1- INTRODUCTION .................................................................................................................................... 3
2- WARNINGS ........................................................................................................................................... 4
3- MOUNTING........................................................................................................................................... 4
4- PANEL INPUTS....................................................................................................................................... 5
4.1 Mains power supply ........................................................................................................................ 5
4.2 Batteries ......................................................................................................................................... 5
4.3 Detection Devices Inputs (Loop Lines) ............................................................................................. 5
4.4 Panel PC Connection ....................................................................................................................... 6
5- PANEL OUTPUTS ................................................................................................................................... 6
5.1 Sounder Outputs (4 Units) ............................................................................................................... 6
5.2 Auxiliary Power Supply Output (24 V DC) ......................................................................................... 7
5.3 Relay Outputs (3 Units) .................................................................................................................... 7
6- PANEL BUTTONS AND INDICATORS ....................................................................................................... 8
6.1 Control Buttons ............................................................................................................................... 8
6.2 Front Panel Indicators ................................................................................................................... 10
6.3 Internal Indicators ......................................................................................................................... 11
7- PANEL FUSES ...................................................................................................................................... 11
8- POWERING THE PANEL ....................................................................................................................... 12
8.1. First Boot of Panel ........................................................................................................................ 12
8.2. Booting Previously Configured Panel ............................................................................................. 16
9- FIRE EVENT MESSAGE FORMAT on PANEL LCD SCREEN ....................................................................... 17
10- FAULT EVENT MESSAGE FORMAT ON LCD SCREEN ............................................................................ 18
11- PANEL MENU .................................................................................................................................... 18
12- NETWORKING PRINCIPLES................................................................................................................. 23
13- TECHNICAL SPECIFICATIONS.............................................................................................................. 26
14- PANEL MODELS ................................................................................................................................. 27
ANNEX-A PANEL DIMENSIONS AND MOUNTING HOLES .......................................................................... 28
ANNEX-B CONNECTION SCHEME ............................................................................................................. 29
ANNEX-C PANEL SPARE PARTS ................................................................................................................ 30
ANNEX-D SERIAL COMMUNICATION CABLE ............................................................................................. 31
ANNEX-E SCHEME OF MENU FUNCTIONS ................................................................................................ 32
ANNEX-F NETWORK CONNECTION SCHEME ............................................................................................ 36
1- INTRODUCTION
Maxlogic ML-121X series intelligent analogue addressable fire alarm control panels are
provided with 0, 1, 2 loop options and 1000 user-defined zone capacity. Up to 127 analogue
addressable devices per loop are allowed to be connected.
Devices operating with VIP protocol such as Photo-Electric Smoke Detectors, Heat Detectors,
Multi-Sensor Detectors, Switch Monitor Modules, Relay Controller Modules, Sounder
Controller Modules, Loop-powered Addressable Sounders and Zone Monitor Modules are
compatible with ML-121X series control panels.
The project planning must be made carefully, in order not to have any difficulties when
commissioning the system. Zone location text (up to 40 characters including blank spaces) for
each device should be predetermined. Then, the devices should be categorized in zones
depending on the physical specifications of the building. After these steps, the panel can be
configured via the software program called ‘Loop Manager’.
The panel is equipped with 4 programmable and fault monitored 24 V DC 500mA sounder
outputs. Panel also contains 3 volt-free 30 V DC 1A relay outputs (fire relay, alarm relay, fault
relay) and a 24V DC 500mA auxiliary power supply output. Furthermore, 4 remote control
inputs (alarm, silence/sound alarm, reset and fault) exist in the panel.
ML-121X series fire alarm control panels have the optional functions described in TS EN 54-2
standards;
Sounder outputs
ML-121X series fire alarm control panels have also the supporting functions described in TS
EN 54-2 standards;
Network: The supporting function used to communicate in network.
NOTE: This user manual is valid for the panel models indicated in 14th section.
Service stations’ communication information that related spare parts have been
provided
Authorized Services:
MAVILI ELEKTRONIK TICARET VE SANAYI A.S.
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY
TEL: +90 216 466 45 05 - +90 216 466 45 10
TEKSIS TEKNIK ELEKTRONIK SIS.TIC. VE SAN. LTD. STI.
