Section - 1: Meo Class 4 - Electrical Oral Questions With Answers
Section - 1: Meo Class 4 - Electrical Oral Questions With Answers
Section - 1: Meo Class 4 - Electrical Oral Questions With Answers
SECTION - 1
1. Steering gear safeties?
Ans: Hydraulic safeties
- Level switch, low level, low low level alarm for hydraulic oil tank.
- Relief valve.
-Manual bypass valve.
- Low pressure valve.
- High lube oil temp. Cut out.
- Low level cut out
Electrical safeties
- Electrical and mechanical stopper for rudder.
- Electrical motor overload alarm.
- Power failure alarm.
- High temp. Alarm.
- Self starting after power failure.
- Short-circuit trip.
- Phase failure alarm.
- 200% insulation in motor.
AJ NOTES 1
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
After maintenance is performed, a no load test should be carried out and general
condition such as noise, temperature, voltage generated etc. of the alternator should be
observed and noted.
AJ NOTES 2
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 3
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 4
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
3. Push the spring loaded valve and the generator should start.
4. Check voltage and frequency.
5. Keep the generator running for 10-15 min and check the exhaust temp and other
parameters.
6. Check the sump level
7. For stopping, use the manual stop button from the panel.
8. After stopping the generator, pressurize the hydraulic accumulator to desired
pressure.
9. Close the valve from accumulator to generator.
AJ NOTES 5
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
replacing the charging unit of the 24V DC supply, and/or replacing any defective
batteries.
20. If on starting Generator you find that voltage is not building up what you do?
Ans: Residual magnetism is lost. So supply power from outside by connecting
battery.
AJ NOTES 6
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
amount of electrons) that flows in both directions and DC is direct current that flows in
only one direction.
The wires outside of our house are connected at two ends to AC generators. DC is found
in batteries and solar cells.
alternating current varies with time, sinusoidally wave, where has DC remains steady.
25. What Precautions you will take before entering battery room?
Ans: a. Inform the bridge & the engine control room
b. Check the oxygen content.
c. Should be ventilated properly.
d. All PPE to be donned properly & rubber hand gloves to be used.
e. No Naked lamps to be taken inside.
AJ NOTES 7
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
26. What is meaning of Power factor. What is best value. What is normal value onboard.
How do you improve?
Ans: The power factor of an AC electric power system is defined as the ratio of
the real power flowing to the load to the apparent power and is a dimensionless
number between 0 and 1. The best value is 0.85. The normal value onboard varies in
between 0.8 to 0.9. Power factor can be improved by connecting a Capacitor in parallel.
AJ NOTES 8
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
35. What precautions to take while using megger on circuits containing Electronic
components?
Ans: When you use a megger, you could be injured or damage equipment you
are working on if the following MINIMUM safety precautions are not observed.
-Use meggers on high-resistance measurements only (such as insulation measurements
or to check two separate conductors on a cable).
-Never touch the test leads while the handle is being cranked. Deenergize and discharge
the circuit completely before connecting a megger.
-Disconnect the item being checked from other circuitry, if possible, before using a
megger.
AJ NOTES 9
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
When it opens, the voltage across the tube allows a stream of electrons to flow across
the tube and ionize the mercury vapor.
Without the starter, a steady stream of electrons is never created between the two
filaments, and the lamp flickers. Without the ballast, the arc is a short circuit between
the filaments, and this short circuit contains a lot of current. The current either
vaporizes the filaments or causes the bulb to explode.
AJ NOTES 10
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
by a reference circuit of zener diodes and resistors.an error signal output from
comparator is then amplified and made suitable for driving the field circuit regulating
thyristors.
AJ NOTES 12
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
• Check and ensure the frequency and voltage of shore supply are matching with
the specifications required by the ship
• Check the phase sequence of the shore supply using phase sequence tester
• Check the tightness of the shore cable connector clamp to ensure they are not
loose
• Ensure to display notice near the vicinity of ship’s receiving terminal box about
high power cable in use
• Check and ensure the ship’s generators are disconnected from the Main Switch
Board of the ship
• A responsible officer must check and record the energy meter reading provided
on shoreside
• Ensure ship’s hull is earthed to the shore before supplying shore power to the
ship
45. Why load picked by crane does not fall if power goes off?
Ans: Because Electro-magnetic brakes get operated.
AJ NOTES 13
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
48. How to carry out Open Circuit & Short circuit test?
Ans: Open Circuit Test:
The purpose of this test is to determine no load loss or core loss. One winding of
the transformer, usually high voltage side if left open and the other is connected to its
supply of normal voltage and frequency. A wattmeter, voltmeter and the ammeter are
connected in the low voltage winding.
With the normal voltage applied to the low voltage side, normal flux will be set up in
the core, hence normal iron losses will occur which are recorded by the Wattmeter.
The load current on the low voltage winding will be small(2 to 5 % of rated full load
current ), the copper loss in the winding will be negligible and will be nil in the high
voltage side winding..
So, the wattmeter reading will represent practically the core loss under no load
condition.
Short-Circuit Test:
This is also known as Impedance test.In this test, the low voltage winding is
short circuited by using a thick conductor (or Ammeter, which serves additional
purpose of Indicating Rated load current).
AJ NOTES 14
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
A low voltage at correct frequency is applied to the primary and is cautiously increased
till full load current is flowing the high voltage side.
In this test, the applied voltage is small percentage of its rated value, hence flux
produced is small with the result that iron losses will be negligible and the Wattmeter
reading will represent the full load Cu-loss.
49. Suppose your motor has short-circuited, then how much value will you get on Megger.
Ans: When there is short circuit the pointer will read “0”.
50. What is the difference between short circuit and short circuit level ?
Ans: - A short circuit is a fault which occurs when the current in a system deviates
its normal path and start flowing through an alternate path.
- Since the alternate path offers very low resistance, the current increases very much
above the normal value.
- Short circuit level (SCL) is the maximum possible current that flows through a
circuit during a short circuit fault.
51. Where does magnetic field cuts the conductor? where does conductor cuts the
magnetic field?
Ans: - Alternator
- Motor
53. What are the methods adopted to prevent ill effects of short circuit fault ?
Ans: Protective relay installed in the system immediately trips and isolates the
equipment during a short circuit fault within a short time. This prevents the effects of
high current flow through the circuit.
The generators, cables, equipment, switch gears, etc. associated with the
system are designed to withstand the heavy current during short circuit fault for this
short duration of time.
AJ NOTES 15
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
57. What is the effect of short circuit fault in high voltage system ?
Ans: High current flow during a short circuit fault result in increased temperatures,
which damages insulation, produces high thermal and mechanical stresses in the
system, may cause arcing, arc flash and arc blast.
58. What is the routine maintenance on the starter of main air compressor which is of
automatic start stop type?
