Example To Calculate Short Circuit Current For Circuit Breaker
Example To Calculate Short Circuit Current For Circuit Breaker
Example To Calculate Short Circuit Current For Circuit Breaker
About
Clients
Services
Blog
Contact
Previous Next
The purpose of this write up is to help the reader estimate the sExample before you
hire the PE to do the official calculation.
All electrical systems are susceptible to short circuits . The short circuit currents can
produce considerable thermal and mechanical stresses in electrical distribution equipment.
Therefore, it’s important to protect personnel and equipment by calculating short-circuit
currents during system upgrade and design. Because these calculations are life-safety
related, they’re mandated by 110.9 of the NEC.
In the example show in Fig 1 our goal is to find the irrupt rating for the two breakers (1600A
and 250A) and also find the withstand rating of the two panels (main and sub panel).
Fig (1)
I F.L = P / (1.73 * V L-L ) ; where P is the transformer power rating in VA, V L-L is the line
to line RMS voltage at the secondary side of the transformer
I F.L= 1,000,000/ 1.73*480= 1,202 A ; the I F.L is the full load current of the transformer
Now to find the short circuit rating of point 1 (i.e if we bolt all the three wires of the
secondary side of the transformer how much current we will see at that point)
I S.C. for 3 Ph= I F.L /Z% ; where Isc is the short circuit current , Z% is the transformer
impedance which is usually can be obtained from the local utility company
I S.C. 3 ph for point 1 = 1202 /0.05 = 24,506 A or 24.5 KA (this is the available short circuit
current at point 1)
The short circuit current at point 2 will be lower than point 1 due to the line impedance ( line
impedance for the cables will impose the current)
The calculation below will show the short circuit current at point 2
F = (1.73 * L* I S.C. 3 ph) / (C *n*V L-L) ; F for three phase fault ——–[1]
C= the conductor factor , value can be obtained from table (1) by locating the conductors
size in the proper configuration
n= the number of parallel runs
L= length in ft
Table (1)
These values are equal to one over the impedance per foot based upon resistance and reactance found in IEEE std. 241
F= (1.73 *50 *24,506)/(28,303*5*480)= 0.031206
I S.C. 3 ph for point 2= 24506* M= 24506*0.969738= 23,764 A or 23.7 KA (this is the available
short circuit current at point 2)
Its worth to mention is that the further the main panel from the transformer the lower is the short
circuit current but you will have bigger voltage drop due to the larger line impedance.
The calculation below will show the short circuit current at point 3 (similar to point 2
calculation)
I hope you find this example and the short circuit calculation useful. please let me know if
you have any questions
By Saad Thabit|January 29th, 2016|C value, F factor, short circuit current, short circuit current calculation|0
Comments
Leave A Comment
Pos t Comme nt
Meta
Log in
Entries RSS
Comments RSS
WordPress.org
?
Recent Comments
Categories
C value
cable weight
F factor
NEC 400.5
open circuit test
short circuit current
short circuit current calculation
short circuit test
tether weight
transformer
transformer losses
transformer model
transformer testing
Uncategorized
wire ampacity
wire weight