Lec7 Distributed Generator Protection-1
Lec7 Distributed Generator Protection-1
e-mail: [email protected]
DG Protection – Content
Distributed Generation (DG) overview
Main characteristics
Importance of DG and its impact on the existing system.
Distributed Generation Protection
Overcurrent protection
Earth fault protection
Neutral Voltage Displacement (NVD) Protection
Islanding and Loss-Of-Mains (LOM) protection
Undervoltage and overvoltage protection
Underfrequency and overfrequency protection
Differential protection of the stator winding
Auto-reclose and check synchronism relay
Reverse power protection
Unbalanced loading and negative phase sequence protection
Loss of excitation protection
Recommended Reading
Nick Jenkins, Ron Allan, Peter Crossley, Daniel Kirschen and Goran Strbac,
“Embedded Generation”, The IET, University Press, Cambridge, 2000.
(Chapter 6)
“Network Protection & Automation Guide”, ALSTOM, 1st Edition, July 2002.
Can be requested from: http://www.alstom.com/grid/npagrequest/
(Chapter 17)
Main Characteristics of DG
Not centrally planned
Not centrally dispatched
Normally smaller than 50-100MW
Usually connected to distribution system
Distributed Generation Basics
Technologies
Small and Large scale combined heat and power units
Energy from waste units
Wind Farms
Tidal and wave energy units
Stand-by generators (diesel)
33kV
132kV
~ 11kV
0.4kV
0.4kV
0.4kV
33kV
132kV
~ 11kV
0.4kV
0.4kV
G G
G 0.4kV
http://www.nationalgrid.com/uk/Electricity/Codes/gridcode/associateddocs/
Distributed Generation Protection Guidelines
DG protection has to achieve the following objectives:
To inhibit connection of the generating equipment to the supply
unless all phases are available, energised and operating within
the specified protection settings
(check sync relay)
G59/1 G59/2
(Small LV connected DG)
Setting Time delay Setting Time delay
UV stage 1 –10% Vn 0.5 s –13% Vn 2.5 s
UV stage 2 – – –20% Vn 0.5 s
OV stage 1 +10% Vn 0.5 s +10% Vn 1.0 s
OV stage 2 – – +15% Vn 0.5 s
UF stage 1 47.0 Hz 0.5 s 47.5 Hz 20 s
UF stage 2 – – 47.0 Hz 0.5 s
OF stage 1 50.5 Hz 0.5 s 51.5 Hz 90 s
OF stage 2 – – 52 Hz 0.5 s
Settings have been revised to reflect the need for Distributed Generation to remain
connected during certain transient system events
Elements of typical DG protection
NVD
3OCI 3DOCI EI
NVD
Interface Protection
5 limb VT DNO’s Equipment
Customer’s Equipment
Interface Protection
LV Incoming CB
2ST 2ST
LOM SYNC
CB Aux. OF UF OV UV
Trip Contact
3OCI
Trip Close
Busbar CB Customer’s LV System
Trip
Generator CB
OF OV
3OCI 3OCI 3OCI RP SYNC
UF UV
Generating
Unit
Customer’s Non- Customer’s
essential Load Essential Load
EI
Neutral Earthing
(as required)
G59/2 – list of symbols
OV Single Stage Over Voltage &
BEF Balanced Earth Fault
UV Single Stage Under Voltage
Ph
CC Circulating Current Phase Unbalance
Unbal
3 Pole Overcurrent
3OCI
(IDMT)
Is Is
K Is K Is G
Vs Voltage Vs2 Vs1 Voltage
level level
Voltage controlled overcurrent protection – 51V
unearthed
Earthing practice
Petersen Coil (resonant earthed system)
Not extensively used in UK - extensively used in part of Europe
Inductor sized so that XL=XC (capacitance of lines) during earth fault
𝐈𝐅 = 𝐈𝐂 + 𝐈𝐋 (𝐈𝐂 , 𝐈𝐋 are 1800 out of phase, therefore 𝐈𝐅 very low)
Arc “self extinguishes” – protection operation not required for
many transient faults
IL IC
http://www.electrotechnik.net/2009/02/petersen-coils-principle-and.html
http://www.ipst.org/TechPapers/2005/IPST05_Paper107.pdf
Inductor earthed transformer – Petersen Coil
𝐈𝐂
𝐕𝟏
𝐈𝟎 ≈ 0
𝐈𝐋
𝐈𝐋
𝐈𝐂 𝐈𝐂
𝟐 𝟐
Earth Fault Overcurrent Protection
Resistor earthed distributed generator
V
CT mounted on a neutral-earth conductor
drives an overcurrent element
51N
If
Time delayed element 51N can be made
more sensitive and can cover up to 95% R
of the stator winding
The tripping time of the time delayed element has to be coordinated with the
network protection
Example – Earthing Transformer resistance
50N
Solution
51N
Earth Fault Overcurrent Protection
Generator connected to the utility network via transformer with
earthed star connected winding on the utility side
I1A
I1B
G I1C
50 50 50
51 51 51
50N
51N
The outputs from the line CTs are residually connected to an earth fault
overcurrent relay.
Both instantaneous 50N and time delayed 51N elements can be included to
provide fast clearance of close up faults and backup for the network protection
G
Ifg 0 Ifn
G
Ifg 0 Ifn
Ifg
1-phase fault
prefault
Fault cleared by
the utility protection
Sequence components
Taking Phase A as a reference:
V0 Va Vb Vc
1
Va V0 V1 V2 3
Vb V0 a 2V1 aV2 V1 Va aVb a 2Vc
1
Vc V0 aV1 a 2V2 3
V2 Va a 2Vb aVc
1
3
V1a
Va
V2b V0a
Vc V1c
V2c
V0b
V0c
V2a
Vb
V1b
[1] Stephen Chapman, “Electric Machinery and Power System Fundamentals”, Chapter 13, McGraw Hill
[2] J.D. Glover, M.S. Sarma, T.J. Overbye, “Power System Analysis and Design”, Chapter 8,9, Cengage Learning
[3] C.L. Fortescue, “Method of symmetrical coordinates applied to the solution of polyphase networks.”, Transactions
of the AIEE 37 (1918), pp. 1027–1140.
Sequence components in symmetrical 3 phase
systems
Va Z s Zm Zm I a
V Z Zs Z m I b
b m
Vc Z m Zm Z s I c
1 1 1
V ZI 1
A 1 a a 2
AV A Z I 3
1 a 2 a
AV A Z A 1 AI
Vseq Z seq I seq Z s 2Z m 0 0
Z seq A Z A 1 0 Zs Zm 0
0 0 Z s Z m
All off diagonal elements become zero
System can be solved as 3 independent single phase equations
Generator connected to the utility network via transformer
with delta connected winding on the utility side
Earth fault
Earth fault
Fault cleared by
the utility protection
Generator connected to the utility network via transformer
with delta connected winding on the utility side
Fault cleared by
V0 the utility protection
1-phase fault
prefault
Neutral Voltage Displacement (NVD) Protection