600

CONTROLLER

Main features
• Universal input configurable from faceplate
• Accuracy better than 0.2% f.s. under
nominal conditions
• Control output: relay, logic, Triac ,
continuous, digital insulated
Main applications • Hot/cold function with selection of cooling
• Extrusion lines fluid
• Injection presses for plastics • 3 alarms with completely configurable
• Heat punches function
• Analog retransmission output
• Presses for rubber
• Isolated digital input with configurable
• Packaging machines function
• Packing machines • Auxiliary input for CT (TA) (50mAac)
• Polymerization and synthetic • Heater break or probe short-circuit alarm
fiber plants • Self-tuning, Auto-tuning, Soft-start, bump-
• Food processing pants less
• Die-casting plants Man/Auto function
• Cooling plants • Double set, set ramp, timed output function
• Optically isolated RS485 serial line.
• Climatic cells and test benches
Protocol:
• Dryers for ceramics and GEFRAN CENCAL or MODBUS RTU
construction parts • Self-diagnosis
• Ovens • Rapid configuration from PC with Winstrum
• Painting plants packet

PROFILE rable from the faceplate keys. TECHNICAL DATA


Microprocessor controller, format 48x48 In addition to control and alarm outputs, you
(1/16 DIN) manufactured using SMT. can have outputs that repeat the state of the Inputs
Provides a complete operator interface pro- digital or retransmission input by process Accuracy 0,2% f.s. ±1digit.
tected by a Lexan membrane that ensures variable, setpoint, drift, alarm limits and val- Sampling time 120msec.
level IP65 faceplate protection. ues acquired from serial line.
It has 4 keys, two green LED displays, each Another output (at 10 or 24Vdc, 30mA max.) TC - Thermocouple
with 4 digits, 4 red signal LED’s for the 4 logic is available to power external transmitters. J 0...1000°C / 32...1832°F
or relay outputs, and 3 other programmable The serial communication option (available in K 0...1300°C / 32...2372°F
LED’s to signal the various operational states RS485 standard) allows connection to super- R 0...1750°C / 32...3182°F
of the instrument. vision systems and PLCs with two protocols: S 0...1750°C / 32...3182°F
The main input for process variable is univer- GEFRAN CENCAL and MODBUS RTU. T -200...400°C / -328...752°F
sal, and many types of signals can be con- Instrument programming is facilitated by B 44...1800°C / 111...3272°F
nected: thermocouples, resistance thermom- grouping parameters in functional blocks E -100...750°C / -148...1382°F
eters, thermistors, normalized linear inputs, (CFG for control parameters, Inp for inputs, N 0...1300°C / 32...2372°F
all with possibility of custom linearization Out for outputs, etc.). L-GOST 0...600°C / 32...1112°F
The instrument can also select display U -200...400°C / -328...752°F
using the faceplate keys.
parameters based on hardware configura- G 0...2300°C / 32...4172°F
The type of input is selected from the face-
tion, automatically masking irrelevant param- D 0...2300°C / 32...4172°F
plate keys; no external shunts are required.
eters. C 0...2300°C / 32...4172°F
A second auxiliary analog input from the cur-
The instrument is supplied with an “EASY” (NI-Ni18Mo) 0...1100°C / 32...2012°F
rent transformer is also available.
configuration with just a few parameters (only custom -1999...9999
With the isolated digital input you can select:
one of the two presettable setpoints, select those for the model ordered and essential for
RTD 2/3 wires
Manual-Automatic mode, reset the alarms controller operation).
PT100 -200...850°C / -328...1562°F
memory, or enable the hold function. In this way, you just have to set the setpoint
JPT100 -200...600°C / -328...1112°F
The instrument can have up to 4 outputs: and alarm, and launch selftuning from the
relay (5A at 250Vac/30Vdc cosϕ = 1), logic button.
PTC
24V ±10% (10V min at 20mA), digital insu- The 600 does all the rest. 990Ω, 25°C -55...120°C / -67...248°F
lated, triac. A PC programming kit is available for even
An analog output in voltage or current is also simpler configuration, composed of a cable NTC
available. and a guided program for Windows environ- 1KΩ, 25°C -10...70°C / 14...158°F
The function of each output is freely configu- ment (see data sheet code GF_eXpress).
DC - Linear Logic Ambient Condition
With scale settable from: (indicated in code with D) Working temperature range: 0...50°C
-1999...9999 24Vdc ±10% (10V min at 20mA) Storage temperature range: -20...70°C
0...60mV / 12...60mV Humidity: 20...85%Ur non condensing
0...10V / 2...10V Digital insulated (indicated in code with M)
0...5V / 1...5V optoinsulated MOS output 1500Vrms Control
0...1V / 0,2...1V equivalent to NO contact On/Off, P, PD, PID for heating and cool-
0...20mA / 4...20mA Vmax 40Vac/Vdc Imax 100mA ing, with parameters settable from keys.
Input impedance: Load ON max 0,8Ω Cooling setpoint relative to heating set-
Ri > 1MΩ for 60mV,1V point.
Triac • Manual reset -999...999 digit
Ri > 10KΩ for 5V, 10V
(indicated in code with T) • Power reset -100,0...100,0%
Ri = 50Ω for 20mA
20...240Vac ± 10%, 50/60Hz, 1A max. • Cycle time 0...200sec
32-segment custom linearization can be
I2t = 128A2sec. • Softstart 0,0...500,0 min
inserted. Leakage current 1,5mA max at 200Vac. For each action:
Auxiliary input • Proportional band 0,0...999,9% f.s.
(alternative to output out 3) Continuous • Integral time 0,0...99,99 min
Input for current transformer (indicated in code with C) • Derivative time 0,0...99,99 min
50mAac, 50/60Hz, Ri=10Ω 0...10V Rload ≥ 250KΩ • Max power limit 0,0...100,0%
0/4...20mA Rload ≤ 500Ω
Digital input for heating/cooling control output only. Alarms
Ri = 4,7KΩ (24V, 5mA) insulation 1500V • 3 alarms settable as absolute, deviation,
or no-voltage contact. Analog retransmission symmetrical deviation to setpoint with
Function configurable for man/auto (indicated in code with W) direct or reverse function.
selection, local/remote (setpoint from 0...10V Rload ≥ 250KΩ • Alarm point can be set anywhere on
serial line, setpoint1/setpoint2; Set/reset 0/4...20mA Rload ≤ 500Ω max resolution selected scale
outputs, start/stop functions from tuning, 12 bit, useful for retransmission of variable. • Alarms can be masked with exclusion at
software on/off, reset alarms memory, power-on, with memory, with delayed trip
hold. Serial line • LBA alarm for setting control
Isolated 2/4 wires, RS422/485 interface • Hysteresis settable for each alarm
Outputs (1200, 2400, 4800, 9600, 19200 baud) • Alarm assigned to current input with dif-
4 configurable outputs: Prot.: GEFRAN CENCAL or MODBUS ferent operating modes.
• OUT1-OUT4: relay only
• OUT2: relay, logic, triac, digital insulated
Power supply Weight
• OUT3: relay, logic, digital insulated,
Standard: 100...240Vac ± 10% 160g in complete version
continuous or analog retransmission as
alternative to aux. input On request: 11...27Vac/dc ± 10%
Freely assignable to control functions and 50/60Hz, max. 10VA
single alarms in “OR” or “AND”. Protection by internal fuse not serviceable
Can be slaved to front panel key or aux. by user
digital input.
Transmitter Power supply
Relay 24V ±10% non-stabilized, 30mA
(indicated in code with R) 15V for transmitter, 30mA
With contacts: 5A at 250Vac/30Vdc, Short-circuit protection
cosj=1

