Operating Manual: Touchmatrix Indicator Dx350 / Dx355
Operating Manual: Touchmatrix Indicator Dx350 / Dx355
Product features:
Available options:
DX350: Basic unit with HTL inputs (A, B), 3 control inputs
DX355: Basic unit with HTL/RS422 inputs (A, /A, B, /B), 3 control inputs
Version: Description
DX350_01a_oi/sn- tg /Jul-20 First Version
DX350_01d_oi/cn/Okt-16 Revised first Version
DX350_02a_oi/cn/Nov-16 Second Version
DX350_02c_oi/cn/Jan-17 Revised Version
DX350_03a_oi/cn/Apr-17 Revised Version
DX350_03b_oi/cn/Jun-17 Other small changes
DX350_04a_oi/cn/Sep-17 Extension DX355, software customization
DX350_05a_oi/cn/April-18 Extension of serial interface with Modbus protocol
DX350_05b_oi/cn/June-18 Addendum to Modbus et accuracy
DX350_05c_oi/cn/July-18 With Modbus description
DX350_06a_oi/tgo/Mar-19 Extension of large display, total counter and total time measurement
DX350_06b_oi/mbo/Aug-19 Extension of QR-code
DX350_06c_oi/tgo/Nov-19 Extension of the “Preselection Mode” and “Input Action”
DX350_06d_oi/mbo/July-20 Extension of chapter 1.4 “EMC Guidelines”, various revisions
Therefore the following measures are mandatory for a successful installation and operation:
Use shielded cables for all signal and control input and output lines.
Cables for digital controls (digital I/O, relay outputs) must not exceed a length of 30 m and are allowed for in
building operation only
Use shield connection clamps to connect the cable shields properly to earth
The wiring of the common ground lines must be star-shaped and common ground must be connected to earth
at only one single point
The device should be mounted in a metal enclosure with sufficient distance to sources of electromagnetic
noise.
Run signal and control cables apart from power lines and other cables emitting electromagnetic noise.
Please also refer to motrona manual “General Rules for Cabling, Grounding, Cabinet Assembly”. You can download
that manual by the link
https://www.motrona.com/en/support/general-certificates.html
• SPEED (only Input A or Input B are used, depending on the parameter setting)
- Tachometers / speed indicator
- Measurement of frequency / RMP indicator
- Monitoring functions for speed and standstill
• PROCESS TIME (only input A is used)
- Processing time indicator (reciprocal speed)
- Baking time indicator
- Flow time indicator
• TIMER (only Input A or Input B are used, depending on the parameter setting)
- Operation as stopwatch (start- / stop function can be freely parameterized)
- Counter for operation hours
- Period measurement
- Total time measurement
• COUNTER (input A and input B are used)
- Pulse counter / sum or differential counter
- Up- or down counter
- Position indicator
- Quadrature counter
- Batch counter / total counter
• VELOCITY (Input A operates as a start input and input B operates as a stop input)
- Runtime measurement as speed indicator.
DX350 DX355
DC Power Supply
The unit accepts DC supply from 18 to 30 V at the terminals 1 and 2. The power consumption depends on the
level of the supply voltage with aprox. 100 mA and the additional current required at the Auxiliary Voltage
Output.
All GND terminals are internally interconnected.
DC version AC version
The encoder voltage is 24 VDC (± 15%) and
The encoder voltage is approx. 1 V lower than should be loaded with max. 150 mA up to 45
the power supply voltage at terminal 1 and 2 degrees Celsius. At higher temperature the
and should be loaded with max. 250 mA. maximum output current is reduced to 80 mA.
At DX355 devices, the auxiliary voltages output is switchable from 24 VDC to 5 VDC.
Namur Tri-State
Unconnected PNP inputs are always “LOW” and unconnected NPN inputs are always “HIGH”.
All inputs are designed to receive impulses from electrical impulse sources.
Notice for mechanical switching contacts:
When exceptionally mechanical contacts are used, please connect an external capacitor between GND (-) and
the corresponding input (+). A capacity of 10 µF will reduce the input frequency to
20 Hz and miscounting due to contact bouncing will be eliminated.
Unconnected PNP inputs are always “LOW” and unconnected NPN inputs are always “HIGH”.
All inputs are designed to receive impulses from electrical impulse sources.
Important:
A parallel operation with voltage and current output at the analog output is not allowed.
Control-Output (AO/AR/CO/CR)
Four control outputs are available at terminal 20, 21, 22 and 23.
Switching conditions can be set in the PRESELECTION MENU. The output Ctrl. Out1 – 4 are fast PNP outputs
with a switching capability of 5 – 30 Volt / 200 mA per channel. The switching states is displayed (display
with unit and status bar) as C1 … C4.
The switching voltage of the outputs must be applied to input terminal 19 (COM+).
