133R0262 HLP-SP110 Series Operating Manual V2016-01 20160328
133R0262 HLP-SP110 Series Operating Manual V2016-01 20160328
133R0262 HLP-SP110 Series Operating Manual V2016-01 20160328
Manual
HLP-SP110 Series
Introduction
Thank you for purchasing and using the general-purpose vectordrive of
HLP-SP110 series.
Please read caref ully the operation manual before putting the drive
to use so as to correctly install and operate the drive, give f ull play to its
f unctions and ensure the safety. Please keep the operation manual handy for
f uture reference, maintenance, inspection and repair.
Due to the driveof a kind of powerelectronics product it must be
installed, tested and adjusted with specialized electrical engineering workers.
The marks of (Danger) , (Caution) and other symbols in
the manual remind you of the saf ety and prevention cautions during
the handling, installation, r unning and inspection. Please f ollow these
instructions to make sure the safe use of the drive. In case of any doubt
please contact our local agent for consultation. Our professional persons are
willing and ready to serve you.
The manual is subject to change without notice.
Index
Introduction I
Chapter 1 Safety Precautions 1
1.1 Before Power-up 1
1.2 During the Power-up 3
1.3 During the Operation 3
1.4 After the Power-off 4
Chapter 2 Standards and Specifications 5
2.1 Label Description 5
2.2 Particular Specifications 6
2.3 Technical Specifications 7
2.4 Derating Specifications 9
2.5 Accessories 10
Chapter 3 Mechanical and Electrical Installation 11
3.1 Mechanical Installation 11
3.1.1 Installation Environment Requirements 11
3.1.2 External and Installation Dimensions 11
3.1.3 Installation and Direction 15
3.1.4 Accessories Installation 16
3.1.5 Removal of the Front Cover 21
3.1.6 Slide Insulating Cover Operation 23
3.2 Peripheral Electrical Devices 25
3.2.1 Selection of MCCB/Fuse/Contactor 27
3.2.2 Selection of Braking Unit and Braking Resistor 28
3.2.3 Selection of EMC Filter 30
3.3 Description of Main Circuit 31
3.3.1 Schematic of Main Circuit Terminals 31
3.3.2 Main Circuit Terminal Screws and Wiring Recommended
Specifications 33
3.4 Description of Control Circuit 34
3.4.1 Schematic of Control Circuit Terminals 34
3.4.2 Control Terminals’ Screws and Wiring Recommended
Specifications 36
3.4.3 Control Curcuit Wiring 36
Caution
● Check to be sure that the voltage of the main circuit AC power
supply matches the input voltage of the drive.
● Install the drive in a safe location, avoiding high temperature,
direct sunlight, humid air or water.
● The d rive can only be used at the places accredited by our
company. Any unauthorized working environment may have the
risks of fire, gas explosion, electric shock and other incidents.
● If more than one drive installed on the same control cabinet, make
additional cooling fan, so that the inside temperature is lower than
40℃,in order to prevent overheating or fire occurs.
● It will affect the service life of the drive if a contactor is installed
on the input side to control the start and stop. Generally it is
required to cont rol it th rough ter minal com mands. Special
attention should be paid to its use in the case of the start and stop
more frequently places.
● Do not install any switch component like circuit breaker or
contactor at the output of the drive. If any of such components
must be installed due process and other needs, it must be ensured
that the drive has no output when the switch acts. In addition, it
is forbidden to install any capacitor for improvement of power
factor or any varistor against thunder at the output. Otherwise
it will cause malfunctions, tripping protection and damages of
components of the drive.
● Please use an independent power supply for the drive. Do avoid
using the common power supply with an electrical welder and
other equipment with strong disturbance. Otherwise it will cause
the drive to protect or even damage the drive.
● Motor overload protection is not included in the default settings. If
this function is desired, set C01.09 (motor thermal protection) to
Danger
● Be sure to turn off the power supply before wiring.
● Mount the drive in the metal and other non-combustible materials
to avoid the risk of fire.
● Don’t install the drive in a space with explosive gas, otherwise,
they lead to explosion.
● R, S, T terminals are power input terminals, never mixed with
U.V.W terminals. Be sure that the wiring of the main circuit is
correct. Otherwise it will cause damages of the drive when the
power is applied to it.
● The ter minal of must be grounded separately and never
connected to N-line. Otherwise it will easily cause the protection
or errors of the drive.
● Do not dissemble or modify any internal connecting cord, wiring
or component of the drive by yourself.
● Never remodel it or exchange control boards and components by
yourself. It may expose you to an electrical shock or explosion,
etc.
● Kee p t he d r ive f rom t he rea ch of ch ild ren or pe r son s not
concerned.
Danger
● Do not plug the connectors of the drive during the power up to
avoid any surge into the main control board due to plugging,
which might cause the damage of the drive.
● Always have the protective cover in place before the power up to
avoid electrical shock injury.
Caution
● Do not measure the signals on circuit boards while the drive is
running to avoid danger.
● The drive has been optimized before sold. Please make proper
adjustments according to the desired functions.
● Do consider the vibration, noise and the speed limit of the motor
bearings and the mechanical devices.
Danger
● Never connect or disconnect the motor set while the drive is in
running. Otherwise it will cause over-current trip and even burn
up the main circuit of the drive.
● Never remove the front cover of the drive while the drive is
powered up to avoid any injury of electric shock.
● Do not come close to the machine when the Reset Function is
used to avoid anything unexpected. The motor may automatically
recover from fault.
Caution
● Even in the case of the main power, the other voltage inputs and
the share load (linkage of DC intermediate circuit) all have been
disconnected from the mains, the internal of the drive still have
residual energy. Before touching any potentially live parts of the
drive, please wait at least 4 minutes for the drives of less than
22KW (including 22KW), and wait at least 15 minutes for the
drives of more than 30kW (including 30kW). Otherwise, it will
expose you to a risk of electrical shock.
Note: For SP110 power less than 7.5kW (including) model, advanced IO
board is standard conf iguration, basic IO board is optional, please specif y
when ordering if need basic IO board; For 11kW and above power model, only
advanced IO board is supported.
Item Specification
Supply voltage three phase 380~480V -20%~+10%;
Power
Frequency 48~62Hz;
supply
Max. imbalance 3%;
three phase 0-100% of supply volt-
Motor Output voltage
age;
output
Output frequency V/F : 0-400Hz , VVC+: 0-200Hz;
Control mode V/F, VVC+;
Start torque 0.5Hz 150%;
Overload capacity 110% 60s, 150% 1s;
PWM switch frequen-
2~16kHz;
cy
Main
control Digital: 0.001Hz;
Speed setting resolu-
functions Analogy: 0.5‰ of the max. operating
tion
frequency ;
Speedopen-loop
30~4000 rpm: tolerance±8 rpm;
control accuracy
Control command
LCP, digital terminal, local bus;
source
Frequency setting
LCP, analog, pulse, local bus;
source
Selectable 4-speed steps ramp up and
Ramp control
down times 0.05-3600.00s;
Speed Open-loop Control; Process Closed-loop Control;
Torque Open-loop Control; AMA Function;Motor Magnetisa-
Basic tion; Slip Compensation;Torque compensation;Automatic
Functions Voltage Regulation; V/F Control, DC Brake; AC brake; Speed
Limit; Current Limit; FlyingStart; Reset Function; Counter;
Timer;
Wobble Function; Jogging; Multi-speed Control via Digital
Applica-
input; SLC(including Order Control and Parallel Control);
tion Func-
Mechanical Braking; UP/DOWN ; Catch up /Slow down;
tions
Relative Scaling Reference etc.
Missing Motor Phase Protection; Low-voltage Protection;
Over-voltage Protection; Over-current Protection; Output
Phase Loss Protection; Output Short Circuit Protection;
Protection Output Grounding Fault Protection;Motor Thermal Protec-
Functions tion; Live Zero Timeout Function;AMA Fails; CPU Fault;
EEPROM Faults; Buttonfreeze; Duplicate Fails; LCP Invalid;
LCP Incompatible; Parameter Read-only; Reference Out of
Range; Invalid While Running etc.
5 digital inputs
2 analoginput, both can receive voltage or
Input current signals.
Advanced In the AI terminal can choose the current or
IO resistance signal by jumper.
board 6relay output;
control Output 2 analogoutput (1 can be selected as current
terminals output or voltage output via jumper switch).
1 +10V, max current output 10mA;
Power supply
1 24V, max current output 200mA;
Communication RS+, RS-, max baud rate 115200bit/s;
5 digital inputs;
Input 2analog input, it can receive voltage or cur-
Basic rent signals.
IO 2relay output;
board Output 2analog input; it can be selected as current
control output or voltage output via jumper switch.
terminals
Power supply 1 +10V, max current output 10mA;
Communication RS+, RS-, max baud rate 115200bit/s;
Enclosure IP20;
-10℃~50℃, derating use when over
Ambient temperature
40℃;
5%-85% (95% without conden-
Humidity
sation);
Environ-
ment ≤75kW: 1.14g;
Vibration test
≥90kW: 0.7g;
Max. altitude above 1000m, derating use when more
sea level than 1000 meters;
Shield cable: 50 meters, unshield
Motor cable length
cable: 100 meters;
DC choke ≥37kW Built-in
others
Braking unit ≤22kW Built-in
2.5 Accessories
LCP-02
Network
Cable Cradle-01
HLP-SP110
LCP-03
CopyCard-01
HLP-SP110
Base Profile
Min:100mm
Min:100mm
Min:100mm
Min:100mm
Min:100mm
Min:100mm
Min:100mm
This cradle
is suitable
for 1.0-
2.0mm
thickness
sheet metal
parts.
Press and hold
the snap roots
when install-
ation,using
buckle defor-
mation install
Stepl:Open a hole in line with the size sheet metal.
of the control panel in the position need Step2:Install the LCP according to the
to instal the LCP,hole size,as shown: direction of the arrow.
Recommended
to install
vertical
mounting
position
arrow,press
with uniform
force.
Step 4: Install the external LCP
Step 3:The LCP is installed in the cradle, communication cable, insert into RJ45
according to the direction of the arrow. terminal from the bottom of hole.
2. LCP-03 Installation
The external dimensions of LCP-03 are shown below (unit: mm):
Step1:该小面板适用于厚度
步骤 1:Open a hole in the control panel where
1.0mm~2.0mm 钣 Step 2: Install the LCP according to the
步骤 2:按照箭头方向,将小面板固定在
it is needed to install LCP-01 or LCP-02, the
金件,在需要安装小面板的位置开一个孔,开 direction of the arrow.
钣金上面。
hole size is as shown.
孔尺寸如图所示:
Projection Scale / Paper size Matr.