FACEPLATE DESCRIPTION

A - Indication of process variable (PV),


green digits h. 10mm
B - Indication of set point (SV),
green digits h. 7mm H
C - “Function” key A
D - “Lower“ key
E - “Raise” key G B
F - Auto/Man selection
G - Function indicator, red LED
H - Indication of output states, red LED
F E D C

Faceplate protection IP65


DIMENSIONS

63

48 70

48

70

45

45

99

10

Dimensions: 48x48mm (1/16 DIN) depth 99mm

CONNECTION DIAGRAM

out 2 out 3 DIGITAL AUXILIARY


(MAIN) (al2) INPUT INPUT
50mA (CT) 4...20mA
out 1
(AL1)

pwr
SUPPLY S
TC Pt100 ptc lin inp lin inp LIN INP LIN INP
3-wires Pt100 Idc (20mA) vdc Transmitter Transmitter
2-wires 2-wires 3-wires
4-20mA

B
RS485 4-wires

SERIAL LINE
SERIAL LINE

Tx
A RS485

Rx out 4

• Maximum driving torque for screws: 0,5 Nm


• Minimum section of flexible or rigid stripped wire: 0,5 mm2
• Maximum section of flexible or rigid stripped wire: 1,5 mm2

! For correct installation, read the instructions and warnings in the instruction manual
ORDER CODE

The controller is available in 2 versions:

BASIC VERSION
Up to 3 output options; option 4 not available. Unit with 12 terminals rear socket.

600 R - - 0 -

OUTPUT 1 POWER SUPPLY


Relay R 0 11...27Vac/dc
1 100...240Vac
OUTPUT 2
Relay R
DIGITAL COMMUNICATION / OUTPUT 4
Logic D
0 None

UTPUT 3 / INPUT
None 0
Relay R
Logic D
Continuous 0...10V (0/4...20mA) C
Analog 0/4...20mA (0...10V) W
TA Input 50mAac H
Digital Input (24V) N

EXPANDABLE VERSION
Up to 4 output options. Unit with internal plug and complete rear socket.
With this version, option 4 can be added at a later stage.
For optional I/O boards, please see “Accessories” section.

600 R - - - -

OUTPUT 1 POWER SUPPLY


Relay R 0 11...27Vac/dc
1 100...240Vac
OUTPUT 2
Relay R
DIGITAL COMMUNICATION / OUTPUT 4
Logic D
E None
Triac (1A) T
2 RS485 (2 wires)
Digital insulated M R Relay output

OUTPUT 3 / INPUT
None 0
Relay R
Logic D
Continuous 0...10V (0/4...20mA) C
Analog 0/4...20mA (0...10V) W
TA Input 50mAac H
Digital Input (24V) N
Digital insulated M

Please, contact GEFRAN sales people for the codes availability.


For correct installation, follow the instructions contained in the manual.

GEFRAN spa reserves the right to make any aesthetic or functional change at any time and without prior notice

Conformity C/UL/US File no. E216851

The instrument conforms to the European Directives 2004/108/CE and 2006/95/CE with reference to the generic standards:
EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3 (emission in residential environment) - EN 61010-1 (safety)

GEFRAN spa via Sebina, 74 - 25050 Provaglio d’Iseo (BS)


Tel. 03098881 - fax 0309839063 - Internet: http://www.gefran.com DTS_600_11-2012_ENG