In case of switching inductive loads it is advisable to use external filtering of the coils.
Menu selection:
Select the parameter menu via arrow buttons and
confirm with “OK”.
The menu selection can be terminated
with „C“.
Parameter selection:
Select the parameter via arrow buttons and
confirm with „OK“.
Parameter editing:
Edit the parameter via arrow button up and down,
shift cursor via left and right and save with „OK“.
Parameter changes becomes active only after closing the menu selection.
Error messages
The error messages described are automatically reset as soon as the corresponding display
value is within the representable range.
OPERATIONAL MODE
This parameter specifies the selected measuring function.
0 SPEED Speed indicator (RPM), tachometer or frequency counter
1 PROCESS TIME Operation as baking time or processing time indicator (reciprocal speed)
2 TIMER Operation as stopwatch
3 COUNTER Operation as position indicator, event-, sum-, differential- or up-down counter
4 VELOCITY Runtime measurement as speed indicator
COUNTING DIRECTION
This parameter determines the direction of counting. (Only in mode COUNTER)
0 FORWARD forward
1 REVERSE reverse
SCALE UNITS
This parameter defines the required engineering unit. This parameter does not affect the calculation of the display value. The number
of decimal places must be defined with the parameter DECIMAL POINT. For the two-line display the unit set as well as the decimal
point of the display value are automatically taken for the total counter or total timer, too. The unit for the batch counter can
separately be selected by using SCALE UNITS (BATCH).
0 Hz Default
1 kHz
2 m/s
3 m/min
4 km/h
5 mph
6 1/min
7 RPM
8 1/sec
9 RPS
10 Stk/h
11 pcs/h
12 mm
13 m
14 inch
15 feet
16 Stueck
17 pcs
18 sec
19 min
20 Min:Sec
21 H:M:S
22 Min:Sec:00
23 l/min
24 gal/min
25 ml/min
26 gr/min
27 inch/min
28 H:M
29 Edit Unit A customized unit with up to 16 digits can be edited using this parameter.
Pressing the "OK" button opens the Edit Unit Menu.
A unit can be created using the arrow keys. (by pressing and holding the arrow keys the
characters scroll fast).
The “OK” butten saves the Edit Unit Menu. The “C” button closes the Edit Unit Menu.
! " # $ % & ' ( ) * + , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
@ A B C D E F G H I J K L M N O
P Q R S T U V W X Y Z [ \ ] ^ _
` a b c d e f g h i j k l m n o
p q r s t u v w x y z { | } ~
LINEARIZATION MODE
This parameter defines the linearization function. See chapter 6.1.
0 OFF No linearization
1 1 QUADRANT Linearization in the 1. quadrant
2 4 QUADRANT Linearization in all 4 quadrants
PIN PRESELECTION
This parameter defines the PIN-code to lock the quick start of the menu PRESELECTION VALUE for entering the
preselection values. (Master PIN 6079).
This Lock function is only useful in conjunction with active lock function in PIN PARAMETER.
0000 No lock
…
9999 Access after entering PIN-Code 9999
PIN PARAMETER
This parameter defines the PIN-code for lock function of all parameters (master PIN 6079).
0000 No lock
…
9999 Parameterization of the unit after entering PIN-code 9999
BACK UP MEMORY
0 NO No back memory –up by power failure
1 YES Backup memory by power failure, actual value will be saved
FACTORY SETTINGS
0 No No default values are loaded
1 Yes Load default values of all parameters (grey marked default values)
DISPLAY VALUE
Desired value, which should be displayed at the setting of BASE FREQUENCY.
1 Smallest value
1000 Default value
99999999 Highest value
DECIMAL POINT
This value defines the position of the decimal point.
0 NO No decimal point
1 0000000.0 Decimal point at the specified position
2 000000.00 Decimal point at the specified position
3 00000.000 Decimal point at the specified position
4 0000.0000 Decimal point at the specified position
5 000.00000 Decimal point at the specified position
6 00.000000 Decimal point at the specified position
7 0.0000000 Decimal point at the specified position
AVERAGE FILTER
Selectable average or filter function to avoid measuring fluctuations by unstable frequencies. At setting 1 to 4 a
floating average calculation is performed. At settings 5 to 8, the device uses an exponential filter. The time constant T
(63%) corresponds to the sampling cycles.
For example: If SAMPLING TIME = 0,1 s and AVERAGE FILTER = Exponential filter, T (63 %) = 2x SAMPLING TIME,
after 0,2 seconds, 63% of the step size are reached
0 No average value will be created
1 2 numbers of floating average cycles
2 4 numbers of floating average cycles
3 8 numbers of floating average cycles
4 16 numbers of floating average cycles
5 Exponential filter, T (63 %) = 2x SAMPLING TIME
6 Exponential filter, T (63 %) = 4x SAMPLING TIME
7 Exponential filter, T (63 %) = 8x SAMPLING TIME
8 Exponential filter, T (63 %) = 16x SAMPLING TIME
FOR/REV DETECTION
This parameter enables the detection of direction of rotation (Input A, Input B with 90°).