1:1 / A3 Danf
3. Base Installation
Base-01 is for 90~132kW, its external dimensions are shown below
(unit: mm):
251.5
251.5
see
1:5 / A3 1:5 / A3 Danfoss standard
The installation steps of Base-01 and Base-02 are the same, shown
below:
Step2: Remove the bottom cable entry sheet metal and fixing screws.
Step3: Move the rubber pieces from the bottom of the sheet metal to the
Base.
HLP
-SK1
90
≤7.5kW
Use a screwdriver to push out the hook of the front cover inward.
HLP-SP110 HLP-SP110
11~22kW
Use a screwdriver to push out the hook of the front cover inward.
HLP-SP11
HLP-SP11 0
0
30~250kW
Use a screwdriver to loosen the screws on the front cover.
HLP-S
P110
HLP-S
HLP-S P110
P110
280~450kW
Screw the lock on the door.
HLP-SP110
Lock
Step 2: Wiring IO and main circuit, push the slide insulating cover
handles inwards and pull them to the bottom, cover the front cover.
Power supply
MCCB
Electromagnetic
contactor
AC input
reactor
Noise filter on
input side HLP-SP110
Noise filter on
output side
Braking unit
AC output
reator
Braking resistor
Motor
Inductance
Maximum
Ratedcurrent (mH)
Model continuous
(A) & 3% Impedance
current(A)
Rated Saturation
Inductance
Model current current (A)
(mH)
(A) & 3% Impedance
HLP-SP1100D7543 2.3 4.8 14.39
HLP-SP11001D543 4 8.5 7.19
HLP-SP11002D243 5.6 11.9 4.9
HLP-SP11004D043 9.9 21 2.69
HLP-SP11005D543 13.3 28.2 1.96
HLP-SP11007D543 17.7 37.5 1.43
HLP-SP110001143 25 53 0.98
HLP-SP110001543 32 67.8 0.72
HLP-SP11018D543 38 80.6 0.58
HLP-SP110002243 45 95.4 0.49
HLP-SP110003043 61 129 0.362
HLP-SP110003743 75 159 0.294
HLP-SP110004543 91 193 0.242
HLP-SP110005543 112 238 0.197
HLP-SP110007543 150 318 0.147
HLP-SP110009043 180 382 0.123
HLP-SP110011043 215 456 0.103
HLP-SP110013243 260 551 0.085
HLP-SP110016043 315 668 0.070
HLP-SP110018543 365 774 0.060
HLP-SP110020043 395 838 0.056
HLP-SP110022043 435 923 0.051
HLP-SP110025043 480 1020 0.009
HLP-SP110028043 540 1145 0.008
HLP-SP110031543 605 1280 0.0055
HLP-SP110035543 660 1400 0.004
HLP-SP110041543 745 1580 0.0035
HLP-SP110045043 745 1580 0.003
Terminals’ specification:
Symbol Description Specification
24Vpower Maxload 200mA, with over load and short
VDD
supply circuit protection functions.
Maxload 10mA, with over load and short
+10V 10Vpower supply
circuit protection functions.
1. Logic:
FOR, >DC 19V Logic: 0;
REV, DI1, <DC 14V Logic: 1;
Digital input
DI2, 2. Voltage: DC0-24v;
DI3, 3. Input resistance: 5kΩ;
4. Input voltage Rang:Max ±30v;
COM Digital ground Isolated from internal GND.
Both VI and AI can be configurated to
0-20mA or 0-10Vby paramters:
VI, AI Analog input
1. Input Impedance: about 10kΩ;
2. Input Impedence: ≤200Ω;
VO can be selected to the current output
or voltage output via J2, default is: voltage
output;
VO, AO Analog output AO only has current output mode;
1. Output Mode: 0~20mAor 0~10V;
2. Voltage Output: load larger than 500Ω;
3. Current Output: load larger than 500Ω;
Analog
GND and communica- Isolated from internal COM.
tion ground
Relay
1. Resistive Load: 250VAC 3A/30VDC 3A;
(FA-FB-
Relay output 2. Inductive Load: 250VAC 0.2A/24VDC
FC, KA-
0.1A (cosφ= 0.4);
KB)
RS485
RS+、RS- Max baud rate: 115200bit/s;
communication
(FA-FB-
FC、KA1-
1、Resistive load:250VAC 3A/30VDC
KB1、KA2-
Ready 3A;
KB2、KA3-
2、Inductive load:250VAC 0.2A/24VDC
KB3、KA4-
0.1A
KB4、KA5-
KB5)
Jumper Switch J3
Opto-
Isolator
Y1
Opto-
Isolator
Yn
Shielded
Cable Near-
end Ground
3.5.3 Grounding
Recommended ground electrode is shown in the figure below:
Drive Other
Devices
Screen
Incremental
Function LED potentiometer
1. State LED
The drive has three operating states: HAND control state, AUTO
control state and OFF state. The operating states are indicated by
HAND, AUTO and OFF Led.
HAND LED: The drive is in the HAND control state when it is
on. The frequency can be changed by tur ning the incremental
potentiometer. Push “HAND” key to set the drive in the HAND state.
OFF Led: The drive is in the OFF state when it is on. Push “OFF” key
to set the drive in the HAND state.
AUTOLED: The drive is in the AUTO state when it is on. In the AUTO
state, the drive is controlled by control terminals or communication.
Push “AUTO” key to set the drive in the AUTO state.
2. FunctionLed
FWD, REVLed: Indicates that the drive runs forwards or reverse.
Hz, A, RPM Led: Indicates the meaning of data displayed on the
screen.
Local remote running lights running lights, OFF LEDs, three LED
lights indicate.
3. Screen
There are 5 LED which can display reference, output frequency,
monitoring data and warning/alarm code.
4. Keys
5. Incremental Potentiometer
Increase/decrease data or parameter, clockwise to increase, counter-
clockwise to decrease.
≥0 STOP
<0 STOP
≥0 FWD
≥0 REV
<0 FWD
<0 REV
Note: A flash light denotes the status coming, Light on indicates the
current state, and light off means not in this state.
Example 1: The first line of the table indicates the drive is stop and the
reference is greater than or equal to 0, means the dirve at some
time in the future will run forward.
Example 2: The fourth line of the table represents the current drive is
reverse running, and the reference setting is greater than or equal
to 0, it means the drive at some time in the future will run forward.
output frequency.
Show counter A
Counter A C16.72 is 65535, display
accuracy:1
Show counter B
Counter B C16.72 is 65535, diaplay
accuracy : 1
Show analog in VI
Analog in VI C16.62 is 10.00V, display
accuracy: 0.01
Show Analog in AI
Analog in AI C16.63 is 20.00mA,
display accuracy: 0.01
Show pulse
inputC16.68is
Pulse Input
50.000kHz, display
accuracy: 0.001
Note: The drive only monitor output frequency, reference and output
current reference by default. For monitoring other status
(DC voltage, etc.), please set the parameter C00.33 (refer to
instructions).
[1]
record, it can display up to ten recent
fault records in turn.
2
2 indicates status of FOR, DI1, DI2, DI3,
DI4 is 0, and status of REV is 1.
Par.
Group Par. No. Name Range Unit Default
0: 50Hz
*C00.03 Regional Settings 0
1: 60Hz
0: Resume
1: Forced stop,
Operating State at
C00.04 ref=old 1
Power-up
2: Forced stop,
ref=0
*C00.06 Grid Type 0~122 *
1: Set-up 1
C00.10 Active Set-up 2: Set-up 2 1
9: Multi Set-up
1: Set-up 1
C00.11 Edit Set-up 1
Parameter Group 00: Operation/Display
2: Set-up 2
0: Not linked
*C00.12 Link Set-up 20
20: Linked
Custom Readout
C00.31 0.00 - 99999.00 0.00
Min. Value
Custom Readout
C00.32 0.00 - 99999.00 100.00
Max. Value
C00.33 LCP Display Option 0~4095 0
0: Disabled
C00.40 HAND Key Option 0
1: Enabled
0: Disabled
1: Enabled
C00.41 OFF Key Option 1
2: Enabled reset
only
0: Disabled
C00.42 AUTO Key Option 1
1: Enabled
0: Disabled
5: 5s
One Key Recovery
C00.46 10: 10s 5
Time
15: 15s
20: 20s
0: 0.1
LCP Potentiometer
C00.47 1: 1 0
Step
2: 10
Par.
Group Par. No. Name Range Unit Default
0: No copy
Parameter Group 00: Operation/Display
timization (AEO)
0: No function
Application Configu-
*C01.07 1: Water supply 0
ration Mode
function
*C01.20 Motor Power Motor dependant kW *
*C01.22 Motor Voltage 50~1000 V *
*C01.23 Motor Frequency 20~400 Hz *
*C01.24 Motor Current Motor dependant A *
*C01.25 Motor Speed 100~9999 rpm *
0: Disabled
1: Enable complete
Automatic Motor
*C01.29 AMA 0
Adaption (AMA)
2: Enable reduced
AMA
Stator Resistance
*C01.30 Motor dependant Ω 0.001
(Rs)
Stator Leakage Reac-
*C01.33 Motor dependant Ω 0.001
tance (X1)
Par.
Group Par. No. Name Range Unit Default
Resonance Dampen-
C01.64 0~3000 % *
ing
Resonance Dampen-
C01.65 0.005~0.050 s 0.005
ing Time constant
C01.71 Start Delay 0.0~10.0 s 0.0
0: DC Hold
C01.72 Start Function 2
2: Coast
0: Disabled
*C01.73 Flying Start 0
1: Enabled
C01.75 Min. Start Frequency 0.00~10.00 Hz 0.00
C01.76 Jump Frequency 0.0~20.0 Hz 0.0
0: Coast
C01.80 Function at Stop 0
1: DC Hold
Min Speed for Func-
C01.82 0.0~400.0 Hz 0.0
tion at Stop
0: No protection
1: Thermistor warn-
Motor Thermal ing
C01.90 0
Protection 2: Thermistor trip
3: ETR warning
4: ETR trip
Thermistor Resource 0: None
*C01.93 0
1: Terminal VI
Par.
Group Par. No. Name Range Unit Default
0: Off
C02.10 Brake Function 0
2: AC brake
Over-voltage Control
C02.15 Grid type dependant V *
Threshold Voltage
AC Brake, Max Cur-
C02.16 0~150 % 100
rent
0: Disabled
C02.17 Over-voltage Control 2: Mode 1 3
3: Mode 2
Over-voltage Control
C02.18 0.01~0.10 s 0.05
Integral Time
Over-voltage Control
C02.19 0~200 % 100
Proportional Gain
Release Brake Cur-
C02.20 0.00~1200.00 A 0.00
rent
C02.22 Activate Brake Speed0.0~400.0 Hz 0.0
0: 0~Max
C03.00 Reference Range 0.000
1: -Max~+Max
C03.03 Maximum Reference C03.02~4999.000 50.000
Par. Group 03: Reference/Ramps
0: Presetreference +
Reference source1,
Main Reference
C03.07 2, 3 0
Calculation
1: Presetreference
priority
C03.10 PresetReference -100.00~100.00 % 0.00
C03.11 Jog speed 0.0~400.0 Hz 5.0
Catch up/Slow down
C03.12 0.00~100.00 % 0.00
Value
Speed Up/Down
C03.13 0.01~50.00 Hz 0.10
Value
Preset RelativeRefer-
C03.14 -100.00~100.00 % 0.00
ence
Par.
