AC Voltage Controllers: AC To Ac Converters
AC Voltage Controllers: AC To Ac Converters
C H A P T E R 5
AC Voltage Controllers
AC to ac Converters
5.1 INTRODUCTION
An ac voltage controller is a converter that controls the voltage, current, and aver-
age power delivered to an ac load from an ac source. Electronic switches connect
and disconnect the source and the load at regular intervals. In a switching scheme
called phase control, switching takes place during every cycle of the source, in
effect removing some of the source waveform before it reaches the load. Another
type of control is integral-cycle control, whereby the source is connected and dis-
connected for several cycles at a time.
The phase-controlled ac voltage controller has several practical uses including
light-dimmer circuits and speed control of induction motors. The input voltage
source is ac, and the output is ac (although not sinusoidal), so the circuit is classi-
fied as an ac-ac converter.
S1
+ vsw −
io
+ +
S2
vs R vo
− −
(a)
vs
io
π+α
ωt
0 α π 2π
vo
π+α
ωt
0 α π 2π
vsw
π+α
ωt
0 α π 2π
(b)
Some basic observations about the circuit of Fig. 5-1a are as follows:
1. The SCRs cannot conduct simultaneously.
2. The load voltage is the same as the source voltage when either SCR is on.
The load voltage is zero when both SCRs are off.
3. The switch voltage vsw is zero when either SCR is on and is equal to the
source voltage when neither is on.
4. The average current in the source and load is zero if the SCRs are on for
equal time intervals. The average current in each SCR is not zero because of
unidirectional SCR current.
5. The rms current in each SCR is 1/ 12 times the rms load current if the SCRs
are on for equal time intervals. (Refer to Chap. 2.)
For the circuit of Fig. 5-1a, S1 conducts if a gate signal is applied during the
positive half-cycle of the source. Just as in the case of the SCR in the controlled
half-wave rectifier, S1 conducts until the current in it reaches zero. Where this cir-
cuit differs from the controlled half-wave rectifier is when the source is in its neg-
ative half-cycle. A gate signal is applied to S2 during the negative half-cycle of the
source, providing a path for negative load current. If the gate signal for S2 is a half
period later than that of S1, analysis for the negative half-cycle is identical to that
for the positive half, except for algebraic sign for the voltage and current.
1 Vm sin (2 )
Vo, rms 1 [Vm sin (t)]2 d(t) 1 (5-3)
A 12A 2
Note that for 0, the load voltage is a sinusoid that has the same rms value
as the source. Normalized rms load voltage is plotted as a function of in Fig. 5-2.
The rms current in the load and the source is
Vo, rms
Io, rms (5-4)
R
har80679_ch05_171-195.qxd 12/15/09 6:01 PM Page 174
0.6
0.4
0.2
0.0
0 40 80 120 160
Delay Angle (Degrees)
Figure 5-2 Normalized rms load voltage vs. delay angle for a single-phase ac
voltage controller with a resistive load.
Vm (sin 2 )
1
12A 2
Vm> 12
sin (2 )
pf 1 (5-5)
A 2
n=1
0.8
0.6
Cn
0.4
n=3
0.2
n=5
n=7
0.0
0 40 80 120 160
Delay Angle (Degrees)
The relationship between output voltage and delay angle is described by Eq. (5-3)
and Fig. 5-2. From Fig. 5-2, the delay angle required to obtain a normalized output
of 86.6/120 0.72 is approximately 90. A more precise solution is obtained from
the numerical solution for in Eq. (5-3), expressed as
sin (2 )
86.6 120 1 0
A 2
which yields
(c) SCR currents are determined from Eqs. (5-6) and (5-7),
Irms 5.77
ISCR, rms 4.08 A
12 12
P 500
pf 0.72
S (120)(5.77)
+ vsw −
io
+
S2
+ R
vs vo
−
L
−
(a)
vs
io
π+α 2π
ωt
0 α π β
vo
β π+α
ωt
0 α π 2π
vsw
β π+α ωt
0 α
(b)
Vm
csin(t ) sin( ) e(t)> d for t
Z
i o (t) d
0 otherwise
where (5-9)
L
Z 2R2 (L)2 , and tan1 a b
R
The extinction angle is the angle at which the current returns to zero,
when t ,
Vm
i o( ) 0 csin ( ) sin ( ) e()> d (5-10)
Z
L (377)(0.05)
⫽ tan⫺1 a b ⫽ tan⫺1 ⫽ 0.756 rad
R 20
L 0.05
⫽ a b ⫽ 377a b ⫽ 0.943 rad
R 20
Vm 120 22
⫽ ⫽ 6.18 A
Z 27.5
␣ ⫽ 90° ⫽ 1.57 rad
har80679_ch05_171-195.qxd 12/15/09 6:01 PM Page 180
Vm
sin ( ) e > 23.8 A
Z
The current is then expressed in Eq. (5-9) as
i o(t) 6.18 sin (t 0.756) 23.8e t>0.943 A for t
The extinction angle is determined from the numerical solution of i() 0 in the
above equation, yielding
3.83 rad 220°
Note that the conduction angle
2.26 rad 130, which is less than
the limit of 180.