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/3 UMRANIYE / ISTANBUL / TURKEY
TEL: +90 216 313 60 60 - +90 216 313 47 49
Expected operation life which has been determined and announced by related ministry
This device’s expected operation life is 7 years.
The panel contains static-sensitive high quality electronic control equipment. Do not use the
panel before reading this manual.
In case of any fault, only the technicians of the manufacturer or technicians authorized by the
manufacturer should repair or maintain the panel.
The person who will operate the system should be well trained on powering and operating the
system.
Two years of warranty is valid from the production date as long as the system is used with
regard of obeying the rules, instructions and recommendations provided by the manufacturer.
Use the recommended cable types defined in this manual for cabling of panel power supply,
sounder power supply and detector line. Do not remove any connections and do not make any
connections while mains power supply is connected. Panel’s earth connection must be made
definitely.
Do NEVER apply 230V AC 50Hz mains power into the detectors and manual call points input
terminals, sounder line outputs and battery connection inputs.
This panel has been designed to operate on 230 V AC 50 Hz power supply. The protective
earth connection must be made definitely and the mains power supply must be presented
through the device via a fuse assigned only to this device. If the earth connection is not made
appropriately, all the conductive parts in the device may result in electrical leakage and this
may create hazard.
‘Automatic Learning’ causes erasing of existing configuration data at the panel. Therefore, it is
recommended to download the configuration data to PC, before ‘Automatic Learning’.
3- MOUNTING
The chosen mounting site of the panel must be clean, dry, not subject to shock or vibration
and easily accessible. The temperature must be in between the temperature range of
-5C° and +50C°. The relative humidity must not be m ore than 95%.
The panel should be mounted on a flat surface in such a way that, the indicators should be at
the eye-level and must not be mounted near the sources of excessive heat or cold and inside
of any cabinet.
Uncover the panel via the allen key provided with the panel.
Panel cable entries from back and top of the panel are available for easy mounting. Mark the
position of the fixing holes according to the respective Annex-A, Figure-2; ensuring that the
wall is flat at the chosen location.
Screws or bolts of a minimum of 4mm diameter must be used to mount the cabinet in all four
mounting positions. Drill and plug the wall then fix the cabinet using all fixing points.
The system is designed to operate with 230V AC 50Hz. Earth connections must be made to
earth terminal and earth resistor must be less than 10Ω. The mains supply of the panel must
be via an independent self-resetting fuse rated 230V AC 6A. This fuse must be separate from
the other fuses and a caution note should be written such as ‘ATTENTION! FIRE ALARM
CONTROL PANEL’S FUSE. DO NOT REMOVE’ to ensure safe operation of the panel.
Recommended cable types are 3x2,5 NYM or 3x2,5 NYA. Connections must be done
according to Annex- B, Figure-1.
Do not connect or disconnect loops, mains supply input and PCB connections while the panel
is energized, to avoid an electric shock.
4.2 Batteries
Batteries provide continuity of operation during a failure of the mains power supply. The panel
uses 2 units of 12 V DC 7Ah dry type batteries. Battery connection scheme can be seen from
Annex-B, Figure-14.
ML-121X series panels are produced with 0, 1, 2 loop models. Panels with
0 loops (no-loop) are used as repeater panels. Each loop is capable of hosting up to 127
addressable devices. Connection of loop line to the control panel must be as like in Annex-B,
Figure-7. A 0Ω resistor must be connected to the unused loops. Each device in the loop must
be addressed via MG-8200 Address Programmer depending on the architectural project of the
site.
The semi-duplex two-wire digital serial synchronous communication between the devices
connected to the loop and the fire alarm control panel is established by the VIP
communication protocol.
Short circuit isolators must be placed in such a way that more than 20 detectors and/or
manual call points shall not be out of service in case of any short circuit occurrence in the
loop.
The devices should be connected to a one-pair cable to create a loop and should turn back to
the panel from the last device.
The loop is energized from the ‘out’ terminal of the panel and the turn back point toward the
panel is the ‘in’ terminal. In case of rupture or short circuit, the loop is energized from both the
‘in’ terminal and the ‘out’ terminal. Thanks to this functionality; it is provided that the devices,
except from the detectors / buttons which are in failure, go on functioning properly while the
part in failure is isolated.