0 OFF Direction of rotation detection off
1 ON Direction of rotation detection on
DISPLAY FORMAT
This parameter selects the Display Format. The corresponding decimal point will be set automatically.
0 SECONDS Display in seconds
1 MINUTES Display in minutes
2 MIN:SEC Display in minutes : seconds
3 MIN.00 Anzeige in Minuten und 1/100 Minuten
4 H:M:S Anzeige in Stunden : Minuten : Sekunden
DISPLAY VALUE
Desired value, which should be displayed at the setting of BASE FREQUENCY.
1 Smallest value
1000 Default value
99999999 Highest value
AVERAGE FILTER
Selectable average or filter function to avoid measuring fluctuations by unstable frequencies. At setting 1 to 4 a
floating average calculation is performed. At settings 5 to 8, the device uses an exponential filter. The time constant T
(63%) corresponds to the sampling cycles.
For example: If SAMPLING TIME = 0,1 s and AVERAGE FILTER = Exponential filter, T (63 %) = 2x SAMPLING TIME,
after 0,2 seconds, 63% of the step size are reached
0 No average value will be created
1 2 numbers of floating average cycles
2 4 numbers of floating average cycles
3 8 numbers of floating average cycles
4 16 numbers of floating average cycles
5 Exponential filter, T (63 %) = 2x SAMPLING TIME
6 Exponential filter, T (63 %) = 4x SAMPLING TIME
7 Exponential filter, T (63 %) = 8x SAMPLING TIME
8 Exponential filter, T (63 %) = 16x SAMPLING TIME
START / STOP
This parameter defines the start/stop condition of the time measurement.
0 COUNT AT A HIGH Time measurement active at Input A is „HIGH“
1 COUNT AT A LOW Time measurement active at Input A is „LOW“
A rising edge at Input A starts the time measurement,
2 START A / STOP B
a rising edge at Input B stops the time measurement.
Period time measurement:
3 PERIODE AT A
displays the time between two rising signal edges at Input A
LATCH-FUNCTION
0 NO Real time display, counting value is visible.
Display shows the result of the last measurement.
1 YES
The time counts in the background.
SET VALUE.
In case of a set / reset command (via keyboard shortcut, control input, or PC user interface), the timer is set to SET
VALUE
0 Smallest value (Reset)
…
99999999 Highest value
Example:
For the total time measurement TOTAL TIME MODE has to be set to YES. The total time measurement runs parallel to
the normal time measurement. If the total time measurement should be automatically reset to O when 1:30 (H:M) is
reached, the reference source must be set e. g. to “SOURCE1”from the corresponding preselection menu to “TOTAL
TIMER”, the corresponding preset value e. g. “PRESELECTION 1” to “1:30” and the corresponding switching condition
“MODE1” to"RESULT> = PRES-> 0"
0 NO No total time measurement
1 YES Total time measurement activated
COUNT MODE
This parameter defines the counter operation.
Input A is a counting input. Input B defines the counting direction:
0 A SINGLE
„LOW“ = forward „HIGH“ = reverse
1 A+B Sum counter: Impulses at A + Impulses at B
2 A-B Differential counter: Impulses at A – impulses at B
3 A/B 90 x1 Quadrature counter: Impulses A, B with edge counting x1
4 A/B 90 x2 Quadrature counter: Impulses A, B with edge counting x2
5 A/B 90 x4 Quadrature counter: Impulses A, B with edge counting x4
FACTOR
Scaling factor. With the summing mode (A+B) and the differential mode (A-B) please note
that the impulse scaling factor will only affect input A
For example: A setting of factor 1.23456 and 100000 input pulses will result in a value of 123456.
0.00001 Smallest value
1 Default value
99.99999 Highest value
SET VALUE
In case of a reset command (via keys, Control-Inputs or PC-user interface), the counter is set to the value entered
here.
-99999999 Smallest value
0 Default value
+99999999 Highest value
DECIMAL POINT
This value defines the position of the decimal point.
0 NO No decimal point
1 0000000.0 Decimal point at the specified position
2 000000.00 Decimal point at the specified position
3 00000.000 Decimal point at the specified position
4 0000.0000 Decimal point at the specified position
5 000.00000 Decimal point at the specified position
6 00.000000 Decimal point at the specified position
7 0.0000000 Decimal point at the specified position
START / STOP
Setting the start and stop condition.
Start = rising edge at input A
RISE TO RISE
Stop = rising edge at input B
Start = falling edge at Input A
FALL TO FALL
Stop = falling edge at Input B
Start = rising edge at input A
RISE TO FALL
Stop = falling edge at Input B
Start = falling edge at Input A
FALL TO RISE
Stop = rising edge at input B
DISPLAY VALUE
Desired value, which should be displayed at the setting of BASE TIME (S).