Ans: Clean contacts, Check tightness of terminals, Pressure switch check.
AJ NOTES 16
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
69. What all testing equipment is used for testing an electric motor?
Ans: Multimeter, Megger, Clampmeter.
AJ NOTES 17
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Ans:
1. Deflecting and Control coil : Connected parallel to the generator, mounted at right
angle to each other and maintain polarities in such a way to produced torque in
opposite direction.
2. Permanent Magnets : Produce magnetic field to deflect pointer with North-South
pole magnet.
3. Pointer : One end of the pointer connected with coil another end deflects on scale
from infinity to zero.
4. Scale : A scale is provided in front-top of the megger from range ‘zero’ to
‘infinity’, enable us to read the value.
AJ NOTES 18
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 19
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
18. Charts indicating drill procedures in case of electric shocks must be displayed near
MSB.
19. Wiring diagram laminated or framed indicating supply system must be displayed
nearby.
20. All the appropriate spares should be properly preserved and protected, individually
packed and identified, and should be readily available for use.
21. Earth fault indication should be fitted and displayed in front panel.
22. 24 volt battery supply emergency light should be provided near MSB.
76. What are the hazards of arc flash and arc blast ?
Ans: 1.Permanent damages to the electrical equipment.
2.Irreversible damage to the human tissue and incurable burns due to very high
temperatures.
3.Arc flash produces intense UV light, resulting permanent or severe damages to the eye
vision.
4.Pressure wave from the arc blast compresses the eyes, resulting permanent or severe
damages to the eye vision.
5.Heavy noise (above 140 dB) may damage hearing ability, sudden pressure changes
may rupture ear drums also.
6.Arc blast explodes the equipment, ejecting parts with tremendous force and velocity.
This may result in damages to personnel and property.
7.Flammable materials present in the vicinity of arc may ignite, causing secondary fires.
AJ NOTES 20
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
80. EXPLAIN HOW THE EMERGENCY GENERATOR STARTS UP IN THE EVENT OF TOTAL
POWER FAILURE?
Ans: The startup of the emergency generator is initiated by an electrical relay,
which monitors the normal mains power supply. Failing mains frequency or voltage
causes the ‘start up’ relay to operate the generator starting equipment. The prime
movers may be electrically cranked from its own 24v battery and starter motor or air
started from its own air reservoir filled local to the generator engine. A manual start up
may also be initiated by push buttons in the main control room and in the emergency
generator room
Also when power loss occurs, the breaker feeding the emergency switch
board from the main switch board opens. This breaker is interlocked with the
emergency generator breaker, which is normally open under normal circumstances, but
in the event of total power failure, this breaker will close when the breaker feeding the
emergency board from the main board opens. Thus the emergency generator will feed
the emergency switch board.
83. E/R CRANE SAFETIES AND WORKING OF DRUM WHEN POWER FAILS.
Ans: Overhead crane safeties:
1) The most important safety feature of the crane is the electromagnetic fail safe brakes
which do not allow the crane to fall with the load even when there is failure of power.
For this:
- Normally centrifugal brakes are used which are fitted inside the rotating drum.
AJ NOTES 21
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
- The brake pads are always in applied state and pushed by magnetic springs when not
in operation or when there is a power failure.
- As the crane is operated or the power is supplied, the spring gets pulled inward or
compressed due to the electromagnetic effect of the current. This allows the crane to be
operated normally.
2) Emergency stop is provided in the remote so that the operator can stop the crane at
any time.
3) The motor is fitted with distance limit switch in both transverse and longitudinal
direction
4) Mechanical stoppers are provided for both directions in case the electrical distance
limit trips fail.
5) The up and down travel of the hook is also attaches with automatic stopper to avoid
overloading of the motor.
6) The motor is fitted with thermal protection trip. When the motor windings get
overheated, trip will activate saving the motor winding from burning.
7) Load limit switch is also fitted which will trip the motor if the load to be lifted is
above the crane capacity.
8) It’s the responsibility of senior officers to operate the crane and to make sure all the
personnel involve in any lifting operation are at a safe distance during operation of the
crane.
9) Additional tools like i-bolts, shackle, wire sling, belts etc. used for lifting must be
checked before use.
10) It should be noted that no one walks or stand below the crane when it is in the
loaded condition.
1) Electromagnetic brakes:
The main parts of an electromagnetic brakes are:
- The brakes shoes, which are connected to two levers,
- The spiral springs, which are connected to the levers, and
- The electromagnetic solenoid, which is connected to the two levers.
Electromagnetic brakes are usually found on machines like cranes and lifts and
they work as back up braking systems. These brakes only work when the electricity
supply stops, to make sure that, for example, the load carried by the crane, or the lift
that moves up and down in a building does not fail. If the load that the crane or the lift
was carrying fell, it could cause serious damage tom property, as well as serious injuries
or even death to people underneath the load or in the lift. The braking action of an
electromagnetic brake works as follows:
- When the electricity is flowing, the electromagnetic solenoid uses magnetic force to
pull the two levers in towards it, which keeps the springs attached to the top of the
levers open.
- The open springs keeps the brake shoes, which are positioned on each shoes, which
are positioned on each side of a shaft, away from the shaft while it is turning.
AJ NOTES 22
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
- When the electricity stops flowing, the electromagnetic solenoid stops working, with
the magnetic force gone, the spiral springs closes, which pushes the brakes shoes
against the shaft to stop it from turning.
2) Thrust Brakes:
The main parts of a thruster brake system are:
-The hydraulic centrifugal pump, which is connected to a thruster piston.
- The thruster piston which is connected to the pump and to the braking springs.
- The braking springs, which are connected to the piston.
- The friction pads and
- The brake disc
AJ NOTES 23
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 24
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Battery Efficiency
The Lead Acid battery is not 100% efficient at storing electricity - you will
never get out as much as you put in when charging. Overall, an efficiency level of 85% is
often assumed. The efficiency will depend on a number of factors including the rate of
charging or discharging. The higher the rate of charge or discharge, the lower the
efficiency. The state of charge of the battery will also affect charge efficiency. With the
battery at half charge or less, the charge efficiency may be over 90%, dropping to nearer
60% when the battery is above 80% charged.
However it has been found that if a battery is only partially charged, efficiency may be
reduced with each charge. If this situation persists (the batteries never reaching full
charge), the life of the battery may be reduced.
Battery Connections:-
In the SERIES CONNECTION, batteries of like voltage and Amp-Hr capacity
are connected to increase the Voltage of the battery bank. The positive terminal of the
first battery is connected to the negative terminal of the second battery and so on, until
the desired voltage is reached. The final Voltage is the sum of all the battery voltages
added together while the final Amp-Hr, Cranking Performance and Reserve Capacity
remain unchanged.