It should be used the short circuit isolator for each ‘in’ and ‘out’ terminals. Thus, if any problem
occurs in between the part from any of the ‘in’ or ‘out’ terminals to the first short circuit isolator
location, this part is isolated and the rest of the loop can go on functioning properly.
Cable connection between panel and PC for data communication is plugged into the PC
Socket which found on front panel of (See Annex-B, Figure-11). The communication cable
shown in Annex-D must be used for communication with computer.
Write enable switch has two positions as “ON” and “OFF”. (Annex-B, Figure-8) When the
panel is energized while the switch is OFF, the panel runs previously saved data. When the
panel is energized while the switch is ON, panel operation modes appears on the screen.
More details are provided in Section-8.
4.5 Remote Control Inputs
There are remote control inputs on the panel which are likely to control the panel remotely by
the help of any remote button. One terminal of the button is connected to the desired input
and other one is connected to GND. (See Annex-B, Figure-6). It should be used the cable with
this code; 2x1,5 N2XH or 2x1,5 NYY for remote control input line.
AL : Reactivates alarm condition, sounders and relays which was silenced and positioned
by Silence Alarm.
FLT : Activates fault condition.
RS : Resets the panel.
SIL : Silences sounders and returns the relays to their initial position.
5- PANEL OUTPUTS
The panel has 4 sounder outputs rated 24 V DC 500mA. In order to monitor the line against to
open or short circuit conditions, normally 16 V DC reverse voltage is seen from the sounder
outputs. During fire alarm outputs are driven by 24 V DC (Annex-B, Figure-4). Current driven
more than 0.5A leads the panel into the fault condition.
2x1,5 N2XH or 2x1,5 NYY cable should be used for the sounder line. 10KOhm resistor,
located on sounder outputs from factory default is used as end-of-line resistor and must be
connected to the end of the sounder line. Otherwise, open circuit fault is monitored on the
sounder line of panel. In case of any open circuit or short circuit faults occurred, it can be
displayed on the screen of panel with the line number.
The panel is equipped with an auxiliary 0.5А 24 V DC power supply output. Exceeding this
level causes fault condition. It can be used for supplying power to peripheral devices.
2x1,5 N2XH or 2x1,5 NYY cables should be used for external power supply line. In case of
mains power supply failure, the batteries provide power supply to the output (24 V DC).
(Annex-B, Figure-3).
The panel has 3 units of relay outputs with volt free changeover contacts rated 1A 30 V DC.
These volt-free outputs; fire relay (normally non-energized), alarm relay (normally non-
energized) and fault (normally energized). (Annex-B, Figure-5). 2x1,5 N2XH or 2x1,5 NYY
cable should be used for relay output line.
5.3.1 Fire Relay : The output is activated on any fire event and it can be used to trigger
any other system. The output is returned to its initial position only by pressing ‘Reset’ button
on panel.
5.3.2 Alarm Relay : The output is activated on any fire event and it can be used to activate
any other system. The output is returned to its initial position only by pressing ‘Alarm Silence’
button on panel. If a new alarm occurs, Alarm relay reactivates.
5.3.3 Fault Relay : The output is activated on any fault event, changes its contact in case
of mains failure. The output returns to its initial position, if fault condition is removed and the
‘Reset’ button on the panel is pressed.
Important notice : Fire alarm panel relays operate as signal-based relays. If these relays
will activate any other devices as like control relays, then a contactor should be used between
the relay and device. In case of high current driven applications, the relay outputs can get
damage if there is no contactor. This situation is not subjected to the warranty condition.
The latest fire event remains at the bottom of the LCD screen. Pressing ‘More Fire’ button
shows all the fire events at the upper part of the LCD screen.
Z o n e s I n A l a r m : 1 A l a r m : 2 F a u l t : 1
* F I R E : M G 6 2 0 8 8 - W a y S w . M o n . Z o n e : 1 *
P : 0 L : 1 A : 2 8 M L - 1 2 X X R e - i n i t i a t e d
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
* F I R E : M G 6 2 0 8 8 - W a y S w . M o n . Z o n e : 1 *
P : 0 L : 1 A : 2 8 M L - 1 2 X X R e - i n i t i a t e d
More Events : If more than one event occurs, it is possible to see all other events by
pressing this button. Pressing this button categorizes the events. It is possible to check other
events by pressing ‘1(UP)’, ‘3(DOWN)’ buttons. To see the desired event category, press the
button with number ‘2 (RIGHT)’. To get back to the main category press ‘EXIT’ button.