1 Smallest value
1000 Default value
999999 Highest value
DECIMAL POINT
This value defines the position of the decimal point.
0 NO No decimal point
1 0000000.0 Decimal point at the specified position
2 000000.00 Decimal point at the specified position
3 00000.000 Decimal point at the specified position
4 0000.0000 Decimal point at the specified position
5 000.00000 Decimal point at the specified position
6 00.000000 Decimal point at the specified position
7 0.0000000 Decimal point at the specified position
STANDSTILL TIME
This parameter defines the time setting for standstill definition.
A time of xx.xx seconds after detection " frequency = 0 Hz " the unit signals "standstill" and reactivates the start-up-
delays. Stand still detection can be set in PRESELECT MENU.
This STANDSTILL TIME is suitable at WAIT TIME unequal 0.000 only.
0.00 Shortest time
…
99.99 Longest time
PRESELECTION 1
Preselection / switching point 1
-99999999 Smallest value
1000 Default value
+99999999 Highest value
PRESELECTION 2
Preselection / switching point 2
-99999999 Smallest value
2000 Default value
+99999999 Highest value
PRESELECTION 3
Preselection / switching point 3
-99999999 Smallest value
3000 Default value
+99999999 Highest value
PRESELECTION 4
Preselection / switching point 4
If the BATCH / TOTAL MODE or TOTAL TIME MODE is active, the batch counter / total counter or total timer is
compared with the preselection value 4.
-99999999 Smallest value
4000 Default value
+99999999 Highest value
This function is only available for devices with option CO, AO or RL.
SOURCE 1
This parameter defines the reference source for preselection 1
0 MEASUREM. RESULT Reference source is the measurement result of the selected operating mode
Reference source is the counter reading of channel A.
1 COUNTER A
(only visible in mode COUNTER COUNT MODE: A+B or A-B)
Reference source is the counter reading of channel B.
2 COUNTER B
(only visible in mode COUNTER COUNT MODE: A+B or A-B)
Reference source is the batch counter.
3 BATCH COUNTER (only visible in mode COUNTER BATCH / TOTAL MODE:
INCREMENT BATCH, DECREMENT BATCH or USE INPUTS ONLY)
Reference source is total counter.
4 TOTAL COUNTER
(only visible in mode COUNTER BATCH / TOTAL MODE: TOTAL COUNTER)
Reference source is the total timer.
5 TOTAL TIMER
(only visible in mode TIMER TOTAL TIME MODE: YES)
MODE 1
Switching conditions for preselection 1. Output/ relay/ display switches under the following conditions:
Absolute value of the display value is greater or equal absolute value of
PRESELECTION 1
0 |RESULT|>=|PRES| With HYSTERESIS 1 not equal 0 the following switching condition is applied:
Display value >= PRESELECTION 1 ON,
Display value < PRESELECTION 1 – HYSTERESIS 1 OFF
Absolute value of the display value is less or equal absolute value of
PRESELECTION 1 (start-up suppression (START UP DELAY) is advisable)
1 |RESULT|<=|PRES| With HYSTERESIS 1 not equal 0 the following switching condition is applied:
Display value <= PRESELECTION 1 ON,
Display value > PRESELECTION 1 + HYSTERESIS 1 OFF
Absolute value of the display value is equal absolute value of PRESELECTION 1
A range (Preselection +/- ½ Hysteresis) can be defined and monitored in
conjunction with the hysteresis.
2 |RESULT|=|PRES|
With HYSTERESIS 1 not equal 0 the following switching condition is applied:
Display value > PRESELECTION 1 + ½ HYSTERESIS 1 OFF,
Display value < PRESELECTION 1 - ½ HYSTERESIS 1 OFF
Display value is greater or equal PRESELECTION 1, e.g. overspeed
With HYSTERESIS 1 not equal 0 the following switching condition is applied:
3 RESULT>=PRES
Display value >= PRESELECTION 1 ON,
Display value < PRESELECTION 1 – HYSTERESIS 1 OFF
Display value is less or equal PRESELECTION 1, e.g. underspeed
(start-up suppression (START UP DELAY) is advisable)
4 RESULT<=PRES With HYSTERESIS 1 not equal 0 the following switching condition is applied:
Display value <= PRESELECTION 1 ON,
Display value > PRESELECTION 1 + HYSTERESIS 1 OFF
Display value is equal PRESELECTION 1. A range (Preselection +/- ½ Hysteresis)
can be defined and monitored in conjunction with the hysteresis.
