it will turn chime off and the panel will require
an Engineer Reset (see Option 1 page 22 for details on
Engineer Reset).
INS045 29
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
Programming System Timers $% - $" The Seven Event Basic Log '! - '*
The system has the following eight time delays and one The control panel has a Seven Event Basic Log which stores
test time which are all programmable: the last 7 alarm activations. The zone that caused the initial
alarm activation will flash, and any subsequently opened
No. Time Delay zones will also be shown (not flashing).
%+ Full Set Exit Time (seconds) The Control Panel also incorporates a time and date
&+ Part Set Exit Time (seconds) stamped, non-volatile, 250 Event Extended Log which can
$+ Full Set Entry Time (seconds) neither be erased nor altered. The 250 Event Extended Log
'+ Part Set Entry Time (seconds) can only be accessed using an LCD keypad or an interface
available from Texecom.
(+ Bell Cut Off Time (minutes)
)+ Part Set Error Tone Suspension Time (seconds)
*+ Bell Delay Time (minutes)
+, The date (see page 28) and time (see page 29) must
be programmed for the 250 Event Extended Log to
#+ Confirmation Time (minutes) function correctly.
"+ Zone Soak Test Time (days)
Clearing the Seven Event Basic Log '!
To program any of the above, from the Programming
Menu, press $ followed by the corresponding time From the Programming Menu, enter '!. The display will
delay number (e.g. for the Part Set Entry Time, enter look like this.
$'). The display will look like this. Zones
1 2 3 4 5 6 7 8 Unset 4,"&#(Z&'$+(I5=;
Zones
Tamper ?#"''(T?<:UV
1 2 3 4 5 6 7 8 Unset ?&#%(G"%()9%#D(;
Tamper MN-(G"+596'
Press ,. The system will chime to confirm that the
Enter the desired time as a two digit number (e.g. for 5 Seven Event Basic Log has been erased. The system will
seconds enter !(). The display will indicate as each digit then automatically revert to the Programming Menu.
is entered. Press ,. The system will chime to
confirm the new time has been accepted. The system will
automatically revert to the Programming Menu and all the
Displaying the Seven Event Basic Log '% - '*
zone lights will illuminate. From the Programming Menu, press ' followed by the
number corresponding to the desired event, % being
30 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
Programming the Suites '# - (" +, Soak Test is not appropriate for Entry/Exit, Push to
The system has a Full Set Suite, four Part Set Suites, a Set, or Keyswitch Zone Types and these zones will
Chime Suite, a Cleaner Suite, a Double Knock Suite, a still be monitored as normal even if they are included
Manual Omit Suite, a Zone Invert Suite, a Zone Disable Suite in the Soak Test Suite.
and a Zone Soak Test Suite all of which are programmable. Zones which fail Soak Test will be automatically added
24 Hour zones (Fire, PA and Tamper), Keyswitch zones to the Manual Omit Suite (see page 32) which should
and Push to Set zones should be monitored constantly and be checked after a Soak Test failure.
should NOT be omitted by the Full or Part Set Suites or the When the Soak Test Suite is programmed the Soak
Cleaner Suite. Test Time is started therefore this should be
programmed first (see page 30).
Programming the Zone Disable Suite '# Zones that have failed Soak Test will be cleared
when the Soak Test Suite is programmed.
The Zone Disable Suite defines the zones that are not
monitored. Disabled zones cannot cause either alarm or If a Soak Test zone activates all subsequent zone activations
EOL tamper. A zone could be disabled: will be logged as well. For example, zones 5, 6, 7 & 8 are on
Soak Test. Zones 7 & 8 activate and are logged (zone
• If it was not being used.
indicator On). The user then returns via Zone 1, Zone 2 &
• While waiting for a faulty detector to be replaced. Zone 3. These zones will all be logged as well but while Zone
2 & 3 indicators will be On, Zone 1 indicator will be Flashing
From the Programming Menu, enter '#. The zones as this was the first non Soak Test zone to be activated. It is
currently included in the Zone Disable Suite will indicate therefore recommended that the 250 Event Extended Log is
(zones not included will remain off). always checked in the event of a Soak Test failure.