Direction buttons:
Button number ‘1’ : It is used to go upward in the panel’s main menu screen and in the
‘More Events’ menu.
Button number ‘2’ : It is used to select the desired feature in panel’s main menu and
desired category in ‘More Events’ screen and go to right direction.
Button number ‘3’ : It is used to go downward in the panel’s main menu screen and More
Events menu.
Button number ‘4’ : It is used to go back to previous menu and go to left direction.
Enter : Enter Button is used to see the menu screen and select the desired
feature inside the menu.
Exit : It is used to go back to previous menu when LCD screen shows main
panel menu or go back to categories menu from the selected category.
Note: Menu features are described in detail in the 11th section of Panel menu. To see the
transitions among menu features please check ANNEX-E Scheme of Menu Functions.
W/Dog Reset : Used for elimination error in case of ‘System Fault’ LED illuminates.
However, if the LED illuminates because of any fault in the central microprocessor preventing
the program to run; the button will be useless for this situation (ANNEX-B, Figure-9).
Microprocessor Reset: Microprocessor can be reset by pressing the ‘Microprocessor Reset’
button. (ANNEX-B, Figure-13)
LCD Lighting : Used to adjust the LCD display contrast with the aid of trimpot
(ANNEX-B, Figure-10).
FIRE : Fire LEDs illuminate in two conditions; if there is a fire situation in the
system or in case of pressing Evacuate button. Each one of these conditions makes the LEDs
illuminate in ‘Red’ colour.
Power On : Panel is energized and operates normally. It illuminates as ‘Green’
continuously.
General Fault : If any fault occurs during operation. It illuminates with the specified
respective faults such as power fault. It illuminates as ‘Yellow’.
Power Fault : It indicates that there is a mains power failure or a problem of battery.
It illuminates as ‘yellow’ and related fault condition can be viewed on the LCD screen.
System Fault : Main microprocessor fault. It Illuminates as ‘Yellow’.
Sounder Disabled : It shows that the sounder outputs on the panel has been disabled and
illuminates as ‘yellow’.
Disablement : If any device or line disabled in the system this LED illuminates as
‘Yellow’.
More Fires : It indicates the presence of more than one fire in the existing event list
of the system. It illuminates as ‘Yellow’.
Evacuate : It indicates that the Evacuate button is pressed. The Evacuate button
must be programmed by Loop Manager Software Program. It illuminates as ‘Red’.
Alarm : It indicates that the alarm button is pressed, it illuminates as ‘Yellow’.
Alarm Silenced : This led shows that incoming alarms are silenced by pressing ‘Alarm
Silenced’ button. It illuminates as ‘Yellow’.
Buzzer Silenced : It indicates that the Buzzer Silenced button is pressed and it
illuminates as ‘Yellow’.
Zone Disablement : It indicates that one or more zones are disabled from the panel menu.
It illuminates as ‘Yellow’.
More Events : If there is more than one event in the system this LED illuminates as
‘Yellow’.
7- PANEL FUSES
Fuses on the panel;
SLCU Fuse (FS1) is a self-resetting fuse and becomes active on 0.5А current overload at the
loop output line. The General fault LED illuminates and on LCD screen ‘Loop open or Short
circuit’ comment is seen. Panel’s loop output becomes unusable. In each single loop card this
fuse is present.
8.1.1. Cabling: Before powering the panel, all connections should be made properly
depending on the connection scheme in ANNEX-B.
8.1.2. Checking cabling: All the connected cables (sounder line, loop etc.) should be
checked for short circuit, open circuit (broken line) etc.
8.1.3. Addressing: All devices in the loop should be assigned to a unique address number
by ‘MG-8200 Address programmer’ device, with regard of architectural project of the site.
8.1.4. Determining connected devices: The devices connected to the panel loop lines
must be determined properly.
In order to determine connected devices, the panel is energized while
‘Write Enable Switch’ is ‘ON’.
(Annex-B, Figure-8)
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ U p / D o w n ] : S cr o l l i n g [ E n t e r ] : A c c e p t
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ E x i t ] : C a n c e l [ E n t e r ] : A c c e p t
Activating this option will erase the panel memory and re-configure the system by scanning all
devices.