Group Par. No. Name Range Unit Default
C03.41 0.05~3600.00 s *
Time
Ramp 1 Ramp Down
C03.42 0.05~3600.00 s *
Time
0: Linear
C03.50 Ramp 2 Type 0
2: S ramp
Ramp 2 Ramp Up
C03.51 0.05~3600.00 s *
Time
Ramp 2 Ramp Down
C03.52 0.05~3600.00 s *
Time
0: Linear
C03.60 Ramp 3 Type 0
2: S ramp
Ramp 3 Ramp Up
C03.61 0.05~3600.00 s *
Time
Ramp 3 Ramp Down
C03.62 0.05~3600.00 s *
Time
0: Linear
C03.70 Ramp 4 Type 0
2: S ramp
Ramp 4 Ramp Up
C03.71 0.05~3600.00 s *
Time
Ramp 4 Ramp Down
C03.72 0.05~3600.00 s *
Time
C03.80 Jog Ramp Time 0.05~3600.00 s *
Limits/Warnings
Par. Group 04:
0: Clockwise
Motor Speed Direc- 1: Counter clock-
*C04.10 2
tion wise
2: Both directions
Par.
Group Par. No. Name Range Unit Default
Motor Speed Low
*C04.12 0.0~C04.14 Hz 0.0
Limit
Motor Speed High-
*C04.14 C04.12~C04.19 Hz 50.0
Limit
C04.18 Current Limit 0~300 % 120
Max Output Frequen-
*C04.19 0.0~400.0 Hz 50.0
cy
0: No function
1: Terminal VI
Frequency Upper 2: Terminal AI
*C04.21 0
Limit Source 11: Local bus
21: LCP potentiom-
eter
0: Disable
1: Counter A save
Par. Group 04: Limits/Warnings
Counter Store at
C04.42 2: Counter B save 0
Power down
3: Both counter A
and B save
Warning Current
C04.50 0.00~I max A 0.00
Low
Warning Current
C04.51 0.00~I max A *
High
Warning Frequency
C04.52 0.0~400.0 Hz 0.0
Low
Warning Frequency-
C04.53 0.1~400.0 Hz 65.0
High
Warning Reference
C04.54 -4999.000~4999.000 0.000
Low
Warning Reference
C04.55 -4999.000~4999.000 50.000
High
Warning Feedback
C04.56 -4999.000~4999.000 0.000
Low
Warning Feedback
C04.57 -4999.000~4999.000 50.000
High
Missing Motor Phase 0: Disable
*C04.58 1
Function 1: Enable
Current limit warn- 0: warning off
C04.59 1
ing fucntion 1: warning on
C04.61 Bypass Speed From 0.0~400.0 Hz 0.0
C04.63 Bypass Speed to 0.0~400.0 Hz 0.0
Par.
Group Par. No. Name Range Unit Default
C05.04 DI Filter Time 2~16 ms 4
C05.05 DI terminal logic function 0 ~ 255 0
DO/RL terminal logic
C05.06 0 ~ 255 0
function
0: invalid
1: freeze output frequency
DI external fault function 2: stop
C05.09 3: jog frequency 0
4: max frequency
5: stop and alarm
C05.10 Terminal FOR 0: No operation 8
1: Reset
C05.11 Terminal REV 2: Coast inverse 11
C05.12 Terminal DI1 3: Coast and reset nverse 15
6: Stop inverse
C05.13 Terminal DI2 8: Start 16
9: Latched start
C05.14 Terminal DI3 10: Reversing 17
11: Start reversing
12: Enable start
forward only
13: Enable start reverse only
14: Jog
15: Preset ref. bit0
Par. Group 05: Digital In/Out
Par.
Group Par. No. Name Range Unit Default
0: No operation
1: Drive ready
3: Remote control
ready
4: Drive running/
No warning
5: Drive running
7: Run in range/No
warning
8: Run on
reference/No
warning
9: Alarm
10: Alarm or
warning
12: Out of current
range
13: Below current
low
14: Above current
high
15: Out of
frequency range
Par. Group 05: Digital In/Out
16: Below
frequency low
17: Above requency
high; 18: Out of
feedback range
C05.40 Relay Function 19: Below feedback 5, 9
low; 20: Above
feedback high
21: Thermal warning
22: Ready
23: Remote ready
24: Ready, voltage
OK
25: Reverse;26: Bus
OK
32: Mech. brake
control
36: Control word
bit11
37: Control word
bit12
40: Out of reference
range, reference is
outside the range set
in
C04.54 and C04.55;
41: Below reference
low, reference is
lower than set in
C04.54;
42: Above reference
high, reference is
higher than set in
C04.55;
Par.
Par. No. NameName Range Unit Default
Group
51: Drive in HANDstate;
52: Drive in AUTOstate;
56: Drive in HANDstate;
57: Drive in AUTOstate;
60: Comparator 0,
using a simple PLC, the
results of comparator 0;
61: Comparator 1,
using a simple PLC, the
results of comparator 1;
62: Comparator 2,
using a simple PLC, the
results of comparator 2;
63: Comparator 3,
using a simple PLC, the
results of comparator 3;
70: Logic rule 0, using a
simple PLC, the results
of logic rule 0;
71: Logic rule 1, using a
simple PLC, the results
Par. Group 05: Digital In/Out
of logic rule 1;
72: Logic rule 2, using a
simple PLC, the results
of logic rule 2;
C05.40 Relay Function 73: Logic rule 3, using a
simple PLC, the results 5,9
of logic rule 3;
80: Simple PLC digital
rutput 1, only active for
DO1;
81: Simple PLC digital
output 2, only active for
DO2;
82: Simple PLC relay 1,
only active for relay 1;
83: Simple PLC relay 2,
only active for relay 2;
84: Simple PLC relay 2,
only active for relay 3;
160: Water supply: low
voltage alarm control
161: Water supply: Over
voltage alarm control
162: Water supply:
Sleep
163: Water supply:Belt
breaking signal
164: Water supply:No
inverter available
192: Water supply:Relay
control
Par.
Group Par. No. Name Range Unit Default
FA/FB/FC;
KA1/KB1;
KA2/KB2;
KA3/KB3;
C05.41[x] Closed relay delay KA4/KB4; S 0.00
Par. Group 05: Digital In/Out
KA5/KB5
0~5:Correspond to
Range:
0.00~600.00
FA/FB/FC;
KA1/KB1;
KA2/KB2;
KA3/KB3;
C05.42[x] Open relay delay KA4/KB4; S 0.00
KA5/KB5
0~5:Correspond to
Range:
0.00~600.00
Live Zero Timeout-
C06.00 1~99 s 10
Time
0: Off
1: Freeze output
Live Zero Timeout 2: Stop
C06.01 0
Function 3: Jogging
4: Max. speed
5: Stop and trip
Par.Group 06: AnalogIn/Out
Te r m i n a l V I L o w 0.00~9.99
C06.10 V 0.07
Voltage
Terminal VI High
C06.11 0.10~10.00 V 10.00
Voltage
Te r m i n a l V I L o w 0.00~19.99
C06.12 mA 0.14
Current
Terminal VI High
C06.13 0.01~20.00 mA 20.00
Current
Te r m i n a l V I L o w
C06.14 -4999.000~4999.000 0.000
Ref./Feedb. Value
Terminal VI High
C06.15 -4999.000~4999.000 50.000
Ref./Feedb. Value
Te r m i n al V I Fi lt e r 0.01~10.00
C06.16 s 0.010
Time
Terminal VI Zero 0.0~20.00 V/
C06.18 0.00
Dead Band mA
Par.
Group Par. No. Name Range Unit Default
0: Voltage mode
C06.19 Terminal VI Mode 0
1: Current mode
Te r m i n a l A I L o w 0.00~9.99
C06.20 V 0.07
Voltage
Te r m i n a l A I H i g h 0.10~10.00
C06.21 V 10.00
Voltage
Te r m i n a l A I L o w 0.00~19.99
C06.22 mA 4.00
Current
Te r m i n a l A I H i g h 0.10~20.00
C06.23 mA 20.00
Current
Te r m i n a l A I L o w -4999.000~4999.000
C06.24 0.000
Ref./Feedb. Value
Te r m i n a l A I H i g h -4999.000~4999.000
C06.25 50.000
Ref./Feedb. Value
C06.26 Terminal AI Filter Time0.01~10.00 s 0.010
V/
C06.28 Te r m i n a l A I Z e r o 0.0~20.00 0.00
Dead Band mA
0: Voltage mode
C06.29 Terminal AI Mode 1: Current mode 1
Par.Group 06: AnalogIn/Out
2:Resistance signal
C06.30 Analog AI minimum 0~400 Ω 0.0
input resistor
C06.31 Analog maximum AI 0~600 Ω 400.0
input resistor
0: 0-20mA
C06.70 Terminal VO Mode 1: 4-20mA 3
3: 0-10V
C06.71 Terminal VO Analog 0~23 0
Output
C06.73 Terminal VO Output 0.00~200.00 % 0.00
Min. Scale
C06.74 Terminal VO Output 0.00~200.00 % 100.00
Max. Scale
Te r m i n a l VO m i n 0.00~C06.76
C06.75 output 0
Voltage mode:
C06.76 Te r m i n a l VO m a x C06.75~10.00 10.00
output Current mode:
C06.75~20.00
C06.81 LCP Pot.Min. Ref. -4999.000~4999.000 0.000
C06.82 LCP Pot.Max. Ref. -4999.000~4999.000 50.000
C06.90 Terminal AO Mode 0: 0-20mA 0
1: 4-20mA
Terminal AO Analog
C06.91 Output 0~23 0
Terminal AO Output
C06.93 Min. Scale 0.00~200.00 % 0.00
Par.
Group Par. No. Name Range Unit Default
Te r m i n a l AO m i n 0.00~C06.96
C06.95 0
output
Te r m i n a l AO m a x Current
C06.96 20.00
output mode:C06.95~20.00
Torque PI Propor-
C07.12 0~500 % 100
tional Gain
Torque PI Integration
C07.13 0.002~2.000 s 0.020
Time
0: No function
Process PID Feed- 1: Terminal VI
C07.20 2: Terminal AI 2
back Source 8: Pulse input DI4
11: Local bus
Process PI Normal/ 0: Normal
C07.30 0
Inverse 1: Inverse
Process PI Anti 0: Disable
C07.31 1
Windup 1: Enable
C07.32 Process PIStart 0.0~200.0 Hz 0.0
Process PI Propor-
C07.33 0.00~10.00 1.2
tional Gain
Par. Group 07: Controllers
Par.