Zones
1 2 3 4 5 6 7 8 Unset B59"(>$'&[,"(((;
Tamper B59"'(M(33333333
Programming the Full Set Suite (!
Press the appropriate numbered button(s) of the
The Full Set Suite defines the zones that will be
zone(s) to be included or excluded. Press ,. The automatically included and excluded (omitted) when the
system will chime to confirm that the new Zone Disable system is full set.
Suite has been accepted. The system will then
automatically revert to the Programming Menu. From the Programming Menu, enter (!. The zones
currently active in full set will indicate (the omitted zones
+, If a zone is disabled in this suite it will be necessary
to enter the suite again to re-enable it.
will remain off).
Zones
1 2 3 4 5 6 7 8 Unset \J,,(G"%(GJ$%"(;
Tamper B59"'(M(01N]^.OP
Programming the Zone Soak Test Suite '"
Press the appropriate numbered button(s) of the
The Zone Soak Test Suite defines the zones that are on zone(s) to be included or excluded (omitted). Press
Soak Test. ,. The system will chime to confirm that the new Full
Soak Test is used to prevent false alarms for a set period after Set Suite has been accepted. The system will then
a new installation or when a detector has been replaced. If a automatically revert to the Programming Menu.
zone on Soak Test activates it will not cause alarm or activate
the communicator interface but it will still be logged. Programming the Part Set Suites (% - ('
Afterwards the zone will have a standing fault and will need to
be omitted before the system can be set. After the Soak Test A Part Set Suite defines the zones that will be automatically
Time (see page 30) zones that have not activated will be included and excluded (omitted) when the system is part set.
automatically removed from the Soak Test Suite. From the Programming Menu, press ( followed by the
From the Programming Menu, enter '". The zones suite number %, &, $, or ' (e.g. to program Part Set
currently included in the Zone Soak Test Suite will indicate Suite 2, enter (&). The zones currently active in the
(zones not included will remain off). selected part set will indicate (the omitted zones will remain
off).
Zones
1 2 3 4 5 6 7 8 Unset B59"(G5&R(C"'%(; Zones
Unset ?&#%(G"%(GJ$%"0;
Tamper B59"'(M(33333333 1 2 3 4 5 6 7 8
Tamper B59"'(M(01N]333P
Press the appropriate numbered button(s) of the Press the appropriate numbered button(s) of the
zone(s) to be included or excluded. Press ,. The zone(s) to be included or excluded (omitted). Press
system will chime to confirm that the new Zone Soak Test
Suite has been accepted. The system will then
,. The system will chime to confirm that the new Part
Set Suite has been accepted. The system will then
automatically revert to the Programming Menu. automatically revert to the Programming Menu.
INS045 31
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
Press the appropriate numbered button(s) of the Double knock should NOT be used for Fire, Panic, or
zone(s) to be included or excluded. Press ,. The Tamper zones.
system will chime to confirm that the new Chime Suite has
been accepted. The system will then automatically revert to Programming the Manual Omit Suite (#
the Programming Menu.
The Manual Omit Suite defines the zones that may be
+, For a description of how to turn Chime on and off
see the User Guide.
manually omitted by the user.
From the Programming Menu, enter (#. The zones
currently included in the Manual Omit Suite will indicate
Programming the Cleaner Suite () (zones not included will remain off).
The Cleaner Suite defines the zones that will be 1 2 3
Zones
4 5 6 7 8 Unset ?"#A$%(:A$%((((;
armed/disarmed when the panel is set/unset with a Cleaner Tamper B59"'(M(31N]^.OP
code.
Press the appropriate numbered button(s) of the
From the Programming Menu, enter (). The zones zone(s) to be included or excluded. Press ,. The
currently included in the Cleaner Suite will indicate (zones system will chime to confirm that the new Manual Omit
not included will remain off). Suite has been accepted. The system will then
Zones
automatically revert to the Programming Menu.