5 RESULT=PRES With HYSTERESIS 1 not equal 0 the following switching condition is applied:
Display value > PRESELECTION 1 + ½ HYSTERESIS 1 OFF,
Display value < PRESELECTION 1 - ½ HYSTERESIS 1 OFF
Display value is zero (Standstill after STANDSTILL TIME(s)),
6 RESULT=0
e. g. standstill monitoring, (only in mode SPEED and PROCESS TIME).
Auto reset to zero: (only in mode TIMER or COUNTER)
Display value is greater or equal PRESELECTION 1, the display value is set to
zero.
7 RESULT>= PRES->0
If the BATCH MODE is active, the batch counter increments or decrements when
the display value is set to zero and when the corresponding source of supply
MEASUREM. RESULT, COUNTER A or COUNTER B was selected.
Auto set to PRESELECTION 1: (only in mode TIMER or COUNTER)
Display value is less or equal zero, the display value is set to PRESELECTION 1
8 RESULT<= 0->SET If the BATCH MODE is active, the batch counter increments or decrements when
the display value is set to PRESELECTION 1 and when the corresponding source
of supply MEASUREM. RESULT, COUNTER A or COUNTER B was selected.
Trailing PRESELECTION 1:
9 RES>=PRES-TRAIL Display value is greater or equal PRESELECTION 2 – PRESELECTION 1 ON,
PRESELECTION 1 is the trailing value from PRESELECTION 2
HYSTERESIS 1
This parameter defines the switching hysteresis of the switch-off point for preselection 1
0 No switching hysteresis
…
9999 Switching hysteresis of 99999
OUTPUT TARGET 1
Assignment of an output or relay for the switching condition of preselection 1.
If more than one switching condition is assigned to one output / relay, the output is set when at least one switching
condition is true
0 NO No assignment
1 CTRL OUT 1 Switching condition assigned to “Ctrl. Out 1”
2 CTRL OUT 2 Switching condition assigned to “Ctrl. Out 2”
3 CTRL OUT 3 Switching condition assigned to “Ctrl. Out 3”
4 CTRL OUT 4 Switching condition assigned to “Ctrl. Out 4”
5 RELAY 1 Switching condition assigned to “Rel. 1”
6 RELAY 2 Switching condition assigned to “Rel. 2”
OUTPUT POLARITY 1
Polarity for the switching condition of preselection 1
0 ACTIVE HIGH Switching condition is true Active „HIGH“
1 ACTIVE LOW Switching condition is true Active „LOW“
OUTPUT LOCK 1
Latch for the switching condition of preselection 1
0 NO No latch for preselection
1 YES Latch for preselection (command LOCK RELEASE will clear latch)
EVENT COLOR 1
Event-depending change of the display color for the switching condition of preselection 1.
EVENT COLOR 1 has the lowest priority. EVENT COLOR 2 … 4 are allowed to overwrite this color change.
0 NO CHANGE No color change.
1 CHANGE TO RED Color change to red
2 CHANGE TO GREEN Color change to green
3 CHANGE TO YELLOW Color change to yellow
SOURCE 2
The reference source for PRESELECTION 2, see PRESELECTION 1 MENU.
MODE 2
Switching conditions for preselection 2. Output/ relay/ display switches under the following conditions:
See chapter PRESELECTION 1 MENU
Trailing preselection 2:
9 RES>=PRES-TRAIL Display value is greater or equal to PRESELECTION 1 – PRESELECTION 2 ON,
PRESELECTION 2 is the trailing preselection from PRESELECTION 1.
HYSTERESIS 2
This parameter defines the switching hysteresis of the switch-off point for preselection 2.
See chapter PRESELECTION 1 MENU.
OUTPUT TARGET 2
Assignment of an output or relay for the switching condition of preselection 2.
See chapter PRESELECTION 1 MENU.
OUTPUT POLARITY 2
Polarity for the switching condition of preselection 2.
See chapter PRESELECTION 1 MENU.
OUTPUT LOCK 2
Latch for the switching condition of preselection 2.
See chapter PRESELECTION 1 MENU.
EVENT COLOR 2
Event-depending change of the display color for the switching condition of preselection 2.
See chapter PRESELECTION 1 MENU.
MODE 3
Switching conditions for preselection 3. Output/ relay/ display switches under the following conditions:
See chapter PRESELECTION 1 MENU
Trailing preselection 3:
9 RES>=PRES-TRAIL Display value is greater or equal to PRESELECTION 4 – PRESELECTION 3 ON,
PRESELECTION 3 is the trailing preselection from PRESELECTION 4.
HYSTERESIS 3
This parameter defines the switching hysteresis of the switch-off point for preselection 3.
See chapter PRESELECTION 1 MENU.
OUTPUT TARGET 3
Assignment of an output or relay for the switching condition of preselection 3.
See chapter PRESELECTION 1 MENU.
OUTPUT POLARITY 3
Polarity for the switching condition of preselection 3.
See chapter PRESELECTION 1 MENU.