Group Par. No. Name Range Unit Default
0: Digital and con-
trol word
C08.01 Control Site 1: Digital only 0
2: Control word
only
Control Word Selec- 0: Disable
C08.02 1
tion 1: Enable
Control Word Time-
C08.03 0.1~6500.0 s 1.0
out Time
0: Off
1: Freeze output
Control Word Time- 2: Stop
C08.04 0
out Function 3: Jogging
4: Max. speed
5: Stop and trip
Reset Control Word 0: Do not reset
C08.06 0
Par. Group 08: Communiction
Timeout 1: Do reset
C08.20 Diagnostic function 0:off; 1:start 1
0: FC
C08.30 Protocol 2: Modbus RTU 0
6: Modbus ASCII
C08.31 Address 0~247 1
0: 2400
1: 4800
2: 9600
3: 19200
bit/s
C08.32 Baud Rate 4: 38400 2
5: 57600
6: 76800
7: 115200
8~9: Reserved
0: Even parity (1
stop bit)
1: Odd parity (1 stop
bit)
C08.33 Parity/Stop Bits 2
2: No parity (1 stop
bit)
3: No parity (2 stop
bit)
C08.35 Min. Response Delay 0.000~0.500 s 0.002
C08.36 Max. Response Delay0.010~10.000 s 5.000
Par.
Group Par. No. Name Range Unit Default
0: Normal
1: Only response
C08.38 Message Response 0
exception message
Par. Group 08: Communiction
2: Not response
0: Not saved at
Modbus Parameter power down
C08.39 0
Write Store 1: Saved at power
down
C08.50 Coasting Select 3
C08.53 Start Select 0: Digital input 3
C08.54 Reversing Select 1: Bus 3
2: Logic AND
C08.55 Set-up Select 3
3: Logic OR
Preset Reference
C08.56 3
Select
0: Off
C13.00 Simple PLC Mode 1: Order execution 0
2: Parallel execution
0: False
1: True
2: Running
3: In current range-
No warning
4: On reference-No
Par. Group 13: SimplePLC
warning
7: Out of current
range
8: Below current
low
C13.01 Start Event 9: Above current 39
high
10: Out of frequency
range
11: Below frequency
low
12: Above frequen-
cy high
13: Out of feedback
range
14: Below feedback
low
Par.
Group Par. No. Name Range Unit Default
15: Above feedback
high
16: Thermal warn-
ing
17: Mains out of
range
18: Reversing
19: Warning
20: Alarm (trip)
21: Alarm (trip lock)
22: Comparator 0
23: Comparator 1
24: Comparator 2
25: Comparator 3
26: Logic rule 0
27: Logic rule 1
28: Logic rule 2
29: Logic rule 3
30: Simple PLC
Par. Group 13: SimplePLC
time-out 0
31: Simple PLC
time-out 1
32: Simple PLC
time-out 2
33: Terminal FOR
34: Terminal REV
35: Terminal DI1
36: Terminal DI2
37: Terminal DI3
38: Terminal DI4
39: Start command
40: Drive stopped
50: Simple PLC
time-out 3
51: Simple PLC
time-out 4
52: Simple PLC
time-out 5
53: Simple PLC
time-out 6
54: Simple PLC
time-out 7
C13.02 Stop Event 0~54 40
0: Do not reset
C13.03 Reset Simple PLC 0
1: Do reset
Par.
Group Par. No. Name Range Unit Default
0: No function
1: Power down save
C13.04 Simple PLCStore 2: Stop save 0
3: Both power down
and stop save
0: Disabled
1: Reference
2: Feedback
3: Motor speed [Hz]
4: Motor current [A]
6: Motor power
[kW]
7: Motor Voltage
C13.10 Comparator Operand 0
[V]
12: Terminal VI
input
Par. Group 13: SimplePLC
13: Terminal AI
input
20: Fault number
30: Counter A
31: Counter B
0: Less than
C13.11 Comparator Operator 1: Approx. Equal 1
2: Greater than
C13.12 Comparator Value -9999.0~9999.0 0.0
C13.20 Simple PLC Timer 0.00~3600.00 s 0.00
Logic Rule Boolean The same as
C13.40 0
1 C13.01’s
0: Disabled
1: AND
2: OR
3: AND NOT
Logic Rule Operator
C13.41 4: OR NOT 0
1
5: NOT AND
6: NOT OR
7: NOT AND NOT
8: NOT OR NOT
Logic Rule Boolean The same as
C13.42 0
2 C13.01’s
Par.
Group Par. No. Name Range Unit Default
Logic Rule Operator The same as
C13.43 0
2 C13.41’s
Logic Rule Boolean The same as
C13.44 0
3 C13.01’s
The same as
C13.51 Simple PLC Event 0
C13.01’s
0: Disabled
1: No action
2: Select set-up 1
3: Select set-up 2
10: Select preset ref 0
11: Select preset ref 1
12: Select preset ref 2
13: Select preset ref 3
14: Select preset ref 4
15: Select preset ref 5
Par. Group 13: SimplePLC
Par.
Group Par. No. Name Range Unit Default
Par.
Group Par. No. Name Range Unit Default
Delay Time of Auto
C14.18 RestartWhen Power 0.0~3600.0 s 0.0
up Again
0: Manual reset
1~10: Auto reset
1-10 times
C14.20 Reset Mode 0
11: Auto reset 15 times
12: Auto reset 12 times
13: Infinite auto reset
Automatic Restart
C14.21 0~600 s 10
Time
0: Normal operation
2: Initialization
3: Backup user set-
C14.22 Operation Mode 0
tings
4: Recover user set-
Par. Group 14: SpecialFunctions
tings
0: Disable
C14.23 Trip lock 1
1: Enable
Current limit alarm
14.24 0~60 s 60
delay
Torque limit alarm
14.25 0~60 s 60
delay
0: Trip
C14.27 Action at Drive Fault 0
1: Warning
Current Controller 1
C14.30 0~300 % 100
Proportional Gain
Current Controller
C14.31 0.005~2.000 s 0.020
1Integration Time
Current Controller
C14.32 2.0~100.0 ms *
Filter Time
Current Controller 2
C14.33 0~300 % 0
Proportional Gain
Current Controller
C14.34 0.001~2.000 s 0.020
2Integration Time
*C14.40 VT Level 40~90 % 90
AEO Min. Magneti-
*C14.41 40~75 % 66
sation
0: Off
*C14.50 RFI Filter Selection 1: On 1
2: Reserved
0: Off
*C14.51 DC Link Compensation 0
1: On
Par.
Group Par. No. Name Range Unit Default
Par.
Group Par. No. Name Range Unit Default
Drive NominalCur-
C16.36 0.00~1200.00 A
rent
C16.37 Drive Max. Current 0.00~2400.00 A
V/
C16.62 Analog Input VI 0.00~20.00
mA
0: 0~20mA
C16.63 Terminal AI Setting
1: 0~10V
V/
C16.64 Analog Input AI 0.00~20.00
mA
V/
C16.65 Analog Output VO 0.00~20.00
mA
C16.66 Digital Output 0~255
Par.
Group Par. No. Name Range Unit Default
1:Mode1
C25.01 Pump type 2:Mode2 3
3:Mode3
0:Use enable
C25.02 Pump enable signal 1:Do not use to en- 0
able
C25.03 Pump number 0~5 0
C25.09 Pump status display 0~65535 0
Built in acceleration
C25.13 0.00~3600.00 S 0.00
time
Internal deceleration
C25.14 0.00~3600.00 S 0.00
time
C25.20 Low frequency set 1 0.0~400.0 HZ 25.0
Low frequency dura-
C25.21 0.00~3600.00 HZ 25.0
tion
C25.22 Low frequency set 2 0.0~400.0 HZ 25.0
Par. Group 25: Wobble
Par.
Group Par. No. Name Range Unit Default
10: 380-440V/50Hz/IT-Grid
11: 380-440V/50Hz/IT-Delta
12: 380-440V/50Hz
20: 440-480V/50Hz/IT-Grid
21: 440-480V/50Hz/IT-Delta
22: 440-480V/50Hz
100: 200-240V/60Hz/IT-Grid
101: 200-240V/60Hz/IT-Delta
102: 220-240V/60Hz
110: 380-440V/60HZ/IT-Grid
111: 380-440V/60Hz/IT-Delta
112: 380-440V/60Hz
120: 440-480V/60Hz/IT-Grid
121: 440-480V/60Hz/IT-Delta
122: 440-480V/60Hz
Selects the set-up to be edited during operation, either the active set-up or
one of the inactive set-ups.
Bit Bit
Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
11 10
Custom Readout
Pulse Output
Pulse Input
AI
VI
Counter B
Counter A
Feedback Value
Temperature
DC-Voltage
Motor Speed
Motor Voltage
0 0 0 0 1 0 0 0 1 0 0 0
“One Key Recovery”is that user can press OFF key to recover the backup
settings if the settings have been backuped. If the settings have not been
backuped, this function is disabled.
One key Recovery Time is used to determine how many seconds should
OFF key pressed to recover the backup settings, it is set to 0 to disable
one key recovery function.
Note: If an alarm happens, press OFF key will reset alarm first.
C00.5* Copy/Save
0: No copy;
1: Copy from set-up 1, Copies all parameters in the Set-up 1 to the
edit set-up (defined in C00.11);
2: Copy from set-up 2, Copies all parameters in the Set-up 2 to the
edit set-up (defined in C00.11);
9: Copy from factory setting, Copies factory setting to the edit set-
up (defined in C00.11);
Attention: Whenselected set-up is thesame to the editset-up,copy
function doesn’t work; bothLCP and parameter database are locked while
copying.
C00.6* Protection
0: Disabled
1: Enabled, prevent unauthorized editing of parameters.
Attention: This function is only valid to LCP, not active to local bus.
Parameters for advanced motor data. The motor data in C01.30 Stator
Resistance (Rs) to C01.35 Main Reactance (Xh) must match the relevant
motor in order to run the motor optimally. The default settings are figures
based on common motor parameter values from standard motors. If the
motorparameters are not set correctly, a malfunction of the drive system
may occur. If the motor data is not known, running an AMA (Automatic
Motor Adaptation) is recommended.
Enter the motor cable length connected between the motor and the drive.
Set correct cable length can suppress noises resulted from the motor.
Use C01.50 Motor Magnetisation at Zero Speed along with C01.52 Min
SpeedNormal Magnetising to obtain a different thermal load on the
motor when running at low speed (under C01.52).
The value of C01.50 is a percentage of the motor current. If the setting is
too low, the torque on the motor shaft may be reduced.