In PARALLEL CONNECTION, batteries of like voltages and capacities are
connected to increase the capacity of the battery bank. The positive terminals of all
batteries are connected together, or to a common conductor, and all negative terminals
are connected in the same manner. The final voltage remains unchanged while the
capacity of the bank is the sum of the capacities of the individual batteries of this
connection. Amp-Hrs, Cranking Performance and Reserve Capacity increases while
Voltage does not.
AJ NOTES 25
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
- A running motor will continue to run with high current in other two phases or a
physical damage to the motor due to disturbance in balanced supply.
- Stationary 3-phase motor will not start as two phases will not be able to provide
rotating magnetic field.
- A Short circuit fault will cause high current to flow in the windings which may burn
out.
- An earth fault provides an easy path for current to flow through the wires and earth.
OPEN Circuit: Earth one end of the wire and using multimeter or megger switched to
res. Value, check between wire at different points and earth. Resistance should show
minimum value.
EARTH fault: Open circuit where possible and check the res. Between wire near “open”
ends and earth. Resistance should show maximum value.
SHORT circuit fault: Remove the terminals at the panel. Turn all switches for that circuit
to ON position. Check for resistance between positive and negative sides of the
conductor. A reading of less than infinite indicates the fault.
AJ NOTES 27
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
3. Initially the slip (relative motion b/w rotor and stator magnetic field) is maximum.
This starting surging current reduces as the motor accelerates up to
its running speed. This causes a voltage dip at the supply bus bars and is accepted if the
voltage dip is not greater than 15% within the run-up period.
For large motors like cargo pumps and bow thrusters, this voltage dip is unacceptable
as it malfunctions the other sources.
Hence to limit the starting current, induction motors are started at reduced voltage and
then have the full supply of voltage.
Types of starters:
DOL (Direct on-line): This is a very simple starting arrangement which is used for
majority of induction motor drives. It does not limit the starting current.
Start Delta starting: It is used to reduce starting current in 6 terminal motor designed to
run in delta connection. It is the most cost effective method of reduced vo ltage starting.
The motor starts in star and then run in delta.
To provide an electrical interlock between contactors KM1 and KM3. This is to prevent a
full short-circuit fault across the supply lines during the changeover from star to delta
Comparison between Star and Delta operation
At the instant of starting when the supply has just been switched on the motor has not
yet started to rotates, there is no mechanical output from the motor. The only factor
which determine the current taken by the motor are the supply voltage (V) and the
impedance of the motor phase winding (Zph).
AJ NOTES 28
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Auto transformer:
The operating principle of this starter is that a step down transformer is used to provide
reduced voltage to the motor while starting
Three autotransformers are connected in the start configuration and taps are selected,
to provide an adequate current for the motor.
The motor is allowed to accelerate and then the full voltage is applied.
Soft starter:
This method of supplying a gradually increasing a.c. voltage during start up
generally refers to an efficient electronic switching techniques. This delayed switching
applies a reduced average a.c. voltage to the motor.
The applied motor voltage is gradually ramped up by the starter software program until
the full voltage level is reached.
To achieve maximum efficiency, the electronic switching circuit can be now by-passed
for normal running.
A ‘soft’ starter may be further adapted to become a voltage controller over the motor
operating load range. In this type of efficient ‘energy manager’ application, the
controller monitor the motors power factor which is a measure of the motor leading.
On light load and full voltage, the power factor is low so the controller reduces the
motor voltage which reduces current while improving power factor and efficiency.
Note- This type of ‘soft start / energy manager’ is not a speed controller. To electrically
change the speed of an induction motor it is necessary to vary the applied frequency,
AJ NOTES 29
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Types
1 Core- Type Transformer
2 Shell-Type Transformer
Transformers can also be classified according to the type of cooling employed. The
different types according to these classifications are:
1 Oil Filled Self-Cooled Type
2 Oil Filled Water Cooled Type
3 Air Blast Type
Auto Transformer
In an autotransformer, portions of the same winding act as both the
primary and secondary sides of the transformer. The winding has at least three taps
where electrical connections are made. Autotransformers have the advantages of often
being smaller, lighter, and cheaper than typical dual-winding transformers, but the
disadvantage of not providing electrical isolation.
An autotransformer has a single winding with two end terminals, and one or more
terminals at intermediate tap points, or a transformer in which the primary and
secondary coils have part or all of their turns in common. The primary voltage is applied
across two of the terminals, and the secondary voltage taken from two terminals, almost
always having one terminal in common with the primary voltage. The primary and
secondary circuits therefore have a number of windings turns in common.
Autotransformers are often used to step up or step down voltages in the 110-115-120 V
range and voltages in the 220-230-240 volt range—for example. Providing 110 V or 120
V (with taps) from 230 V input, allowing equipment designed for 100 or 120 volts to be
used with a 230 volt supply
Welding Transformer:-
A welding transformer is a step down transformer that reduces the voltage
from the source voltage to a lower voltage that is suitable for welding, usually between
15 and 45 volts. The secondary current is quite high. 200 to 600 amps would be typical,
but it could be much higher. The secondary may have several taps for adjusting the
secondary voltage to control the welding current. The taps are typically connected to a
AJ NOTES 30
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 31
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Avalanche Diode: This type of diode operates in the reverse bias, and used avalanche
effect for its operation.
Laser Diode: This type of diode is different from the LED type, as it produces coherent
light. These diodes find their application in DVD and CD drives, laser pointers, etc.
Schottky Diodes: These diodes feature lower forward voltage drop as compared to the
ordinary silicon PN junction diodes. The voltage drop may be somewhere between 0.15
and 0.4 volts at low currents, as compared to the 0.6 volts for a silicon diode.
Zener diode: A Zener diode is a type of diode that permits current not only in the
forward direction like a normal diode, but also in the reverse direction if the voltage is
larger than the breakdown voltage known as "Zener knee voltage”.
Photodiode: Photodiodes are used to detect light and feature wide, transparent
junctions. Photodiodes can also be used to generate electricity, used as solar cells and
even in photometry.
Varicap Diode or Varactor Diode: This type of diode feature a reverse bias placed upon it,
which varies the width of the depletion layer as per the voltage placed across the diode.
Rectifier Diode: These diodes are used to rectify alternating power inputs in power
supplies.
Small signal or Small current diode: These diodes assumes that the operating point is not
affected because the signal is small
Large signal diodes: The operating point in these diodes get affected as the signal is
large.
Transient voltage Supression diodes: This diode is used to protect the electronics that
are sensitive against voltage spikes.
Gold doped diodes: These diodes use gold as the dopant and can operate at signal
frequencies even if the forward voltage drop increases.