(b) The rms load current is determined from Eq. (5-14).
3.83
(c) The rms current in each SCR is determined from Eq. (5-16).
Io, rms 2.71
ISCR, rms 1.92 A
12 12
(d) Average SCR current is obtained from Eq. (5-17).
3.83
EXAMPLE 5-3
AC VOLTAGE CONTROLLER
PARAMETERS: Control1 0
ALPHA = 90
+ S1
−
F = 60 +
D1
Vrms = 120
TALPHA = {ALPHA/(360*F)}
A
R1
VOFF = 0 Vs D2 + S2 20
+ + 1
VAMPL = {Vrms*sqrt(2)}
−
− Control2 0 L1
FREQ = {F}
Control1 Control2 50m
V1 = 0 V1 = 0
V2 = 5 VC1 V2 = 5 VC2 2
+ +
TD = {TALPHA} − TD = {TALPHA + 1/(2∗F)} −
0 TR = 1n TR = 1n 0
TF = 1n 0 TF = 1n 0
PW = {0.5/F} PW = {0.5/F}
PER = {1/F} PER = {1/F}
Figure 5-5 The circuit schematic for a single-phase ac voltage controller. The full version of Schematic
Capture is required for this circuit.
har80679_ch05_171-195.qxd 12/15/09 6:01 PM Page 182
Using the PSpice A/D input file for the simulation, the Probe output of load current and
related quantities is shown in Fig. 5-6. From Probe, the following quantities are obtained:
Note that the nonideal SCRs (using the default diode) result in smaller currents and
load power than for the analysis in Example 5-2 which assumed ideal SCRs. A model for
the particular SCR that will be used to implement the circuit will give a more accurate
prediction of actual circuit performance.
5.0 A
(50.000m, 2.5916)
(50.000m, 1.8660)
(50.000m, 1.0090)
0A
-5.0 A
15 ms 20 ms 30 ms 40 ms 50 ms 60 ms 70 ms
I (R) RMS ( I (R)) RMS ( I (S1) AVG ( I (S1))
Time
S4
S3
A B b a
S6 R R
N n
S5 R
C c
S2
(a)
vAB vAN
van 2
vAC
2
van
(b)
van
vbn
vcn
iS1
iS2
iS3
iS4
iS5
iS6
(c)
van
(d)
vAB vAN
vAC
van 2 2
van
(e)
0.8
Normalized Output Voltage
0.6
0.4
0.2
0
0 20 40 60 80 100 120 140
Delay Angle (Degrees)
three-phase source. The range of output voltage for the three-phase voltage con-
troller is between full source voltage and zero.
Harmonic currents in the load and line for the three-phase ac voltage con-
troller are the odd harmonics of order 6n 1, n 1, 2, 3, . . . (that is, 5th, 7th,
11th, 13th). . . . Harmonic filters may be required in some applications to prevent
harmonic currents from propagating into the ac system.
Since analysis of the three-phase ac voltage controller is cumbersome, sim-
ulation is a practical means of obtaining rms output voltages and power delivered
to a load. PSpice simulation is presented in Example 5-4.