Magn.current
C01.50
100%
C01.52 Hz
Frequency
C01.55[0]~C01.55[5] is respective to V0~V5, C01.56[0]~C01.56[5] is
respective to F0~F5, Vn is motor rated voltage, Fn is the motor rated
frequency.
The set of C01.56 must met F0=0 and F1≤F2≤F3≤F4≤F5.
Simplify V/F characteristic by merging 2 or more points (voltages and
frequencies), which respectively are set equal.
The slope (ratio of V/F) after point (F5, V5) must be equal to the slope
between point (F5, V5) and the previous point.
Voltage
Frequency
400V model:
Voltage
100%
60%
0
Change-over Frequency
Motor speed
Slip compensation 0%
Motor load
Rated load
slip compensation on power generating load
When having more than one motor on the same shaft there is a need for
some kind of load share between the drives controlling the motors. This
has typically been made with two drives running in speed open loop
mode and one with negative slip compensation.
Enter the slip compensation reaction speed. A high value results in slow
reaction, and a low value results in quick reaction. If low-frequency
resonance problems arise, use a longer time setting.
This parameter enables a delay of the starting time. The drive begins
with the start function selected in C01.72. Enter the time delay required
before commencing acceleration. Setting start delay to 0.0 sec. disables
start function when start command is given.
Select the start function during start delay. This parameter is linked to
C01.71 Start Delay.
0: DC Hold, Energizes motor with a DC holding current (C02.00 DC
Hold Current) during the start delay time;
2: Coast, Motor coasted during the start delay time (drive off);
This function applies for the inertia load to restart due to mains drop-out;
If [0] Clockwiseis selected in C04.10, and no rotating motor is found, It
is possible to use DC-brake command to ramp down the motor speed to 0
rpm, and then start the motor in the normal way; If [2]Both directions is
selected in C04.10, and no rotating motor is found, the drive will assume
the motor is stationary or in low-speed rotation, and then start the motor
in the normal way. When Flying start is enabled, C01.71 Start delay and
C01.72 Start function is disabled.
Warning: This function is not suitable for hoisting applications.
Par. No. Name Range Unit Default
C01.75 Min. Start Frequency 0.00~10.00 Hz 0.00
If the drive frequency reference is less than C01.75 Min. Start Frequency,
the drive will not run even the start command is given (the start command
will be shielded). Only the drive frequency reference is greater than or
equal C01.75, then the drive starts to run. The drive still accelerates from
0 to frequency reference using ramp time.
Freq. ref.
3Hz 8Hz 15Hz
Par. setting
Freq. ref > Freq. ref > C01.75,
C01.75, the start command
Freq. ref <
the start is given,
C01.75
command is Freq. ref > C01.76
C01.75 = 5.00 the start
given, the drive runs at
C01.76 = 10.0 command is
Freq. ref < 10Hz immediately,
shielded, the
C01.76 then accelerates
drive stop.
the drive runs from 10Hz to 15Hz
at 10.0Hz using ramp time.
Freq. ref > C01.75,
the start command
Freq. ref < Freq. ref <
is given,
C01.75 C01.75
Freq. ref > C01.76
C01.75 = 10.00 the start the start
the drive runs at
C01.76 = 5.0 command is command is
5Hz immediately,
shielded, the shielded, the
then accelerates
drive stop. drive stop.
from 5Hz to 15Hz
using ramp time.
Select the drive function after stop command is given or start command
is removed (standby), and output frequency is ramped down to C01.82
Min Speed for Function at Stop.
0: Coast, Leaves motor in free mode. the drive is off;
1: DC Hold, the motor is energized with a DC current. See C02.00
DC Hold Current for more information;
Diagram of Function at Stop is shown below:
Output
输出频率 Output
输出频率
Frequency Frequency
C01.82 C01.82
Time
时间 Time
时间
Output
输出电压 Output
输出电压
Voltage Voltage
0V C02.00
Time
时间 Time
时间
Start
运行信号 OFF Start
运行信号
ON ON OFF
Command Command
或 ON 或 ON
or Stop OFF or Stop
OFF
Command
停止信号 Command
停止信号
Coast
惯性停车 DC Hold
直流夹持
Par. No. Name Range Unit Default
Min Speed for
C01.82 0.0~400.0 Hz 0.0
Function at Stop
The drive determines the motor temperature for motor protection in two
different ways:
• Via a thermistor sensor connected to the analog input terminal VI
(C01.93 Thermistor Source).
•Via calculation (ETR = Electronic Terminal Relay) of the thermal
load,
based on the actual load and time. The calculated thermal load
is compared with the rated motor current IM,N and the rated motor
frequency fM,N. The calculations estimate the need for a lower load at
lower speed due to less cooling from the fan incorporated in the motor.
0: No protection;
1: Thermistor warning, a thermistor connected to analog input VI
gives a warning if upper limit of motor temperature range is exceeded, (see
01.93, Thermistor Resource);
2: Thermistor trip, a thermistor connected to analog input VI gives
an alarm and makes the drive trip if upper limit of motor temperature
range is exceeded, (see 01.93, Thermistor Resource);
3: ETR warning,if calculated upper limit of motor temperature
range is exceeded, a warning occurs
4: ETR trip,if calculated upper limit of motor temperature range is
exceeded, an alarm occurs and the drive trips.
Output
输出频率Hz
Frequency
DC直流制动
Brake
Cut切入频率
in Speed
Time
时间t
Demagnetization
电机消磁时间 Time
Output
输出电压V
DC Braking Time
直流制动时间
Voltage
DC Brake
直流制动量
Time
时间t
ON
Start
运行命令
Command OFF
Over-voltage control (OVC) reduces the risk of the drive tripping due to
an over voltage on the DC link caused by generative power from the load.
0: Disabled;
2: Mode 1, used to consume surplus energy by increasing the output
frequency;
3: Mode 2, used for very short deceleration;
Attention: If C02.10 = 1 (Resistor brake), C02.17 = 2 or 3, resistor brake
function starts first, if the DC link voltage still can not be
controlled, OVC starts.
Over-voltage control (OVC) reduces the risk of the drive tripping due to
an over voltage on the DC link caused by generative power from the load.
Note: These parameters are only active when selecting [2] Mode 1or [3]
Mode 2 in C02.17 Over-voltage Control
Set the motor current for release of the mechanical brake, when a start
condition is present.
Attention: When Mechanical brake control output is selected but no
mechanical brake is connected, the function will not work.
If start delay time has passed, and motor current is below
Release brake current, drive trips.
Output
输出频率Hz
Frequency
Activate
机械制动
Brake频率
Speed
Time
时间t
Output
输出电流A
Current
Release
机械制动
Brake
电流
Current
Time
时间t
Mechanical
抱闸控制
Brake
Control ON ON
OFF
Time
时间t
Start
运行命令 ON
command OFF
C03.1* References
Diagram of Reference Calculation is shown below:
The jog speed is a fixed output speed at which the drive is running when
the jog function is activated.
The drive with the highest priority will operate at jog speed when a
variety of run command activates. Removing the jog signal makes the
drive run according to the selected configuration, this parameter is set
limited by C04.14.
Par. No. Name Range Unit Default
C03.12 Catch up/Slow down Value 0.00~100.00 % 0.00
Select the reference input to be used for the first, second and third
reference source.
0: No function;
1: Terminal VI, useanalog input VI as reference source, see C06.1*;
This parameter is used for setting whether to save the data changed in the
Speed Up/Down function if the drive stops or after it power down.
C03.4* Ramp1
There are 4 ramps built in the drive. For each of four ramps (C03.4*,
C03.5*, C03.6* and C03.7*), configure the ramp parameters: ramp type,
ramp up time and ramp down time.
Ramp Type:
0: Linear, motor ramps up/down with constant acceleration /
deceleration;
2: S ramp, motor rampsup/down with non-linear acceleration/
deceleration;
Ramp UpTime is the time motor accelerates from 0Hz to rated motor
frequency (C01.25).
Ramp Down Time is the time motor decelerates from rated motor
frequency (C01.25) to 0Hz.
Diagram of Ramp Type, Ramp Up Time and Ramp Down Time are
shown below:
Output Frequency
Rated
Motor S ramp
Linear
Speed Deceleration
Acceleration
Linear
S ramp
Deceleration
Acceleration
Ramp Up Time Ramp Down Time
Time
Enter the jog ramp time, i.e. the acceleration/deceleration time between
0Hz and the rated motor frequency (C01.25).
Jog ramp time starts upon activation of a jog signal via a selected digital
input or serial communication port.
Set the minimum limit for Motor Speed, the motor speed low limit can
be set to correspond to the minimum output frequency of the motor shaft.
The Motor Speed Low
Limit must not exceed the setting in C04.14 Motor Speed High Limit
Set the maximum limit for Motor Speed, the motor speed high limit can
be set to correspond to the maximum manufacture’s rated motor speed.
The motor speed high limit must exceed the Motor Speed Low Limit in
C04.12.
This parameter is used to set drive output current limit, 100% equals
motor current set in C01.24. If the output current exceeds the C04.18
motor current limit, the drive will report A.59 warning and current limit
controllers (see C14.3*) start.
Enter the I low / I high value. When the motor current falls below I low or
exceeds I high, a signal can be produced on relays or terminal DO1/DO2.
See [12] Out of current range, [13] Below current low and [14] Above
current high in C05.30/31/40.
Diagram of Warning Current Low and Warning Current High are shown
below:
Output
Current
C04.51 Warning Current High
Terminal DO1/DO2/Relay
ON
[13]Below current low
OFF
ON
Terminal DO1/DO2/Relays
OFF OFF
[14]Above current high
Output Frequency
Terminal DO1/DO2/Relays
ON
[16]Below of frequency low
OFF
ON
Terminal DO1/DO2/Relays
OFF OFF
[17]Above frequency high
Enter the low/high reference warning value. When the actual reference
falls below C04.54 or exceeds C04.55, a signal can be produced on
relays or terminal DO1/DO2. See [40] Out of reference range, [41] Below
reference low and [42] Above reference high in C05.30/31/40.
Enter the low/high feedback warning value. When the feedback falls
below C04.56 or exceeds C04.57, a signal can be produced on relays or
terminal DO1/DO2. See [18] Out of feedback range, [19] Below feedback
low and [20] Above feedback high in C05.30/31/40.