Super barrier diodes: These are also called as the rectifier diodes. This diodes have the
property of low reverse leakage current as that of normal p-n junction diode and low
forward voltage drop as that of Schottky diode with surge handling ability.
Point contact diodes: The construction of this diode is simpler and are used in analogy
applications and as a detector in radio receivers
Peltier diodes : This diode is used as heat engine and sensor for thermoelectric cooling.
Gunn diode : This diode is made of materials like GaAs or InP that exhibit a negative
differential resistance region.
USES: Aside from the many electronic appliances and gadgets we commonly use
today, diodes are also used in public facilities. Traffic lights, scoreboards, and vending
machines are examples of diode-dependent devices.
98. ZENER DIODE AND ITS USES? HOW IT IS DIFFERENT FROM NORMAL DIODE?
Ans: A Zener diode is a type of diode that permits current not only in the forward
direction like a normal diode, but also in the reverse direction if the voltage is larger
than the breakdown voltage known as "Zener knee voltage" or "Zener voltage".
AJ NOTES 32
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
A Zener diode exhibits almost the same properties, except the device is
specially designed so as to have a greatly reduced breakdown voltage, the so-called
Zener voltage.
The Zener diode is therefore ideal for applications such as the generation of a
reference voltage (e.g. for an amplifier stage), or as a voltage stabilizer for low-current
applications
-------END-------
AJ NOTES 33
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
SECTION – 2
1. BRUSHLESS ALTERNATOR?
Ans: A brushless alternator is composed of two sections: main alternator and the
smaller exciter. The exciter has stationary field coils and a rotating armature (power
coils). The main alternator uses the opposite configuration with a rotating field and
stationary armature. A bridge rectifier, called the rotating rectifier assembly, is mounted
on a plate attached to the rotor. Neither brushes nor slip rings are used, which reduces
the number of wearing parts. The main alternator has a rotating field as described
above and a stationary armature (power generation windings).
Residual magnetism is a property in which certain amount of excitation remains back in
the conductor even after the removal of the magnets. It is required as we need some
magnetism to start off the generation before the field winding has power to produce the
full field.
Varying the amount of current through the stationary exciter field coils varies the 3-
phase output from the exciter. This output is rectified by a rotating rectifier assembly,
mounted on the rotor, and the resultant DC supplies the rotating field of the main
alternator and hence alternator output. The result of all this is that a small DC exciter
current indirectly controls the output of the main alternator.
Basic Theory
When an electric current is passed through a coil of wire, a magnetic field is
produced (an electromagnet). Conversely, when a magnetic field is moved through a
coil of wire, a voltage is induced in the wire. The induced voltage becomes a current
when the electrons have some place to go such as into a battery or other
load. Both of these actions take place in alternators, motors and generators or dynamos.
Voltage is generated when a coil of wire is moved through a magnetic field. It doesn’t
matter whether the coil is moving or the magnetic field is moving. Either configuration
works equally well and both are used separately or in combination depending on
mechanical, electrical and other objectives. The old DC generators (dynamos) used a
stationary field and rotating armature. Automotive alternators use the opposite
configuration with a rotating field and stationary armature. In a brushless alternator,
both configurations are used in one machine.
Terminology
The stationary part of a motor or alternator is called the stator and the
rotating part is called the rotor. The coils of wire that are used to produce a magnetic
field are called the field and the coils that produce the power are called the armature.
2. SELF-EXCITED GENERATOR?
Ans: A kind of excitation of generators where the magnetic field of the main poles
is excited by a current supplied to the windings of the main poles from the armature
(rotor) winding. A self-excited generator is thus distinguished from a separately excited
generator, in which the windings of the main poles receive current from an external
source. Self-excitation is made use of most often in DC generators. When a self-excited
generator is started, the initial current in the field winding is produced by the
electromotive force (emf) induced in the armature winding by the residual magnetic
field of the main poles. To sustain self-excitation, the initial current must reinforce this
AJ NOTES 34
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
field. The additional magnetic flux increases the emf in the armature and, consequently,
the current in the windings of the main poles. Because, however, of magnetic saturation
in the magnetic circuit, the increments in magnetic flux corresponding to equal
increments in current become smaller as the current builds up. The process of self-
excitation continues as long as the emf in the armature exceeds the voltage drop in the
field winding. At a certain magnitude of the magnetic flux, electric equilibrium is
reached, and there is no further increase in magnetic flux, armature emf, and excitation
current. Self-excitation can be achieved when the value of the resistance of the field
winding does not exceed a certain limit, which depends on the electric parameters of
the generator.
4. WHAT IS AVR?
Ans: AVR-means automatic voltage regulator AVR regulates the voltage of a
generator. When voltage drops, due to load increase, AVR gives voltage to exciter and
exciter more excites the alternator and voltage improve.
The AVR senses the voltage in the main generator winding and controls
the power fed to the exciter stator and hence the main rotor to maintain the generator
output voltage within the specified limits, compensating for load, speed, temperature
and power factor of the generator.
A frequency measuring circuit continually monitors the shaft speed of the generator and
provides under-speed protection of the excitation system by reducing the generator
output voltage proportionally with speed below a pre-settable threshold. A further
enhancement of this feature is an adjustable VOLT per Hertz slope to improve engine
recovery time on turbo charged engines. Soft start circuitry is included to provide a
smooth controlled buildup of generator output voltage. Uncontrolled excitation is
AJ NOTES 35
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
limited to a safe period by internal shutdown of the AVR output device. This condition
remains latched until the generator has stopped. Provision is made for the connection of
a remote voltage trimmer, allowing the user fine control of the generator’s output. The
AVR has the facility for droop CT connection, to allow parallel running with other
similarly equipped generators.
5. ALTERNATOR SAFETIES AND HOW WILL YOU TRY OUT REVERSE POWER TRIP AND
WHY REVERSE POWER TRIP?
Ans: The three main type alternator protection are:
a. Over current protection.
b. Reverse power trip
c. Under voltage trip
When two generators are running in parallel and one generator can carry the load,
reverse power trip can be tested by load shifting using governor control. When the load
has shifted sufficiently and the off loaded generator is carrying a small percentage of
load, its breaker trips and fuel supply to its prime mover cuts off. This means reverse
power relay has operated. The relay can be tested by simulation (using the test push
button on the relay) to see if it initiates a trip signal.
Reverse power trip is provided to protect generator. Situation of a generator is feeding a
system through switchgear having several generators connected in parallel with this
generator. The flow of current, when the system is running normally, is from the
generators to the switchgear. If one generator experiences problems and its terminal
voltage falls below the system voltage, the generator will act as a motor, just as a motor
can act as a generator, and current will flow from the switchgear to the generator. This
is reverse power. The effects can range from minor to extreme in the event of a
complete mechanical failure of the generator which fails.
6. SYNCHRONIZING METHODS?
Ans: Synchroscope is the main method.
