Dact-E3: Analog and Networking Systems

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Analog and Networking Systems

DACT-E3
Digital Alarm Communicator Transmitter
General
The Digital Alarm Communicator Transmitter (DACT-E3) is a digital communications
circuit. It is an optional component of the following systems.

• E3 Series® Expandable Emergency Evacuation System


• S3 Series Small Addressable Fire Alarm Control Panel
The DACT-E3 sends digital signals over the telephone network that transmits to a
central station. This module can be located in the main cabinet or remotely located via
a local RS-485 serial interface.

The DACT-E3 is compatible with digital alarm communicator receivers (DACRs) that
receive the following signaling formats:
• SIA DC8 • 3+1 2300 Hz
• SIA DCS20 • 4+2 1400 Hz
• Ademco Contact ID • 4+2 2300 Hz
• 3+1 1400 Hz DACT-E3
In addition to the DACT-E3 being compatible with digital signaling formats, the DACT-
E3 features numerous formats for communication to a central station. As a digital
communicator, the DACT-E3 complies with FCC Part 8, Telecommunication
Standards for DC and AC Ringer Equivalence.

Installation
The DACT-E3 is adaptable for installation in the standard E3 Series and S3 Series
System cabinets. Typically, the DACT-E3 module mounts on standoffs on top of the
left side of the ILI-MB-E3/ILI95-MB-E3 or SLP (Smart Loop Panel) module. Either
unit can be easily connected to the backbox or sub-assembly plate depending on the
cabinet module.

For instructions on how to install the DACT-E3, refer to the following documents:
• E3 Series Expandable Emergency Evacuation Manual, P/N:LS10080-051GF-E
• DACT-E3 Installation Instructions, P/N:9000-0581
• S3 Series (Small Addressable Fire Alarm Control Panel) UL Listing Document,
P/N:LS10005-051GF-E
Ordering Information
DACT-E3: Digital Alarm Communicator Transmitter

FEATURES & BENEFITS


• Listed under UL®® • Communicates with • Sends information in a • Performs on and off- • Compatible with the
Standard 864, 9th the following sub- variety of formats hook status to the IPDACT Internet
Edition assemblies via the RS- (including full Contact phone lines Communicator
485: ID)
• Transmits and verifies • Traces proper central
data to the central - E3 Series • Offers pre- station “ACK” and
station - ILI-MB-E3 programmed dialing to “Kiss-off” tone
- ILI95-MBE3 the central station
• Activates hang-up and
- S3 Series, SLP phone number release phone lines
DACT-E3 Technical Specifications
SYSTEM STANDARDS For a complete listing of all
compliance approvals and
Operating Voltage: 24 VDC (from the PM-9/ The DACT-E3 is designed to comply with the following certifications, please visit:
PM-9G power supply) standard: http://www.gamewell-
UL Standard: UL 864 9th Edition fci.com/en-US/
Operating Current: 0.018 amp documentation/Pages/
AGENCY LISTINGS AND APPROVALS Listings.aspx
Alarm Current: 0.018 amp
Operating Temperature: 32° to 120° F (0° to 49° C) These listings and approvals apply to the modules E3 Series® and Gamewell-FCI ®
Relative Humidity: 0 to 93%, non-condensing at specified in this document. In some cases, certain are registered trademarks of
modules or applications may not be listed by certain Honeywell International Inc.
90° F (32° C) approval agencies, or listing may be in process. Consult
UL® is a registered trademark
TEMPERATURE AND HUMIDITY RANGES the factory for the latest listing status.
of Underwriters Laboratories
UL Listed: S1869 Inc.
This system meets NFPA requirements for opera-
tion at 0 – 49°C/32 – 120°F and at a relative FM Approved: 3025415
This document is not intended
humidity 93% ± 2% RH (noncondensing) at 32°C ± MEA Approved, Fire Dept. of New York: COA# 6077 to be used for installation
2°C (90°F ± 3°F). However, the useful life of the CSFM: 7165-1703-0125 purposes. We try to keep our
system's standby batteries and the electronic com- product information up-to-
ponents may be adversely affected by extreme tem- City of Chicago: Class 1, Class 2 and High Rise
date and accurate. We cannot
perature ranges and humidity. Therefore, it is City of Denver
cover all specific applications
recommended that this system and its peripherals or anticipate all requirements.
be installed in an environment with a normal room All specifications are subject to
temperature of 15 – 27°C/60 – 80°F. change without notice.

For more information


Learn more about Gamewell-FCI’s DACT-E3 and other products
available by visiting www.Gamewell-FCI.com

Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
9020-0610 | L | 09/17
www.honeywell.com ©2017 Honeywell International Inc.