Time
Coast inverse, [3] Coast and reset inverse, [42] Coast and [46] Stop;
20: Freeze output, freezes the output frequency, If freezing output is
active, stop the drive via a terminal programmed for [2] Coast inverse, [3]
Coast and reset inverse, [42] Coast and [46] Stop;
21: Speed up, when Speed up is activated for less than 400 ms. the
resulting reference will be increased by C03.13 Speed Up/Down Value. If
Speed up is activated for more than 400 ms, the resulting reference will
ramp according to ramp 4;
22: Speed down, similar to [21] Speed up;
23: Set-up select, select one of the two set-ups, see C00.10;
28: Catch up, select catch up to increase the resulting reference value
by the percentage set in C03.12Catch up/slow Down Value;
29: Slow down, similar to [28]Catch up;
32: Pulse input, select pulse input when using a pulse sequence as
either reference or feedback. Scaling is done in par. group C05.5*, the
function is available for C05.15 Terminal DI4 only;
34: Ramp bit0, ramp bit0, bit1 are used for select one of the four
ramps;
35: Ramp bit1, same as [34];
C05.4* Relay
32: Mech. brake control, enter mechanical brake control signal, see
C02.2*;
36: Control word bit11, bit11 in control word is active;
37: Control word bit12, bit12 in control word is active;
40: Out of reference range, reference is outside the range set in
C04.54 and C04.55;
41: Below reference low, reference is lower than set in C04.54;
42: Above reference high, reference is higher than set in C04.55;
51: Drive in HANDstate;
52: Drive in AUTOstate;
56: Drive in HANDstate;
57: Drive in AUTOstate;
60: Comparator 0, using a simple PLC, the results of comparator 0;
61: Comparator 1, using a simple PLC, the results of comparator 1;
62: Comparator 2, using a simple PLC, the results of comparator 2;
63: Comparator 3, using a simple PLC, the results of comparator 3;
70: Logic rule 0, using a simple PLC, the results of logic rule 0;
71: Logic rule 1, using a simple PLC, the results of logic rule 1;
72: Logic rule 2, using a simple PLC, the results of logic rule 2;
73: Logic rule 3, using a simple PLC, the results of logic rule 3;
80: Simple PLC digital rutput 1, only active for DO1;
81: Simple PLC digital output 2, only active for DO2;
82: Simple PLC relay 1, only active for relay 1;
83: Simple PLC relay 2, only active for relay 2;
84: Simple PLC relay 2, only active for relay 3;
160: Water supply: low voltage alarm control
161: Water supply: Over voltage alarm control
162: Water supply: Sleep
163: Water supply:Belt breaking signal
164: Water supply:No inverter available
192: Water supply:Relay control
Par. No. Name Range Unit Default
FA/FB/FC;
KA1/KB1;
KA2/KB2;
C05.41[x] Closed relay delay s 0.00
KA3/KB3;
KA4/KB4;
KA5/KB5
Par. No. Name Range Unit Default
FA/FB/FC;
KA1/KB1;
KA2/KB2;
C05.42[x] Open relay delay s 0.00
KA3/KB3;
KA4/KB4;
KA5/KB5
Live Zero Time-out Function is used for analog input signal detection.
To active the Live Zero Timeout Function, if voltage input is selected,
then the low input voltage (C06.10, C06.20) settings must be greater than
1V; if current input is selected, the low input current (C06.12, C06.22)
settings must be greater than 2mA or more. If the analog input signal is
lower than 50% of the settings of parameters of C06.10, C06.12, C06.20,
C06.22, and lasts longer than the settings of C06.00Live Zero Timeout
Time, this feature takes effect.
If the analog input signal is back to normal within the delay time,
thenreset the timer.
Diagram of Live Zero Timeout Function is shown below:
Analog Input
50%
C06.10,C06.12,
C06.20,C06.22, Live Zero Timeout
C06.00 Time
Live Zero Timeout
Time
C06.1*Analoge Input VI
Parameters for configuring the scaling and limits for analog input VI.
C06.10is used to set low voltage input;C06.12is used to set low current
input; The low voltage and current analog input scaling value corresponds
to the lowref./feedb. value, set in C06.14.
C06.11is used to set high voltage input;C06.12is used to set high
current input; The high voltage and current analog input scaling value
corresponds to the high ref./feedb. value, set in C06.15.
There are 4 kind of curves between terminal VI input voltage/current and
its scale value:
Ref./Feedb.
VI Input
and
Ref./Feedb.
参考值/反馈值
C06.15
C06.10
/C06.12
0
C06.11 10V/ VI Input
VI模拟量值
/C06.13 20mA
C06.14
and
Ref./Feedb.
参考值/反馈值
C06.14
C06.15
0
C06.10 C06.11 10VI VI Input
VI模拟量值
/C06.12 /C06.13 20mA
and
Ref./Feedb.
VI Input
and
Enter the terminal VI filter time. This is a first-order digital low pass
filter for suppressing electrical noise in terminal VI.A high time constant
value improves dampening but also increases the time delay through the
filter.
Set the dead-band of VI at 0 speed. When analog input VI ref. low and
ref. high have opposite signs, there must be a set point that corresponding
to an analogue value equals 0. In order to prevent the set point jitter
at zero point due to analog interference, this parameter should be set
properly.
Ref./Feedb.
C06.15
B
0 A C
VI Input
C06.18
C06.14
Terminal AI Low
C06.20 0.00~C06.21 V 0.07
Voltage
Terminal AI High
C06.21 C06.20~10.00 V 10.00
Voltage
Terminal AI Low
C06.22 0.00~C06.23 mA 0.14
Current
Terminal AI High
C06.23 C06.22~20.00 mA 20.00
Current
Terminal AI Low
C06.24 -4999.000~4999.000 0.000
Ref./Feedb. Value
Terminal AI High
C06.25 -4999.000~4999.000 50.000
Ref./Feedb. Value
Terminal AI Filter
C06.26 0.01~10.00 s 0.01
Time
Terminal AI Zero
C06.28 0.0~20.00 V/mA 0.00
Dead Band
0: Voltage mode
C06.29 Terminal AI Mode 1: Current mode 0
2: Resisitor(RI) mode
0 No Function
If C03.00 = 0,
then 0% = 0, 100% = C03.03;
11 Reference
If C03.00 = 1,
then 0% = -C03.03, 100% = C03.03;
12 Feedback
13 Output current 0% = 0, 100% = C16.37
16 Power 0% = 0, 100% = C01.20
0% = C06.20/C06.22,
23 Terminal AI Input
100% = C06.21/C06.23
Terminal VO
C06.75 0.00~C06.76 % 0.00
Min Output
Terminal VO Voltage mode: C06.75~10.00
C06.76 % 10.00/20.00
Max Output Current mode: C06.75~20.00
These two parameters is used to set VO min and max value for terminal VO,.
Example:
Under speed open mode, set C03.03 =50.000,C06.70 = 3(0 ~ 10V),
C06.71 = 10(output frequency, 0% = 0Hz, 100% = 50Hz),
C06.73 = 0.00%(0Hz),C06.74= 100.00%(50Hz),
C06.74 = 100.00%(50Hz), C06.75 = 2V,C06.76 = 8V
Relationship betweenoutput frequencyandoutputvoltageVOis shown
below:
VO
8V
2V
8V
2V
Enter the proportional gain value for the torque controller. Selection of a
high value makes the controller react faster. Too high a setting leads to
control instability.
Enter the integration time for the torque controller. Selection of a low
value makes the controller react faster. Too low a setting leads to control
instability.
This parameter is active in closed loop process control mode (See C01.00
Configuration Mode).
Output
Frequency
Speed open loop Process closed loop
C07.32
ON Time
Start OFF OFF
Command
These parameters are used to set process PID controller output low/high
limit, 100% corresponds to C04.19.
The drive start, stop, reverse, jog commands can be given both through
digital input terminals and communication control word, this parameter
is used to set the drive control command site.
Communication control word is the control command sent by drive,
it is 16-bit fixed-length (a word). It can be set by written register (address
2809) or coils (address 0~15) via ModBus or FC protocol. For the
meaning of control word each bit, please refer to register 2810 and coils
0~15 description in appendix A Modbus Communication Specification.
0: Digital and control word, control by using both digital input
andcontrol word;
1: Digital only, control by using digital inputs only;
2: Control word only, control by using control word only;
This parameter is used to select whether the control word is active or not.
Enter the maximum time expected to pass between the reception of two
consecutivetelegrams. If this time is exceeded, it indicates that the serial
communicationhas stopped. The function selected in C08.04 Control
Word Timeout Function willthen be carried out. The time-out counter is
triggered by a valid control word.
Resetting control word timeout will remove any timeout function. After
control word timeout occurs, a control word interrupt flag will be within
the drive. It must be use the parameter to clear the flag (Do reset), else
even to restore communication or clear "E.17" alarm, the drive will
continue to report control word timeout.
0: Do not reset, control word timeout is not reset;
1: Do reset, control word timeout is reset;
Select the address for the bus. FC-bus range is 1-126, and Modbus range
is 1-247.
This parameter only effective for Modbus and FC bus always has even
parity.
C08.5* Digital/Bus
This parameter only active only when C08.01 Control site is set to [0]
digital and control word.
Select control of the coasting, start, reverse, set-up and preset reference
function via the terminals (digital input) and/or via the bus.
0: Digital input, activate via a digital input;
1: Bus, activate via serial communication port;
2: Logic AND, activate via serial communication port and a digital
input;
3: Logic OR, activate via serial communication port or a digital
input;
Enter the simple PLC stop event. For options, see C13.01 Start Event.
This parameter is used to select whether the simple PLC state is saved or
not at power down/stop.
C13.1* Comparators
Comparators are used for comparing continuous variables (e.g. output
frequency, output current, analog input etc.) with fixed preset values. In
addition, there are some constant value in conjunction with the preset
value for comparison, please refer to options in C13.10. In each of the
scanning integral the comparator will be evaluated once. And directly
use the results (true or false). Parameters in this group are all array-type
parameter with index 0-4 . Select 0 to programme Comparator 0, select
index 1 to programme Comparator 1, and so on.
For example: Motor current is 25A, C13.10 [0] =4, C13.12 [0] =23, C13.11
[0] =2, then the output of comparator 0 is TRUE.
0: Disabled;
1: Reference;
2: Feedback;
3: Motor speed [Hz];
4: Motor current [A];
6: Motor power [kW];
7: Motor Voltage [V];
12: Terminal VI input, depending on your choice is current input or
voltage input;
13: Terminal AI input, depending on your choice is current input or
voltage input;
20: Fault number, please refer to chapter 8;
30: Counter A;
31: Counter B;
0: Less than, if the variable selected in C13.10 is less than the set
value in C13.12, the comparator output is TRUE, else FALSE;
1: Approx. Equal, if the variable selected in C13.10 equals the set
value in C13.12, the comparator output is TRUE, else FALSE;
2: Greater than, opposite with option [0];
Enter the “trigger level” for the variable that is monitored by this
comparator.
C13.2* Timers
Use the timer output to define an event (see C13.51) or acts as Boolean
inputs of the logic rules (see C13.40, C13.42 or C13.44).
Select the second boolean (TRUE or FALSE) input for the selected logic
rule. Options refer to C13.01.
Select the third boolean (TRUE or FALSE) input for the selected logic
rule. Options refer to C13.01.