Y-Connected RL Load
The load voltages for a three-phase voltage controller with an RL load are again
characterized by being a line-to-neutral voltage, one-half of a line-to-line volt-
age, or zero. The analysis is much more difficult for an RL load than for a resis-
tive load, and simulation provides results that would be extremely difficult to
obtain analytically. Example 5-4 illustrates the use of PSpice for a three-phase ac
voltage controller.
EXAMPLE 5-4
■ Solution
A PSpice A/D input file for the Y-connected three-phase voltage controller with an RL
load is as follows:
Probe output of the steady-state current in one of the phases is shown in Fig. 5-9.
The rms line current, load power, and power absorbed by the SCRs are obtained by en-
tering the appropriate expression in Probe. The THD in the source current is determined
from the Fourier analysis in the output file. The results are summarized in the following
table.
20 A
A–PHASE CURRENT
0A
-20 A
10 ms 20 ms 30 ms 40 ms 50 ms
I (RA)
Time
Figure 5-10 ia
(a) Three-phase ac A
voltage controller with
a delta-connected
resistive load;
R
(b) Current waveforms iab S5
for 130;
(c) Current waveforms
S2
for 90. S4
S1 R
ica
S3
ib ibc
B
R
S6
ic
C
(a)
iab
ica
ia = iab - ica
(b)
iab
ica
ia = iab - ica
(c)
har80679_ch05_171-195.qxd 12/17/09 2:40 PM Page 191
v1
Torque
Load
v2
v3
Speed w3 w1
w2
C Load
5.6 Summary
• Voltage controllers use electronic switches to connect and disconnect a load to an
ac source at regular intervals. This type of circuit is classified as an ac-ac converter.
• Voltage controllers are used in applications such as single-phase light-dimmer
circuits, single-phase or three-phase induction motor control, and static VAR control.
• The delay angle for the thyristors controls the time interval for the switch being on
and thereby controls the effective value of voltage at the load. The range of control
for load voltage is between full ac source voltage and zero.
• An ac voltage controller can be designed to function in either the fully on or fully
off mode. This application is used as a solid-state relay.
• The load and source current and voltage in ac voltage controller circuits may
contain significant harmonics. For equal delay angles in the positive and negative
half-cycles, the average source current is zero, and only odd harmonics exist.
har80679_ch05_171-195.qxd 12/15/09 6:01 PM Page 193
Problems 193
5.7 Bibliography
B. K. Bose, Power Electronics and Motor Drives: Advances and Trends, Academic
Press, New York, 2006.
A. K. Chattopadhyay, Power Electronics Handbook, edited by M. H. Rashid, Academic
Press, New York, 2001, Chapter 16.
M. A. El-Sharkawi, Fundamentals of Electric Drives, Brooks/Cole, Pacific Grove,
Calif., 2000.
B. M. Han and S. I. Moon, “Static Reactive-Power Compensator Using Soft-Switching
Current-Source Inverter,” IEEE Transactions on Power Electronics, vol. 48, no. 6,
December 2001.
N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters,
Applications, and Design, 3d ed., Wiley, New York, 2003.
M. H. Rashid, Power Electronics: Circuits, Devices, and Systems, 3d ed., Prentice-Hall,
Upper Saddle River, N. J., 2004.
R. Valentine, Motor Control Electronics Handbook, McGraw-Hill, New York, 1996.
B. Wu, High-Power Converters and AC Drives, Wiley, New York, 2006.
Problems
Single-phase Voltage Controllers
5-1. The single-phase ac voltage controller of Fig. 5-1a has a 480-V rms 60-Hz
source and a load resistance of 50
. The delay angle is 60. Determine (a) the
rms load voltage, (b) the power absorbed by the load, (c) the power factor, (e) the
average and rms currents in the SCRs, and (f) the THD of the source current.
5-2. The single-phase ac voltage controller of Fig. 5-1a has a 120-V rms 60-Hz
source and a load resistance of 20
. The delay angle is 45. Determine (a) the
rms load voltage, (b) the power absorbed by the load, (c) the power factor, (d) the
average and rms currents in the SCRs, and (e) the THD of the source current.