S e l e c t C on f i g T y p e
D i s a b l e P r og r a m En ab l e S w i t c h
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ E x i t ] : M a i n M e n u
When program enable switch is OFF, Automatic Learning starts. As a result, new
configuration data is created depending on the currently connected devices and the previous
configuration data is erased. The new data is saved to the memory of panel.
8.1.4.2. PC Program
A special software program called ‘Loop Manager’ is used for programming the panel.
Creating zone location texts, creating cause-effect scenarios, device settings etc. are all done
through ‘Loop Manager’ Software.
The selection of ‘Download from Panel’ or ‘Upload to Panel’ operations is made through the
‘Loop Manager’ Software as shown on the below screen.
Data transfer can be initiated through the Loop Manager; there is no need to follow any
procedure on the panel. It is sufficient to click on ‘Start Downloading’ Button.
When data transfer completed, the following comment is displayed on the program;
In this case, the panel should be deenergized, the connection cables should be checked and
all the above steps should be repeated after debugging the problem.
P l e a s e W a i t .
After uploading or downloading, panel gets back to its normal condition as below;
M a v i l i E l e k t r o n i k A . S . 0 2 1 6 4 6 6 4 5 0 5
V e r s i o n : 1 . 0 . 22
M L - 1 2 X X R e - i n i t i a t e d
A c c e s s L e v e l 2
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ E n t e r ] : M e n u
Status information format of checked units in the panel is as like OK/Fault. In case the internal
device has version number, then this number appears on the screen.
Panel automatically starts to load the information after 10 seconds countdown and go over to
normal operating condition. During 10 seconds countdown, report results of the internal units
can be seen by using ‘1’ and ‘3’ buttons or ‘write enable switch’ position can be changed.
After panel displays all detected units on to screen, the data is loaded automatically and panel
pass to normal operating mode.
M a v i l i E l e k t r o n i k A . S . 0 2 1 6 4 6 6 4 5 0 5
V e r s i o n : 1 . 0 . 22
M L - 1 2 X X R e - i n i t i a t e d
A c c e s s L e v e l 2
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ E n t e r ] : M e n u
On fire event, the panel displays a message in 4 lines as shown below; alarm relays and fire
relays get activated, buzzer and sounders ring.
Z o n e s I n A l a r m : 1 D i s . : 2 F a u l t : 1
* F I R E : MG 6 2 0 8 8 - W a y S W. Mo n . Z o n e : 1 *
P : 0 L: 1 A: 2 8 M L - 1 2 X X Re - i n i t i a t e d
F L OO R C O R R I D OR
2. In the 2nd row; the device model and zone number in which fire alarm comes is
dispalyed.
3. In the 3rd row; panel, loop, address number, and panel name of the device in which fire
alarm comes is displayed.
4. In the 4th row; zone name of the device where fire alarm comes is displayed.
Z o n e s I n A l a r m : 0 D i s . : 0 F a u l t : 1
* F A U LT - MG 9 4 0 0 M u l t i s e n s o r Z o n e : 1 *
P : 0 L : 1 A : 2 8 M L - 1 2 X X A u t o - l e a r n e d
M E E T I N G R O O M
D i s c o n n e c t e d D e v i c e
a) Access level 1: ‘Button Control’ key is ‘Disabled’. In this case; ‘Silence Buzzer’, ‘Lamp
Test’, ‘More Fires’, ‘More Events’ buttons can be used. ‘Button Control’ key must be switched
ON in order to unlock other buttons.
b) Access level 2: Some menu functions are active in this access level. Press ‘Enter’ while
‘Button Control’ key is enabled to access panel menu.
The button number ‘1’ is used to move ‘up’, and the button number ‘3’ is used to move
downward. To confirm the selected option press ‘enter’ button or press the button number ‘2’.
In order to get back to previous menu, press ‘Exit’ or press the button number ‘4’.
ACCESS LEVEL 2 MENU
+DEVICES
+DISABLEMENTS
+SET SYSTEM TIME
+FIRE ALARM COUNTER
+DELAY CONFIGURATION
+TEST
+ACCESS LEVEL 3
ACCESS LEVEL 2 MENU INSTRUCTIONS
+DEVICES: The following information for the devices connected to every single loop can be
displayed: Address information, zone location texts, device models, analogue values, status of
devices (Enabled/Disabled).