C13.5* Events/Actions
This group of parameter is used for setting evens or actions for Simple
PLC. All parameters in this parameter group are array [30] parameters
with index 0 to 29. Select index 0 to event/action 0, select index 1 to
event/action 1, and so on.
Select the boolean input to define the Simple PLC event. Options refer to
C13.01.
Switching frequency has asignificant inf luence to the drive and the
motor. Select appropriate switch frequency can help to adjust acoustic
noise from the motor、power consumption and the drive efficiency. When
switching frequency increases, the consumption and the noise of the
motor are reduced, but the drive’s temperature will increase, and motor
leakage and the interference to the external device will increase; the
contrary, the opposite.
Damping gain factor can help to improve the response speed of the DC
link of the making the DC loop signal more smooth.
If the power input voltage is low, enable low voltage mode can improve
load capacity. If the voltage is 15% lower, enable low voltage mode can
make the drive afford long-term full load; If the voltage is 20% lower, the
drive needs to down load; If the voltage is normal, do not enable the low
voltage mode, otherwise it will reduce the drive useful life.
When motor voltage 12%~20% higher than rated, motor temperature will
increase, insulation capability destroyed, the torque output is unstable,
- 134 - HLP-SP110 Series Operating Manual
HLP-SP110 Series
This parameter is used to define the drive action when power up again
after power loss during running.
If it is set to 3600.0, the drive does not respond to the start command
valid upon drive power-on (for example, start terminal is ON before
power-on). The drive responds only after the start command is cancelled
and becomes valid again.
If it is set to 0.0~3599.9, the drive will respond to the start command
delaying the C14.18 setting time upon drive power-on (for example, start
terminal is ON before power-on).
set number of automatic reset, fault still cannot be removed, the drive
will remaina tripstate. It needs power off and on to reset the trip after
shootingfault.
Be attention to select option [13], it may cause infinite auto reset.
Enter time interval from trip to start of automatic reset function after
an alarm. This parameter is active when C14.20 Reset Mode is set to
automatic reset [1]-[13].
Select how the d r ive should react at i ner ter fault (out put shor t
circuit,over-current, earth fault or over-voltage).
0: Trip, driveissues an alarmand tripsimmediately if it detects a
fault;
1: Warning, when a fault occurs, drive issues a warning and stops
the PWM outputs, and repeatlly try to open the normal PWM, if the fault
still can’t be removed, the drive issues an alarm and trips.
0: Off, only the power supply is IT mains system can select [0] Off.
In this mode, the linkage can be reduced;
1: On, to ensure the drive meets EMC standards, select [1] On;
2: Reserved;
Attention: The RFI Filter selection in the model (<=22kW) is not
controlled by this parameter, but selected by screwing off/on the RFI
switch.
View how many days the drive has run. The value is saved automatically
at power off and can’t be reset.
View how many hours the motor has run. Reset the counter in C15.07
Reset Running Hours Counter.
View the power consumption of the motor as a mean value over one hour.
Reset the counter in C15.06 Reset kWh Counter.
View the number of times the drive has been powered up. This parameter
can’t be reset.
View the number of the drive temperature faults that have occurred. This
parameter can’t be reset.
0: Do not reset;
1: Do reset, kWh counter is reset to zero (see C15.02 kWh Counter);
Attention: This parameter can’t be set via local bus.
0: Do not reset;
1: D o r e s e t , r u n n i n g h o u r s c o u n t e r i s r e s e t t o z e r o (s e e
C15.01Running Hours);
Attention: This parameter can’t be set via local bus.
View the alarm code and look up its meaning in chapter 8. This parameter
is an array [10] parameters. It contains aalarm log showing reasons for
the ten latest trips. C15.30[0] represents the latest, C15.30[9] is a recent
10th, this parameter cannot be reset.
View the warning code and look up its meaning in chapter 8. This
parameter is an array [10] parameters. It contains a warning log showing
reasons for the ten latest warnings. C15.38[0] represents the latest,
C15.38[9] is a recent 10th, this parameter cannot be reset.
View latest valid control word that sent to the drive via local bus.Turn
it into 16-bit binary code. For the meaning of eachbits, please refer
to register 2809 and coils 0~15 description in appendix A Modbus
Communication Specification.
View active status word, the following shows the definition for each bit.
Frequency Not In
Bit10 Frequency In Range
Range
Bit11 Stop Running
Brake Resistor Is
Bit12 Brake Resistor Fault
Normal
Bit13 Voltage Limit Out Of Voltage Limit
Bit14 Undefined Undefined
Bit15 No Terminal Warning Terminal Warning
View the state of the event under execution by the simple SLC.
C16.5* Ref./Feedb.
View signal states from active digital inputs, which indicates in a 16-bit
binary code. If the drive detects digital input terminals connected, the
corresponding position is set to “1”, otherwise “0”. Digital input terminal
and the corresponding relationship between the binary code are as below:
View actual state of digital output, which indicates in a 4-bit binary code;
If the digital output terminal is active, the corresponding position is set
to “1”, otherwise “0”. Corresponding relationship betweenstate of the
digital output terminals and the binary code are as below:
View the output status of the relay, the corresponding bit is set to
“1”whenthe relay output is active, otherwise it will be set to “0”.
View the alarm/warning word sent via the serial communication port in
hex code. Convert this parameter to a 32-bit binary code, definition of
the bits in word showed in the table below, among which that reserved by
manufacturers are undefined bits:
Alarm Word1 Alarm Word 2 Warning Word 1 Warning Word 2
Bit
/C16.90 /C16.91 /C16.92 /C16.93
0 Brake Detect Undefined Undefined Undefined
Power Card Over Power Card Over
1 Undefined Undefined
Temp. Temp.
2 Earth Fault Trip Earth Fault Undefined
3 Reserved Option Part Undefined Undefined
Control Card Control Card
4 Undefined Undefined
Temp Temp
5 Over Current Undefined Over Current Undefined
6 Torque Limit Undefined Undefined Undefined
Motor Over Ther- Motor Over Ther-
7 Undefined Undefined
mal mal
Motor Over Ther- Motor Over Ther-
8 Damaged Part Damaged Part
mal ETR mal ETR
9 DriveOverload Undefined Drive Overload Undefined
10 Under Volt Undefined Under Volt. Undefined
C25.0* Ref./Feedb.
Set value
Pressure
sensor
Contactor2 Contactor4
Contactor1 Contactor3
[3] water supply mode 3, the inverter does not go through the relay of
the direct drive pump, the other auxiliary pump through a set of relays
connected to the grid
Contactor1
Contactor2
Contactor3
Set value
Contactor4
Pressure test
REALY
C25.01 C25.03
C5.40[0] C5.40[1] C5.40[2] C5.40[3] C5.40[4] C5.40[5]
When system pressure is larger than C25.34 for some time(C25.35), over
pressure alarm is valid and correlative output terminal is valid.
0:Invalid
C25.50 Sleep mode 0
2:Effective
[0] invalid;
[2] sleep mode valid;
If C25.50 = 0, system will not enter into sleep mode
0:Disabled
C25.85 Belt breakage detection 1:warning 0
2:Alarm
[0] Disabled;
[1] Warning;
[2] Alarm
Belt breakage
C25.89 0.0~600.0 S 20
detection: time delay
The parameter is used to express detection delay time.
K1 K2 Command
OFF OFF Stop
ON OFF Run forward
OFF ON Run reverse
ON ON Stop
K1 K2 Command
OFF OFF Stop
ON OFF Run forward
OFF ON Stop
ON ON Run reverse
7.3 Multi-speed
In scenarios where the running frequency of the drive need not be
adjusted continuously and only several frequencies are required, the
multi-speed control can be used. The drive supports a maximum of
16 running frequencies in each set-up, which are implemented by
state combinations of four DI terminals. Set the parameter number
corresponding to DI terminals to a value among 15 to 18 (Preset ref. bit
0~3), and then the DI terminals are specified as the multi-frequency input
terminals. The multiple frequencies are set based on the multi-frequency
table in group FC. In addition, you need to set C03.03 (Maximum
Reference). The following figure shows how to set the multi-speed
function.
Term. Par. Value State Combinations Multi-speed%
0 0 0 0 C03.10[0]
0 0 0 1 C03.10[1]
0 0 1 0 C03.10[2]
In the preceding figure, FOR, REV are set as two-line mode 1, DI1,
DI2, DI3 and DI4 are used as the multi-frequency input terminals, each
of which has a bit value. The state combinations of these terminals
correspond to multiple frequencies, When (DI4, DI3, DI2, DI1) = (0, 0,
1, 0), the state combination value is 2, corresponding to the value set in
C03.10[2]. The target runningfrequency is automatically calculated by
C03.10[2] x C03.03.
The drive supports a maximum of four DI terminals to be used as the
multi-frequency input terminals. You can also use less than four DI
terminals, and the empty bit is considered to be 0.
Ref.
FOR C05.10 8
REV C05.11 11
DI1 C05.12 21
DI2 C05.13 22
COM
Output frequency
Reference
time
Start command
Speed up
Speed down
Output 40Hz
Frequency
25Hz
12Hz
10Hz 8Hz
Time
-20Hz
-50Hz
Parameters setting:
Fault
Warning Alarm Error Reason analysis
Description
Fault
Warning Alarm Error Reason analysis
Description
Thermistor damage,uncorrectly
Motor Over
E.11 installed or motor cooling equip-
Temperature
ment failure.
Fault
Warning Alarm Error Reason analysis
Description
Motor phase
E.30* Check the phase and motor.
U missing
Fault
Warning Alarm Error Reason analysis
Description
Motor phase
E.31* Check the phase and motor.
V missing
Motor phase
E.32* Check the phase and motor.
W missing
24V Power
E.47* 24V voltage power card failure
Card Fault
AMA check
Motor voltage and motor current
E.51 Unom and
error setting.
Inom
AMA
Motor parameter is out of the
E.55 Paremeter
range
Error
AMA
E.57 AMA takes too long to run.
Time-out
Fault
Warning Alarm Error Reason analysis
Description
Parameter
E.80 Make parameter initialized.
Initialization
Fault
Warning Alarm Error Reason analysis
Description
24V Power
E.88* 24V PowerCard Fault
Card Fault
LCP Con-
nection with No communication between LCP
Er.84
the drive and the drive.
failed
Button is
Er.85 Refer to parameter group C00.4*.
disabled
Parameter
Er.89 Try to write read-only parameter.
read-only
Parameter
value is in-
Er.91 Invalid parameter value to write.
valid in this
mode
Chapter 9 Maintenance
9.1 Note
Confirm the main circuitpower supply has been turned off, and the
display has disappeared before carry out inspection and maintenance.
Make sure the system is in dynamic state, please pay attention to the
following:
• Check whether the power supply voltage matches to the rated
voltage of the drive;
• Check whether the motor makes unexpected noises or abnormal
vibration when running;
• Check whether there are abnormal heating;
• Check whether the drive output voltage,output current, output
f requency, and monitor display is g reater than the value
commonly used.