1 2 3 4 5 6 7 8 Unset 4,"&9"#(GJ$%"((;
Tamper B59"'(M(33333333
32 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
1 2 3 4...7 8
Personal Attack
User Number
Entering a PA code will cause an immediate alarm,
Each user is identified by the alarm system as User 1 sounding both the internal and external sounders.
through to User 8.
Duress
A Duress code behaves exactly as a User code (Level 1)
Access Code but will in addition activate the Duress channel on the
Each user has a programmable 4 digit Personal communicator interface to secretly summon assistance.
Identification Number (PIN) which the user enters in order Master User
to operate the alarm system.
A Master User may set, unset, silence an alarm and reset the
system. In addition a Master can test the system outputs
Access Level (see page 24), perform a Walk Test (see page 24) and view
the Basic Log (see page 30). A Master User can also assign
Each user has a programmable Access Level that
new Customer Access code and Access Levels.
determines how the alarm system responds and which of
the system facilities the user can access. Cleaner
Each Access Level has an associated number (1 – 8) which If the system is full set or part set then a Cleaner code will
is used when programming the Access Level of a user. automatically omit the Cleaner Suite zones (see page 32)
without affecting the other zones. In addition pressing a key
There are eight possible user Access Levels: will NOT cause the system to start entry mode. On leaving
User the cleaner should enter their Access code and press either
INS045 33
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
Access
Programming Access Codes )% - )#
Access Access Can be From the Programming Menu, enter ) followed by the
Level
Level Type Programmed by
Number User Number % to # i.e. for User 5, enter )(. The
display will look like this.
User %+ Customer Master '$&%
Engineer &+ Installer Boss %&$' Zones
1 2 3 4 5 6 7 8 Unset
Tamper
?KL(^2(_'"#(^((;
LJ,,(M(````
PA (Panic) $+ Customer Master '$&%
Duress '+ Customer Master '$&% Enter the new Access code ----. The display will
Master User (+ Customer Master '$&% indicate as each digit of the new code is entered. Press
Cleaner )+ Customer Master '$&% ,, the system will chime to confirm the new code
Customer Master '$&% has been accepted. The system will then automatically
Null *+ Installer Boss %&$' revert to the Programming Menu.
Boss
Engineer
#+ Installer Boss %&$' Programming Access Levels *% - *#
From the Programming Menu, enter * followed by the
User Number % to # i.e. for User 5, enter *(. The
+, The Master User can only assign Customer Access
Types and the Boss Engineer can only assign
display will show the Access Level currently selected.
Installer Access Types. Zones
1 2 3 4 5 6 7 8 Unset _^2(_'"#(^(((((;
Tamper CD8"(MLJ,,
34 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
INS045 35
Programming the Control Panel Veritas R8 Plus & Excel Installation Manual
From the Programming Menu, enter #%. The zone lights Event Meaning
indicating the current status of the eight channels will
illuminate. Code: ???????? Access code entered for user ????????
Zones
Full Set The alarm system has been full set
1 2 3 4 5 6 7 8 Unset C"'%(45AA(:Y?'(;
Tamper :J%8J%'(33333333 Part Set #? The system has been part set using suite #?
System Unset The alarm system has been unset
Press the appropriate numbered button(s) to toggle
one or more of the outputs. Press . to return to Zones Omitted Zones have been manually omitted
the Programming Menu. All the zone lights will illuminate. System Reset The alarm system has been reset
Code: Anti-Code The alarm system has been reset using the
anti-code
The 250 Event Extended Log !"
Keypad Entry Entry mode started using the keypad
The Control Panel incorporates a time and date stamped, Zone ? Open Zone ? has been activated
non-volatile, 250 Event Extended Log which can neither be
Zone ? Shut Zone ? has been restored
erased nor altered.