5-3. The single-phase ac voltage controller of Fig. 5-1a has a 240-V rms source and a
load resistance of 35
. (a) Determine the delay angle required to deliver 800 W
to the load. (b) Determine the rms current in each SCR. (c) Determine the power
factor.
5-4. A resistive load absorbs 200 W when connected to a 120-V rms 60-Hz ac voltage
source. Design a circuit which will result in 200 W absorbed by the same
resistance when the source is 240 V rms at 60 Hz. What is the peak load voltage
in each case?
5-5. The single-phase ac voltage controller of Fig. 5-1a has a 120-V rms source at 60 Hz
and a load resistance of 40
. Determine the range of so that the output power
can be controlled from 200 to 400 W. Determine the range of power factor that
will result.
5-6. Design a circuit to deliver power in the range of 750 to 1500 W to a 32-
resistor
from a 240-V rms 60-Hz source. Determine the maximum rms and average currents
in the switching devices, and determine the maximum voltage across the devices.
har80679_ch05_171-195.qxd 12/15/09 6:01 PM Page 194
5-7. Design a circuit to deliver a constant 1200 W of power to a load that varies in
resistance from 20 to 40
. The ac source is 240 V rms, 60 Hz. Determine the
maximum rms and average currents in the devices, and determine the maximum
voltage across the devices.
5-8. Design a light-dimmer for a 120-V, 100-W incandescent lightbulb. The source is
120 V rms, 60 Hz. Specify the delay angle for the triac to produce an output
power of (a) 75 W (b) 25 W. Assume that the bulb is a load of constant resistance.
5-9. A single-phase ac voltage controller is similar to Fig. 5-1a except that S2 is
replaced with a diode. S1 operates at a delay angle . Determine (a) an
expression for rms load voltage as a function of and Vm and (b) the range of
rms voltage across a resistive load for this circuit.
5-10. The single-phase ac voltage controller of Fig. 5-1a is operated with unequal
delays on the two SCRs (1 2). Derive expressions for the rms load voltage
and average load voltage in terms of Vm, 1, and 2.
5-11. The single-phase ac voltage controller of Fig. 5-4a has a 120-V rms 60-Hz source.
The series RL load has R 18
and L 30 mH. The delay angle 60.
Determine (a) an expression for current, (b) rms load current, (c) rms current in
each of the SCRs, and (d) power absorbed by the load. (e) Sketch the waveforms
of output voltage and voltage across the SCRs.
5-12. The single-phase ac voltage controller of Fig. 5-4a has a 120-V rms 60-Hz
source. The RL load has R 22
and L 40 mH. The delay angle 50.
Determine (a) an expression for current, (b) rms load current, (c) rms current in
each of the SCRs, and (d) power absorbed by the load. (e) Sketch the waveforms
of output voltage and voltage across the SCRs.
5-13. The single-phase ac voltage controller of Fig. 5-4a has a 120-V rms 60-Hz
source. The RL load has R 12
and L 24 mH. The delay angle is 115.
Determine the rms load current.
5-14. The single-phase ac voltage controller of Fig. 5-4a has a 120-V rms 60-Hz source.
The RL load has R 12
and L 20 mH. The delay angle is 70. (a) Determine
the power absorbed by the load for ideal SCRs. (b) Determine the power in the load
from a PSpice simulation. Use the default diode and Ron 0.1
in the SCR model.
(c) Determine the THD of the source current from the PSpice output.
5-15. Use PSpice to determine the delay angle required in the voltage controller of
Fig. 5-4a to deliver (a) 400 W, and (b) 700 W to an RL load with R 15
and
L 15 mH from a 120-V rms 60-Hz source.
5-16. Use PSpice to determine the delay angle required in the voltage controller of
Fig. 5-4a to deliver (a) 600 W, and (b) 1000 W to an RL load with R 25
and
L 60 mH from a 240-V rms 60-Hz source.
5-17. Design a circuit to deliver 250 W to an RL series load, where R 24
and
L 35 mH. The source is 120 V rms at 60 Hz. Specify the rms and average
currents in the devices. Specify the maximum voltage across the devices.
Problems 195
5-19. The three-phase Y-connected voltage controller has a 240-V rms, 60-Hz line-to-
line source. The load in each phase is a series RL combination with R 16