• Check whether the cooling fan installed at the lower part of the
drive runs normally;
• Check whether the ambient temperature is too high and whether
there is dust,iron filings, corrosive fluid in the drive;
• Check whether the ambient temperature of the drive is between
-10℃~40℃, and whether the humidity is between 5%-85% (95%
is without condensation), phenomenon of water droplets is not
allowed;
• The driveshould be discarded as industrial waste. It is forbidden
to burn it;
1. Application Mode
1.1 Interface Mode
Specification:
1. No m at t e r wh ich mo de, t he d r ive is u se d a s a slave i n
communication. When master sends commands using broadcast address,
the slave does not respond;
2. It is recommended to use shield cables in multiple connection.
The basic parameter of the devices, such as baud rate and digital check
bit in RS485 should be the same as slave device’s and there should be no
repeated addresses in slave devices.
2. Protocol Format
Modbus protocol supports both RTU and ASCII mode.
Specification:
Specification:
1. Frame header is "0x3A" while the default frame end is "0x0D"
"0x0A";
2. In ASCII mode, all data bytes other than frame header and end
are sent in the form of ASCII code; high-4-bit byte and low-4-bit byte are
sent successively;
3. In ASCII mode, the data is 7-bit long. For 'A'~'F', their uppercase
ASCII codes are used;
4. Data is subjected to LRC check which covers the information
portion from slave address to data;
3. Function Code
Function code supported by the drive Modbus protocol are as shown in
the table below:
Register
Specification R/W
address
The internal error code of last
6 R
communication error
* Reg 8 specification
Reg 8 is parameter index register. The drive has some array type
parameters. When accessing these parameters, it should be set index
first.
For example, write value into C03.10[2]. It should write 2 into Reg 8 first,
then write value into 3099 (the register address of C03.10 is 310 × 10-
1=3099, hexadecimal is 0x0C1B).
Bit 0 1
Bit0 Preset reference bit0 set to 0 Preset reference bit0 set to 1
Bit1 Preset reference bit1 set to 0 Preset reference bit1 set to 1
Bit2 DC brake No DC brake
Bit3 Coast stop No coast stop
Bit4 Quick stop No quick stop
Bit5 Freeze freq No freeze freq
Bit6 Ramp stop Run
Bit7 No reset Reset
Bit8 No jog Jog
*Reg 60800~60835specification
C39.00~C39.35 is user-defined parameters.Users can set other parameter
number into C39.00 ~ C39.35, then users can read and write these
parameters quicky by communication.
Registers in Modbus is 16 bits. For using one message (eg. Write Multiple
Registers) to modify parameters which data type is UINT32/INT32 or
array, it need set index in C39.50~C39.85 which correspond to parameter
number in C39.00~C39.35.
For example:
Par.No. Value Par.No. Value Reg. Spec.
C39.00 303 C39.50 0 60800 C03.03 low 16 bits
C39.01 303 C39.51 1 60801 C03.03 high 16 bits
C39.02 310 C39.52 0 60802 C03.10[0]
The data type of C03.03 is UINT32. Set C39.50 to 0 (index) to make Reg.
60800 corresponds to C03.03 low 16 bits, set C39.51 to 1 (index) to make
Reg. 60801 corresponds to C03.03 high 16 bits.
The data type of C03.10 is INT16, it is an array. Set C39.52~C39.54 to 0, 1,
2 respectively to make Reg. 60802~60804 correspond to C03.10[0]~[2].
The data type of C13.12 is INT32, it is an array. For this data type,
hundreds digit represents high or low 16 bits, tens digit and ones digit
represent array index. So set C39.10=1312, C39.60=102 makes Reg.
60810 corresponds to C13.12[2] high 16 bits
7. Error message
There may be errors in the communication process, for example, some
parameters are read-only, but the PC/PLC sends a written directive, the
drive will return an error message.
Error message data frame format is shown as the figure below:
8. Examples
8.1 Read Holding Registers (0x03)
8.1.1 Read Output Frequency
Read the value of C16.13 to get the output frequency.
Transmit: 01 03 3F 01 00 02 99 DF (Hexadecimal)
Receive: 01 03 04 00 00 01 F4 FA 24 (Hexadecimal)
Transmit data specification:
Field Description
01 Address
03 Function
Register address (ADDRH ADDRL). The register address of
3F 01
C16.13 is 1613*10-1=16129 (0x3F01)
00 02 The number of read registers is 2
99 DF CRC check
Field Description
01 Address
03 Function
04 The byte number of received data
00 00 01 0x000001F4 converts to decimal number is 500. So the value
F4 of C16.13 is 500*0.01 = 50.0
FA 24 CRC check
Field Description
01 Address
03 Function
Register address (ADDRH ADDRL). The register address of
3E 9D
C16.03 is 1603*10-1=16029 (0x3E9D)
00 01 The number of read registers is 1
18 0C CRC check
Field Description
01 Address
03 Function
02 The byte number of received data
Status word: 0x0258
02 58 0x0258 converts to binary number is 0000 0010 0101 1000. They
correspond to parameter C16.03 bit 0~15.
B8 DE CRC check
Field Description
01 Address
06 Function
Register address (ADDRH ADDRL). The register address of
0C 1B
C03.10 is 310 *10-1=3099 (0x0C1B)
The value which will be written into C03.10[0] is 40.00%
0F A0
(Decimal: 4000, Hexadecimal: 0x0FA0).
FF 15 CRC check
Field Description
01 Address
06 Function
Register address (ADDRH ADDRL). The register address
0C 1B
of C03.10 is 310 *10-1=3099 (0x0C1B)
The value which has be written into C03.10[0] is 40.00%
0F A0
(Decimal: 4000, Hexadecimal: 0x0FA0).
FF 15 CRC check
Field Description
01 Address
06 Function
0A F9 Register address 2809 (0x0AF9)
The value which will be written into Reg. 2809 is 0x047C
(Control word)
04 7C
0x047C converts to binary number is: 0000 0100 0111 1100,
They correspond to Reg. 2809 bit 0~15.
59 02 CRC check
Field Description
01 Address
06 Function
0A F9 Register address 2809 (0x0AF9)
The value which has be written into Reg. 2809 is 0x047C
04 7C
(Control word)
59 02 CRC check
Write register 2809 to control the drive running and write register 2810
to set the drive output frequency.
Transmit: 01 10 0A F9 00 02 04 04 7C 19 9A 09 32 (Hexadecimal)
Receive: 01 10 0A F9 00 02 92 21 (Hexadecimal)
Transmit data specification:
Field Description
01 Address
10 Function
0A F9 Register address 2809 (0x0AF9)
00 02 The number of write registers is 2
04 The byte number of write data is 4
Field Description
01 Address
10 Function
0A F9 Register address 2809 (0x0AF9)
00 02 The number of write registers is 2
92 21 CRC check
Field Description
01 Address
01 Function
Coil address (ADDRH ADDRL), 0x0030 converts to decimal
00 30
number is 48.
Data bits number is 16 (48~63), 0x0010 converts to decimal
00 10
number is 16.
3C 0C CRC check
Field Description
01 Address
01 Function
02 The number of read byte is 2
Field Description
01 Address
01 Function
Coil address (ADDRH ADDRL), 0x0030 converts to
00 20
decimal number is 32.
Data bits number is 16 (32~47), 0x0010 converts to decimal
00 10
number is 16.
3C 0C CRC check
Field Description
01 Address
01 Function
02 The number of read byte is 2
Status word: 0x0258.
02 58 0x0258 converts to binary number is 0000 0010 0101 1000,
they correspond to coils 32~47.
B9 66 CRC check
05 Function
Coil address (ADDRH ADDRL), 0x0040 converts to
00 40 decimal number is 64, it means parameter save control at
power down.
FF 00 means saved to EEPROM at power down
FF 00
00 00 means saved to RAM at power down
8D EE CRC check
Field Description
01 Address
05 Function
Coil address (ADDRH ADDRL), 0x0040 converts to
00 40 decimal number is 64, it means parameter save control at
power down.
FF 00 means saved to EEPROM at power down
FF 00
00 00 means saved to RAM at power down
8D EE CRC check
Field Description
01 Address
0F Function
Coil address (ADDRH ADDRL), 0x0000 converts to
00 00
decimal number is 0.
Data bits number is 32 (0~31), 0~15 represents control word,
00 20
16~31 represents reference.
04 The number of write byte is 4.
7C 04 Control word , swap high and low, the data is 0x047C.
Reference, If you want to set output frequency to 20Hz, it
9A 19
should write 20 ÷ 50 × 16384 = 6553.6 ≈ 6554 (0x199A).
37 B3 CRC check
Field Description
01 Address
0F Function
Coil address (ADDRH ADDRL), 0x0000 converts to
00 00
decimal number is 0.
00 20 The number of write bits is 0x0020 (32 bits), that’s 4 bytes.
54 13 CRC check
2. Installation
D
Use netcable to connect the copy card and the drive. Plug one terminal
1 into
2 the copy card
3 RJ45 port
4 which is 5placed on the
6 back and plug
7 the 8
other terminal into drive RJ45 port. As shown in the following figure: 1 2 3 4
A
A A
B B
E
B
1:1 A4 Danfoss Standard
Designation
Design
F Approval
E E
Confidential: Property of Danfoss A/S, Nordborg, Denmark.
Not to be handed over to, copied or used by third party. Two- or three
Projection Scale
1:1
No. COPY-CARD
Size
A4
Material
Danfoss Standard
dimensional reproduction of contents to be authorized by Danfoss A/S.
Mrk. Approval/Rev Date
Rev. Designation
copy-card.drw D
Sheet
1 2 Replace
Design 3 F
4
F Approval
Confidential: Property of Danfoss A/S, Nordborg, Denmark.
Not to be handed over to, copied or used by third party. Two- or three
No. COPY-CARD
dimensional reproduction of contents to be authorized by Danfoss A/S. Rev. Sheet 1/1
1 2 3 4
E
1:2
Projection Scale Size Material
7:50 A3 Danfoss Standard
Designation
Design
Confidential: Property of Danfoss A/S, Nordborg, Denmark.
Not to be handed over to, copied or used by third party. Two- or three
- 189 -
No. A3-EXPLODED
F
1 2 3 4 5 6 7 8
HLP-SP110 Series
3. Operation
3.1 Upload
3.2 Download
1) Connect copy card and drive according to 2. Installation;
2) After the drive power on, Power indicator on the copy card will be
ON. If the connection between copy card and drive is not OK, Fail
indicator will be ON;
3) Press Download key, parameters in copy card begin copying to drive.
Trans indicator will be blinking during transfer.
4) If an error occurs during transfer, Fail indicator will be ON; If data
download success, Trans indicator will be OFF;