OUTPUT LOCK 3
Latch for the switching condition of preselection 3.
See chapter PRESELECTION 1 MENU.
START UP DELAY 3
Start-up suppression for the switching condition of preselection 3.
This adjustment is only valid for the switching condition |RESULT|<=|PRES| or RESULT<=PRES and
mode SPPED and PROCESS TIME. (Start Up Delay 1 and 2 have a time-dependent start up suppression).
0 OFF No start-up suppression
Automatic start up suppression,
1 AUTO
until the preselection value / switching point is exceeded for the first time.
EVENT COLOR 3
Event-depending change of the display color for the switching condition of preselection 3.
See chapter PRESELECTION 1 MENU.
MODE 4
Switching conditions for preselection 4. Output/ relay/ display switches under the following conditions:
See chapter PRESELECTION 1 MENU
Trailing preselection 4:
9 RES>=PRES-TRAIL Display value is greater or equal to PRESELECTION 3 – PRESELECTION 4 ON,
PRESELECTION 4 is the trailing preselection from PRESELECTION 3.
HYSTERESIS 4
This parameter defines the switching hysteresis of the switch-off point for preselection 4.
See chapter PRESELECTION 1 MENU.
OUTPUT TARGET 4
Assignment of an output or relay for the switching condition of preselection 4.
See chapter PRESELECTION 1 MENU.
OUTPUT POLARITY 4
Polarity for the switching condition of preselection 4.
See chapter PRESELECTION 1 MENU.
OUTPUT LOCK 4
Latch for the switching condition of preselection 4.
See chapter PRESELECTION 1 MENU.
START UP DELAY 4
Start-up suppression for the switching condition of preselection 4.
This adjustment is only valid for the switching condition |RESULT|<=|PRES| or RESULT<=PRES and
mode SPPED and PROCESS TIME. (Start Up Delay 1 and 2 have a time-dependent start up suppression).
0 OFF No start-up suppression
Automatic start up suppression,
1 AUTO
until the preselection value / switching point is exceeded for the first time.
EVENT COLOR 4
Event-depending change of the display color for the switching condition of preselection 4.
See chapter PRESELECTION 1 MENU.
SERIAL FORMAT
This parameter defines the bit data format.
0 7-EVEN-1 7 data Parity even 1 Stop
1 7-EVEN-2 7 data Parity even 2 Stops
2 7-ODD-1 7 data Parity odd 1 Stop
3 7-ODD-2 7 data Parity odd 2 Stops
4 7-NONE-1 7 data no Parity 1 Stop
5 7-NONE-2 7 data no Parity 2 Stops
6 8-EVEN-1 8 data Parity even 1 Stop
7 8-ODD-1 8 data Parity odd 1 Stop
8 8-NONE-1 8 data no Parity 1 Stop
9 8-NONE-2 8 data no Parity 2 Stops
SERIAL INIT
This parameter defines the baud rate for the initialization to the user interface OS6.0. With settings larger than 9600
the initialization time can be reduced.
0 NO Initialization with 9600 baud. Then the device operates with the value selected by the user.
Initialization with the baud rate set by SERIAL BAUD RATE. Then the device operates with
1 YES
the value selected by the user.
SERIAL PROTOCOL
Determines the sequence of characters send, when using the serial output for cyclic data transmission under time
control (xxxxxxx = value SERIAL VALUE).
Setting „1“ removes the unit address from the string which allows a slight faster transmission cycle.
Transmission report = Unit Nr., +/-, data, LF, CR
0
1 1 +/- X X X X X X X LF CR
This register determines the cycle time in seconds for cycling transmission of SERIAL VALUE when using the serial
output. (On a serial request, the cycling transmission is stopped for 20 s)
All cyclic transmission is switched off. The unit will send data upon a serial request or
0.000
with command SERIAL PRINT.
…
60.000 Cycle time in seconds.
SERIAL VALUE
This parameter defines the value to be transmitted.
Setting Code Register contents
0 :0 Measurement_Result
1 :1 Speed_Value
2 :2 Time_Result
3 :3 Counter
4 :4 Velocity_Speed
5 :5 Batch_Counter
6 :6 Minimal_Value
7 :7 Maximal_Value
8 :8 Counter_Total
9 :9 Time_Result_Total
MODBUS
This parameter enables the Modbus protocol and determines the Modbus address.
For details of the Modbus communication please refer to the additional manual Modbus_RTU
Modbus disabled
0
Serial interface is using Lecom protocol (Motrona default protocol)
Modbus enabled: Serial interface is using Modbus RTU protocol
1 … 247
The set value is the Modbus address of the device.
ANALOG FORMAT
This parameter defines the output characteristics. The analogue output is proportional to the display value.
With setting ANALOG FORMAT (-10 … +10 V) in MODE COUNTER the polarity of the analog output depends on the
polarity of the display value.