EOL Tamper There has been an EOL zone tamper
+, The 250 Event Extended Log can only be accessed
using an LCD keypad or a computer running Veritas
EOL Restore The EOL zone tamper has been restored
Alarm There has been an alarm activation
UDL software.
Keypad PA A keypad PA alarm has been activated
The date (see page 28) and time (see page 29) must
RKP PA Restore The keypad PA alarm has been restored
be programmed for the 250 Event Extended Log to
function correctly. Lid Tamper The panel lid has been removed
Lid Restore The panel lid tamper has been restored
Viewing the Extended Log !" Bell/Gbl Tamper The bell/global tamper has been activated
Bell/Gbl Restore The bell/global tamper has been restored
From the Programming Menu, enter !" followed
Code PIN Tamper Too many invalid key presses has caused a
by ). The display will look like this. tamper alarm
)Q"9%(a--0 Code PIN Restore The code tamper alarm has been restored
RKP Online A keypad has been recognised by the
_'"#(456"(0((((; control panel
00(78#((012--3--
RKP Offline A keypad has stopped communicating with
Use the ' key to scroll up and down through the the control panel
other events. Mains LO The AC mains has failed
+,
+
Wherever a M symbol appears on the display, press
to display more information i.e. zone types etc.
Mains OK
Volts LO
The AC mains has been restored
The battery voltage is low
Volts OK The battery voltage is ok
When completed, press ,. The system will return to Line Cut The phone line has been removed from the
the Programming Menu. communicator
Line Restore The phone line has been restored
User Programming User Programming mode was selected
Eng. Programming Installer Programming mode was selected
Date Changed The control panel date has been changed
Time Changed The control panel time has been changed
SSD Change Site specific data has been changed
Non-SSD Change Non site specific data has been changed
Defaults Loaded The factory default values have been loaded
Sys Check = 5 Factory set parameters
Unknown No event
36 INS045
Veritas R8 Plus & Excel Installation Manual Programming the Control Panel
From the Programming Menu, enter !#. The From the Programming Menu, enter !&. The
display will look like this. display will look like this.
B:L)(0(C)bC((((; Z#5&6+&'%(C"*%(;
MB59"(0 T?<:UV(%5(G"96
Select characters by pressing the corresponding key Press ). The system will chime to confirm that the text
the appropriate number of times (to select a character on has been broadcast to the other keypads. The system will
the same key, press ' to move the cursor along). Press then automatically revert to the Programming Menu.
). The system will chime to confirm that the Text has
been accepted. The system will then automatically revert to Default Text !!
the Programming Menu.
This option will default all of the programmable text values.
From the Programming Menu, enter !!. The
display will look like this.
>"S&J,%(C"*%(((;
T?<:UV(%5(I5&6
INS045 37
Specifications Veritas R8 Plus & Excel Installation Manual
5. Specifications
Control Panel Environmental
Operating Temperature -10°C (+14°F) to
Power supply +50°C (+122°F)
Mains Supply Voltage: 230VAC (±10%) Storage Temperature -20°C (-4°F) to
115VAC (±10%) +60°C (+140°F)
Maximum Total Current Rating Maximum Humidity 95% non-condensing
230VAC/115VAC (±5%) 1ADC EMC Environment Residential, Commercial,
Ripple <5% Light Industrial & Industrial
Rechargeable Battery Type 12V Sealed Lead Gel Acid
Keypads
Electrical Electrical
Current Consumption Operating Voltage 10V - 13.7VDC
Quiescent <50mA Current Consumption <85mA
In Alarm <150mA Volume Dual Level
Fuses Cable 4-Core, ≤100m, Star, Daisy
FTB Mains 230V 125mA, 250V, 20mm Chain or any combination
FTB Mains 115V 250mA, 250V, 20mm
F1 - Battery 1 Amp, 250V, 20mm
F2 - Bell 1 Amp, 250V, 20mm Safety Notes
F3 - Auxiliary 500mA, 250V, 20mm
F4 - Network 500mA, 250V, 20mm - Mains voltage is factory set and not adjustable - see
label on transformer.