Back-up methods are
a. Lamp dark method
b. Lamp bright method
c. Rotating lamp method or Sequence methods (preferable)
In cylindrical type rotors the excitation windings are wedged into axial slots around the
steel rotor. Unwound sections of the rotor form the pole faces between the winding
slots.
8. THERMOCOUPLE?
Ans: A Thermocouple is a sensor used to measure temperature. Thermocouples consist
of two wire legs made from different metals. The wires legs are welded together at one
end, creating a junction. This junction is where the temperature is measured. When the
junction experiences a change in temperature, a voltage is created. The voltage can then
be interpreted using thermocouple reference tables (linked) to calculate the
temperature. There are many types of thermocouples, each with its own unique
characteristics in terms of temperature range, durability, vibration resistance, chemical
resistance, and application compatibility. Type J, K, T, & E are “Base Metal”
thermocouples, the most common types of thermocouples. Type R, S, and B
thermocouples are “Noble Metal” thermocouples, which are used in high temperature
applications (see thermocouple temperature ranges (linked) for details).
Thermocouples are typically selected because of their low cost, high temperature limits,
wide temperature ranges, and durable nature.
2) Trickle charging: Trickle charging is the charge given to the battery that is already
fully charged. It compensates for the loss of battery capacity due to internal leakage
between plates. It is a small makeup current for topping up purpose, to ensure that the
battery is fully charged at all times.
Fuses:
Fuses perform phase-by-phase (single pole) protection with a high break capacity at
low volume. They limit I2t and electro-dynamic stress.
They are mounted:
AJ NOTES 37
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Most magnetic circuit breakers for motor protection are current-limiting devices and so
contribute to coordination. Their very short cut-off time breaks the short-circuit current
before it reaches its maximum amplitude
AJ NOTES 38
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
2. (a) Faraday’s first law: Whenever there is a change in the magnetic field linked with a
circuit, an induced e.m.f is produced in it.
(b) Faraday’s second law: The magnitude of induced e.m.f is equal to the rate of
change of the magnetic flux linked with a closed circuit.
Therefore faraday’s laws gives the magnitude of the induced e.m.f.
AJ NOTES 39
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
(1) 300% and not more than 375% of the rated full – load current of one steering – gear
motor for a direct –current motor.
(2) 175% and not more than 200% of the locked – rotor current of one steering – gear
motor for an alternating – current motor.
21. WHY DON’T WE GET A SHOCK WHILE TESTING FOR VOLTAGE WITH A LINE
TESTER?
Ans: Rating of voltage is 230V only. The current is low enough not to hurt us and
just enough to light up the bulb. But the same tester can’t be used to check higher
voltages. Since, our body resistance is very high we do not experience a shock.
22. CB PROTECTION INCLUDING SHUNT TRIP, UNDER VOLTAGE AND THERMAL TRIP?
Ans: A circuit breaker is an automatically operated electrical switch designed to
protect an electrical circuit from damage caused by overload or short circuit. Its basic
function is to detect a fault condition and interrupt current flow. Unlike a fuse, which
operates once and then must be replaced, a circuit breaker can be reset (either
manually or automatically) to resume normal operation. Circuit breakers are made in
varying sizes.
A shunt trip is a solenoid device on a circuit breaker that trips the circuit breaker by
applying a voltage to the shunt trip. This trip mechanism is not part of the instantaneous
and short time-delay trip of the breaker, but as the term implies, it is a shunt
mechanism which operates in parallel with, but independent of, the breakers current
actuated trip.
The under voltage trip accessory trips the circuit breaker when the voltage drops to a
value between 35% and 70% of the control voltage. If the under voltage trip is not
energized, it is impossible to close the circuit breaker, either manually or electrically. An
attempt to close the circuit breaker produces no movement of the main contacts.
Closing is allowed when the supply voltage of the under voltage trip reaches 85% of the
rated voltage.
Thermal circuit protectors utilize a bimetallic strip electrically in series with the circuit.
The heat generated by the current during an overload deforms the bimetallic strip and
trips the breaker.
AJ NOTES 40
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 41
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
- High voltages AC generators are much simpler and cheaper than DC generators of the
same range. It is because in AC generators there is no commutator which is costly part
and is damaged.
- Alternating current can be stepped up or stepped down with a static device called
transformer. When voltages is stepped up current decreases to a small value. Small
current produces less heat and can be transmitted through a thin conductor. Thus it is
possible to transmit AC at high voltages. This reduces the size of conductor,
transmission losses are increases transmission efficiency. At the receiving station,
voltages can be stepped down to the required value by using step down transformer.
This is most important reason for generating and using electrical energy as AC.
- A.C. induction motors are simplest in construction, cheaper in cot and require less
maintenance whereas D.C. motors are complicated.
26. IF YOUR OVERHAULED MOTOR IS NOT STARTING, WHAT WILL YOU CHECK?
Ans:
- Ensure the terminal for power supply is in good condition. Check the connection bar
for terminal (U, V, W). Connection type - STAR OR DELTA.
- Confirm the power supply VOLTAGE for electric motor. 230/400.
- Using the multimeter, check the continuity of winding from phase to phase ( U to V, V
to W , W to U ).Each phase to phase must have a continuity if winding is OK.
- Check the motor winding ohms reading using multimeter or ohmmeter for phase to
phase terminal( U to V,V to W ,W to U ).The ohms reading for each winding must be the
same (or nearly the same).
Insulation resistance of motor winding using Insulation tester meter set to the 500 Volt
scale (1000v DC). 1. Check from phase to phase (U to V, V to W, W to U) and 2. Check
from phase to earthing (U to E, V to E , W to E ). Minimum test value of the electric
motor is 1 Meg Ohm (1 MΩ).
- If every step is completed, decide the condition of electrical motor either OK or NEED
TO REPAIR.
27. SINGLE PHASING, HOW WILL YOU COME TO KNOW WHICH PHASE HAS GONE HOW
YOU WILL TEST?
Ans: Single phasing:
- In single phasing, one of the three phases of motor one phase goes wrong i.e. open
circuit fault occurs in any of the one phase wire.
- When a three phase motor is "single phased", it is a power system problem, not a
motor problem. A three phase motor needs three EQUAL phases in order to operate
properly. When the symmetry of the motor is interrupted by the loss of a phase, the
motor will die quickly unless the controls have single phase protection. Many heater
type overload relays do not have this.
AJ NOTES 42
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
- It will overheat
- If fault not diagnosed & rectified, then motor will burn
Causes:
Single phasing occurs as a result of several possibilities. A loose wire, a bad
connection, bad starter contacts, overload relay problems, a bad breaker, a blown fuse,
and other things can cause this destructive condition.