0 -10…10V -10 … +10 V
1 0…20M 0 … 20 mA
2 4…20MA 4 … 20 mA
ANALOG START
This parameter defines the start value of the analog conversion. This start value is corresponding to the display value
for an analog output of 0 V or 0/4 mA.
-99999999 Smallest start value
0 Default value
+99999999 Highest start value
ANALOG END
This parameter defines the end value of the analog conversion. This end value is corresponding to the display value
for an analog output of (+/-) 10 V or 20mA.
-99999999 Smallest end value
10000 Default Wert
+99999999 Highest end value
0 NO No function
Mode Timer: Reset the value to 0. (d) (s)
1 RESET/SET VALUE Mode Counter: Reset / set the value from channel A and B to „SET
VALUE“. Mode Velocity: Reset the value to 0.
2 FREEZE Freeze actual display value (s)
3 KEY LOCK disable touch screen (s)
4 LOCK RELEASE Loosen locking of all outputs / relay (d)
5 RESET MIN/MAX Reset of the min. / max. values (d) (s)
6 SERIAL PRINT Sending of serial data, see parameter SERIAL VALUE (d)
7 TEACH PRESEL. 1 Current display value is stored as PRESELECTION 1 (d)
8 TEACH PRESEL. 2 Current display value is stored as PRESELECTION 2 (d)
9 TEACH PRESEL. 3 Current display value is stored as PRESELECTION 3 (d)
10 TEACH PRESEL. 4 Current display value is stored as PRESELECTION 4 (d)
11 SCROLL DISPLAY Display switching (see display in operation mode) (d)
12 CLEAR LOOP TIME Release all latched switching conditions
13 START PRESELECT N.A.
14 ACTIVATE N.A.
15 STORE DATA N.A.
16 TESTPROGRAM N.A.
The display lights up red. The color can be changed by the event- (d)
17 SET RED COLOR
dependent color switching in the PRESELECTION 1... 4
The display lights up green. The color can be changed by the event- (d)
18 SET GREEN COLOR
dependent color switching in the PRESELECTION 1... 4
The display lights up yellow The color can be changed by the event- (d)
19 SET YELLOW COLOR
dependent color switching in the PRESELECTION 1... 4
20 INCREMENT BATCH Increase the batch counter (see mode counter) (d)
21 DECREMENT BATCH Decrease of the batch counter (see mode counter) (d)
Reset / set the value of the batchcounter / totalcounter (d) (s)
22 SET BATCH / TOTAL
(see Mode Counter)
23 INC. BRIGHTNESS Display brightness is increased (d) (s)
24 DEC. BRIGHTNESS Display brightness is reduced (d) (s)
25 SET TOTAL TIME Reset / set the total time measurement (see Mode TIMER) (d) (s)
Reset /set the value of counter from port A to the set value in SET VALUE (d) (s)
26 SET COUNTER A
- only in Mode „COUNTER“ possible
Reset /set the value of counter from port B to the set value in SET VALUE (d) (s)
27 SET COUNTER B
- only in Mode „COUNTER“ possible
Counter (channel A) is disabled and stops counting any further pulses as (s)
28 LOCK COUNTER A
long as this command is present.
Counter (channel B) is disabled and stops counting any further pulses as (s)
29 LOCK COUNTER B
long as this command is present.
(s) = static switching (level evaluation)
INPUT CONFIG must be set to active LOW / HIGH
(d) = dynamic switching (edge evaluation)
INPUT CONFIG must be set to RISING/FALLING EDGE
Dx350_06d_oi_e.docx / Jul-20 page 48 / 67
Continuation “Command Menu”:
INPUT 1 CONFIG
This parameter defines the switching characteristics of the input “Ctrl. In 1”.
0 ACTIVE LOW Active at „LOW“ (static)
1 ACTIVE HIGH Active at „HIGH“ (static)
2 RISING EDGE Activate at rising edge
3 FALLING EDGE Activate at falling edge
INPUT 2 ACTION
This parameter defines the function of the input “Ctrl. In 2”.
See parameter INPUT 1 ACTION.
INPUT 2 CONFIG
This parameter defines the switching characteristics of the input “Ctrl. In 2”.
See parameter INPUT 1 CONFIG.
INPUT 3 ACTION
This parameter defines the function of the input “Ctrl. In 3”.
See parameter INPUT 1 ACTION.
INPUT 3 CONFIG
This parameter defines the switching characteristics of the input “Ctrl. In 3”.
See parameter INPUT 1 CONFIG.
COLOR
This parameter defines the display color.
Event-depending change of the display color by a switching condition is possible (see PRESELECTION 1…4 MENU)
Event-depending changes are only available for devices with option CO, AO or RL.
