PV System Sizing Worksheets: Appendix A
PV System Sizing Worksheets: Appendix A
PV System Sizing Worksheets: Appendix A
Table A.1 - Calculate AC Loads. If there are no AC Loads, skip to Step 5, Table A.2.
2. Convert AC Watt-Hours/week into DC Watt-hours/week. Multiply Total from Table A.1 by 1.2 to correct for
inverter loss.__________
4. Divide Line 2 by Line 3. This is Total amp-hours per week used by AC loads.__________
Appendix A 109
Table A.2 – Calculate DC Loads
Description of DC Loads Watts X Hrs/Wk = Wh/Wk
7. Total amp hours per week used by DC loads. Divide Total from Table A.2 by Line 6.__________
8. Enter Total amp hours per week used by AC loads from Line 4. __________
9. Total amp hours per week used by all loads. Add Lines 7 and 8. __________
10. Average amp hours per day. Divide Line 9 by 7 days. __________
12. Enter the maximum number of consecutive cloudy weather days expected in your area, or the number of days
of autonomy you would like your system to support.__________
110 Appendix A
13. Multiply the amp-hour requirement by the number of days of autonomy (Line 11 x Line 12). This is the amount
of amp-hours your system will need to store.__________
14. Enter the depth of discharge for the battery you have chosen. This provides a safety factor to help avoid
over-draining the battery bank. (For example, if the discharge limit is 20%, use 0.2.) This number should not
exceed 0.8. __________
15. Divide the amp-hours of storage needed (Line 13) by the depth of discharge limit (Line 14). __________
16. Select the multiplier from Table A.3 below that corresponds to the average winter-time ambient temperature
your battery bank will experience. __________
Table A.3: Battery Ambient
17. Total battery capacity needed: Multiply the amp-hours (Line 15) by Temperature Multiplier
Line 16. This number ensures that your battery bank will have enough o
F o
C Factor
capacity to overcome cold weather affects. __________
80oF 26.7oC 1.00
18. Enter the amp-hour rating for the battery you have chosen________ 70oF 21.2oC 1.04
60oF 15.6oC 1.11
19. Number of batteries wired in parallel: Divide the total battery
o o
capacity (Line 17) by the battery amp-hour rating and round off to the 50 F 10.0 C 1.19
next highest number.__________
40oF 4.4oC 1.30
o o
20. Number of batteries wired in series: Divide the nominal system 30 F -1.1 C 1.40
voltage (12V or 24V) by the battery voltage and round off to the next 20oF -6.7oC 1.59
highest number._________
21. Total number of batteries required: Multiply the number of batteries in parallel by the number of batteries
in series. __________
22. Total average amp-hours per day (from the Load sizing worksheet, Line 10). __________
23. Multiply Line 22 by 1.2 to compensate for efficiency loss from battery charge/ discharge. __________
24. Average Sun Hours in your area (see Appendix B). __________
25. Total solar array amps required: Divide Line 23 by Line 24.__________
26. Optimum or peak amps of solar modules used. See module specifications.__________
27. To determine total number of solar modules in Table A.4: Number of Modules Needed to Provide
parallel required, divide Line 25 by Line 26, then DC Battery Voltage
round off to the next highest whole DC Battery Voltage # of Modules in Each Series
number.__________ String
12 1
28. Number of modules needed to provide DC
battery voltage (see Table A.4). ___________ 24 2
48 4
Appendix A 111
29. To determine total number of solar modules required, multiply Line 27 by Line 28. ___________
Worksheet Summary
Load, average amp-hours per day (Line 10) __________
Battery capacity required (Line 17) _____________
Capacity and voltage of batteries selected (Line 18) ___________
Total number of batteries required (Line 21)__________
Peak amps of solar modules (Line 26) ____________
Total number of solar modules required (Line 29) __________
Adapted from Creative Energy Technologies ( www.cetsolar.com ) and the Energy Efficiency and Renewable
Energy Clearinghouse ( www.eere.energy.gov/consumerinfo/factsheets/ec7.html )
PV System Sizing Worksheets adapted with permission from Creative Energy Technologies (www.cetsolar.com).
112 Appendix A