How to test:
Testing for this possibility needs to be done quickly since motors are not happy with
this condition at all. The obvious test is to look at the current in each phase. This is
where multiple meters will help so you can see all three phases at once. You can also
look at the voltage, again with multiple meters if possible. Look at the phase to ground
readings first. The phase to ground voltage will equal the phase to phase voltage divided
by 1.7; thus 480 volts phase to phase will be 277 volts phase to ground. The advantage
of taking phase to ground measurements is that each reading is independent of
whatever is happening in the other phases. However, you can read phase to phase if you
want. You would see an unbalance there too. The phase to ground reading will show you
the bad phase, though; this will make troubleshooting easier.
These tests need to be made as close to the motor as possible, preferably in the
motor's connection box while the motor is driving the load. If the motor is not
connected, or you take your readings at the starter or breaker with the motor off, you
can get fooled. A bad set of contacts in a contactor or breaker can just barely touch and
still tell you that you have good voltage. Ask those same contacts to deliver enough
current to run a loaded motor, and the voltage will take a dive.
You could continue to test at various stages of the power system upstream of the
motor, but that keeps subjecting the motor to the stress of running in the single phase
condition. Otherwise, make sure the circuit is off and locked out, and then start taking
things apart.
The first place to look is at those suspect contactor contacts. But, Bo Diddley said
"you can't judge a book by looking at the cover." Contacts can be like me - real ugly but
still functional. Contacts that are gone don't work very well, though. Also look at the
connections in and out of the contactor. Loose or burned wires or terminals are
probably the second most frequent offenders.
If the contactor looks good, take continuity readings from the line to the load side
of each phase of the overload relay. It should look like a short circuit.
If everything is good at the starter, check wires, connections, and devices ahead of
the starter until the problem is found and corrected.
28. WHY DO WE USE 440V SUPPLY FOR MOTORS AND 220V SUPPLY FOR LIGHTING
(ACCOMMODATION)? WHAT ARE THE ADVANTAGES?
Ans:
- Using 440 volt for motors will result in the reduction of motor load current, half the
value of current resulting from the use of 220 volts. The load current is responsible for
the energy line losses, by the formula, kw loss = I.I.R/1000. So with less current, at 440
volts, there will be a reduction in line losses when 440volts is used for, motors rather
AJ NOTES 43
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
200 volts. ALSO, with higher current, the wire size for 220 volt motors will be twice
bigger than those used for 440 volt motors. It means, there will be higher cost of
installation cost on 220 volt motors than those for 440 volt motors.
For lighting, 220 volts is used giving residential users, a safe line voltage. Most lights
are rated not above 220 volts, including lamp ballasts.
And ships having 440 volts 3 phase supply will have near to 220 volts of supply for
single phase, generally all the accommodation lights will be of single phase.
30. WHAT IS THE DIFFERENCE BETWEEN STAR DELTA AND AUTO TRANSFORMER
STARTER? WHY NOT STAR ALWAYS?
Ans: Star Delta method used reduced supply voltage in starting. The method achieved
low starting current by first connecting the stator winding in star configuration, and
then after the motor reaches a certain speed, throw switch changes the winding
arrangements from star to delta configuration. By connecting the stator windings, first
in star and then in delta, the line current drawn by the motor at starting is reduced to
one-third as compared to starting current with the windings connected in delta. At the
time of starting when the stator windings are start connected, each stator phase gets
voltage V(L)/√3 , where V(L) is the line voltage. Since the torque by an induction motor
is proportional to the square of the applied voltage, star- delta starting reduced the
starting torque to one – third that obtainable by direct delta starting.
Auto Transformer
The operation principle of auto transformer method is similar to the star delta starter
method. The starting current is limited by (using a three phase auto transformer)
reduce the initial stator applied voltage. The auto transformer starter is more expensive,
more complicated in operation and bulkier in construction when compared with the
star – delta starter method. But an auto transformer starter is suitable for both star and
delta connected motors, and the starting current and torque can be adjusted to a
desired value by taking the correct tapping from the auto transformer. When the star
delta method is considered, voltage can be adjusted only by factor of 1/√3
AJ NOTES 44
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
36. TWO GENERATOR RUNNING IF ONE GEN LOAD DROPS WHAT IS THE FAULT.?
Ans: Reasons- Engine is not developing power,some problem with governor. Speed
drop set too tight
AJ NOTES 45
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
4. For e.g. there is a moment when lamp A will be dark and lamp B & C will be bright,
similarly there will be instance when B is dark and others are bright and C is dark and
other two are bright. This example indicates that machine is running fast and the
movement of the lamps from dark and bright gives an clockwise movement
5. Clockwise movement indicates fast and anti-clockwise direction indicates slow
running of incoming generator.
40. IF YOU PRESS THE ACB CLOSE BUTTON ON AN IDLE GENERATOR WHAT WILL
HAPPEN?
Ans: Normally, the breaker won’t close until you synchronise, so even if you press the
breaker close, it will not close. The breaker has under-voltage protection which will not
let you close it.
AJ NOTES 46
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 47
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 48
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 49
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
72. WHAT IS DARK LAMP AND BRIGHT LAMP METHOD FOR SYNCHRONIZING? HOW IS
THE CONNECTION MADE?
Ans: Formerly, three light bulbs were connected between the generator terminals and
the system terminals. As the generator speed changes, the lights will rise and fall in
intensity at a rate proportional to the difference between generator frequency and
system frequency. When the voltage at the generator is opposite to the system voltage
(either ahead or behind in phase), the lamps will be bright. When the voltage at the
generator matches the system voltage, the lights will be dark. At that instant, the circuit
breaker connecting the generator to the system may be closed and the generator will
then stay in synchronism with the system.
73. APART FROM RENEWING BEARINGS IS THERE ANY REASON FOR OPENING UP
MOTORS FOR MAINTENANCE?
Ans: Insulation checks and renewal (example using insulation spray on stator winding
insulation).
AJ NOTES 50
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 51
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
92. IF A MOTOR IS WOUND STAR AND YOU WANT TO CHANGE TO DELTA WHAT
SHOULD YOU DO?
Ans: Open the terminal connection box. Remove the shorting link connecting the
common connection (star) point of A2, B2 and C2. With the 3 phase windings marked
A1A2, B1B2, C1C2, connect A2 to B1, B2 to C1 and C2 to A1.
94. WHAT IS THE VOLTAGE AVAILABLE FROM EACH CELL IN A LEAD ACID BATTERY?
Ans: 2 V DC.
AJ NOTES 52
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
-------END-------
AJ NOTES 53
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
SECTION – 3
1. IF ALL YOUR AIR BOTTLES ARE AT LOW PRESSURE AND THERE IS A BLACKOUT HOW
DO YOU START THE GENERATORS?