0 RED Red display
1 GREEN Green display
2 YELLOW Yellow display
BRIGHTNESS (%)
This parameter defines the brightness of the display in percent
10 Min. brightness
90 Default value
100 Max. brightness
CONTRAST
This parameter defines the viewing angle.
0 Viewing angle from top
1 Viewing angle from center
2 Viewing angle from bottom
UP-DATE-TIME (S)
This parameter defines the update time in seconds of the display only.
0.005 Shortest update time
0.1 Default value
9.999 Longest update time
FONT
This parameter defines the setting of the font style.
0 Standard
1 Font 1
START DISPLAY
This parameter defines the start display after switching on device.
0 STANDARD Display with unit and status bar
Two-line display without units
1 DOUBLE (only the parameter „BATCH TOTAL MODE“ or TOTAL TIME MODE“ or „COUNT
MODE A+B / A-B is active)
Two-line display with units
2 DOUBLE WITH UNITS (only the parameter „BATCH TOTAL MODE“ or TOTAL TIME MODE“ or „COUNT
MODE A+B / A-B is active)
3 LARGE Large display (only the parameter „LARGE DISPLAY“ is active)
4 COMMAND Display with command keys (only with operating mode TIMER or COUNTER)
Display for quick start for enter preselection values
5 QUICKSTART
(only for option CO/AO/RL)
6 MINIMUM/MAXIMUM Display with minimum and maximum value
LARGE DISPLAY
This parameter defines to switch on / off the large display.
By splitting ratio the display value for the large display can be divided.
(Applies only for all 99999999 number formats!)
0 NO Large display off
1 1:1 Large display with splitting ratio 1:1
2 1:10 Large display with splitting ratio 1:10
3 1:100 Large display with splitting ratio 1:100
4 1:1000 Large display with splitting ratio 1:1000
5 1:10000 Large display with splitting ratio 1:10000
P1(X) - P24(X)
X-coordinate of the linearization point.
This value representing the display value which the unit show in the display without linearization.
-99999999 Smallest X-coordinate
0 Default value
+99999999 Largest X-coordinate
P1(Y) - P24(Y)
Y-coordinate of the linearization point
This is the display value, which the unit should show in the display with linearization.
E.g. P2(X) is replaced by P2(Y).
-99999999 Smallest Y-coordinate
0 Default value
+99999999 Largest Y-coordinate
To request for a data transmission you must send the following request string to the converter:
EOT AD1 AD2 C1 C2 ENQ
EOT = control character (Hex 04)
AD1 = unit address, High Byte
AD2 = unit address, Low Byte
C1 = register code, High Byte
C2 = register code, Low Byte
ENQ = control character (Hex 05)
The following example shows the request string for readout of the actual input frequency of a monitor
(Code=1) from a unit with unit address 11:
ASCII-Code: EOT 1 1 : 1 ENQ
Hex-Code: 04 31 31 3A 31 05
Binary-Code: 0000 0100 0011 0001 0011 0001 0011 1010 0011 0001 0000 0101
For the operation of the interface module and the understanding of this manual basic knowledge in Modbus
RTU communication is presupposed.
Parameter setting
Required parameter settings in DX350 / DX355 “Serial menu”:
UNIT NUMMER
Not valid for Modbus communication
(For setting of Modbus address see parameter “MODBUS”)
SERIAL FORMAT
This parameter defines the bit data format.
0 7-EVEN-1
1 7-EVEN-2
2 7-ODD-1
Do not use with Modbus protocol
3 7-ODD-2
4 7-NONE-1
5 7-NONE-2
6 8-EVEN-1 8 data bits Parity even 1 stop bit
7 8-ODD-1 8 data bits Parity odd 1 stop bit
8 8-NONE-1 Do not use with Modbus protocol
9 8-NONE-2 8 data bits no Parity 2 stop bits
SERIAL INIT
Not valid for Modbus communication
SERIAL PROTOCOL
Not valid for Modbus communication
SERIAL VALUE
Not valid for Modbus communication
MODBUS
This parameter enables the Modbus protocol and determines the Modbus address.
0 Do not use for Modbus protocol (Modbus disabled)
Modbus enabled: Serial interface is using Modbus RTU protocol
1 … 247
The number set here determines the Modbus node address.
Modbus Communication
The following Modbus functions are available:
Access to parameters
Holding Register 0x0000 / 0x0001 hex and following allow access to the device parameters.
The holding register numbers for a certain parameter can be calculated by the parameter # that can be found
in the parameter table in the touchMatrix® device manual:
Holding Register low = (parameter #) x 2
Holding Register high = (parameter #) x 2 + 1
Example:
Access to parameter # 51 “PRESELECTION 1” by Holding Register 0x0066 and 0x0067 hex.
The X-Coordinates must use continuously increasing settings, i.e. P1(X) must have the lowest and P24(X) must
have the highest setting. If the measured value is bigger than the last defined X-value, the corresponding Y-
value is displayed.