+General:
+Automatic Control: In case this option is selected, devices
connected to the system are continuously checked for any contamination. Interrogation count
can be selected as (8, 16, 64, 255). The contamination control is done depending on the
selected value. An analogue value greater than 75 is considered as the contamination
threshold by the panel. Upon detecting any contaminated device, a message appears on the
screen. This message disappears after cleaning or replacing the device with the new one and
resetting the panel.
+Interrogation Count: x
-Measuring contamination status
C o n t a m i n a t i on C o n t r o l
M e a s u r i n g c o n t a m i n a t i o n s t a t u s
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ E x i t / L e f t ] : B a c k
+Measure
-Interrogation Count: x
-List Results
-Print Results
Loop: n
+Automatic Control
+Interrogation Count: x
-Measuring Contamination Status
+Manual Control
-Measure
-Interrogation Count: x
+List Results
+Print Results
C o n t a m i n a t i on C o n t r o l
M G 9 1 0 0 O p t . S m o k e D e t . Z o n e : 1
P : 1 L : 1 A : 4 3
C o n t a m i n a t e d d e v i c e
_ _ _ _ _ _ _ _ __ _ _ _ _ _ _ __ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[ U p / D o w n ] : S c r o l l [ E n t e r ] : U p d a t e
-Analog Update: Due to this feature, the analogue values of system devices
can periodically be followed.
Note: See, Annex-E Menu Functions Scheme for switch between menu functions.
So that Maxlogic series fire alarm control panels can operate in network, each panel must contain 1 unit
of ML-1201 Network Module.
Please, see Section “15- Panel Models” which includes ML-121X.N models having network module by
default. ML-1201 Network Module should NOT be added for those panels which have a network
module by default.
ML-1201 Network Module is compatible with all Maxlogic Series Intelligent Analogue Addressable Fire
Alarm Control Panels.
Up to 64 Maxlogic Series Intelligent Analogue Addressable Fire Alarm Control Panels can operate in a
network structure. “16 loops x 127 devices x 64 panels = 130.048 devices” can operate in a network.
All models of Maxlogic Series Fire Alarm Control Panels can operate in the same network.
(ML-121X.N, ML-123X.N, ML-124X.N, ML-125X.N)
** GCU (Gateway Controller) allows the network to be monitored graphically and controlled remotely
from a distant place. GCU connect to the network line as a control panel. The panels must be
connected to each other with FTP Cat6 Network Cable.
In case of open circuit (broken line), network continues In case of open circuit fault of the network line, the
operating. system can detect the exact point of problem.
1 0 0 0 0 0 0 0 0
11 0 1 0 1 0 0 0 0
23 0 1 1 0 1 0 0 0
54 1 0 1 0 1 1 0 0
Panel
1 2 3 4 5 6 7 8
Address
SWITCH 2- Used to set the communication speed, operation type and end of line
resistor of Panel which will operate in the network.
250 Kbps 1 0 0 0 0 0
100 Kbps 0 1 0 0 0 0
50 Kbps 0 0 1 0 0 0
20 Kbps 0 0 0 1 0 0
10 Kbps 0 0 0 0 1 0
5 Kbps 0 0 0 0 0 1
Communication
1 2 3 4 5 6
Speed
Operating voltage : 24 V DC
ML-1210.N Maxlogic intelligent analogue addressable fire alarm panel, 0 Loop, Network, 230V AC, 50 Hz, 83 Watt, IP30
ML-1211 Maxlogic intelligent analogue addressable fire alarm panel, 1 Loop, 127 Address, 230V AC, 50 Hz, 83 Watt, IP30
Maxlogic intelligent analogue addressable fire alarm panel, 1 Loop, 127 Address, Network, 230V AC, 50 Hz,
ML-1211.N
83 Watt, IP30
ML-1212 Maxlogic intelligent analogue addressable fire alarm panel, 2 Loop, 254 Address, 230V AC, 50 Hz, 83 Watt, IP30
Maxlogic intelligent analogue addressable fire alarm panel, 2 Loop, 254 Address, Network, 230V AC, 50 Hz,
ML-1212.N
83 Watt, IP30