Ans: If main air bottles are empty, the emergency air bottle can be used to start the
main generator. If even the emergency air bottle is empty, then it can be filled by
running emergency air compressor (powered by emergency generator). Once the
emergency air bottle is filled, this air can be used to start the main generator.
3.EVEN THOUGH THE MAIN ENGINE RUNS AT VARYING SPEEDS, HOW DOES THE
ALTERNATOR MAINTAIN CONSTANT FREQUENCY?
Ans: By use of thyristor controlled frequency (rpm) converters.
4.WHY IS 440 V USED FOR MOTORS AND 110/220 V USED FOR LIGHTING?
Ans: Motor load currents are large. Motors are 3-phase loads. A higher 440V voltage
means lesser current for the same power and hence losses and size of cable wires is
lower. Lighting is single phase loads and its load currents are small, hence lower voltage
means less insulation in the cable wires.
5. FOR A GIVEN LINE VOLTAGE, FOUR HEATING COILS WILL PRODUCE MAXIMUM HEAT
WHEN CONNECTED IN-
Ans: Parallel.
10. THE DIRECTION OF INDUCED EMF CAN BE FOUND WITH THE HELP OF -
Ans: Lenz’s Law.
AJ NOTES 54
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
16.WHAT IS A SOLENOID?
Ans: Single layered coil.
AJ NOTES 55
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
30. WHAT IS THE SPECIFIC GRAVITY OF ELECTROLYTE USED IN LEAD ACID BATTERY?
Ans: 1280 at full charge and 1180 at discharge.
AJ NOTES 56
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
cooling system and starting equipment should be functional i.e, batteries should be
charged fully or air receiver full.
40.WHAT ARE THE TWO MAIN TYPES OF BATTERIES COMMONLY USED ON BOARD
SHIPS?
Ans: Lead acid and alkaline.
AJ NOTES 57
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Once the victim has been removed from the electrical source if the breathing is feasible
or ceased artificial respiration should be started at once. Delay on starting artificial
respiration can prove fatal
Note: if artificial respiration is started once 70% of the victims recover. If there is 3
minutes delay only 20% of the victims recover.
AJ NOTES 58
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
54. HOW DO YOU ENSURE THAT BATTERIES ARE ALWAYS IN GOOD WORKING ORDER?
Ans: Where lead acid batteries are used they require a constant trickle charge, but for
both types of batteries a regular charge of up is necessary.
Check state of battery reaching a hydrometer; lead acid – specific gravity 1270. Alkaline
is 1190 but SB for alkaline batteries does not change much during charge or discharge
Ensure cells are covered with electrolyte if not top up with distilled water. Keep
batteries dry and clean
Terminals should be smeared with petroleum jelly.
55. What are the advantages and disadvantages of shaft generator on ships?
Ans: Advantages
1.Slightly reduce total fuel consumption.
2.Reduced running hours of auxiliary generator.
3.Reduced noise in E/R.
4.Can made overhauling the G/E at sea.
Disadvantages
1.Cannot be used at rough sea.
2.Increase load on main engine
3.More complicated mechanism.
4.Complete black on main engine slow down.
AJ NOTES 59
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
57. What is earth lamp? How will you know when earth fault occur and how to trace it?
Ans: - It is a set of lamps, which show the presence of earth fault in distribution system.
- Each lamp is connected between one phase and common neutral point.
- If earth fault occurs the lamp will show dim light or goes out because potential is zero.
- The location of fault can be traced by switching off the individual branch circuit
breaker and check the condition of earth lamp.
- When the branch circuit with the fault is switched off, the earth lamp will return to
normal brightness.
AJ NOTES 60
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Ans: -Ammeter
-Voltmeter
-Wattmeter
-Frequency meter
-Ohm meter
-Synchroscope.
AJ NOTES 61
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Fuse
1. Have only breaking function, and fitted in the circuit to protect the circuit from
damaging effect of high current flow
2. It breaks the circuit by melting the fuse metal itself
3. After breaking, the blown fuse must be renewed
AJ NOTES 62
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Ventilation
- Independent exhaust fan provided
- Inlet duct should be below battery level, and outlet at top of the compartment
AJ NOTES 63
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
73. How can you know battery is over charge ? Effect of overcharge ?
Ans: - When battery is overcharged bubbles will form at the surface, the current flowing
into the cell causes breakdown or electrolysis of water in the electrolyte.
- Both hydrogen and oxygen are evolved and released through cell vent caps into the
battery compartment.
- There is an explosion risk if hydrogen is allowed to accumulate. (4% of H2 in air).
Depolarisation
Liberation of hydrogen ions at – ve electrode (cathode) and that will decrease the
current flow.
AJ NOTES 64
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 65
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Exciters
The source, which generates the field current for excitation of field magnets.
Equalizing bar
Equaliser is a low resistance circuit, connected across armature ends of series coils of
parallel compound generators, via a special bar in switchboard
Equaliser is fitted to stabilize parallel operation of compound Dc generators.
Rotary converter
1. A rotating diode to convert AC to DC current for alternator excitation
2. Synchronous motor and generator combined unit
3. Filed and armature coils are similar to DC generator, except that slip rings are located
on the end of the shaft opposite to commutator
4. AC turns the converter (as synchronous motor) and DC is taken from commutator
brush
AJ NOTES 66
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
3.On load, practically check for excessive temperature rises and load sharing stability
when running in parallel.
86. How to parallel the two generator with the aid of synchroscope on ships ?
Ans: 1. All meters and indicators must have in good working order.
2. Start the incoming generator with the correct staring procedure.
3. Check the working condition by readings pressure gauges, thermometer and audible
and visual.
4. Watch for a minutes until prime mover come to stable.
5. Check the voltage of existing and incoming generator on the switchboard, check trip if
have reset.
6. Move the selector switch to incoming generator. At that time, synchroscope pointer
will rotate clockwise or counter clockwise direction.
7. Check the frequency and voltage of existing and incoming.
AJ NOTES 67
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
8. Carry out the adjustment by means of speed adjuster of prime mover to obtain the
condition such that synchroscope pointer rotate in the clockwise direction at a speed of
about 4sec/rev.
9. Close the circuit breaker of incoming generator when the pointer reaches just before
12‘ O clock position.
10. Made off the selector switch.
11. Made load shearing the two generators by the speed adjuster of generator.
87. How do you parallel the two generators if synchroscope is out of order ?
Ans: 1. If synchroscope is out of order, the two generators can be paralleled by
emergency synchronizing lamps with sequence method.
2. The lamps are fitted as triangle forms, one on top and two on bottom.
3. To make parallel, reset if any trip
4. Move the selector switch to incoming generator. At that time, synchronizing lamps
will give bright and dark sequence rotate clockwise or counter clockwise direction.