F5 - Power Supply Output 1.6 Amp, 250V, 20mm
Removal of the transformer is prohibited and will
Rechargeable Battery Capacity 12V 1.2Ah to 7Ah
invalidate the warranty.
Number Of Zones 8
Only use batteries of the specified type.
Zones Types N/C, N/O or EOL
Dispose of used batteries safely according to the
EOL Loop Threshold manufacturer's instructions.
Low (closed) Resistance 10kΩ, 1% Locate the battery inside the panel in the space
High (open) Resistance 33kΩ, 1% (or 10kΩ+22kΩ) provided.
Tamper Loop Threshold This equipment is designed for dry indoor use only.
Minimum Open Resistance 110kΩ
Maximum Closed Resistance When replacing a fuse always observe the specified rating
20kΩ
and type - failure to do so is dangerous and will invalidate
Network the warranty. Fuses should comply with IEC 127.
+ +12V Power
The press-seal bag must NOT be stored inside the panel.
- 0V Power
T Transmitted Data
Warranty
R Received Data
Types Of Remote Keypads LED or 32 Character LCD All Texecom products are designed for reliable, trouble-
Number Of Remote Keypads Up to six (mixed) free operation. Quality is carefully monitored by extensive
computerised testing. As a result the Control Panel is
Communicator Outputs 1 to 8 100mA switched to 0V
covered by a two year warranty against defects in material
Internal Speaker or workmanship (details on request).
Minimum Load 16Ω
As the Control Panel is not a complete alarm system but
Low Volume Adjustable
only a part thereof, Texecom cannot accept responsibility
High Volume >90dB at 1m
or liability for any damages whatsoever based on a claim
that the Control Panel failed to function correctly. Due to
Physical our policy of continuous improvement Texecom reserve
the right to change specification without prior notice.
Dimensions 282mm x 225mm x 80mm
The Veritas R8Plus/Veritas Excel, Veritas R8 Keypad, and
Battery Compartment Up to one 12V 7Ah battery Veritas Excel Keypad are protected by UK & International
Registered Design. Registered Design Numbers: 2041830,
2047440 and 2089016
Veritas is a trademark of Texecom Ltd.
38 INS045
Veritas R8 Plus & Excel Installation Manual Specifications
INS045 39
Installation Records Veritas R8 Plus & Excel Installation Manual
6. Installation Records
Installation Details
Installation Engineer:
Installation Company:
Address:
Telephone:
Installation Date:
Low High
Zone Zone Type Area Protected Loop Resistance Loop Resistance
(Clear) (Fault)
1
2
3
4
5
6
7
8
Date/Time Reason for Site Visit Work Carried Out Name of Engineer
-,The User Guide contains ESSENTIAL SAFETY INFORMATION and MUST be given to the user.
40 INS045
Veritas R8 Plus & Excel Installation Manual Installation Records
+, Customer codes can only be programmed when the Programming Menu is accessed using a Master User code.
Installer codes can only be programmed when the Programming Menu is accessed using a Boss Engineer code.
INS045 41
Installation Records Veritas R8 Plus & Excel Installation Manual
Notes
42 INS045
Veritas R8 Plus & Excel Installation Manual Registered Installer Application Form
Name: Position:
Company: Fax:
Tel: E-Mail:
Mobile: Web Site:
Address:
POSTCODE:
How many of the following Texecom products do you currently install each month?
Detectors:
Control panels:
Batteries:
Cameras:
Accessories:
INS045 43
There’s only ONE way to get
TECHNICAL SUPPORT...
REGISTER!
And receive the following exclusive benefits:
Texecom Limited, Bradwood Court, St. Crispin Way, Haslingden, Lancashire BB4 4PW, England.
Technical Support:
Tel: +44 (0)1706 234833
Tel: +44 (0)1706 234811
Fax: +44 (0)1706 213187
© TEXECOM LTD. 2000 - 2003
INS045-10