5. Check the frequency and voltage of existing and incoming.
6. Carry out the adjustment by means of speed adjuster of prime mover to obtain the
required frequency.
7. Adjust the speed to meet the slow clockwise direction.
8. Incoming machine breaker is closed by hand when the top lamp (key lamp) dark and
the both bottom lamps are equal brightness.
9. Off the selector switch and make load sharing the two generators by speed adjusting.
88. How do you monitor the correct instant for synchronizing without the aid of
synchroscope or synchronizing lamps ?
Ans: 1. It can be synchronized with 500V voltmeter as follow.
2. Connect a pair of 500V voltmeter probes across the one phase of the incoming
machine circuit breaker and bus bar.
3. Adjust the generator speed until the voltmeter slowly fluctuates from zero to
maximum.
4. Close the breaker when the voltmeter passes through zero.
89. Can you parallel the load of main G/E with emergency G/E and shore supply ?
Ans: It cannot paralleled, circuit breaker interlocks are arranged in this system.
AJ NOTES 68
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 69
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
-------END-------
AJ NOTES 70
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
SECTION – 4
1. How to prevent Static Electricity hazards in oil tanker ?
Ans: 1. Earthing device, earth bond across flanges on pipeline
2. Inert gas
AJ NOTES 72
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
Open circuit:
The path for the flow of current is broken. A switch s one method of creating an
―open‖ intentionally
Grounded circuit:
A circuit that has come in contact with the earth, by coming in contact somewhere in
itself, or by a conductor which is connected with the earth
Shore connection on ships:
Shore connection box is provided at convenient position, to receive shore power supply,
so that ship‘s generators can be shut down, in port or during Dry Docking.
13. How will you check the frequency of shore power supply ?
Ans: 1. Shore power supply connection box shows phase sequence of shore power
generator with bright and dark lights
2. Frequency can be check at Main Switchboard, after shore supply is ‗on‘ through link
switch or circuit breaker.
16.Causes of Overheating ?
Ans: 1. Overloading
2. Blocking up of ventilation passages with dirt
AJ NOTES 73
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 74
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
AJ NOTES 75
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
2.Out going material negative, remaining material positive. After having high potential
spark occur.
3.This is occurs in thin oil. Explosion occurs when tank cleaning operation and gas
freeing operation.
AJ NOTES 76
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
This allows less people to control more machinery in a more accurate and efficient
manner.
36.Why normal insulation resistance (IR) values are unreliable for high voltage
machinery ?
Ans: 1.IR values taken for a machinery at different temperatures are unreliable,
especially when the temperature difference is more than 10 °C.
2.Also for high voltage system, it takes to stabilise the IR values. So instantaneous
readings may lead to false interpretations.
AJ NOTES 77
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
3.This resistive heating produces hot spots or over heated areas. It is unsafe and may
gradually reduce useful life time of the equipment.
40.How the hot spots in the bus bars or surrounding area is checked ?
Ans: 1. It is necessary to keep the system running live to analyse any hot spots.
2.A recording infrared camera can take thermal images of different parts of the system
from a safe distance.
3.These thermal images are processed in a computer program to display hot spots and
temperature variations.
AJ NOTES 78
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
So for an electric motor, working in high voltage system draw very low current
compared to that of low voltage system. As current carrying capacity of conductor
reduces, size of the conductor can also be reduced much. This considerable reduction in
conductor material result in reduced size of machinery and save space for installation.
43. Why copper loss and iron loss is less in high voltage system ?
Ans: From the above comparison on current flow between a high voltage system and
low voltage system, it is clear that current draw with high voltage is much lesser. Hence
copper loss or I²R losses and iron loss are considerably lesser.
44. What is meant by arcing, arc flash and arc blast in high voltage system ?
Ans: - Arcing is the production of unintentional electric arc during opening circuit
breaker, isolator or contactor due to the discharge of electricity through the medium
between the two contacts. (In fact arcing occurs during closing the breaker also).
- Arcing also occurs when heavy current flow to earth during an earth fault or short
circuit fault due to insulation failure.
- During arcing temperatures at the arc terminals can go upto 20000 ºC or more, which
is around 4 times the temperature of sun‘s surface.
- The intense light formed at the point of arc is called as arc flash.
- Instant heating of air surrounding the arc occurs and conductors vaporises, resulting
in formation of a high pressure wave. If the pressure wave is not released, it results in
an explosion called arc blast.
AJ NOTES 79
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
additional switching to reverse the controlled motor depending upon the compounding
arrangements.
The driving motor or prime motor for the Ward Leonard System can be a dc
motor, an ac motor, a diesel engine, etc. Any form of constant and almost constant speed
drive can be used, since its function is only to drive the generator.
Troubleshooting Alarm Monitoring and Control System on ships
Faults in Alarm Monitoring and Control System
The alarm monitoring and control system on the ship may give false alarms and
incorrect data printouts. These faults could be:
1. Localized to a particular area of engine operation or
2. General to the engine room
When the alarms are specific to a certain area of the engine room it would be suspected
that the following faults could be present
1.Cable fault: If the cable connecting the sensors with the control room were damaged,
the resulting short/open circuits could generate false alarms
2.Control card/panel fault: The alarms could be grouped within a certain alarm or
monitoring panel, and there could be a defect within this panel.
3.External interference: Machinery could be operating in the suspect area, which is
poorly screened, and the resulting interference could be transmitted via the instrument
cables to the monitoring panels.
When the alarms are general to the whole engine room, then the main supply to the
alarm and monitoring panel would be checked for:
1.Earth faults: A combination of earth faults could affect the earth potential and hence
the reading of the instrumentation.
2.Supply voltage level: The monitoring circuit would use low 24V supply, and this would
need to be at the correct level without any voltage ripple present.
The following action should be taken to ensure continued safe operation of the vessel if
the defects with alarm monitoring and control system were general to the engine room.
- The problem with intermittent alarms and incorrect printouts would be that the
engineer on duty would be unable to rely on the information given to him by the remote
instrumentation and alarm panel. Hence a greater use would need to be taken of the
local readings from pressure gauges and thermometers.
- This would mean that the UMS operation would be stopped and watch-keeping
practices with a manned engine room would be commenced. The watch keepers would
be instructed to complete a full manual log of the various operational parameters of
pressure, temperature and the various tank levels. This manual log would be taken
every watch period of four hours.
- The engineering staff would be divided between the various watch duties, ensuring
that all watch keepers were certified and had the appropriate duty and rest periods
assigned to them.
- Any machinery units requiring manual control would have their operation explained
to all engineers, and a procedural checklist compiled for the operation of all such
machinery.
AJ NOTES 80
MEO CLASS 4 – ELECTRICAL
ORAL QUESTIONS WITH ANSWERS
NOTES
AJ NOTES 81